| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.7 LAccepted-Finance | L1 | Accepted-Finance Being lowest | |
| 2 | L2₹38.2 L+₹1.5 L (4.04%)Rejected-Finance | L2 | Rejected-Finance not being lowest | |
| 3 | L3₹39.7 L+₹3.0 L (8.22%)Rejected-Finance | L3 | Rejected-Finance not being lowest | |
| 4 | L4₹39.8 L+₹3.0 L (8.31%)Rejected-Finance 24 25 MANGAL ARCADE TELCO ROAD OPP HOTEL DOUBLE TREE MOHAN NAGAR CHINCHWAD PUNE 411019 | PUNE | MAHARASHTRA | 411019 | L4 | Rejected-Finance not being lowest | |
| 5 | L5₹43.7 L+₹7.0 L (19.1%)Rejected-Finance OFFICE NO 101 MALAN PLAZA NEXT TO ESSAR PETROL PUMP NEAR GODAMBLE CORNER RAHATNI PIMPRI DP ROAD RAHATANI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | L5 | Rejected-Finance not being lowest |
Tender Value
₹47.1 L
EMD Value
₹94,160
Closing Date
3 Jan 2023, 6:00 pmClosed
Garrison Engineer (CME) Kirkee
Garrison Engineer (CME) Kirkee, Phugewadi, Dapodi, Kendriya vidyalay Gate , beside Unlimited (Mega Mart) Mall, Pune - 411 012
Special repair for conversion of overhead conductors to underground electric cables near Meena cycle shop to JCOs Md accn at CME
2022_MES_565327_2
8377/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer (CME) Kirkee
Class D, category b(i)
9 documents required · 9 mandatory
₹500
Yes
Garrison Engineer (CME) Kirkee
₹94,160
Yes
9 Jan 2023
19 Dec 2022
5 Jan 2023
19 Dec 2022
3 Jan 2023
20 Dec 2022
Amount
Dismantling of old unsv ACSR/AAC conductor and keep in setting aside for credit complete all as specified and directed.
Dismantling cross-arms of MS channel or angle sections etc complete and setting aside for credit complete all as specified and directed.
Dismantling insulator any type and size and setting aside for credit complete all as specified and directed.
Dismantling steel poles/struts any size and setting aside for credit complete all as specified and directed.
Dismantling and taking down HPSV/HPMV/CFL street light fittings of any size and setting aside for credit complete all as specified and directed.
Dismantling and taking out old unsv XLPE cable any size alongwith DWC pipe and setting aside for credit complete all as specified and directed.
Dismantling stay assembly complete(demolition of concrete etc and removing old material from site for taking credit.
M & L and erect in true vertical position steel tubular swaged poles complete with MS base plate of 6 mm thick of size 300 mm x 300 mm, finial taper plug, pole cap, bolts, nuts and washers and screwed pole made out of FRW MS tubing conforming to IS-2713 (Part-II) 1980 type 410-SP-31 ( 9 metres long ) pole including drilling of holes of required size and Nos for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embeded in concrete, etc complete all as specified and directed. .
Supply, laying connecting and testing cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured , electric power cables ( heavy duty) with stranded aluminium conductor 1100 volts grade in trenches/ passing through pipe/fixing on walls, floors etc incl using suitable clamp of cross sectional area 4 core 25 Sqmm all as specified and directed.
All as per item No. 9 above, but of the size 3.5 core 35 Sqmm
All as per item No. 9 above, but of the size 3.5 core 70 Sqmm
All as per item No. 9 above, but of the size 3.5 core 120 Sqmm
All as per item No. 9 above, but of the size 3.5 core 150 Sqmm
All as per item No. 9 above, but of the size 3.5 core 185 Sqmm
All as per item No. 9 above, but of the size 3.5 core 240 Sqmm
All as per item No. 9 above, but of the size 3.5 core 300 Sqmm
Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 50 mm and inner dia 38 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable incl couplers & bends complete all as specified and directed.
Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 90 mm and inner dia 76 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable incl couplers & bends complete all as specified and directed.
Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 120 mm and inner dia 103 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable incl couplers & bends complete all as specified and directed.
Excavation in trenches not exc. 1.5m wide and not exc. 1.5m deep and making good surface for laying /removing of cable and getting out in all as specified and directed by Engr-in-charge
Soft/loose soil
Hard/dense soil
Excavation in trenches exceeding 1.5m wide and not exc. 3 m in depth for pole foundation/laying cables and getting out in Soft/disintegrated rock all as specified and directed.
Returning filling in excavated soil in trenches, watering and well ramming in layers not exc. 25 cm complete all as specified and directed.
Removal of surplus excavated spoil to distance exc. 1.5 km outside the MD land and depositing where directed at a level not exc. 1.5m above the starting point all as specified and directed.
M & L PCC 1:4:8 type D2 using 40 mm graded stone aggregate for plinth blocks of LT poles etc incl fair finishing the exposed surfaces even and smooth without using extra cement including necessary form work complete all as specified & directed.
M & L PCC 1:3:6 type C1 using 20 mm graded stone aggregate for coping of poles incl fair finishing the exposed surfaces even and smooth without using extra cement including necessary form work complete all as specified & directed.
M & L for bituminous road cutting to a width of 45 cm and depth 50 cm for laying of pipe for passing of UG cables and making good with PCC (1:3:6) type C1 (using 20mm grade stone aggregate) all as specified and directed.
M & L GI tubing light grade with and including all fittings for protection of cable laid in trenches or fixing to pole ducts/road crossing/on wall with suitable size of FI clamp complete of the following sizes :-
40mm dia bore
50mm dia bore
Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.
S&F PVC insulated cable with copper condcutor 1.5 sqmm three core drawn through pole from pole junction box to street light connector and testing complete all as specified and directed.
S&F street light bracket made out of 40mm dia light grade GI pipe of 1.5 Mtr long bend to shape including pole bracket made out of MS strip 40x5 mm flat, nut bolts, washers etc and fixed on wall/pole all as specified and directed.
M & L fabrication of junction box made out of fibre material complete with TPN ,aluminium bus bar and suitable for one number MCB (SP) including one No MCB (SP) 10 Amps 240 volts with glands for incoming & out going cable including fixing of flat iron clamps of size 20x4mm on PCC/Steel tubular pole complete all as specified and directed by Engr-in-Charge.
M & L for earthing complete with GI earth plate electrode of size 60 x 60 x 0.6 cms thick burried directly in ground vertically at a depth of not less than 2.25 Mtrs below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanised iron strip 32 x 6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, 40 mm dia GI tubing light grade protection pipe upto test point, 20 mm dia GI watering pipe with funnel and wire mesh, PCC 1:3:6 type C1 earth chamber of outer dimension 54 x 54 x 30 cm and internal diamension 30 x 30 x 30 cm with RCC 1:2:4 type B1 cover of size 54 x 54 x 10cm reinforced with 6mm dia mild steel round bar @ 15cm c/c both way and 8 mm dia mild round bar handle adequate qty of charcoal dust and salt layers all around the earth plate including excavation and earth work in any type of soil, removal of surplus soil and returning filling in all as required at site all as specified in electrical plate No 3 of SSR Part-I and directed by Engr-in-Charge.
Supply, installation, testing and commissioning in replacement weather and vermin proof factory made CPRI approved LT feeder pillar box of size 1.8m x 1.5m x 0.6m (Approx), out door cubicle/KIOSK type totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm grouted in CM, 45 cm below ground level and 60 cm above ground suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and aluminium bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including connecting the following:- (SS-8)
Aluminium bus bar rectangular 600 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 4 pole 630 A thermal magnetic release, adjustable type, 36 kA - 01 No (I/C)
MCCB 4 pole 400 A thermal magnetic release adjustable type, 36 kA - 01 No (O/G for FP-269)
MCCB 4 pole 315 A thermal magnetic release, adjustable type, 36 kA- 01 No (O/G for FP-263)
MCCB 4 pole 250 A thermal magnetic release, adjustable type, 25 kA- 2 Nos (O/G for Left blocks & spare)
MCCB 4 pole 200 A thermal magnetic release, adjustable type, 25 kA- 01 No (O/G for FP-278)
MCCB 4 pole 100 A thermal magnetic release,adjustable type, 16 kA-01 No (O/G for Bopkhel gate)
MCCB 4 pole 63 A thermal magnetic release, adjustable type, 16 kA-01 No (O/G for st light)
MCCB 4 pole 32 A thermal magnetic release adjustable type, 16 kA - 01 No (O/G for SS-8 area)
Three pole Contactor 63 A Current Rating 70A General use 10A, 415V with coil - 01 No.
Digital timer switch with inbuilt backup operated on 415 volts AC 50Hz, - 01 No.
Digital volt meter 0-500 V -1 No.
Digital ammeter 0-600 Amps - 1 No.
Phase indicator lamp LED Type - 1 Set
MCB SP 6-32A - 03 No (for street light phase separation)
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, installation, testing and commissioning weather and vermin proof factory made CPRI approved LT feeder pillar box of size 1.2m x 1.0m x 0.6m (Approx), out door cubicle/KIOSK type totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm grouted in CM, 45 cm below ground level and 60 cm above ground suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and aluminium bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set, including connecting the following:- (Near Block 263)
Aluminium bus bar rectangular 500 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 4 pole 315 A thermal magnetic release, adjustable type, 36 kA- 01 No (I/C)
MCCB 4 pole 250 A thermal magnetic release, adjustable type, 25 kA- 01 Nos (O/G for FP at 267)
MCCB 4 pole 63 A thermal magnetic release, adjustable type, 16 kA-05 No (O/G for 262, 263, 264, 265 & spare)
Digital volt meter 0-500 V -1 No.
Digital ammeter 0-600 Amps - 1 No.
Phase indicator lamp LED Type - 1 Set
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, installation, testing and commissioning weather and vermin proof factory made CPRI approved LT feeder pillar box of size 1.2m x 1.0m x 0.6m (Approx), out door cubicle/KIOSK type totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm grouted in CM, 45 cm below ground level and 60 cm above round suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and aluminium bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set, including connecting the following:- (Near block 267)
Aluminium bus bar rectangular 300 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 4 pole 200 A thermal magnetic release, adjustable type, 25 kA- 01 No (I/C)
MCCB 4 pole 63 A thermal magnetic release, adjustable type, 16 kA-04 No (O/G for 266, 267, 268 & spare)
Digital volt meter 0-500 V -1 No.
Digital ammeter 0-600 Amps - 1 No.
Phase indicator lamp LED Type - 1 Set
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, installation, testing and commissioning weather and vermin proof factory made CPRI approved LT feeder pillar box of size 1.5m x 1.2m x 0.6m (Approx), out door cubicle/KIOSK type totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm grouted in CM, 45 cm below ground level and 60 cm above round suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and aluminium bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set, including connecting the following:- (Near block 269)
Aluminium bus bar rectangular 600 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 4 pole 400 A thermal magnetic release adjustable type, 36 kA - 01 No (I/C)
MCCB 4 pole 250 A thermal magnetic release, adjustable type, 25 kA- 01 Nos (O/G for FP 437)
MCCB 4 pole 200 A thermal magnetic release, adjustable type, 25 kA- 02 No (O/G for FP-435 & spare)
MCCB 4 pole 160 A thermal magnetic release,adjustable type, 16 kA-01 No (O/G for existing MAP FP)
MCCB 4 pole 63 A thermal magnetic release, adjustable type, 16 kA-02 No (O/G for 269 & 270)
Digital volt meter 0-500 V -1 No.
Digital ammeter 0-600 Amps - 1 No.
Phase indicator lamp LED Type - 1 Set
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, installation, testing and commissioning weather and vermin proof factory made CPRI approved LT feeder pillar box of size 1.8m x 1.2m x 0.6m (Approx), out door cubicle/KIOSK type totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm grouted in CM, 45 cm below ground level and 60 cm above round suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and aluminium bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set, including connecting the following:- (Near block 435)
Aluminium bus bar rectangular 300 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 4 pole 200 A thermal magnetic release, adjustable type, 25 kA- 01 No (I/C)
MCCB 4 pole 63 A thermal magnetic release, adjustable type, 16 kA-07 No (O/G for 434-2, 435-2, 639, 640 & spare)
Digital volt meter 0-500 V -1 No.
Digital ammeter 0-600 Amps - 1 No.
Phase indicator lamp LED Type - 1 Set
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, installation, testing and commissioning weather and vermin proof factory made CPRI approved LT feeder pillar box of size 1.8m x 1.2m x 0.6m (Approx), out door cubicle/KIOSK type totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm grouted in CM, 45 cm below ground level and 60 cm above round suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and aluminium bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set, including connecting the following:- (Near block 437)
Aluminium bus bar rectangular 400 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 4 pole 250 A thermal magnetic release, adjustable type, 25 kA- 01 No (I/C)
MCCB 4 pole 63 A thermal magnetic release, adjustable type, 16 kA-10 No (O/G for 436-2, 437-2, 438-2, 439-2, 440 and spare)
Digital volt meter 0-500 V -1 No.
Digital ammeter 0-600 Amps - 1 No.
Phase indicator lamp LED Type - 1 Set
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, installation, testing and commissioning in replacement weather and vermin proof factory made CPRI approved LT feeder pillar box of size 1.8m x 1.5m x 0.6m (Approx), out door cubicle/KIOSK type totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm grouted in CM, 45 cm below ground level and 60 cm above round suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and aluminium bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set, including connecting the following:- (SS-11)
Aluminium bus bar rectangular 800 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 4 pole 630 A thermal magnetic release, adjustable type, 36 kA - 01 No (I/C)
MCCB 4 pole 250 A thermal magnetic release, adjustable type, 25 kA- 03 Nos (O/G for FP-481, 454 & 453)
MCCB 4 pole 200 A thermal magnetic release, adjustable type, 25 kA- 03 Nos (O/G for FP-477, 479 & spare)
MCCB 4 pole 63 A thermal magnetic release, adjustable type, 16 kA-01 No (O/G for st light)
MCCB 4 pole 32 A thermal magnetic release adjustable type, 16 kA - 01 No (O/G for SS-11 area)
Three pole Contactor 63 A Current Rating 70A General use 10A, 415V with coil - 01 No.
Digital timer switch with inbuilt backup operated on 415 volts AC 50Hz, - 01 No.
Digital volt meter 0-500 V -1 No.
Digital ammeter 0-600 Amps - 1 No.
Phase indicator lamp LED Type - 1 Set
MCB SP 6-32A - 03 Nos. (for street light phase separation)
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Supply, installation, testing and commissioning weather and vermin proof factory made CPRI approved LT feeder pillar box of size 1.5m x 1.0m x 0.6m (Approx), out door cubicle/KIOSK type totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm grouted in CM, 45 cm below ground level and 60 cm above round suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and aluminium bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set, including connecting the following:- (Near block 481)
Aluminium bus bar rectangular 400 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job
MCCB 4 pole 250 A thermal magnetic release, adjustable type, 25 kA- 01 No (I/C)
MCCB 4 pole 63 A thermal magnetic release, adjustable type, 16 kA-8 No (O/G for 448, 449, 450, 481, 482, 483, 484 & spare)
Digital volt meter 0-500 V -1 No.
Digital ammeter 0-600 Amps - 1 No.
Phase indicator lamp LED Type - 1 Set
Provision of cubicle to accommodate the above mentioned accessories.
Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable.
Techmat trading solution
Priyanka Power line
metro electrical services
M/S. Niksun Electro-Infra Private Limited
N AND G CONSTRUCTION
N D ELECTRICAL
Mahindra Electric Stores
Prasur Electricals & Engineering Co.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .