| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.5 LAccepted-AOC 225 NAROT COLONY MODEL TOWN PATHANKOT PB 145001 | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹31.2 L+₹4.0 L (14.9%)Rejected-Finance | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹34.1 L+₹7.0 L (25.6%)Rejected-Finance | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹38.5 L+₹11.3 L (41.8%)Rejected-Finance | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹39.7 L+₹12.6 L (46.3%)Rejected-Finance | L5 | Rejected-Finance Not Lowest |
Tender Value
Refer Docs
EMD Value
₹97,000
Closing Date
15 Sept 2022, 6:00 pmClosed
GE (SOUTH) PATHANKOT
GE (SOUTH) PATHANKOT
REPR OF PERMTR STREET POST TOP LNTRN AND GATES LIGHT INCL CONTRL PANL SYST CRAN MISC INSTNS SYS INCL ATDNG BRAKDNS AND DAYTODAY AT LTOH LINE UG CABL LT PILRBOX LT CBLE DG SET CPCTOR PANEL SWTCAR TO AC REF ALED WORKS AT UNCHIBASSI UNDER GE S PKT
2022_MES_540017_2
GES/PKT/T-27/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (SOUTH) PATHANKOT
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE (SOUTH) PATHANKOT
₹97,000
Yes
25 Oct 2022
24 Aug 2022
17 Sept 2022
24 Aug 2022
15 Sept 2022
1 Sept 2022
Amount
Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr deep hard /dense type of soil getting out and levelling of bottom surface to required level for poles/stay assebly/ cable all as specifed and directed.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25m thick all as specified and directed.
Removing excavated material from site to a distance not exc 50 mtr away and depositing where directed not exc 1.5mtr from the starting point all as directed.
M&L for Sub class ‘B’ bricks old size laid dry flat over the cable abutting each other, length of cable equal to width of brick all as required.
Supplying & Laying in trenches clear sand for cushioning under ground cable 8 cm below and 15 cm above complete in level all as specified.
Removing existing 1100 volts grade, XLPE/ PVC, armoured, electric power cables (heavy duty) with aluminium conductor of sizes 6 Sqmm 4 core to 70 Sqmm 3.5 core from trench/ duct/ pipe carefully for identifying the defects and relaying the same after rectification of defects complete all as directed. Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe shall be measured and paid for seperately under respective item of Schedule.
Supply and lay cable XLPE insulated armoured heavy duty electric cable with aluminium counductor, 1100 volts grade of crosssectional area 16 Sq mm 2 core.Note: Earth work (Excavation, Returning & refilling and removal), sand cushining, cable protection cover, GI protection pipe shall be measured and paid for seperately under respective item of Schedule
All asper item No 7 above but of size 16 Sq mm 4 Core
All asper item No 7 above but of size 25 Sq mm 3.5 Core
All asper item No7 above but of size 25 Sq mm 4 Core
All asper item No 7 above but of size 35 Sq mm 3.5 Core
All asper item No 7 above but of size 70 Sq mm 3.5 Core
S&F in replacement of old u/s service cable size 10 sqmm, twin core multistranded 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service with galvanised steel wire complete all as spd and directed.
M&L for testing & commissioning of straight through jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 6 to 16 Sqmm 3.5/4 core with working voltage 1100 volts .
M&L for testing & commissioning of straight through jointing kit, heat shrinkable type suitable for LT/ UG cables of size 16 to 50 Sqmm 3.5/4 core with working voltage 1100 volts .
M&L for testing & commissioning of straight through jointing kit, heat shrinkable type suitable for LT/ UG cables of size 70 to 120 Sqmm 3.5/4 core with working voltage 1100 volts .
M&L for testing & commissioning of straight through jointing kit, heat shrinkable type suitable for LT/ UG cables of size 150 to 185 Sqmm 3.5/4 core with working voltage 1100 volts .
M&L for GI pipe light grade 40 mm dia for cable protection on road crossings/ plinth protection with fixed to the pole wall etc. suitable fittings for cable protection .
M&L for GI pipe light grade 50 mm dia for cable protection on road crossings/ plinth protection with fixed to the pole wall etc. suitable fittings for cable protection .
Taking down defective LED street light fitting of any size/ capacity from height of pole/walls/high mast of any location exceeding 7.0 m height for repair work and re-fixing back after repair work including checking, inspecting, testing and commmissioning complete all as directed. Note: a) The M/L for Items like electronic drivers,surge protection devices etc shall be measured and paid separately under relevant items here in under this Schedule. b) Necessary tools like ladders & other T&P required etc shall be arranged by the Contractor. c) The rate quoted deemed to be inclusive for minor parts nut bolts, circle clips, clamps etc if any required at site.d) The M/L for repairs to LED panel is not included in the scope and shall be measured and paid separately.
supply and fix in repair Electronic digital Timer (Astronomical) suitable for street light timer DB panels .
