Loading…
Loading…
| # | Company | Amount |
|---|---|---|
| 1 | ₹36.4 Cr BONAGUND VERINAG ANANTNAG J K 192212 | ₹36.4 Cr |
Tender Value
₹48.3 Cr
EMD Value
₹48.3 L
Closing Date
21 Apr 2025, 11:00 amClosed
Construction of Boys and Girls Hostel and Male and Female Technician Accommodation at SMVDIME Kakryal, Katra, UT of J and K on PMC mode
NBCC/CPG/SMVDIME/KATRA/476
NBCC/CPG/SMVDIME/KATRA/476
Open Tender-Domestic
Civil Works General
Prayagraj, Uttar Pradesh
₹59,000
₹48.3 L
28 Mar 2025
28 Mar 2025
21 Apr 2025
21 Apr 2025
19 May 2025
S. NO. DESCRIPTION AMOUNT ( DSR ) AMOUNT (NON-DSR)
1 STRUCTURE WORK
CONCRETE WORK Rs. 19,33,233.53 Rs. 0.00 Rs. 19,33,233.53
REINFORCED CEMENT CONCRETE Rs. 24,39,99,527.15 Rs. 0.00 Rs. 24,39,99,527.15
MARBLE & GRANITE WORK Rs. 86,28,190.62 Rs. 0.00 Rs. 86,28,190.62
3 ELECTRICAL WORKS
SUBSTATION EQUIPMENTS Rs. 0.00 Rs. 18,67,785.80 Rs. 18,67,785.80
EARTHING INSTALLATION Rs. 0.00 Rs. 26,62,808.00 Rs. 26,62,808.00
LT CUM DG CHANGE OVER PANEL, MAIN DISTRIBUTION
EARTHING AND LIGHTINING PROTECTION INSTALLATION Rs. 11,92,415.36 Rs. 0.00 Rs. 11,92,415.36
WIRING IN STEEL AND PVC CONDUIT Rs. 93,60,425.60 Rs. 0.00 Rs. 93,60,425.60
LIGHTING FIXTURE AND FANS Rs. 0.00 Rs. 1,88,37,910.00 Rs. 1,88,37,910.00
EXTERNAL LIGHTING SYSTEM Rs. 0.00 Rs. 14,85,808.00 Rs. 14,85,808.00
FIRE ALARM SYSTEM Rs. 18,67,822.00 Rs. 13,800.00 Rs. 18,81,622.00
PUBLIC ADDRESS SYSTEM Rs. 5,28,740.00 Rs. 3,57,569.06 Rs. 8,86,309.06
CCTV (IP VIDEO SURVEILLANCE) SYSTEM Rs. 4,09,360.00 Rs. 54,17,120.00 Rs. 58,26,480.00
DATA , VOICE SYSTEMS Rs. 42,180.00 Rs. 52,936.00 Rs. 95,116.00
SMOKE EXTRACTION SYSTEM Rs. 0.00 Rs. 14,58,192.00 Rs. 14,58,192.00
SANITARY FIXTURES & FITTINGS Rs. 61,78,382.35 Rs. 5,35,600.00 Rs. 67,13,982.35
INTERNAL & EXTERNAL WATER SUPPLY Rs. 26,68,722.38 Rs. 3,26,528.00 Rs. 29,95,250.38
SOIL, WASTE, VENT PIPES & FITTINGS FOR INTERNAL Rs. 7,06,296.80 Rs. 8,14,236.00 Rs. 15,20,532.80
STROM WATER PIPES & FITTINGS Rs. 8,41,513.40 Rs. 7,10,466.00 Rs. 15,51,979.40
EXTERNAL SEWERAGE SYSTEM Rs. 5,26,299.20 Rs. 4,57,490.38 Rs. 9,83,789.58
5 FIRE FIGHTING
FIRE PUMP & PIPE & ACESSERIES Rs. 19,48,249.00 Rs. 9,49,000.00 Rs. 28,97,249.00
Multiplication factor for modified Analysis of Rate @0.973 on
Grand Total (DSR+NDSR) Rs. 48,28,90,399.61
Grand Total (DSR+NDSR) Rs. 48,28,90,399.61
TOTAL COST OF BOQ (DSR/NON DSR) Rs. 48,28,90,400.00
Digitally signed by ANUJ
Construction of Boys & Girls Hostel and Male& Female Technician Accommodation at SMVDIME Kakryal, Katra, UT
BILL OF QUANTITY
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Earth work in excavation by mechanical means (Hydraulic excavator)
over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10
2.6 sqm on plan) including getting out and disposal of excavated earth
lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge.
Filling available excavated earth (excluding rock) in trenches, plinth,
sides of foundations etc. in layers not exceeding 20cm in depth,
consolidating each deposited layer by ramming and watering, lead up
to 50 m and lift upto 1.5 m.
Supplying and filling in plinth with sand under floors, including
watering, ramming, consolidating and dressing complete.
Supplying chemical emulsion in sealed containers including delivery
2.34.1 Chlorpyriphos/ Lindane emulsifiable concentrate of 20% Litre 501.16 234.75 117647.31
Diluting and injecting chemical emulsion for PRE
2.35 CONSTRUCTIONAL anti-termite treatment (excluding the cost of
chemical emulsion) :
Treatment of soil under existing floors using chemical emulsion @
one litre per hole, 300 mm apart including drilling 12 mm diameter
holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse
sand) to match the existing floor:
2.35.3.1 With Chlorpyriphos/Lindane E.C. 20% with 1% concentration Sqm 2004.64 310.05 621538.63
4 CONCRETE WORK
Providing and laying in position cement concrete of specified grade
4.1 excluding the cost of centering and shuttering - All work up to plinth
1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural
4.1.8 sources : 8 graded stone aggregate 40 mm nominal size derived Cum 225.38 6812.00 1535292.74
from natural sources)
Making plinth protection 50mm thick of cement concrete 1:3:6 (1
cement : 3 coarse sand (zone-III) derived from natural sources : 6
graded stone aggregate 20 mm nominal size derived from natural
4.17 sources) over 75mm thick bed of dry brick ballast 40 mm nominal Sqm 531.08 749.30 397940.79
size, well rammed and consolidated and grouted with fine sand,
including necessary excavation, levelling & dressing & finishing the
5 REINFORCED CEMENT CONCRETE
Centering and shuttering including strutting, propping etc. and
removal of form for
5.9.1 Foundations, footings, bases of columns, etc. for mass concrete Sqm 5569.20 392.15 2183961.78
Walls (any thickness) including attached pilasters, butteresses, plinth
and string courses etc.
5.9.3 Suspended floors, roofs, landings, balconies and access platform Sqm 18753.71 927.25 17389379.98
5.9.4 Shelves (Cast in situ) Sqm 256.02 927.25 237394.55
5.9.5 Lintels, floor beams, girders, bressumers and cantilevers Sqm 14506.33 736.40 10682462.56
5.9.6 Columns, Pillars, Piers, Abutments, Posts and Struts Sqm 9270.35 961.30 8911588.99
5.9.7 Stairs, (excluding landings) except spiral-staircases Sqm 1131.08 208.55 235886.75
5.9.16 Edges of slabs and breaks in floors and walls
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Steel reinforcement for R.C.C. work including straightening, cutting,
5.22 bending, placing in position and binding all complete upto plinth level.
5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. Kg 271849.44 107.85 29318962.57
Steel reinforcement for R.C.C. work including straightening, cutting,
5.22A bending, placing in position and binding all complete above plinth
5.22A.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. Kg 863399.31 107.85 93117615.12
Providing and laying in position ready mixed or site batched design
mix cement concrete for reinforced cement concrete work; using
coarse aggregate and fine aggregate derived from natural sources,
Portland Pozzolana / Ordinary Portland /Portland Slag cement,
admixtures in recommended proportions as per IS: 9103 to
5.33 accelerate / retard setting of concrete, to improve durability and
workability without impairing strength; including pumping of concrete
to site of laying, curing, carriage for all leads; but excluding the cost of
centering, shuttering, finishing and reinforcement as per direction of
the engineer-in-charge; for the following grades of concrete.
Note: Extra cement up to 10% of the minimum specified cement
content in design mix shall be payable separately. In case the
cement content in design mix is more than 110% of the specified
minimum cement content, the contractor shall have discretion to
either re-design the mix or bear the cost of extra cement.
5.33.1 All works upto plinth level.
Concrete of M25 grade with minimum cement content of 330 kg /cum
Concrete of M30 grade with minimum cement content of 350 kg /cum
5.33.2 All works above plinth level.
Concrete of M25 grade with minimum cement content of 330 kg /cum
Concrete of M30 grade with minimum cement content of 350 kg /cum
Add for using extra cement in the items of design Mix over ans avove
the specified cement content therein
Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each
four floors or part thereof.
Total Structural Work 248006974.73 0.00
6.0 BRICK WORK
Brick work with common burnt clay F.P.S. (non modular) bricks of
class designation 7.5 in foundation and plinth in:
6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 40.00 7132.25 285290.00
Brick work with common burnt clay F.P.S. (non modular) bricks of
6.4 class designation 7.5 in superstructure above plinth level up to floor
V level in all shapes and sizes in :
6.4.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 321.26 9105.95 2925355.69
Half brick masonry with common burnt clay F.P.S. (non modular)
6.12 bricks of class designation 7.5 in foundations and plinth in :
6.12.2 Cement mortar 1:4 (1 cement : 4 coarse sand) Sqm 40.00 905.05 36202.00
Half brick masonry with common burnt clay F.P.S. (non modular)
6.13 bricks of class designation 7.5 in superstructure above plinth level up
to floor V level.
6.13.2 Cement mortar 1:4 (1 cement :4 coarse sand) Sqm. 334.74 1123.80 376181.32
Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars
at every third course of half brick masonry.
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Providing and laying autoclaved aerated cement blocks masonry with
100/125 mm thick AAC blocks in super structure above plinth level
6.38 up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). Cum 600.42 10195.45 6121514.83
The rate includes providing and placing in position 2 Nos 6 mm dia
M.S. bars at every third course of masonry work.
Providing and laying autoclaved aerated cement blocks masonry with
150mm/230mm/300 mm thick AAC blocks in super structure above
plinth level up to floor V level with RCC band at sill level and lintel
6.47 level with approved block laying polymer modified adhesive mortar all Cum 1961.08 8333.65 16342980.74
complete as per direction of Engineer-in-Charge. (The payment of
RCC band and reinforcement shall be made for seperately).
8.0 MARBLE & GRANITE WORK
Providing and fixing 18 mm thick gang saw cut, mirror polished,
premoulded and prepolished, machine cut for kitchen platforms,
vanity counters, window sills, facias and similar locations of required
size, approved shade, colour and texture laid over 20 mm thick base
8.2 cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with
white cement, mixed with matching pigment, epoxy touch ups,
including rubbing, curing, moulding and polishing of edges to give
high gloss finish etc. complete at all levels.
8.2.2 Granite stone slab of colour black, Cherry/Ruby red
Providing edge moulding to 18 mm thick marble stone counters,
Vanities etc., including machine polishing to edge to give high gloss
finish etc.complete as per design approved by Engineer-in-Charge.
8.3.2 Granite work Metre 460.93 510.95 235514.23
Extra for fixing marble /granite stone, over and above corresponding
basic item, in facia and drops of width upto 150 mm with epoxy resin
based adhesive, including cleaning etc. complete.
Extra for providing opening of required size & shape for wash basin/
kitchen sink in kitchen platform, vanity counter and similar location in
8.5 marble/ Granite/ stone work, including necessary holes for pillar taps Each 196.00 978.70 191825.20
etc. including moulding, rubbing and polishing of cut edges etc.
Providing and fixing rubbed stone slab table, edges rounded and
polished, 75 cm high 50 cm deep and 18mm thick, fixed in urinal
partitions by cutting a chase of appropriate width with chase cutter
8.10 and embedding the stone in the chase with epoxy grout or with
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 6 mm nominal size) as per direction of Engineer-in-charge
and finished smooth.
8.10.2 Granite Stone of approved shade Sqm 8.10 4051.85 32819.99
Providing and fixing Ist quality ceramic glazed wall tiles conforming to
IS: 15622 (thickness to be specified by the manufacturer), of
approved make, in all colours, shades except burgundy, bottle green,
black of any size as approved by Engineer-in-Charge, in skirting,
8.31 risers of steps and dados, over 12 mm thick bed of cement mortar Sqm 5289.84 1267.95 6707254.91
1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry
@ 3.3kg per sqm, including pointing in white cement mixed with
pigment of matching shade complete.
9.0 WOOD & PVC WORK
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Providing and fixing ISI marked flush door shutters conforming to IS :
2202 (Part I) nondecorative type, core of block board construction
9.21 with frame of 1st class hard wood and well matched commercial 3 ply
veneering with vertical grains or cross bands and face veneers on
both faces of shutters:
35 mm thick including ISI marked Stainless Steel butt hinges with
necessary screws
Extra for providing lipping with 2nd class teak wood battens 25 mm
9.23 minimum depth on all edges of flush door shutters (over all area of Sqm 1656.69 462.35 765970.62
door shutter to be measured).
Extra for providing vision panel not exceeding 0.1 sqm in all type of
9.24 flush doors (cost of glass excluded) (overall area of door shutter to
9.24.1 Rectangular or square Sqm 95.76 199.15 19070.60
Providing and fixing aluminium extruded section body tubular type
universal hydraulic door closer (having brand logo with ISi, IS : 3564,
9.84 embossed on the body, door weight upto 36 kg to 80 kg and door Each 830.00 983.15 816014.50
width from 701 mm to 1000 mm), with double speed adjustment with
necessary accessories and screws etc. complete.
Providing and fixing aluminium tower bolts, ISI marked, anodised
(anodic coating not less than grade AC 10 as per IS : 1868 )
transparent or dyed to required colour or shade, with necessary
screws etc. complete :
Providing and fixing aluminium handles, ISI marked, anodised
(anodic coating not less than grade AC 10 as per IS : 1868)
transparent or dyed to required colour or shade, with necessary
screws etc. complete :
Providing and fixing aluminium hanging floor door stopper, ISI
marked, anodised (anodic coating not less than grade AC 10 as per
IS : 1868) transparent or dyed to required colour and shade, with
necessary screws etc. complete.
9.101.1 Single rubber stopper Each 830.00 39.60 32868.00
Providing and fixing bright finished brass 100 mm mortice latch and
lock, ISI marked, with six levers and a pair of anodised (anodic
9.103 coating not less than grade AC 10 as per IS : 1868) aluminium lever Each 794.00 868.95 689946.30
handles of approved quality with necessary screws etc. complete.
Providing & Fixing decorative high pressure laminated sheet of plain /
wood grain in gloss / matt/ suede finish with high density protective
9.127 surface layer and reverse side of adhesive bonding quality
conforming to IS : 2046 Type S, including cost of adhesive of
approved quality.
Providing and fixing fire resistant door frame of section 50 x 60 mm
on horizontal side & 35 x 60 mm on vertical sides having built in
rebate made out of 1.6 mm thick GI sheet ( Zinc coating not less than
120gm/sqm) suitable for mounting 120 minutes Fire Rated Glazed
Door Shutters. The frame shall be filled with mineral wool Insulation
having density minimum 96Kg/sqm . The frame will have a provision
of G.I. anchor fastners 14 nos ( 5 each on vertical style & 4 on
9.161 horizontal style of size M10 x 80 ) suitable for fixing in the opening meter 467.00 2202.9 1028754.30
along with factory made template for SS ball bearing hinges of Size
100x89x3mm for fixing of fire rated glazed shutter . The frame shall
be finished with a approved fire resistant primer or powder coating of
not less than 30 micron in desired shade as per the directions of
Engineer - in- Charge . (Cost of SS ball bearing hinges is excluded).
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Providing and fixing 60 mm thick glazed fire resistant door shutters of
120 minutes Fire rating conforming to IS:3614 (Part II) or EN1634-
1:1999, tested and certified as per laboratory approved by Engineer-
in-Charge, with suitable mounting on door frame, consisting of
vertical styles, top rail & side rail 60 mm x 60 mm wide and bottom
rail of 110 mm x 60 mm made out of 1.6mm thick G.I. sheet (zinc
9.162 coating not less than 120gm/sqm) duly filled mineral wool insulation Sqm 204.54 12017.9 2458141.27
having density minimum 96 kg/cum and fixing with necessary
stainless steel ball bearing hinges of size 100x89x3mm of approved
make, including applying a coat of approved fire resistant primer or
powder coating not less than 30 micron etc all complete as per
direction of Engineer-in-Charge (panelling to be paid for seperately).
FIXTURES FOR FIRATED DOORS
Supply & fixing of SS 304 grade Ball Bearing Hinges of size 100 x 75
MRF-1 x 3mm complete with SS Screws ( 4 Nos per panel ) Each 456.00 340.00 155040.00
Supply & fixing SS Touch Type / PHA2000 Series SS Touch type
Panic Bar single / double leaf panic exit devices. (Required For Fire
Staircase & Lift Lobby Location Doors ) as per the directions of
Engineer-in-charge
Double Leaf Panic Bar Set Each 90.00 19500.00 1755000.00
MRF-3 Supply and Fixing of intumescent fire seal of size 10x4mm Rmt. 467.00 150.00 70050.00
MRF-4 Supply and Fixing of face mounted Smoke seal Rmt. 467.00 140.00 65380.00
Supply and Filling the gap between wall & Door frame by using
silicone sealant and Wool insulaion on both side of the door
Supply & fixing of Door Closers Size 2-5 with sliding arm BLC 605 (
Except shaft door)
MRF-7 Supply & fixing of anchor fastners of M10X120mm length. Set 126.00 90.00 11340.00
Providing and fixing factory made single extruded WPC (Wood
Polymer Composite) solid door/window/Clerestory windows & other
Frames/Chowkhat comprising of virgin PVC polymer of K value 58-
60 (Suspension Grade), calcium carbonate and natural fibers (wood
powder/ rice husk/wheat husk) and non toxic additives (maximum
toxicity index of 12 for 100 gms) fabricated with miter joints after
applying PVC solvent cement and screwed with full body threaded
star headed SS screws having minimum frame density of 750
26.86 kg/cum, screw withdrawal strength of 2200 N (Face) & 1100 N
(Edge), minimum compressive strength of 58 N/mm2, modulus of
elasticity 900 N/mm2 and resistance to spread of flame of Class A
category with property of being termite/borer proof, water/moisture
proof and fire retardant and fixed in position with M.S hold
fast/lugs/SS dash fasteners of required dia and length complete as
per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash
fasteners shall be paid for separately).
Note: For WPC solid door/window frames, minus 5mm tolerance in
dimensions i.e depth and width of profile shall be acceptable.
Variation in profile dimensions on plus side shall be acceptable but
no extra payment on this account shall be made.
10.0 STEEL WORK
Steel work welded in built up sections/ framed work, including cutting,
10.25 hoisting, fixing in position and applying a priming coat of approved
steel primer using structural steel etc. as required.
In stringers, treads, landings etc. of stair cases, including use of
chequered plate wherever required, all complete
In gratings, frames, guard bar, ladder, railings, brackets, gates and
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
11.0 FLOORING WORK
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate) finished with a floating coat of neat cement,
including cement slurry, but excluding the cost of nosing of steps etc.
11.3.1 40 mm thick with 20 mm nominal size stone aggregate Sqm 20.00 614.20 12284.00
Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1
11.6 cement : 3 coarse sand), finished with a floating coat of neat cement.
Kota stone slab flooring over 20 mm (average) thick base laid over
and jointed with grey cement slurry mixed with pigment to match the
11.26 shade of the slab, including rubbing and polishing complete with
base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and
pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3
11.27 coarse sand) and jointed with grey cement slurry mixed with pigment Sqm 411.85 2354.70 969777.88
to match the shade of the slabs, including rubbing and polishing
11.24 Extra for pre finished nosing to treads of steps of marble stone. Meter 1536.00 719.90 1105766.40
Extra for marble stone flooring in treads of steps and risers using
single length up to 2.00 metre.
Providing and laying Ceramic glazed floor tiles of size 300x300 mm
(thickness to be specified by the manufacturer) of 1st quality
conforming to IS : 15622 of approved make in colours such as
11.37 White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement Sqm 1435.40 1096.55 1573985.02
mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement
slurry @ 3.3 kg/sqm including pointing the joints with white cement
and matching pigment etc., complete
Providing & Laying vitrified floor tiles in different sizes ( thickness to
be specified by the manufacturer) with water absorption's less than
0.08% and confirming to IS : 15622 of approved make in all colours
and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4
coarse sand) including grouting the joints with white cement and
matching pigments etc, complete.
Providing and laying Vitrified tiles in different sizes (thickness to be
specified by manufacturer), with water absorption less than 0.08 %
and conforming to I.S. 15622, of approved make, in all colours &
11.46 shade, in skirting, riser of steps, over 12 mm thick bed of cement
mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with
white cement & matching pigments etc. complete..
Grouting the joints of flooring tiles having joints of 3 mm width, using
epoxy grout mix of 0.70 kg of organic coated filler of desired shade
11.48.2 (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / Sqm 9801.63 309.05 3029194.93
grouting and finishing complete as per direction of Engineer-
incharge. Size of Tile 600x600 mm
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2
coarse sand : 4 stone aggregate 10 mm and down gauge), including
finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per
standard design :
Making khurras 45x45 cm with average minimum thickness of 5 cm
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400
micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse
sand) and a coat of neat cement, rounding the edges and making
and finishing the outlet complete.
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm
x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70
and initial emittance > 0.75 on waterproof and sloped surface of
terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1
12.55 cement : 4 coarse sand) and grouting the joints with mix of white Sqm 1936.39 1703.95 3299511.74
cement & marble powder in ratio of 1:1, including rubbing and
polishing of the surface upto 3 cuts complete, including providing
skirting upto 150 mm height along the parapet walls in the same
13.0 FINISHING WORK
13.4 12 mm cement plaster of mix :
15 mm cement plaster on rough side of single or half brick wall of
13.6 20 mm cement plaster of mix :
13.16 6 mm cement plaster of mix :
Extra for plastering exterior walls of height more than 10 m from
ground level for every additional height of 3 m or part thereof.
Providing and applying plaster of paris putty of 2 mm thickness over
13.26 plastered surface toprepare the surface even and smooth complete. Sqm 10459.90 262.70 2747814.91
Distempering with 1st quality acrylic distemper (ready mixed) having
VOC content less than 50 gram/litre, of approved manufacturer and
of required shade and colour all complete to achieve even shade and
New work (two or more coats) over and including water thinnable
13.41.1 priming coat with cement primer having VOC content less than 50 Sqm 5110.75 185.65 948810.25
13.45 Finishing walls with textured exterior paint of required shade :
New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and
13.45.1 including priming coat of exterior primer applied @ 2.20kg/10 sqm Sqm 13303.53 223.60 2974668.28
Painting with synthetic enamel paint of approved brand and
anufacture to give an even shade :
13.61.1 Two or more coats on new work Sqm 78.19 155.90 12189.46
Providing and applying white cement based putty of average
thickness 1 mm, of approved brand and manufacturer, over the
plastered wall surface to prepare the surface even and smooth
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Wall painting with premium acrylic emulsion paint of interior grade,
having VOC (Volatile Organic Compound ) content less than 50
13.82 grams/ litre of approved brand and manufacture, including applying
additional coats wherever required to achieve even shade and
21.0 ALUMINIUM WORK
Providing and fixing aluminium work for doors, windows, ventilators
and partitions with extruded built up standard tubular sections/
appropriate Z sections and other sections of approved make
conforming to IS: 733 and IS: 1285, fixing with dash fasteners of
required dia and size, including necessary filling up the gaps at
junctions, i.e. at top, bottom and sides with required EPDM rubber/
21.1 neoprene gasket etc. Aluminium sections shall be smooth, rust free,
straight, mitred and jointed mechanically wherever required including
cleat angle, Aluminium snap beading for glazing / paneling, C.P.
brass / stainless steel screws, all complete as per architectural
drawings and the directions of Engineer-in-charge. (Glazing, paneling
and dash fasteners to be paid for separately) :
21.1.1 For fixed portion
Powder coated aluminium (minimum thickness of powder coating 50
For shutters of doors, windows & ventilators including providing and
fixing hinges/ pivots and making provision for fixing of fittings
wherever required including the cost of EPDM rubber / neoprene
gasket required (Fittings shall be paid for separately)
Powder coated aluminium (minimum thickness of powder coating 50
Providing and fixing glazing in aluminium door, window, ventilator
shutters and partitions etc. with EPDM rubber / neoprene gasket
21.3 etc. complete as per the architectural drawings and the directions of
engineer-in-charge . (Cost of aluminium snap beading shall be paid
in basic item):
With float glass panes of 5 mm thickness (weight not less than 12.50
Filling the gap in between aluminium frame and adjacent
RCC/Brickwork/ Stone Work by providing weather silicon sealant
over backer rod of approved quality as per architectural drawings
and direction of Engineer-in-charge
21.8.1 Upto 5mm depth and 5mm width Metre 4107.50 96.75 397400.63
22.0 WATER PROOFING
Providing and laying water proofing treatment to vertical and
22.3 horizontal surfaces of depressed portions of W.C., kitchen and the
like consisting of :
(i) Ist course of applying cement slurry @ 4.4 Kg/sqm mixed with
water proofing compound conforming to IS 2645 in recommended
proportions including rounding off junction of vertical and horizontal
surface. (ii) IInd course of 20mm cement plaster 1:3 (1 cement : 3
coarse sand) mixed with water proofing compound in recommended
proportion including rounding off junction of vertical and horizontal Sqm 1666.34 769.60 1282417.57
surface. (iii) IIIrd course of applying blown or residual bitumen applied
hot at 1.7 Kg. per sqm of area. (iv) IVth course of 400 micron thick
PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide
and pasted to each other with bitumen @ 1.7 Kg/sqm.)
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Providing and laying integral cement based water proofing treatment
including preparation of surface as required for treatment of roofs,
balconies, terraces etc consisting of following operations: (a)
Applying a slurry coat of neat cement using 2.75 kg/sqm of cement
admixed with water proofing compound conforming to IS. 2645 and
approved by Engineer-in-charge over the RCC slab including
adjoining walls upto 300 mm height including cleaning the surface
before treatment. (b) Laying brick bats with mortar using broken
22.7 bricks/brick bats 25mm to 115 mm size with 50% of cement mortar
1:5 (1 cement : 5 coarse sand) admixed with water proofing
compound conforming to IS : 2645 and approved by Engineer-in-
charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement
:5 coarse sand ) admixed with water proofing compound conforming
to IS : 2645 and approved by Engineer-in-charge to required slope
and treating similarly the adjoining walls upto 300 mm height
including rounding of junctions of walls and slabs.
(c) After two days of proper curing applying a second coat of cement
slurry using 2.75 kg/ sqm of cement admixed with water proofing
compound conforming to IS : 2645 and approved by Engineerin-
charge. (d) Finishing the surface with 20 mm thick jointless cement
mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water
proofing compound conforming to IS : 2645 and approved by
Engineerin-charge including laying glass fibre cloth of approved
quality in top layer of plaster and finally finishing the surface with
trowel with neat cement slurry and making pattern of 300x300 mm
square 3 mm deep. (e) The whole terrace so finished shall be
flooded with water for a minimum period of two weeks for curing and
for final test.“All above operations to be done in order and as directed
and specified by the Engineer-in-Charge :
With average thickness of 120 mm and minimum thickness at khurra
Sunken area filling - Providing and laying on sunken areas broken
light weight concrete block bats of approximately 600 kg. per Cum
density laid, consolidated, finished smooth, including finishing &
MRW-01 grouting the top layer with 20 mm thick water proof cement mortar (1: Cum 81.96 7500.00 614666.25
4 ratio, 1 cement: 4 Sand) with CICO and as per specifications and
TOTAL CIVIL WORK 149210579.43 3683976.25
SUPPLY, INSTALLATION, TESTNG & COMMISSIONING OF SUB-
STATION EQUIPMENT
The rates under this section shall also include:
Supporting rigid frame work.
2 mm thick MS housing complete with dust and vermin proof covers
and lockable doors as called for.
All fixing accessories such as foundation bolts, nuts and bolts etc as
Touching up all damaged paint with approved paint shade.
All protection relays shall be numerical type
Compliance of technical specifications.
SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF SUB-
STATION EQUIPMENT
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supplying and erection of H Beam 13 Mtr Long 152x152 or 150x150
mm 37.1 Kg/Mtr. weight M.S. Pole complete with aligning and
keeping it in truly vertical position, including digging pit of required
size in all type of soil/rocks filling with 1:3:6 cement concrete of 0.60
mtr. dia. around the pole up to ground level including muffing of 0.45
mtr. dia. from ground level to 0.45 mtr. high as per specifications with
20 cm. thick base foundation in 1:4:8 cement concrete as
required refilling the pit with boulder and soil as required,
including painting of pole with bitumen paint below GL and two coats
of red oxide and two coats of aluminium paint or synthetic enamel
paint above GL as directed complete as per specification. The depth
of burying of pole shall be 1/6th of the length of .-2
Supplying and fixing of angle / channel / flat iron / RS Joist fittings for
over head lines as cross arms / brackets / clamps etc. including nut
bolts, required holes, welding, cutting, fabricating with necessary
materials including two coats of red oxide and two coats of
aluminium or synthetic enamel paint etc. as required.
Supplying and erection of 16mm dia 1.8 m long with 7/3.15mm stay
wire set complete with stay rod, anchor plate of size 300x300x5mm,
thimble, stay clamp, turn buckle, bow tightener etc. with stay wire,
NSR-3 strain insulator, nut bolts as per specifications including excavation in Each 16.00 1394.00 22304.00
all type of soil/ rocks and foundation in cement concrete 1:3:6 of
required size and other necessary materials complete as required as
per specifications.
Supplying and fixing polymer 11KVKV HT Disc (strain) insulator of
NSR-4 approved make on existing pole or bracket with GI hardware and Each 12.00 232.00 2784.00
other necessary materials complete as required.
Supplying and erection of D.P. structurre over existing support with
painting in an approved manner consisting of following:-
(a) D.C. cross arm with clamp and nuts bolts (100x50mm channel) –
(b) 11KV D.O. fuse unit, lighting arrester and A.B. switch mounting
channels with nuts and bolts (75x10mm channel) as required – 01
(c) Transformer mounting cross arms with clamps nuts and bolts
(100x50mm. Channels) – 1 set.
(d) Transformer clamping set with nuts and bolts etc. complete. 1 set.
(e) Transformer belting set with nuts and bolts etc. complete. – 1 set.
(f) Distribution pannel mounting channel and clamp with nuts and
bolts etc. (75x40mm channel).-1 set
(g) G.I. Pipe/bend as required for cable laying. -1 Job
(h) S/f DTR metering unit i/c meter box as per TLEB specification
complete. 01 Nos.
(i) G.I. pipe earthing complete with G.I. strip 25x3 mm as required
complete. 01 Job
(j) A.B. Switch as per T.N.E.R.C norms completed. 01 Set polymer
(k) L.A. as per T.N.E.R.C. norms completed. 03 Nos. - 01 Set
(L)D.O. fuse Unit set as per T.N.E.R.C. norms completed. 03 Nos. -
(M) D.P. structure complete as above. Complete as above (a to L)
Supplying and fixing polymer 11KV KV pin insulator with GI pin, of
NSR-6 approved make on existing pole or bracket with other necessary Each 12.00 261.00 3132.00
materials complete as required.
Supplying and drawing AAAC Rabbit conductor 0.05 sq inch (55
sq.mm al.eq) conductor of approved make with stringing making off
NSR-7 complete with binding at existing insulator, jointing, jumpering, km. 0.80 44136.00 35308.80
teeing off connecting etc. as required and clearing of obstacles (if
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supplying, laying, Terminating,testing and commissioning of XLPE
insulated and PVC sheathed heavy duty power cable confirming to
IS 7098/Part-I/88 with latest amendments, 1100 volts grade
armoured cable of approved make with aluminium solid / stranded
conductor. The cable shall be laid in air/in existing pipe/in existing
cable trench/on existing cable tray with clamp as required as per
specifications including providing of metal/PVC cable identification
tags at both ends and every 10 Mtr. length of cable with inscriptions
a)Un armoured cable 1 core 300 Sq.mm KM 0.12 255525.00 30663.00
b)Un armoured cable 1 core 150 Sq.mm KM 0.06 110000.00 6600.00
Supplying laying,terminating, testing and commissioning of XLPE
insulated and PVC sheathed heavy duty Arial bunch power cable
confirming to IS-7098/Part-I/88 with latest amendment, 1.1 KV grade
unarmoured cable of approved make with aluminium solid/stranded
conductor. The cable shall be laid in air as per specifications:
Supplying and fixing 2 ply 12 gauge barbed wire around the existing
HT/LT electric pole for safety measures as per IE rules including all
NSRE-01 stapples and all other necessary materials complete as Each 8.00 300.00 2400.00
required as per specifications.
Providing and fixing enamelled danger caution plate/board on
existing electric poles or wherever required of size 250x200 mm,
made of 1.6mm thick mild steel sheet and vitreous enamelled white,
with latest, figures and the conventional skull and cross-bones in
NSR-10 signal red colour (as per IS-5-1978 with latest amendment) on the
front side. The rear side of the plate shall also be enamelled. The
corner of the plate shall be rounded off with required material such
as screws, wires clamps, nut bolts etc. complete.
Supplying installing, connecting, testing and commissioning of
140KVA 11/.433 KV (COPPER wound without tap changing
arrangement) NLL 0.5 KW & FLL 3.0 KW 3 star rated, 3 Phase, 50
Hz, 11/0.433 KV, Delta/Star connected, Copper wound, oil filled,
Indoor/outdoor type, Distribution/Station transformer of accepted
standard specification, 3 star catagory class, with accessories such
as drain & filter valve, earthing terminals, lifting arrangements of
suitable size, dehydrating breather with silica gel of suitable size,
NSR-11 Conservator tank, air release devise, Rating & diagram plate Each 2.00 444094 888188.00
including CI rollers, Radiators with shut off valve, Cable end boxes on
HT & LT side bushings, Explosion vent with diaphragm, Off load tap
changing switch, Buchholz relay, thermometer pocket with 6” dial
type thermometer & OTI, wherever required complete with first
filling of oil with installation on existing DP structure or
foundation etc. complete as per specification.
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Providing and fixing of wiremesh fencing surrounding the existing DP
structure oldistribution transformer and panel system of different
sizes by adequate size of angle, flat iron and MS wire mesh jali
including nut, bolts, required holes, welding etc.and other necessary
materials as required. Frame is fabricated by MS angle of size
35x35x5mm runs horizontally on top and bottom of the frame. MS
wire mesh jali of size lxi” square of 13 guage MS bar, is
attached/fixed with the frame including strengthening to
1ali/wiremesh by flat iron of size 20x3mm on all sides of the frames.
The gate fabricated in the shape of frame is mentioned above, size
of angle 35x35x5mm is used on all sides. The opening is provided in
middle of two frames with the locking arrangement.The fabricated
wire mesh frame is painted with red oxide paint and alluminium paint
on portion above ground level a;d black paint on portion errected in
ground before errection Providing 13:6 cement concrete of 0 30
metre dra from ground level to 0.5 metre depth with 10cm base
foundatin. The rate includes for excavation in all type of soil/rock with
lead, lift and dressing etc. with curing and finishing of cement
concreting etc. complete. The Measurement and payment shall be
done as per measurements of wire mesh jali in Sqm. The other
materials/works shall be deemed to be included in quoted rates and
no extra payment will be made for any item/work involved in the
Supply of fire buckets 5 nos. in each set duly filled with fine sand and
fixed on an angle iron frame as per requirement of local authorities.
Fire buckets shall be painted red from outside and white from inside
with additional handle at the bottom.
Supply of tool kit with 1 pair 11KV rubber hand gloves of approved
TOTAL CARRIED TO SUMMARY 0.00 1867785.80
EARTHING INSTALLATION
Rates shall also include the following :
All fixing accessories such as brass saddles, brass screws rawl plugs
Jointing by rivetting and brazing after rivetting in case of copper and
welding / bolting in case of GI earthing.
Cutting chases holes and making good the same wherever required.
Effecting adequate and proper interconnections.
Use of copper thimbles.
Earthing system shall comply to IS:3043-1987.
All earthing pits shall be interconnected.
All equipment motors, DB’s, panels to be connected on either ends
(double earthing) with suitable strip / wires.
Supplying & laying, connecting testing and commissioning of
NSR 15 to following 1100 volt grade PVC sheathed XLPE insulated aluminium
18 conductor armoured cables as per specification in existing under
ground pipe as complete as required .
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supplying & laying of following 1100 volt grade XLPE insulated PVC
sheathed copper conductor armoured cables as per specification in
existing trenches, cable trays, ducts clamped includes anchor
fastners wall with suitable clamps, saddles fixing bolts including
connecting testing and commissioning.
NSR-19 4 core 6 sq.mm Copper RM 200.00 273.00 54600.00
NSR-20 2 core 6 sq.mm copper RM 400.00 266.00 106400.00
Cable end termination of the following PVC sheathed XLPE
insulated aluminium conductor armoured cables of 1100 volt grade
including supplying and fixing of crimping long barrel lugs, Single
compression glands with earthing facility at both ends of cables etc.
complete as required.
NSR-25 4 core 6 sq.mm Copper No. 16.00 307.00 4912.00
NSR-26 2 core 6 sq.mm copper No. 24.00 307.00 7368.00
TOTAL CARRIED TO SUMMARY 0.00 2662808.00
Supply and fixing of perforated type factory fabricated GI cable trays
of the following sizes including providing GI suspenders and supports
as per specifications..
TOTAL CARRIED TO SUMMARY 0.00 139440.00
LT CUM DG CHANGE OVER PANEL, MAIN DISTRIBUTION
The rates for the distribution boards apart from the Breakers and
instruments shall also include the following:
Supporting rigid steel framework.
Cubicle type, 14 gauge CRCA sheet steel enclosed & Type 3b
modular construction.
Complete with interconnections and distribution bus bars along with
connector strip.
Proper bonding to earth as per standard.
Painting/lettering on Breakers and distribution boards, the location
they serve, providing on each panel its circuit diagram.
Providing cable clamps / supports within distribution boards cable
TPN MCCB’s shall mean 3 pole MCCB’s with adequate size of
All MCB’s shall be of minimum 10 KA breaking capacity.
The breaking capacity of MCCB’s are mentioned panel wise. All
MCCB’s shall be with thermal magnetic releases as per BOQ and
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
i. MCCB rating upto 250 Amps with thermal magnetic releases.
Distribution panels / bus ducts / rising mains shall be Powder Coated
with Siemens gray paint shade no. RAL-7032 .
Degree of protection for following type of distribution panel enclosure
shall be as per IS:13947-1993.
i. IP 52 for indoor panels.
ii. IP 55 for outdoor panels.
All MCCB’s shall be provided with operating mechanism for door
GI earth bus shall be provided through out the length of each board
as per schematic diagram.
All measuring instruments (Meters) shall be of digital electronic (LED
Type) of approved make .
All hinged door shall be earthed through 2.5 sq mm tinned braided
All panels shall have provision of the following:
All MCB’s used for protection of resistive and lightly inductive load
shall be type “B” characteristic and inductive (motor) load shall be of
type “C” characteristic and discharge lamps and UPS etc. shall be of
type D characteristic.
CT’s shall be properally mounted and clamped. Connection of CT’s
for measuring instrument / relays shall be done through connector /
Model, current capacity location and frame size of switchgear shall
be written inside of the panel doors with paint / permanent marker as
approved shop drawings / site requirement.
Compliance to the technical specifications.
LT CUM DG CHANGE OVER PANEL, MAIN DISTRIBUTION
Supply,Installation, testing and commissioning of LT CUM DG
CHANGE OVER PANEL, MAIN DISTRIBUTION BOARDS,
fabricated out of 14 gauge CRCA sheet steel in cubicle
compartmentised modular 3b construction, free standing floor
mounted, dust and vermin proof with reinforcement of suitable size
angle iron, channel, `T’ sections and / or flats wherever necessary.
16 gauge CRCA sheet steel shall be used for final distribution panels.
3 mm thick cable gland plates shall be provided on top as well as at
NSR-29 the bottom of the panels. Panels shall be treated with all anticorrosive
process before powder coating as per specifications and final
approved shade. 2 Nos. earthing terminals shall be provided for all
distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4
wire, 50 HZ supply system. Lifting hooks shall also be provided in
case of large panels. Approval shall be taken for each panel in the
form of shop drawings before fabrication.Galvanised hardwares with
zinc passivation shall be used in fabrication of panels.
Incoming -Mains Supply
400 Amps 4 Pole, Microprocessor based MCCB with Over voltage ,
UnderVoltage, Over load and Earth Fault protection with 400 Amps 4
Pole contactor with Auto-Manual operation with following
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
VAF digital electronic meter with inbuilt selector switch and 400/5
Amps 15 VA, CL 1 CTs . - 1 Set
Phase indicating light shall be provided with 2 Amps SP MCB's. - 3
ON/OFF indicating light shall be provided with 2 Amps SP MCB's. - 2
Under voltage relay MV12 or equivalnt (27) - 1 Set
Over voltage relay MV 12 or equivalent (59) - 1 Set
Auto-manual selector switch - 1 Set
Phase reversal relay - 1 Set
Auxiliary contacts required for necessary interlocking of breakers.
required CTs for APFCR- 1 Set.
Incoming -DG Supply
400 Amps 4 Pole, Microprocessor based MCCB with Over voltage ,
UnderVoltage, Over load and Earth Fault protection with 400 Amps 4
Pole contactor with Auto-Manual operation with following
VAF digital electronic meter with inbuilt selector switch and 400/5
Amps 15 VA, CL 1 CTs . - 1 Set
Phase indicating light shall be provided with 2 Amps SP MCB's. - 3
ON/OFF indicating light shall be provided with 2 Amps SP MCB's. - 2
Engine cranking relay - 1 Set
Microprocessor based engine control automatic failure stand by relay
including all accessories
Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to
Suitable rating battery charger shall be provided as per specifications
DC ammeter / Voltmeter for battery charger
24 V DC Shunt trip coil. - 1 Set
Auto-manual / test selector / switch - 1 Set
Auxiliary contacts required for necessary interlocking of breakers.
600 Amps TPN Aluminium bus bars with heat shrinkable insulation
sleeve. - 1 Set
250 Amps 4Pole MCCB with Multifunction Energy meter including
CTs complete as required - 1 No.
100 Amps 4Pole MCCB with Multifunction Energy meter including
CTs complete as required - 2 No.
63 Amps 4Pole MCCB with Multifunction Energy meter including
CTs complete as required - 3 No.
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
250 Amps 4Pole MCCB with Multifunction Energy meter including
CTs complete as required - 1 No.
100 Amps 4Pole MCCB with Multifunction Energy meter including
CTs complete as required - 1 No.
63 Amps 4Pole MCCB with Multifunction Energy meter including
CTs complete as required - 1 No.
All MCCB's shall be of 25 KA (Ics) breaking capacity.
All MCB's shall be of 10 KA breaking capacity.
All the outgoing feeders shall be provided with ON/OFF Indication
NSR-29 LT CUM DG CHANGE OVER PANEL_described as above Set. 2.00 614900.00 1229800.00
250 Amps 4Pole MCCB with following accessories:
VAF digital electronic meter with inbuilt selector switch and 250/5
Amps 10 VA, CL 1 CTs . - 1 Set
Phase indicating light shall be provided with 2 Amps SP MCB's. - 3
300 Amps TPN Aluminium bus bars with heat shrinkable insulation
sleeve. - 1 Set
40 Amps 4Pole MCB - 2 No.
63 Amps 4Pole MCB - 15 No.
All MCCB's shall be of 25 KA (Ics) breaking capacity.
All MCB's shall be of 10 KA breaking capacity.
All the outgoing feeders shall be provided with ON/OFF Indication
NSR-30 MDB-1_described as above Set. 2.00 348443.00 696886.00
NSR-31 MDB-2 (Emergency)
63 Amps 4Pole MCCB with following accessories:
VAF digital electronic meter with inbuilt selector switch and 60/5
Amps suitable VA, CL 1 CTs . - 1 Set
Phase indicating light shall be protected by 2 Amps SP MCB's. - 3
150 Amps TP+N Aluminiun bus bars with heat coloured shrinkable
insulation sleeve. - 1 Set
40 Amps DP MCB- 9No.
All MCCB's shall be of 25 KA (Ics) breaking capacity.
All MCB's shall be of 10 KA (Ics) breaking capacity in C curve.
NSR-31 Common Area Panel_ described as above Set 2.00 290000.00 580000.00
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supply,Installation, testing and commissioning of LT CUM DG
CHANGE OVER PANEL, MAIN DISTRIBUTION BOARDS,
fabricated out of 14 gauge CRCA sheet steel in cubicle
compartmentised modular 3b construction, free standing floor
mounted, dust and vermin proof with reinforcement of suitable size
angle iron, channel, `T’ sections and / or flats wherever necessary.
16 gauge CRCA sheet steel shall be used for final distribution panels.
3 mm thick cable gland plates shall be provided on top as well as at
NSR-32 the bottom of the panels. Panels shall be treated with all anticorrosive
process before powder coating as per specifications and final
approved shade. 2 Nos. earthing terminals shall be provided for all
distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4
wire, 50 HZ supply system. Lifting hooks shall also be provided in
case of large panels. Approval shall be taken for each panel in the
form of shop drawings before fabrication.Galvanised hardwares with
zinc passivation shall be used in fabrication of panels.
Providing and fixing of Main Distribution Panel ,outdoor type pole
mounting weather, dust and vermin proof made of 14 gauge MS
sheet with clamping arrangements, lockable hinged door duly painted
on all sides with red oxide after antirust and corrosion treatment, two
coats of synthetic enamel paints of approved make and shade,
consisting of following fittings:
250 Amps 4 Pole, Microprocessor based MCCB with Over voltage ,
UnderVoltage, Over load and Earth Fault protection with following
VAF digital electronic meter with inbuilt selector switch and 250/5
Amps 15 VA, CL 1 CTs . - 1 Set
Phase indicating light shall be provided with 2 Amps SP MCB's. - 3
300 Amps TPN Aluminium bus bars with heat shrinkable insulation
sleeve. - 1 Set
125 Amps 4Pole MCCB with Tariff Energy meter including CTs
complete as required - 3 No.
125 Amps 4Pole MCCB with Tariff Energy meter including CTs
complete as required - 1 No.
All MCCB's shall be of 25 KA (Ics) breaking capacity.
All MCB's shall be of 10 KA breaking capacity.
All the outgoing feeders shall be provided with ON/OFF Indication
NSR32 MDB_described as above Set. 2.00 341611 683222.00
NSR-33 METER PANEL-1&2
125 Amps TP+N MCCB with following accessories:
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
VAF digital electronic meter with inbuilt selector switch and 125/5
Amps 10 VA, CL 1 CTs . - 1 Set
Phase indicating light shall be provided with 2 Amps SP MCB's. - 3
150 Amps TPN Aluminium bus bars with heat shrinkable insulation
sleeve. - 1 Set
40 Amps DP MCB with space for 40A ISI mark Single phase Tariff
energy meter-24 No.
All MCCB's shall be of 25 KA (Ics) breaking capacity.
All MCB's shall be of 10 KA breaking capacity.
All the outgoing feeders shall be provided with ON/OFF Indication
NSR-33 Meter Panel-1&2_described as above Set. 4.00 348443 1393772.00
NSR-34 COMMON AREA PANEL
125 Amps TP+N MCCB with following accessories:
VAF digital electronic meter with inbuilt selector switch and 125/5
Amps suitable VA, CL 1 CTs . - 1 Set
Phase indicating light shall be protected by 2 Amps SP MCB's. - 3
150 Amps TP+N Aluminiun bus bars with heat coloured shrinkable
insulation sleeve. - 1 Set
32 Amps DP MCB- 2No.
63Amps 4Pole MCCB- 5No.
40 Amps 4Pole MCB with export and Import meter- 1No.
All MCCB's shall be of 25 KA (Ics) breaking capacity.
All MCB's shall be of 10 KA (Ics) breaking capacity in C curve.
NSR-34 Common Area Panel_ described as above Set 2.00 290000 580000.00
FINAL DISTRIBUTION BOARDS :
Supply, installation, testing and commissioning of the following FDB's
fabricated out of 1.2 mm thick CRCA sheet steel, dust and vermin
proof, double door construction, powder coated with approved shade
NSR-35 . Approved lockable covers arrangement, recessed in wall or
surface mounted final distribution boards of the following description:
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
10 way SPN DB with 8No. 10 SP MCB’s with 1No. 40A DP RCCB of
100mA as incomer.(All MCB shall be 'C' curve)
Supply, installation, testing and commissioning of 63 Amps 4 pole
MCCB’s in MS Painted enclosure of approved make design and
painted with approved paint shade.
TOTAL CARRIED TO SUMMARY 0.00 6169352.00
EARTHING AND LIGHTINING PROTECTION INSTALLATION
Rates shall also include the following :
All fixing accessories such as brass saddles, brass screws rawl plugs
Jointing by rivetting and brazing after rivetting in case of copper and
welding / bolting in case of GI earthing.
Cutting chases holes and making good the same wherever required.
Effecting adequate and proper interconnections.
Use of copper thimbles.
Earthing system shall comply to IS:3043-1987.
All earthing pits shall be interconnected.
All equipment motors, DB’s, panels to be connected on either ends
(double earthing) with suitable strip / wires.
EARTHING AND LIGHTINING PROTECTION INSTALLATION
Providing and fixing 25 mm X 5 mm G.1. strip on surface or in recess
for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for
loop earthing as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm
thick including accessories, and providing masonry enclosure with
5.4 cover plate having locking arrangement and watering pipe of 2.7 set 32.00 5696.98 182303.36
metre lonq etc. with charcoal/ coke and salt as required.
Providing and fixing of lightning conductor finial, made of 25 mm dia
300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6
6.2 mm thick G.I. base plate including holes etc. complete as required. each 24.00 518.00 12432.00
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or
surface of wall for lightning conductor complete as required.(For
horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or
surface of wall for lightning conductor complete as required.(For
Providing and laying G.I. tape 32 mm X 6 mm from earth electrode
directly in ground as required.
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia
including accessories, and providing masonry enclosure with
cover plate having locking arrangement and watering pipe etc.
with charcoal/ coke and salt as required.
TOTAL CARRIED TO SUMMARY 1192415.36 0.00
A WIRING IN STEEL AND PVC CONDUIT
Wiring for light point/ fan point/ exhaust fan point/ call bell point with
1.5 sq.mm FRLS PVC insulated copper conductor single core
cable in surface / recessed medium class PVC conduit, with
1.10 modular switch, modular plate, suitable GI box and earthing the
point with 1.5 sq.mm FRLS PVC insulated copper conductor single
core cable etc. as required.
Wiring for group controlled (looped) light point/fan point/exhaust
fan point/ call bell point ( without independent switch etc.) with 1.5
sq. mm FRLS PVC insulated copper conductor single core cable
1.55 in surface/recessed PVC conduit, and earthing the point with 1.5
sq. mm FRLS PVC insulated copper conductor single core cable
etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated
copper conductor single core cable in surface/ recessed medium
1.12 class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated meter 280.00 334.00 93520.00
copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring along with earth wire with the
1.14 following sizes PVC insulated copper conductor, single core cable in
surface / recessed Steel conduit as required.
1.14.4 2 X 6 sq. mm + 1 X 6 sq. mm earth wire meter 300.00 439.00 131700.00
Supplying and fixing of following sizes of Medium class PVC condute
along with accessories in surface/recess including cutting the walland
making good the same in case of recessed conduit as required.
Supplying and fixing suitable size GI box with modular plate and
cover in front on surface or in recess, including providing and fixing 3
pin 5/6 A modular socket outlet and 5/6 A modular switch,
connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and
cover in front on surface or in recess, including providng and fixing 2
1.56 Nos. 3 pin 5/6 A modular socket outlet and 2 Nos. 5/ 6 A modular Each 968.00 676.00 654368.00
switch, connections etc. as required. (For light plugs to be used in
non residential buildings).
Supplying and fixing suitable size GI box with modular plate and
cover in front on surface or in recess, including providng and fixing
1.57 25 A modular socket outlet and 2 SPMCB,including connections& Each 8.00 727.00 5816.00
Painting etc. as required. (For light plugs to be used in non residential
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supplying and fixing suitable size GI box with modular plate and
cover in front on surface or in recess, including providing and fixing 6
pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular
switch, connections etc. as required.
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction
box/ wooden block including connections etc. as required.
Supplying and fixing two module stepped type electronic fan
1.25 regulator on the existing modular plate switch box including Each 3024.00 369.00 1115856.00
connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing modular
plate & switch box excluding modular plate as required.
Providing and fixing circular/hexagonal Fan box cast iron /metal
sheet Box for ceiling fan clamp of internal dia 140mm , 73 mm
Civil DSR height,Top id of 1.5mm thick MS sheet with its Top surface hacked of
2023 proper bonding top lid shall be screwed into cast iron /metal sheet Each 3024.00 220.65 667245.60
10.18 Box by mean of 3.3mm dia round headed screw one lock at the
corners.clamp shall be made of 12mm dia ms Bar band toshape as
per standrd drawing.
TOTAL CARRIED TO SUMMERY 9360425.60 0.00
LIGHTING FIXTURE AND FANS
Recessed mounted 12W LED down lighter with die cast aluminium
NSRL-35 housing with inbuilt controller and robust consction complete as No. 394.00 2777.00 1094138.00
required. (Toilet)
Recessed mounted 10W wall Surface Mounted lighter with die cast
NSRL-36 aluminium housing with inbuilt controller and robust consction No. 962.00 461.00 443482.00
complete as required.
Wall mounted 10W Bulk Head light fixture with die cast aluminium
NSRL-37 A housing with inbuilt controller and robust consction complete as Nos 82.00 1691.00 138662.00
Recessed mounted 10W Mirror lighter with die cast aluminium
NSRL-37 B housing with inbuilt controller and robust consction complete as No. 196.00 717.00 140532.00
Recessed mounted 12W Ceiling Down lighter with die cast
NSRL-38 aluminium housing with inbuilt controller and robust consction No. 388.00 3228.00 1252464.00
complete as required.
Recessed mounted 15W Ceiling Down lighter with die cast
NSRL-39 aluminium housing with inbuilt controller and robust consction No. 1170.00 2941.00 3440970.00
complete as required.
Recessed mounted 20W Wall Tube lighter with die cast aluminium
NSRL-40 housing with inbuilt controller and robust consction complete as No. 824.00 589.00 485336.00
Recessed mounted 20W Ceiling Tube lighter with die cast aluminium
NSRL-41 housing with inbuilt controller and robust consction complete as No. 160.00 543.00 86880.00
Supply and fixing of Ceiling fan of 1200mm sweep (white colour),
suitable for operation on 230 / 240V, 50 Hz, single phase, A.C,
NSRL-42 supply complete with double ball bearing motor, required down rod, Nos 3024.00 3638.00 11001312.00
capacitor, three MS blades etc complete.1200 MM Celing fan(Havells
Fusion Five Star 3 Blade (1200 mm)
300MM Exhaust fan in approved colour by engineering Incharge with
NSRL-44 Supply installation and testing of Call Bell app complete Nos 20.00 383.00 7660.00
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Self contained single sided exit sign for wall / ceiling / pendant
cantilever mounting with LED tube for non maintained battery backup
emergency lighting for 3 hours duration, approved equal in quality
Aviation obstruction light with Light Emitting Diods (LEDs). Complete
with all accessories as approved.
TOTAL CARRIED TO SUMMERY 0.00 18837910.00
EXTERNAL LIGHTING SYSTEM
Rate for supply and installation of fixtures shall also include the
All component that may be required to make the installation complete
in all respects, such as :
Suitable length of connecting wires.
Internal wiring between accessories.
Connecting wires to the point through connection block.
Bonding to earth wires.
Drilling holes in supports wherever required.
Fixing clamps, GI bolts and nuts/brass screws, saddles, rawl bolts
and other fixing accessories as required.
Painting with enamel paint of clAmps and other fixing accessories.
Testing of all fixture after installation.
Supply, Installation, testing and commissioning of the following
lighting fixtures or approved equivalent:
35 WLED based Street lighting Fixture, housing made up of Pressure
Die Cast Housing LM 6 Alloy/ Anti Dust Exposed Lens,sturdiness
and embossed brand name/logo name of manufacturer. The fixture
should have a minimum system efficacy of 110 lumen/Watt . The
fixture shall have a CRI of minimum 70. The fixture shall be designed
for a system life of 50,000 hours @70% lumen maintenance. Ingress
Protection of IP66 (lamp and gear Compartment) and Mechanical
Impact Resistance Rating of IK >=08.The fixture driver should have
an operating voltage range of 140-270 V, surge protection of >=3KV,
PF >0.9 , THD<10% and SDCM<5. The fixture should be top
openable & easy access to the Gear Compartment. The driver
should be BIS approved, fully potted and encapsulated with 440V
Stress Voltage protection for 8 Hrs. High Cut off : 325V(+/- 15V) and
Auto Restart function should also be available within the fixture.The
NSRL-47 fixture should comply with the parameters as per IS10322. The LED No. 48.00 9223.00 442704.00
driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics,
IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007
for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and
IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have
inhouse lab approved by NABL or ministry of science of govt of India.
LM 79 and LM80 reports need to be submitted from a NABL/UL
accredited lab to verify above parameters.
Note : Light shall be mount direct on boundry wall with 3feet high
existing pole and 600 mm long 40mmdia existing single arm.
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supply, Installation, Testing and Commissioning of 27W LED Post
Top with a system lumen output of 2300 lumens and a minimum
system efficacy of >85 lm/W. The luminaire shall have a rated
system lifetime of 25,000 burning hours at L70. The luminaire should
NSRL-48 have a color temperature of 3000K and CRI > 70. The luminaire shall No. 8.00 2050.00 16400.00
meet IP65 with THD < 20% and PF > 0.9. The luminaire shall have
closed diffused optics with polycarbonate diffuser board. The total
power consumption should not exceed 27W (including driver).
Supply, Installation, Testing and Commissioning of 60mm dia and 2
feet long heavy class GI pipe pole along with welded 12mm thick
base plate hole for 4No. 200mm long Mounted nut,Bolt stud with
double washer (The cost of nut,Bolt stud with double washer shall be
included and the pole shall have two coat of Aluminimum/GI paint) .
Supply, Installation, Testing and Commissioning of pole single arm
made of 40mm dia and 2 feet long heavy class GI pipe including
mounting clamp and nut bolt with double washer complete as
Supply, laying, testing and commissioning of following size PVC
insulated aluminium conductor 1100 V grade armored cable
NSRL-51 including excavation sand filling providing brick protection, back filling
of earth, watering, ramming and consolidating of earth, complete:
Making end termination of following size PVC insulated aluminium
NSRL-52 conductor 1100 V grade armored cable including cost of crimping
lugs, insulation tapes, double compression glands etc. complete.
Wiring with 2 x 2.5 sq. mm. PVC insulated copper conductor 1100 V
grade wires in 16 gauge 25 mm dia heavy guage PVC conduit
NSRL-53 including connecting at the lighting fixtures complete. The cost shall RM 1152.00 136.00 156672.00
include supply and installation of conduit pipe, chasing of wall and
Supply, installation, testing and commissionin of
250MMX250MMx150MM polycarbonate weather proof (IP-55)
junction boxes including terminal / connector block complete as
Supplying and laying of following size DWC HDPE pipe ISI marked
along with all accessories like socket, bend, couplers etc. conforming
NSRL-55 to IS 14930, Part II complete with fitting and cutting,jointing etc.
Recessed in floor/Wall, complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal) RM 800.00 128.00 102400.00
TOTAL CARRIED TO SUMMARY 0.00 1485808.00
FIRE ALARM SYSTEM
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supplying, installation, testing and commissioning of micro
processor based intelligent addressable main fire alarm
panel, central processing unit with the following loop modules and
capable of supporting not less than 240 devices (including
detectors) and minimum 120 detectors per loop and loop length
up to 2 km, network communication card, minimum 320 character
graphics/ LCD display with touch screen or other keypad and
minimum 4000 events history log in the non volatile memory
(EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up
17.2.1 with 24 volt sealed maintenance free batteries with automatic
charger. The panel shall have facility to connect printer to
printout log and facility to have seamless integration with
analog/digital oice evacuation system (which is part of the
schedule of work under SH: PA System) and shall be
complete with all accessories . The panel shall be compatible for
IBMS system with open protocol BACnet/ Modbus over IP
complete as per specifications.
Supplying, installation, testing & commissioning of addressable
17.2.10 fire control module complete as required. each 8.00 3003.00 24024.00
Supplying, installation, testing & commissioning of addressable
17.2.11 phone control module complete as required. each 4.00 3267.00 13068.00
Supplying, installation, testing & commissioning of addressable
17.2.14 manual call point complete as required. each 28.00 3871.00 108388.00
Supplying, installation, testing & commissioning of addressable
17.2.15 horn cum strobe complete as required. each 54.00 3506.00 189324.00
Supplying, installation, testing & commissioning of addressable
17.2.16 strobe complete as required. each 54.00 3367.00 181818.00
Supplying, installation, testing & commissioning of fire
17.2.17 fighter telephone handset complete as required. each 28.00 5740.00 160720.00
Supplying, installation, testing & commissioning of fire fighter
17.2.19 phone jack complete as required. each 54.00 1600.00 86400.00
Supply , Installation , Testing and Commissioning of Monitor Module.
Supplying and drawing following sizes of FRLS PVC insulated copper
1.17 conductor, single core cable in the existing surface/ recessed steel/
PVC conduit as required.
Supplying and fixing of following sizes of steel conduit along with
accessories in surface/recess including painting in case of surface
conduit, or cutting the wall and making good the same in case of
recessed conduit as required.
TOTAL CARRIED TO SUMMERY 1867822.00 13800.00
PUBLIC ADDRESS SYSTEM
Supplying and drawing following sizes of FRLS PVC insulated copper
1.17 conductor, single core cable in the existing surface/ recessed steel/
PVC conduit as required.
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supplying and fixing of following sizes of medium class PVC conduit
along with accessories in surface/recess including cutting the wall
and making good the same in case of recessed conduit as required.
Supplying, installation, testing & commissioning of 1.5/3/6W
17.3.2 ceiling speaker complete as required. each 236.00 965.00 227740.00
Supply, installation, testing and commissioning of rack mounted dual
Channel Digital Power Amplifier capable of delivering 300 W RMS
power output or 480 W RMS burst output; complete with 100 V Line
Matching Transformer, built-in fan for temperature control, Distortion
NSR-57 typically 0.03% @ 1 KHz, Hum and Noise 90 dB below rated output No. 4.00 45255.26 181021.06
selection facility,provision for hookup with Fire Alarm Panel, complete
with connections and required circuitry. Same shall be intergrate with
Fire alarm system.
Supply, installation, testing and commissioning of 19" equipment rack
made out of 2 mm thick CRCA sheet duly powder coated; in-built
amplifier mounting; amplifier, controller, suitable for housing of above
control equipment.
Supply, installation, testing and commissioning of micro phone for
NSR-59 remote location and interface with controller including communication Nos. 4.00 9873.00 39492.00
cable and all accessories.
TOTAL CARRIED TO SUMMERY 528740.00 357569.06
CCTV (IP VIDEO SURVEILLANCE) SYSTEM
Supply, installation, testing and commissioning of Out door type
Fixed camera with discreet and tamper-resistant casing. Varifocal
2.8-10 mm lens with fixed iris. Multiple, individually configurable
NSR-60 H.264 and Motion JPEG streams; max HDTV 720p or 1 MP Nos. 12.00 33102 397224.00
resolution at 30 fps. Video motion detection and active tampering
alarm. Power over Ethernet. Midspan not included.The camera shall
have sound in facility.
Supply, installation, testing and commissioning of Fixed dome with
discreet and tamper-resistant casing. Varifocal 2.8-10 mm lens with
fixed iris. Multiple, individually configurable H.264 and Motion JPEG
NSR-61 streams; max HDTV 720p or 1 MP resolution at 30 fps. Video motion Nos. 132.00 14518 1916376.00
detection and active tampering alarm. Power over Ethernet. Midspan
not included.The camera shall have sound in facility.
Supply, installation, testing and commissioning of 24 channel NVR
with two video outputs . Contractor shall size the NVR for real time
400 FPS / 4 CIF resolution 30 days of continous recording and
NSR-62 submit data sheet of their storage calculation for both MPEG 4 and Nos. 4.00 110340 441360.00
H.264 recording formats. The NVR with IP connectivity, DVD R/W &
USB connectivity with all necessary softwarealong with standalone
UPS with 15 min. Battery back.
Supply, installation, testing and commissioning of 55" totally flat
NSR-63 colour LCD monitor with mouted accesseries complete as required. Nos. 4.00 63881 255524.00
Supply, installation, testing and commissioning of Joy Sticks with
mouted accesseries complete as required.
Supply, Installation, Testing & Commissioning of CAT 6 UTP, LSZH
Patch Cord as per ANSI/TIA/EIA 568C.2 and UL 94-V-0, ROHS
Compliant, patch cord 1 Mtr for rack side switch to jack panel
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supply, Installation, Testing & Commissioning of loaded 24 port CAT
6 UTP, Transparent shutter jack panel, 1U height, UL-94V-0, Black
with cable support bar, clear label marks and earthing plug for
CAT6A cable termination at rack end.
Supply, Installation, Testing and Commissioning of 24 port L2
Managed switch having port density 24 Nos. of 10M/100M/1G RJ45
Port POE/POE+ ports , 4 Nos. of 1G/10G SFP+ Port , 1X console
port , Available POE power 370 W , 128 Gbps switching bandwidth ,
32K MAC address support , Support L2 feature STP, RSTP ,MSTP .
NSR-67 Support 802.1Q VLAN , port based VLAN , 4K VLAN entries , MAC Nos. 4.00 24000 96000.00
based VLAN , IP subnet based VLAN . Support IEEE 802.3ad LACP
. L3 features - static routing , DHCP server , Device Management
system - topology view , floor view , map view , dashboard , traffic
monitoring , cable diagnostics.CE,FCC certified
Supply, Installation, Testing & Commissioning of I LIU ,PDU for
Supply, Installation, Testing & Commissioning of armoured 6 core
fiber Singlemode OS2 (9/125 Micro), Corrugated ECCS Armor,
HDPE (UV) Sheathing, Theoxtropic gel filled OFC cable with 2 Nos
steel music wire embedded in side sheathing as stregth member for
switch connectivity. Cable should be ROHS compliant and as per
IEC60749-1 with product warranty of 30 years.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the
existing surface/ recessed Steel/ PVC conduit as required.
Supplying and fixing of following sizes of medium class PVC conduit
along with accessories in surface/recess including cutting the wall
and making good the same in case of recessed conduit as required.
TOTAL CARRIED TO SUMMERY 409360.00 5417120.00
DATA , VOICE SYSTEMS
Supplying and fixing following piano type switch/ socket on the
existing switch box/ cover including connections etc. as required.
1.24.6 Telephone socket outlet Each 20.00 148.00 2960.00
Supplying and fixing following size/ modules, GI box alongwith
1.27 modular base & cover plate for modular switches in recess etc. as
Supplying and fixing following Modular base & cover plate on existing
modular metal boxes etc. as required.
Supply, Installation, Testing & Commissioning of 42 U (600W/1000D)
NSR-70 floor mount rack with fans , 2 cable managers , satationary shelf , 2 Nos. 4.00 52.00 208.00
Nos. of hardware pkts.
Supply, Installation, Testing & Commissioning of 15U wall mount
NSR-71 rack with fans , 2 cable managers , satationary shelf , 2 Nos. of Nos. 4.00 4123.00 16492.00
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supply, Installation, Testing & Commissioning of CAT 6A UTP
Universal (both tool & toolless) information outlet (I/O) in accordance
with ANSI TIA 568 C.2, IEC 60603-7-4 2nd Edition, ISO/IEC TR
11801-9901-2014, ROHS Compliant. The I/O should have minimum
750 mating cycle and 200 insertion cycle and UL approved, for Data,
Voice, & Wi-Fi at user end.
Supply, Installation, Testing & Commissioning of loaded 24 port CAT
6A UTP, Transparent shutter jack panel, 1U height, UL-94V-0, Black
with cable support bar, clear label marks and earthing plug for
CAT6A cable termination at rack end.
Supplying and drawing following pair 0.5 mm dia FRLS PVC
1.18 insulated annealed copper conductor, unarmored telephone cable in
the existing surface/ recessed steel/ PVC conduit as required.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the
existing surface/ recessed Steel/ PVC conduit as required.
Supplying and fixing of following sizes of medium class PVC conduit
along with accessories in surface/recess including cutting the wall
and making good the same in case of recessed conduit as required.
TOTAL CARRIED TO SUMMERY 42180.00 52936.00
Supply, installation, Testing and commissioning of the following UPS
SYSTEM as per specifications and complete in all respects.
10 KVA 3 phase input (415 V + 15%), three phase output (415 V +
1%) in stand alone mode with isolation transformer with 15 minutes
battery backup each complete with battery rack & inter connector for
batteries & Isulation switch for each bank battery.
Quoted price shall be inclusive of the following:
Approved rating single core copper conductor cable connecting as
All equipment shall be housed in individual cabinets.
Battery backup must be given for full resistive load. Battery should
be sealed maintenance free type.
Battery monitoring system shall be provided.
TOTAL CARRIED TO SUMMARY 0.00 1400000.00
Design, manufactures, supply,installation, testing,commissioning,
approvals / laisoning (All local / state/ central statutory bodies) and
handing over in satisfactory working conditions of elevators as per
specification ans approved make.
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
13Passenger (884Kg.) Elevator with 2200X2350 mm shaft,
machine room consisting of ACVVVF Panel, 4800mm over
head,1600mm Pit including withiring, 1.5MPS speed, 6 No. Stops ,
car size with 900x2100mm car entrance and door opening for
NSR-75 stracture with Automatic with Centre opening ACVVVF Motor Door No. 8.00 2613324.60 20906596.80
operator with electronic / infrared sensor door detector, all floor
opening in same side ,moon rock finish stainless steel complete in
all respect as per specification.
(i) Necessary wiring/control wiring, conduit/raceway if required for
satisfactory operation of elevators shall be in the scope of lift vendor.
(ii) Size of car should be fit in lift well.
TOTAL CARRIED TO SUMMERY 0.00 20906596.80
SMOKE EXTRACTION SYSTEM
AXIAL FLOW FANS
Supply, Installation, Testing and Commissioning of Long Casing
(motor should completely accommodated inside the casing) AXIAL
FANS for exhaust air suitable for installing in any position in
Horizontal or vertical. Fan shall be AMCA Certified. The motor shall
be of class F/H (H class wherever specified in the item, to withstand
a temperature of 250 degree celcius for 2 hours) suitable for 415 V ±
NSR-76 10% volts three phase 50cycle, AC supply & meeting criterion as per
ASHRAE standard 90.1-2010 and high efficiency (IS 12615). The fan
shall be equipped with mounting bracket Inlet & outlet cone required
at discharge. The fan shall be low RPM (less than 1450 RPM) and
capacities shall be as follows:-
Duty :- Smoke Extraction (Fresh Air)
Air Quantity : 8000 CFM
Static Pressure : 25 mm wg
NSR-76 Fan Motor H.P: 2.5 H.P Class-f Motor Nos. 8.00 131179.00 1049432.00
SMOKE EXTRACTION SYSTEM
AXIAL FLOW FANS
Supply, Installation, Testing and Commissioning of Long Casing
(motor should completely accommodated inside the casing) AXIAL
FANS for exhaust air suitable for installing in any position in
Horizontal or vertical. Fan shall be AMCA Certified. The motor shall
be of class F/H (H class wherever specified in the item, to withstand
a temperature of 250 degree celcius for 2 hours) suitable for 415 V ±
NSRS-01 10% volts three phase 50cycle, AC supply & meeting criterion as per
ASHRAE standard 90.1-2010 and high efficiency (IS 12615). The fan
shall be equipped with mounting bracket Inlet & outlet cone required
at discharge. The fan shall be low RPM (less than 1450 RPM) and
capacities shall be as follows:-
Duty :- Smoke Extraction (Fresh Air)
Air Quantity : 7000 CFM
Static Pressure : 25 mm wg
NSRS-01 Fan Motor H.P: 2.5 H.P Class-f Motor Nos. 4.00 85000 340000.00
AIR DISTRIBUTION
Supply, installation, balancing and commissioning of factory
fabricated GSS sheet metal rectangular/round ducting complete with
neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers,
NSRA-02 supports etc. as per approved drawings and specifications of
following sheet thickness complete as required.
(It shall be as per SMACNA standards)
Thickness 26 G Galvanized Sheet Steel Ducting Sqm. 40.00 1719.00 68760.00
TOTAL CARRIED TO SUMMARY 0.00 1458192.00
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supply, installation, testing and commissioning of 160 KVA prime
continuous (actual) rating radiator cooled type diesel generating set
(alternature at 40 deg C temperature) with Acoustic Enclosure along
with electronic governor base frame, Alternator (capable of delivering
true 40 kVA output), Static Excitation System, Lube Oil System,
NSD-01 Batteries, Battery charger, Instrumentation, 990 liter day oil fuel Nos. 2.00 1250000.00 2500000.00
tanks, Silencer with bellows, alarms, Engine Control Panel, AVM
pads, AVR Panel,Terminal arrangements in termination box suitable
to 3.5cx50 sqmm aluminium cables with all other associated
equipment / work as per specifications. The DG Set shall comply
Supply, installation, testing and commissioning of exhaust pipe 'B'
class heavy duty MS pipe with all fixing accessories and hardwares.
NSD-02 The exhaust pipes shall be insulated with 75 mm thick mineral wool
insulation wrapped in chicken mesh and clad with 24 gauge
aluminium sheet including all support.
TOTAL CARRIED TO SUMMARY 0.00 2590000.00
TOTAL ELECTRICAL 13400942.96 63359317.66
SANITARY FIXTURES & FITTINGS
14.80 Providing & fixing White vitreous china water closet squatting
pan (Indian type) along with “S” or “P” trap including dismantling of
old WC seat and “S” or “P” trap at site complete with all operations
including all necessary materials, labour and disposal of dismantled
material including malba, all complete as per the direction of
Engineer-in charge.
14.80.2 Orissa pattern W.C Pan of size 580x440 mm Each 22.00 4478.75 98532.50
Providing and fixing of white vitreous china pedestal type water closet
(European type W.C. pan) with seat and lid, 10 litre low level white
P.V.C. flushing cistern, including flush pipe, with manually controlled
device (handle lever), conforming to IS : 7231, with all fittings and
fixtures complete, including cutting and making good the walls and
floors wherever required
17.2.1 W.C. pan with ISI marked white solid plastic seat and lid Each 176.00 6515.55 1146736.80
17.34 Providing and fixing toilet paper holder
Providing and fixing of low flow type two way bib cock and flow
restrictor 6 LPM at 3 Bar Pressure as per approved make complete
in all respect as per engineer in the charge. (Only for EWC.)
Providing and fixing of Health faucet with 1 m of C.P. brass flexible
pipe and direction of Engineer-in-charge.
Providing and fixing wash basin with C.I. brackets, 15 mm dia CP
Brass single hole basin mixer of approved quality and make,
17.7A including painting of fittings and brackets, cutting and making good
the walls wherever required:
a) White Vitreous China Wash basin size 550x400 mm with a 15
mm CP Brass single hole basin mixer
Providing and fixing kitchen sink with C.I. brackets, C.P. brass chain
with rubber plug, 40 mm C.P. brass waste complete, including
17.9 painting the fittings and brackets, cutting and making good the walls
wherever required:
17.9.1 White glazed fire clay kitchen sink of size 600x450x 250 mm Each 102.00 3892.75 397060.50
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Providing and fixing CP Brass 32 mm size Bottle Trap of approved
17.22A quality & make and as per the direction of Engineer-in-charge. Each 304.00 1034.80 314579.20
Providing and fixing CP Brass Single lever telephonic wall mixer of
17.22B quality & make as approved by Engineer in charge. 15 mm nominal Each 310.00 6940.75 2151632.50
Providing and fixing PTMT liquid soap container 109 mm wide, 125
mm high and 112 mm distance from wall of standard shape with
bracket of the same materials with snap fittings of approved quality
and colour, weighing not less than 105 gms.
Providing and fixing PTMT soap Dish Holder having length of
18.65 138mm, breadth 102 mm, height of 75 mm with concealed fitting Each 198.00 111.45 22067.10
arrangements, weighing not less than 106 gms
Providing and fixing of C.P. brass angle valve for basin mixer and
geyser points of approved quality conforming to IS:8931
Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1
17.16A metre long with S.S. triangular plate to Eureopean type W.C. of Each 1109.00 349.15 387207.35
quality and make as approved by Engineer - in - charge
Providing and fixing of following capacity of vertical or horizontal
storage type hot water heater fixed to wall with anchor bolts & nuts,
15mm CP brass angle stop cock and 15mm CP brass non-return
valve complete including making connections with 15mm dia CP
connecting pipes on inlet and outlet, suitable length of power cable
and 15 amps plug direction of Engineer-in-charge.
Capacity: 25 Ltr. (Only for bath areas) Each 4.00 25000.00 100000.00
INTERNAL & EXTERNAL WATER SUPPLY
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,
having thermal stability for hot & cold water supply, including all
CPVC plain & brass threaded fittings, including fixing the pipe with
18.7 clamps at 1.00 m spacing. This includes jointing of pipes & fittings
with one step CPVC solvent cement and testing of joints complete as
per direction of Engineer in Charge.(For Domestic & Flushing water
Internal work - Exposed on wall
18.7.1 15 mm nominal outer dia Pipes Metre 9.00 286.80 2581.20
18.7.2 20 mm nominal outer dia Pipes Metre 188.00 335.00 62980.00
18.7.3 25 mm nominal outer dia Pipes Metre 90.00 401.55 36139.50
18.7.4 32 mm nominal outer dia Pipes Metre 110.00 518.75 57062.50
18.7.5 40 mm nominal outer dia Pipes Metre 145.00 702.95 101927.75
18.7.6 50 mm nominal outer dia Pipes Metre 39.00 934.15 36431.85
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,
having thermal stability for hot & cold water supply including all CPVC
plain & brass threaded fittings This includes jointing of pipes & fittings
with one step CPVC solvent cement, trenching, refilling & testing of
joints complete as per direction of Engineer in Charge. External work
18.9.7 65 mm nominal outer dia Pipes Metre 11.00 1674.40 18418.40
Concealed work, including cutting chases and making good the
18.8.1 15 mm nominal outer dia Pipes Metre 874.00 497.80 435077.20
18.8.2 20 mm nominal outer dia Pipes Metre 418.00 537.60 224716.80
18.8.3 25 mm nominal outer dia Pipes Metre 690.00 627.25 432802.50
Providing and fixing G.I. pipes complete with G.I. fittings and
clamps,including cutting and making good the walls etc.
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Internal work - Exposed on wall
18.10.1 15 mm nominal outer dia Pipes Metre 4.00 366.40 1465.60
18.10.2 20 mm nominal outer dia Pipes Metre 168.00 437.30 73466.40
18.10.3 25 mm nominal outer dia Pipes Metre 34.00 551.70 18757.80
18.10.4 32 mm nominal outer dia Pipes Metre 364.00 667.00 242788.00
18.10.5 40 mm nominal outer dia Pipes Metre 244.00 811.90 198103.60
18.10.6 50 mm nominal outer dia Pipes Metre 254.00 1048.35 266280.90
Providing and fixing of 'B' class heavy duty G.I. pipes confirming to
IS: 1239 Including welding fitting like elbow, tee flages, taper,
FF-DSR nuts,bolt gaskit etc, and fixing of pipe on the ceiling/wall with suitable
2019 clamp /support fram and painting two or more coat of enamle paints
of required shed complete as required.
Internal work - Exposed on wall
Providing, laying, testing & commissioning of 'B' class heavy duty G.I.
pipe conforming to IS 1239 including welding, fittings like elbows,
tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on
the wall/ceiling with suitable clamp/support frame and painting with
two or more coats of synthetic enamel paint of required shade
complete as required
Providing and fixing G.I. pipes complete with G.I. fittings including
trenching and refilling etc
18.12.3 25 mm dia nominal bore Metre 4.00 467.75 1871.00
18.12.4 32 mm dia nominal bore Metre 22.00 540.30 11886.60
18.12.5 40 mm dia nominal bore Metre 22.00 617.05 13575.10
Making connection of G.I. distribution branch with G.I. main of
18.13 following sizes by providing and fixing tee, including cutting and
threading the pipe etc. complete :
25 to 40 mm nominal bore
18.13.2 50 to 80 mm nominal bore Each 8.00 1785.35 14282.80
Fixing water meter and stop cock in G.I. pipe line including cutting
18.14 and threading the pipe and making long screws etc. complete (cost Each 4.00 812.30 3249.20
of water meter and stop cock to be paid separately).
Providing and fixing gun metal gate valve with C.I. wheel of approved
quality (screwed end) :
18.17.2 32 mm nominal bore. Each 4.00 689.60 2758.40
18.17.3 40 mm nominal bore Each 4.00 826.10 3304.40
Providing and fixing ball valve (brass) of approved quality, High or
low pressure, with plastic floats complete
18.18.2 20mm nominal bore Each 50.00 462.50 23125.00
18.18.3 25mm nominal bore Each 94.00 464.05 43620.70
Providing and fixing motorised butterfly valve rating PN 1.0 with float
type sensors suitable for 240 volts with working pressure rating of
not less than 5 kg/cm2 with control panel and sensors to open valve
when water level is low in tanks and to close when water level is
high in water tanks including butterfly valves, necessary cables,
conduits, upto junction box etc. complete. (upto 6 mt qty approx.)
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
NSRW-4 32 mm dia ( FLUSHING RISER) Each 4.00 19305.00 77220.00
NSRW-5 40 mm dia ( DOMESTIC RISER) Each 4.00 23077.00 92308.00
Providing and fixing M.S fabricated hot dipped galvanized coating
puddle flange comprising of 600 mm dia long M.S class 'B' pipe
(screwed end up to 50 mm & flange for more than 50 mm dia) with 6
mm thick M.S plates of required size including cutting holes in centre
NSRW-06 to of plate, inserting pipe & making welded (Arc) joint complete. Same
NSRW- 12 shall be installed with TEC welded joint in position with reinforcement
bars of RCC tank wall/slab including making cutout in shuttering
during concrete casting of tank of following diaMtr.. (Location:
overhead tanks.)(Jindal star)
Painting G.I. pipes and fittings with two coats of anti-corrosive
bitumastic paint of approved quality :
18.40.3 25 mm dia nominal bore Metre 4.00 18.35 73.40
18.40.4 32 mm dia nominal bore Metre 22.00 22.20 488.40
18.40.5 40 mm dia nominal bore Metre 22.00 25.24 555.28
SOIL, WASTE, VENT PIPES & FITTINGS FOR INTERNAL
Providing and fixing unplasticised PVC pipe clips of approved design
to unplasticised - PVC rain water pipes by means of 50x50x50 mm
hard wood plugs, screwed with M.S. screws of required length,
including cutting brick work and fixing in cement mortar 1:4 (1 cement
: 4 coarse sand) and making good the wall etc. complete.
Providing, fixing, jointing and testing in position the following uPVC
pipes conforming to IS: 4985 of 6 kg/sqcm pressure rating including
NSRW-13 to all fittings, solvent weld joints, testing complete for drainage system
NSRW-15 cut to required length to be laid under floor and exposed including
covering all around with cement concrete and making good the same
complete as required.
Providing & fixing 75mm x 50mm UPVC waste with reducing elbow &
nipple (floor drain ) including cutting chases, the floor / slab, repairs
complete as required and connection to upvc waste pipe.
Providing & Fixing, Testing & Commissioning of Heavy class S.S.
grating with Cockroach proof SS strainer of approved design
including setting in floor with cement mortor to match with floor finish
as per architect requirement suitable for waster and FT.
Providing and fixing uPVC clean out plug with uPVC socket complete
NSRW-18 with all necessary fitting complete as required by the engineer-in-
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
STROM WATER PIPES & FITTINGS
Providing and fixing on wall face unplasticised Rigid PVC rain water
pipes conforming to IS : 13592 Type A, including jointing with seal
ring conforming to IS : 5382, leaving 10 mm gap for thermal
expansion, (i) Single socketed pipes.
Providing and fixing to the inlet mouth of rain water pipe cast iron
grating 15 cm diameter and weighing not less than 440 grams.
NSRW-19 Providing and fixing CPVC gratings for Rain Water Pipes.
Providing and laying non-pressure NP2 class (light duty) R.C.C.
pipes with collars jointed with stiff mixture of cement mortar in the
proportion of 1:2 (1 cement : 2 fine sand) including testing of joints
Designing and constructing brick masonry manhole chamber of the
following size in brick work of class 75 in cement mortar 1:4
(1cement:4 fine sand), SN-4. top slab with 1:2:4 mix (1cement : 2
coarse sand :4 graded stone aggregate 20mm. nominal size) RCC
foundation slab 1:2:4 mix (1 cement : 2 coarse sand:4 graded stone
aggregate 40 mm nominal size) both inside and outside cement
plastering 12 mm thick with cement motar 1:3 (1cement :3 coarse
sand) finished with a floating coat of neat cement on inside face,
proper water proofing to ensure no ground water seepage in the
NSRW-20 manhole, M.S. polypropylene coated foot rests at 300 mm spacing,
benching and making channels in 1:2:4 cement concrete neatly
finished, including necessary centering and shuttering,
reinforcement, excavation, in all kind of soil, dewatering, refilling,
watering, ramming and removing the surplus excavated earth,
making good the same complete as required. Contractor shall submit
the structural design and drawings for the approval of Project
Manager prior to execution including SFRC Cover and frame (heavy
duty HD-20 grade designation)
NSRW-20 For Rectagular Manhole size 0.90X 0.80 m RM 22.00 5000.00 110000.00
Providing orange colour safety foot rest of minimum 6 mm thick
plastic encapsulated as per IS : 10910 on 12mm dia steel bar
conforming to IS : 1786 having minimum cross section as 23
mmx25mm and over all minimum length 263 mm and width as
165mm with minimum 112 mm space between protruded legs having
2 mm tread on top surface by ribbing or chequering besides
necessary and adequate anchoring projections on tail length on 138
19.16 mm as per standard drawing and suitable to with stand the bend test Each
and chemical resistance test as per specifications and having
manufacture's permanent identification mark to be visible even after
fixing, including fixing in manholes with 30x20x15 cm cement
concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms,
depth upto 1.5 m, including getting out the excavated soil, and then
2.10 returning the soil as required, in layers not exceeding 20 cm in depth,
including consolidating each deposited layer by ramming, watering,
etc. and disposing of surplus excavated soil as directed, within a lead
2.10.1 All kinds of soil
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Making desiliting chamber in rectangular shape, finished size upto
3.0 m x 1.5 m x 2.0. Including the all civil work {earth work in all type
of soil, providing and laying in position P.C.C & R.C.C, required
centering and shuttering, reinforcement steel, erecting brick work in
NSRW-22 FPS bricks of class designation of cement mortar in 1 :6, laying 12 to
15 mm thick cement plaster of 1 : 2 : 4 (1 Cement : 2 Coarse sand :
4 fine Sand). as per drawing or as per direction of engineer - in-
Rates includes the cost of providing and laying, Fixing
a) 450 mm thick coarse sand
b) 400 mm thick layer of Boulder of 50 mm to 100 mm in size,
c) 400 mm thick layer of of boulder 50 to 200 mm in size.
NSRW-22 d) Heavy duty manhole cover of 5400 x 540 x 100 mm two number Each 4.00 150000.00 600000.00
e) fixing heavy duty pvc rungs @ 300 c/c
f) fixing 250 mm dia to 450 mm dia inlet & outlet points
g) making required cutout of required size. (refer enclosed drawing)
EXTERNAL SEWERAGE SYSTEM
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse
19.6 sand : 10 graded stone aggregate 40 mm nominal size) all-round
R.C.C. pipes including bed concrete as per standard design:
250 mm dia. R.C.C. pipe
Providing and fixing stoneware gully trap of the following sizes in
brick masonary chamber of standard design with first class bricks
and trap to be set in cement concrete 1:2:4, both side 12mm thick
plastering with floating coat of neat cement. Making necessary
connections & providing water tight D.I. cover with frame of 300mm x
NSRW-23 300mm internal size. The weight of cover & frame not be less than 8 No 34.00 2000.00 68000.00
kg as per standard design. Including necessary excavation,
dewatering, refilling, watering, ramming and removing the surplus
excavated material and making good the same complete as
Designing and constructing brick masonry manhole chamber of the
following size in brick work of class 75 in cement mortar 1:4
(1cement:4 fine sand), SN-4. top slab with 1:2:4 mix (1cement : 2
coarse sand :4 graded stone aggregate 20mm. nominal size) RCC
foundation slab 1:2:4 mix (1 cement : 2 coarse sand:4 graded stone
aggregate 40 mm nominal size) both inside and outside cement
plastering 12 mm thick with cement motar 1:3 (1cement :3 coarse
sand) finished with a floating coat of neat cement on inside face,
proper water proofing to ensure no ground water seepage in the
NSRW-24 manhole, M.S. polypropylene coated foot rests at 300 mm spacing,
benching and making channels in 1:2:4 cement concrete neatly
finished, including necessary centering and shuttering,
reinforcement, excavation, in all kind of soil, dewatering, refilling,
watering, ramming and removing the surplus excavated earth,
making good the same complete as required. Contractor shall submit
the structural design and drawings for the approval of Project
Manager prior to execution including SFRC Cover and frame (heavy
duty HD-20 grade designation)
For Rectagular Manhole size 0.90X 0.80 m Each 28.00 5000.00 140000.00
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Providing orange colour safety foot rest of minimum 6 mm thick
plastic encapsulated as per IS : 10910 on 12mm dia steel bar
conforming to IS : 1786 having minimum cross section as 23
mmx25mm and over all minimum length 263 mm and width as
165mm with minimum 112 mm space between protruded legs having
2 mm tread on top surface by ribbing or chequering besides
necessary and adequate anchoring projections on tail length on 138
19.16 mm as per standard drawing and suitable to with stand the bend test Each 28.00 553.70 15503.60
and chemical resistance test as per specifications and having
manufacture's permanent identification