Supply only the following spares suitable for LED street/ Flood light fittings of
Supply and fixing in repair Electronic driver potted type IP-65, suitable for 90 to 120 W LED light fitting
Supply and fixing in repairElectronic driver potted type IP-65, suitable for 70 to 80 W LED light fitting
Supply and fixing in repairElectronic driver potted type IP-65, suitable for 30 to 60 W LED light fitting
Supply and fixing in repairSurge protection device of capacity 10 KV suitable for LED light fitting
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 60 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 7200 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 70 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable street light fittings from any height and Supply & Supply & fixing LED street light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,with lumen output not less than 9000 lumens suitable wattage for efficiency not less than 100 lumens/Watt,min wattage 90 watt, with ingress protection IP 65 and SPD of capacity 10 KV etc complete and testing on completion all as specified and as directed.Note: The GI pipe if rquired bracket will be measured and paid separately under relevant schedule items
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 15000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 120 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed.
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 20000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 100 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed.
Supply & fix replacement decorative path way light lighting LED decorative post top lantern for 360 degree 40 watts 230 volts, 50 HZ, maple shaped in sothing opal/ prismatic finish made up of polycarbonate,including all accessories prewired complete.Note :- (i) Minimum 2 years gaurntee period of LED fittings (ii) Driver shall be IP 66 degree of protection potted seal type. (iii) Power factor more than 0.9.
S&F in repair PVC insulated 3 core 2.5 Sq mm stranded Aluminium conductor cable for connecting OH line/junction box to street light fitting testing and commissioning all as directed.
Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable including making good the excavated portion by means of PCC 1:3:6, type C1 matching with the surroundings all as directed.
M&L for PCC 1:3:6 type C1 with 20 mm graded aggregate for coping of poles and stay including form work.
Supply and fixing timelite distribution boards (street light DBs) 40 A 3 pole with 230 V Astronomical time switch complete all as directed including dismantling old one .
Earthing complete with Galvanised Steel earthplate of size 60x60cmx6.3mm thick electrode and GI wire 8 sqmm dia as earth lead, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to earth wire 4 sqmm by means of nuts, bolts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I, including testing on completion (Rates inclusive of neccessary excavation in any type of soil, earth work, PCC pit, CI cover, funnel with watering pipe, suitable size of light grade GI Protection pipe for earth strip in ground etc. all as required at site for complete earthing).
S&F loop-in/loop-out box of outer size size 250x210x115 mm made out of FRP(Hot moulded type) with weather proof canopy and locking screws along with with 5/6 Amps MCB - 01 No, 50 Amps rated 3 pole connector- 01 Nos, neutral link mounted and Din rail suitable size for mounting MCB/Connector etc complete in the box, duly fixed to to steel tubular/rail/PCC/RCC pole using 25 x 3mm FI clamp, including suitable gland and lugs for connecting cable complete all as directed including dismantling old one.
Material and Labour for Galvanised iron round bracket made out of 40mm dia GI tubing including making provision for fixing of 04/06 no flood light on 11 mtr steel tubular pole ad fixing and connecting up of LED lights (LED lights shall be measured seperately under respective items of sch ) complete all as specified and directed. Note: The inner diameter of ring shall not be less than 1.0 meter
M&L for bracket for street light fitting made out of 40 mm bore pipe light grade GI tube bent to shape required, not less than 1.20 meter long, fixed with and including MS flat iron clamps made out of 40x6 mm FI, bolts, nuts, washers etc complete including dismantling old defective.
M&L for bracket for street light fitting made out of 25 mm bore pipe light grade GI tube bent to shape required,not less than 1.20 meter long, fixed with and including MS flat iron clamps made out of 40x6 mm FI, bolts, nuts, washers etc complete including dismantling old defective.
M&L for preparation of old painted steel surfaces of 9 m long steel poles incl removing oily/ greasy spots and applying one coat of aluminium paint complete including applying a coat of white wash on pole coping and lettering the pole details with white letters/ blackground etc complete all as directed
Repairs to High Mast/ mid mast pole motor of Capacity 1.0 HP/0.75 KW 415 Volts 50 Hz 3 Phase 930 RPM and necessary rewinding with super enamelled copper wire all as per existing and servicing/greasing of reduction gear box complete all as specified and as directed.
Decarbonising of the control panel of High mast/Mid mast and including sevicing of parts such as contactors/timers including replacement of pitted lugs,thimbles, control wiring etc complete including painting with a coat of synthetic enamel paint
S & F in repair 3 pole power contactor with coil voltage 230 volt AC of current carring capacity 32 to 40 Amps complete including control wiring thimbles etc complete all as directed.
M&L for preparation of old painted surfaces of 9 m long PCC poles incl removing oily/greasy spots and applying one coat of synthetic enamel paint of black and yellow in alternate strips of 30 cm width upto 1.5 m height including applying a coat of white wash on pole coping and lettering the pole details with with white letters/ blackground etc complete all as directed
S&F in repair powder coated Mild steel junction box wtih MCB SP 03-10 Amps-01 No outdoor type, CRCA sheet with front openable hinged door , locking arrangements with 4 Nos Aluminum bus bars, 200 Amps, mounted on porcelain insulator, glands and lugs etc. and fixed to pole/ PTL post etc with suitable size flat iron clamps, nuts , bolts complete including taking down all as specified and directed.
S&F in repair powder coated Mild steel junction box wtih MCB SP 03-10 Amps-01 No outdoor type , CRCA sheet with front openable hinged door, locking arrangements with 2 Nos Aluminum bus bars, 200 Amps, mounted on porcelain insulator, glands and lugs etc. and fixed to pole/ PTL post etc with suitable size flat iron clamps, nuts, bolts complete including taking down all as specified and directed.
Supply and fixing galvanised steel tube light grade of 15 mm dia, over the electrict pole with the help of suitable size MS clamp, passing the service cable from the busbar to the light fitting throught it, and making connection, of the cable to both the ends from bus bar to the light complete all as directed and specified.
Dismentling & Supply and erect steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 metres long) all as directed incl dismantling old one. NOTE :- Earth work, Cement concrete in foundation, coping etc will be measured and paid separately under relevant item.
M&L for PCC 1:4:8 type D2 with 40 mm graded aggregate as in foundation complete.
M&L for PCC 1:3:6 type C1 with 20 mm graded aggregate for coping of poles and stay including form work.
Repair, maint and making the fully functioning of flameproof electric operated crane of cap 2 Ton to 5 ton after checking long travell motion , cross travel motion , hoisting motion (electrically and mechanically) in presence of user rep and MES rep & rectify any type of defects immediately when found including servicing, greasing, top up gear box oil & carrying out routine maintenance as directed by Engineer in Charge (Note :- (i) any accessories found unserviceable that shall be replaced under respective items of this Sch. (ii) : Labor for lowering, mounting arrangement such as ladder , pulley block, rope system, T&P , any type nut, bolt, washers and other connected mechanism shall be contractor arrangement and rates are deemed to be included in this Job. No extra payment will be made to the contract against lowering/lifting the spare etc at a height of 20' to 30' (iii) Repair/maint of each flame proof EOT crane of capacity 2 to 5 Ton (total 17 Nos) for two times or as per complaint of EOT cranes in a month.
Dismantling the main driving shaft of forward/reverse drive of flameproof EOT crane after unscrewing nuts, bolts, washers including other connected accessories with shaft such as breaking assembly, coupling, bearings rings, gear box lowering down the smaller portion of shaft from up to 30' approximate height for removing and threading, repairing manufacturing cutting teeth keys one Nos bearing housing cabinet and replacement of one Nos tapper bearing welding of foundation rest pad making drills holes in rest pads matching with main foundation of trolly, cleaning, greasing and oiling of all the bearing, bearing housing, gear box etc complete for smooth functioning including providing nut, bolts with locking arrangement & washers of any type/size as site requirement complete including re-assembly with connected accessories after repair including carrying out necessary alignment of all the parts connected with shaft all as specified and directed by Engineer-in-charge (Capacity of crane - 2 to 5 Ton )
Dismantling of micro -up and down drive arrangement of flameproof EOT crane after un-screwing L- key bolts/ screws nuts, washers etc which includes gear box of micro drive main box of up -down drive, braking arrangements including dismantling of 3 set (3 pair) of micro coupling, micro-drive arrangement for under taking repair including getting down all as dismantled parts from existing platform at a minimum height about 20' to 30' approximately reassembling and re alignment all the parts complete including testing on load on both micro and main drive complete all as specified and directed by Engineer -in-charge (capacity of Crane 2 to 5 Ton )
Dismantling/strip opening gear of micro main shaft drive for replacement of 2 Nos gun metal bushes having internal lining for oiling arrangement, replacement of all the nuts/ bolts of bush side plate with L-key, bolts of size as per sample oiling/greasing of gear box including necessary cast iron repair to broken foundation which includes welding lathing and grinding complete all as specified and directed by Engineer -in-charge.(Crane capacity 2 to 5 Ton )
Dismantling and refixing after repair brake shoe leather suitable any motion of flameproof EOT crane 2 to 10 ton cap complete all as specified and directed.
Dismantling/strip opening flameproof micro drive box complete with rectifier transformer arrangement, magnetic disc both side coupling for remotting both the side ends of driving shaft (Gear box coupling side and braking arrangement coupling side) making multi key arrangement on both the shaft and couplings (teeth system ) to avoid any kind of play in coupling and shaft including replacement of 4 Nos carbon bushes, replacement of 02 Nos gun metal bushes including making oiling arrangement in bushes and side covers of bushes/housing of micro drive re-assembling/testing complete (crane capacity up to 5 Ton) all as specified and directed by Engineer -in-charge.
Dismantling/strip opening of up/down micro electric braking arrangement after un-screwing nuts, bolts washers, re-adjustment of braking springs, replacement of brake leathers, replacement of two Nos 440 volts any make brake coils, replacement of both gun metal bushes of shaft housing in brake box making oiling/greasing arrangement complete re-assembling and testing complete all as specified and directed by Engineer -in-charge.(Crane capacity 2 to 5 Ton )
M&L for replacement coupling as per sample or approved by GE suitable for perfect alignment between flameproof motor and driven machine all as directed by Engineer in charge
M&L for replacement of L Key bolts 1" x 10mm as per sample or approved by GE including applying moose threads found worn out and taking out broken bolts from body/housing of machine for 2 to 5 ton capacity flameproof EOT Crane complete all as specified and directed.
Dismantling/ lowering of burnt flame proof/weather proof three phase 440 volts , 50 Hz , 960 RPM , class F, 5 HP induction motor from platform complete including strip opening the same and rewinding with super enameled copper winding wire of same size /gauge as existing earlier complete including all backing material , insulation material and re- installation the same at original site complete all as specified and directed Engineer in charge.
All as per item No-65 above but capacity of motor 3 HP.
M & L for of Power contactor 3 pole 16 Amp , 110 Volt as per sample or approved by GE complete all as specified and directed by Engineer in charge.
M & L for of Power contactor 3 pole 40 Amp , 110 Volt as per sample or approved by GE complete all as specified and directed by Engineer in charge.
M & L for of Over load relay 1.7 to 2.4 Amp as per sample or approved by GE complete all as specified and directed.
M&L for of main bearing as per site requirment suitable for 2 to 10 Ton cap crane all as specified and directed.
M&L for breake oil suitable for flameproof EOT crane up to 5 Ton cap as per manufacture recommendation or directed by Engr In Charge.
M&L for grease suitable for flameproof EOT crane up to 5 Ton cap as per manufacture recommendation or directed by Engr In Charge.
S & F Thruster for flame proof EOT crane cap upto 5 Ton complete with all accessories all as specified and directed.
M&L for Earthing complete with galvanised cast iron earth plate electrode of size 600x600x6.3 mm thick as earth electrode with top edge of the earth plate not less than 1.5mtr below ground level using using galvanised iron strip 32x6mm earthing lead as earth continuity conductor connected to earth plate by means of GI thimbles nuts bolts washers all as directed including providing earth wire protection pipe GI light grade15mm dia from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and RCC pit cover in PCC 1:3:6 adequate quantity of charcoal dust and salt all around the earth plate, earth work in any type of soil remain surplus excavated material all as required at site and specified in EP No 5 of SSR part I 1991 or directed by Engineer-in-charge incl testing on completion.
Taking out carefully unserviceable cable up to 95 Sqmm from trenches and relaying same after repairs in same or other indicated location after testing complete all as directed by Engr-in-Charge.( Note: Earth work, sand, bricks will be measured and paid separately)
Supply and laying in trenches or fixing to wall/ pole or passing through pipe PVC insulated heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 70 Sqmm 3.5 core.M (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification)
All as per item No 76 above but cable of size 50 Sqmm 3.5 Core
All as per item No 76 above but cable of size 35 Sqmm 3.5 Core
Cable jointing kit for 1100 volt grade cable for straight through termination heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 25 to 50 Sqmm 3.5/4 core.
All as per item No 79 above but for 71 to 150 Sqmm size.
Taking down carefully copper/aluminum point wiring (light, fan,socket or power) complete, (fittings such as switches, ceiling roses, pendants, regulators sockets etc to be measured separately), removing materials to store for keeping in safe custody for reuse at site and making good disturbed surfaces of walls, flors, etc.
M&L for point wiring with steel conduit 1100 volts grade single core FRLS having multi stranded copper conductor of 2.5 Sq mm nominal cross sectional area (ISI marked with valid CML No) drawn in and includin stove enamelled steel conduit less than 25 mm dia with all fitting and fixing accessories in surface wiring system and with 1.50 Sqmm PVC insulated unsheathed multistranded copper conductor cable as continuous earth conductor connected to earth dolly complete all as specified and as directed.
Taking down carefully sub main wiring of any nos of wire and size with earth wire from wooden batten/ surface conduit/casing caping complete with its all accessories
M & L sub-main wiring with 4.0 Sq.mm (nominal area) PVC unsheathed multi strandard copper conductor PVC insulated 1100 volt grade single core cable drawn through and including rigid PVC conduit medium grade minimum 20mm size and its accessories complete along with 4.0 Sqmm cable but in green colour as continuous earthing wire and connecting to common earth dolly completely concealed ,surface,in walls/ceiling/roofs all as directed and specified including dismantling old one Note : Three runs of PVC copper cable and one run of PVC conduit will be measured as one Rm.
S&F switch flame proof rotary type with termination box in LM6 16A single pole 250 V complete all as specified and directed
Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 16A, 250V, 2P+earth
Supply and fixing in repair flameproof weather proof exhaust fan with louver shutter of size 380mm with 0.25 Hp flame proof motor240 volts, 50 Hz, single phase inculuding making hole, and making good surface after fixing the fan.
Supply and fixing in repair On load Changeover Switch 4 Pole 630A 415V, Manual Changeover in Open Execution. Nos of pole -04.Site convertible fuse version for open execution .Site convetible dual shaft position .SS enclosure version does not require separate cable gland box Staggered terminals
Supply & fixing in repairs of MCCBs of following current carrying capacity including necessary connecting terminals to bus bar, nut bolts etc complete all as directed .
(i) 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA 250 A rated.
(ii) 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 200 A rated
(iii) 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 160 A rated
(iv) 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA,125 A rated .
(v) 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 36 KA, 400 A rated .
(vi) 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 50 KA, 630 A rated .
M & L for replacement of unsv/broken thermoplastic polycarbonate spring type locks suitable for panel locking (Mi DV 01 with Mi SR 4) complete
Restretching of ACSR conductor of any size of over head lines LT/HT on poles including binding with insulators, jointing jumpers etc including connections of incoming and out going cables complete all as specified and directed. Note: ACSR conductor Required for winding etc to be included in quoted rates.
Dismantling unserviceable cross arms including clamps, bolts, nuts, washers etc from pole.
Supply, fabricate and fix cross arms any size along with, brackets, clamps, bolts, nuts, washers, bracers etc including drilling holes, cold/hot complete and fixed to pole including one primer coat and one under and finishing coat of paint.
Dismantlin of ACSR conductor of any size, from insulator etc from the structure/over head line all as directed.
M&L replacement of ACSR conductor of any size as ordered by Engr-in-charge including tightening and bindingh with new binding wires to insulators all as directed.
Dismantling insulators any type, size
M&L pin type insulator vitreous, white, brown, or green insulator includig one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut 100 mm height, 65 mm dia for 1100 volts grade.
Dismentling old feeder pillar & Supply, installing, testing and commissioning of LT feeder pillar box factory made cubicle outdoor type, fabricated out of 3.00 mm thick CRCA sheet floor mounted with angle iron base frame made of 40 x 40 x 6mm , 50 cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415 V 3 Phase 4 wire ,Square copper bus bar Chamber 320 Amp Capacity weather proof, with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer complete including supply fixing and making provision of the following :- (a) MCCB 4 pole 415 volts 3 phase 200 Amp 25 KA -01 No (f) LED Indicator RYB -01 Set ( Set of three). Note: The panel shall be as per CPRI certificate. Note : PCC will be measured and paid separately.
Cutting, trimming of hanging/ extended braches of trees upto a distance 3 meter from the overhead HT/LT line and making the line clear upto the entire length of the feeder including removal and disposal of the cut tree branches 50 meters away from the site complete all as specified and directed. Note : The Rates shall inclusive of T&P, hydraulic ladder, equipment such as motorised diesel operated hacksaw etc complete. One span comprises of 3 to 5 conductors of any distance between one pole to adjacent pole including trimming of all tree branches in vicinty & around poles /conductor & will be measured as one span. Necessary prior permission shall be obtained from concerned I/C JE E/M before carrying out the work. All safety measures & insurance to the staff undertaking the Job shall be the Contractor's responsibility.
S&F in repair Capacitor duty contactor with 1 No Aux contact 230V AC coil voltage suitable for minimum 10 KVAR capacitor.
S&F in repair Capacitor duty contactor with 1 No Aux contact 230V AC coil voltage suitable for minimum 25 KVAR capacitor.
M&L in replacement of existing unserviceable contactor current carring range 9 A to 18 Amp (AC-3 duty) at different places in APFC panels including required electrical connections with suitable size of single core pvc copper cable & testing all as directed .
M&L in replacement of existing unserviceable MCB 25-40 Amps TPN 415 volts at different places in LT Panels/APFC panels including required electrical connections & testing all as directed.
M&L in replacement of existing unserviceable MCB 32 - 63 Amps TPN 415 volts at different places in LT Panels/APFC panels including required electrical connections & testing all as directed.
Maintenance and servicing of 100 KVA to 200 KVA DG set consisting of replacement of fuel filter, air filter and lub oil filter including replacement of eninge oil all as directed and testing on full connected load of any make as per OEM. Note: Engine oil will be measured and paid seperately.
M&L for replecement of existing unservicible Fan Belt and testing complete for the capacity of 100 KVA to 200 KVA DG Sets and any make as per OEM.
M&L for replecement of existing unservicible Hose Pipes with clamps and testing complete for the capacity of 100 KVA to 200 KVA DG Sets and any make
All as per Srl Item No. 113 but for the capacity of 320 KVA DG Sets
Taking out the old unserviceable radiator from the DG set and taking it to work shop for overhauling & cleaning descaling with restore plus solution, removal of leakage, welding brazing & refixing it duly repaired etc complete all as directed for the capacity of 100 KVA to 200 KVA DG Sets and any make as per OEM.
M&L for repair and overhauling of unsv self starter 12V/ 24V of any capacity DG set including repair/ replacement unsv/ defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy complete all as specified and directed.
M&L for repair and overhauling of unsv dynamo/ alternator 12 V/24V of any capacity DG set including repair/ replacement unsv/defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy complete all as specified and directed.
S & F in repair Hour meter 6 Digit, LCD, Terminal connection 9-64 v ,10- 60VDC of any capacity DG set complete all as specified and directed.
Taking out the old unserviceable battery from the DG Set and supply and fix new 12V, 180 AH maintenance free battery including testing and commissioning complete all as specified and directed
M&L for repair of Water pump of 100 to 160 KVA DG set including replacement of defective unsv spare part of any make and model and refix the same after repair complete all as specified and as directed
M&L for Calibration of Fuel pump including replacement of unsv/defective spares of 320 KVA DG Set of any make and model complete all as directed.
M&L for Calibration of Fuel pump including replacement of unsv/defective spares of 100 to 163 KVA DG Set of any make and model complete all as directed.
M&L for overhauling and calibration of fuel injector assembly including replacement of unsv/defective spares of 320 KVA DG Set of any make and model complete all as directed.
M&L for overhauling and calibration of fuel injector assembly including replacement of unsv/defective spares of 50 to 63 KVA DG Set of any make and model complete all as directed.
Supply and fix in replacement battery leads set, PVC insulated multisranded, copper conductor of min size 35 sqmm 1 mtr long each duly fixed with brass clamps, copper lugs suitable for DG sets of different capacities.
M/L for replacement of coolant for radiator for DG set at various locations.
M/L for replecement of Lub Oil (Engine Oil) of grade 20W40 for Engine for DG set at various locations.
M & L for replacement of starter ring gear assembly for capacity 320 KVA DG set.
Shifting of Dg Set from Depot pump house to domestic pump house of Capacity 40 KVA to 63 Kva at 18 FAD Uchi bassi.
M/L for cleaning the fuel tank both internally and externally by removing all the dust/ sediments etc including replacement of PVC pipe fuel level indicator, writing of tank capacity, date of cleaning and next due date for tank to be cleaned for following capacities of 100 KVA to 200 KVA DG Set and any make as per OEM.
M&L for taking down the defective split/Window unit of the following capacity, shifting to work shop, taking out the defective unserviceable hermetically sealed compressor from the unit, replacing the compressor with new compressor of the same capacity, fixing to the unit inter connecting the refrigerating lines, flushing out the cooling coil & condenser, removal the coil & carbon thoroughly, cleaning with CTC, leak testing, pressure testing with Nitrogen gas, dehyderating, Vaccumissing, charging of Refrigerant gas, testing at work shop. Shifting to the location reinstalling the same in its Original position connecting up all etestion electrical, connection and Testing & Commissioning. All as specified as directed by Engineer-in-Charge.
1.5 TR Capacity
2 TR Capacity Note : Rate quoted is deemed to be inclusive of cutting, welding, brazing, sealing the refrigerant tubing, replacement of strainer, CTC, Nitrogen gas, Refrigerant gas, required to and from Transportion and Handling. M/L for spares will be measured and paid separately.
M&L for taking down the damage condenser fan blade of 1.5TR split/Window type AC’s of any make and supply & fixing suitable new fan blade and testing & commissioning the unit.
All as per Item No. 135 above but 2 TR Split AC
M&L for taking down the damaged blower unit of any make split/Window AC and supply and fixing of new blower unit of suitable type and testing & commissioning the unit.
M&L for complete scraping out the crusting painting of the complete body of out door unit metallic surface, cleaning the surface thoroughly, apply putty/ metal paste, prepare the surface, apply 2 coat of synthetic enamel paint over a coat of red oxide primer for 1.5 / 2TR capacity split type AC’s.
M&L for cleaning flushing the refrigeration system thoroughly with CTC, and Nitrogen gas, leak testing and locating the leaks, rectifying the leaks, by brazing the joints, replacing the damaged copper pipes, silver rod/ copper. Pressure testing, dehydrating, vaccumissing, gas charging testing & commissioning the system the work includes required strainer, N2 gas, Refrigeration gas and transportions Handling the unit. All as specified as directed by Engineer-in-Charge.
1.5 TR Capacity
2 TR Capacity
M&L for taking down the unserviceable temperature sensor probes and supply & fixing new sensor probe suitable for any type, make split/Window type AC’s and testing & commissioning.
M&L for taking down the defective unserviceable printed circuit Board and S/F of new printed circuit board for any make split/window type AC unit.
M&L for taking down the defective unserviceable sealed fan motor & S&F new fan motor of the same capacity & size to suit the split/window AC unit of any make and capacity of 1.5 / 2 TR all as per existing at site
M&L for taking down the damaged air filter set and S/F of new air filter set for split/window type AC’s of 1.5 / 2TR capacity.
M&L for taking down the defective unserviceable starting/ running capacitors 80/100 MFD 230V / 50Hz and supply and Fixing the new starting capacitor of the same capacity to split / window type AC’s and testing.
M&L for taking down the defective unserviceable starting relay and supply and fixing new rely suitable for 1.5/2TR Window / Split type AC’s and Testing.
M&L for taking down the defective unserviceable Thermostatic switch and S/F new thermostatic suitable for window type AC’s and Testing.
M&L for taking down the damaged drain pipe and S/F of new insulated drain pipe suitable for split type AC’s.
M&L for taking down the defective capillary tube set and supply & Fixing new suitable capillary set for split type AC’s.
M&L for taking down the rusted out door unit stand and supply & fixing the stand with required anchor fastner and nut & bolts and rubber bushes for 1.5 / 2 TR Split unit.
M&L for taking down the burned out door unit fan motor and rewinding, overhauling renewal of worn out shaft & bushes, and fixing to the unit, of 1.5 / 2 TR Split units.
M&L for taking down the defective remote control unit and S/F of new remote control unit for split/window type AC of 1.5/ 2 TR of any make and testing.
M&L for taking down the defective definite purpose magnetic contactor of the split/window AC’s of any make, and supply & fixing of new contactor of 240 VAC. 30 Amps 50 Hz, and coil volt of 208/240V 50/60Hz and Testing.
M&L for taking down the defective unserviceable sealed motor of indoor unit of any make split unit of 1.5/2 TR capacity and S/F new fan motor suitable for Split type AC’s.
M&L for taking down the defective starting capacitor of split / window type AC’s and supply & fixing the new starting capacitor of 80/100 MFD 230V, 275SV-50Hz and Testing for 1.5/2TR AC Unit.
M&L for taking down the burned wiring kit and supply & fixing and testing of new wiring kit suitable for 1.5/2TR split and window type Ac unit.
M&L for taking down by disconnecting water connections and shifting elective water cooler to work shop, taking down the defective sealed compressor and replacing with new compressor, the work includes flushing the complete system condenser, cooling coil with Nitrogen, removal all carbon, oil & dirt, brazing & inter connecting the refrigeration lines, de-hydrating, purging with refrigerant, vaccumissing and charging of R22 / 134a Refrigerant and testing & commissioning and shifting to original location and connecting up the electrical & water connection for the following capacity water coolers. All as specified as directed by Engineer-in-Charge.
40/60/80 Ltrs. capacity water cooler
120/150 Ltrs. capacity water cooler
M&L for complete tinkering the corroded sheet metal parts, side panel, door, with existing gauge M.S. Sheet and renewal of the bottom base plate, mounting lets, fan motor base plate, and condenser should cover etc., with existing size gauge G.I. sheet, with required Angle Iron, Nut & Bolts all as per the existing size and shape including cutting, bending, welding and completing fixing all other components, complete scraping with old paint, prepare the surface, painting 2 coat of enamel paint over a coat of primer and complete cleaning the water tank and shifting to the location and testing any capacity of water coolers. All as specified as directed by Engineer-in-Charge.
Material and Labour for charging the water cooler of the following capacitor including taking down, transporting to workshop flushing out the cooling coil, condenser, brazing the refrigerant lines, replacing of liquid line copper strainer, leak testing, purging with refrigerant, vaccumissing and charging of R22/R 134a gas, testing & commissioning and shifting to the location and connecting up the electrical & water connection. All as specified as directed by Engineer-in-Charge.
a) 40/60/80 Ltrs. capacity water cooler
b)120/150 Ltrs. capacity water cooler
M&L for painting the water cooler including scraping out the old paint prepare the surface, painting 2 coat of enamel paint over a coat of primer, the work including necessary putty, metal paste etc, and disconnecting from the position and refixing after painting for any capacity of the water coolers.
M&L for to the water cooler tank and cooling coil by dismantling the water cooler and carried out the lead soldering to cooling coil to the tank outer surface where ever the detached portion and rectify the leaks portion and re-assembly the water cooler of any capacity.
M&L for taking down the damaged thermal insulation of the water cooler, and renew the thermal insulation as per the existing thickness and assembling the body with necessary sheet metal screws etc., for any capacity water coolers.
M&L for taking down the defective starting relay and S/F of new starting relay for any capacity water cooler.
M&L for taking down the defective overload relay and S/F of new over load relay suitable for any capacity water cooler.
M&L for taking down the defective Running capacitor and Supply & Fixing new running capacitor 20/10 MFD, 440 VAC 50/60 Hz suitable water cooler.
M&L for taking down the defective starting capacitor and Supply & Fixing new starting capacitor 60/80 MFD, 230V, 270SU-50 Hz for water cooler upto 120 Ltrs. Capacity.
M&L for taking down the defective Running capacitor and Supply & Fixing new running capacitor of 25/36 MFD, 440 VAC, 50/60 Hz suitable for 150 Ltrs. Capacity water cooler.
M&L for taking down the defective thermostatic switch and Supply and Fixing of new thermostatic switch for water coolers.
S&F of Left/ Punch cook for water cooler of any capacity.
S&F float valve for water cooler of any capacity
M&L for taking down the damaged drain connections and drain pipe and S/F of new drain connection & pipe with necessary clamps, Nipple, coupling etc, for any capacity water cooler.
M&L for taking down the defective unserviceable sealed fan motor and S/F new fan motor with suitable capacitor for water cooler upto 40/80, 60/120 ltrs. Capacity.
M&L for taking down the damaged condenser fan blade and supply and fixing of new fan blade suitable for 40/60/80 water coolers.
M&L for taking down the corroded air cooler condenser and supply and fixing of new air cooled condenser with necessary brackets and fixing arrangements including welding brazing etc., for water cooling 40/60/80 Ltrs. Capacity.
M&L for taking down the complete corroded sheet metal body of out door unit of split unit and supply and fixing of new out door unit suitable 1.5 TR split unit the work includes dismantling the components and reassembly and fixing to the existing location and testing for any make of split unit.
M&L for taking down the complete corroded sheet metal body of indoor unit of split unit and supply and fixing of new indoorunit suitable 1.5 TR split unit the work includes dismantling the components and reassembly and fixing to the existing location and testing for any make of split unit.
M&L for taking down the corroded air cooled condenser and supply and fixing of new air cooled condenser suitable for 1.5 TR Split Ac
M&L for taking down complete old corroded, unserviceable window AC of 1.5 Ton capacity and depositing to MES Store and supply and fixing a new window AC of 1.5 Cpacity
M&L for complete carryout the servicing to Split/ Window type AC’s including taking down from the position, dismantling the sheet metal parts, blowing out the dust, carryout the chemical cleaning to chocked cooling coil & condenser coil, by spray the dilated chemical cleaning agent, till remove complete chocking, flushing across the coils, cleaning all the sheet metal parts, filter, grill and fixing all the dismantled parts with sheet metal screws, lubricating the fan motor bush / bearing, checking all the electrical connections, renew any burned legs / clip and fixing back to position and testing.(Note: Gas Charging if required will be measured and paid seperately).
Supply and charging refrigerant R-22 complete one time for topping up or making full qty including plugging the leakage complete and as directed.
Supply and charging the refrigerator gas R-134A / R-34A /R-407/any environmental friendly refrigerant gas complete all as specified and as directed.
Supply and charging compressor oil suitable for AC's, water cooler ,Refrigerator and deep freezer complete including testing etc, complete all as specified and as directed.
Removing the old paint of the body of refrigerator of any capacity and making the body dent proof and preparing the surface and Painting the refrigerator with 2 coats of synthetic enameled paint of superior quality to match with existing paint with spray painting complete all as specified and directed.
S&F in replacement of existing UNSV sealed Compressor unit for Refrigerator of capacity 165 to 185 Ltrs including Gas charging.
S&F in replacement of existing UNSV sealed Compressor unit for Refrigerator of capacity 285 to 320 Ltrs including Gas charging.
S&F in replacement of existing UNSV cooling Thermostat switch suitable for refrigerator/deep freezer of any capacity.
Dismatling, repairing & refixing of of the following damaged/burnt components with new components of 48V DC 150 Amps SMPS power plant including testing complete all as specifed and directed by Engr-in-Charge.
SMPS controller with its daughter cards
48V SMPS modules
Control supply
Surge protection cartridge
Note: In case the tenderer quotes different rates for similar item then lowest rate shall only be applicable for payment and contractor shall not have any claim on this account.
GEE EMM ASSOCIATES
Standard engineers
P S BUILDERS
JAI DURGA CONSTRUCTION CO
R K ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .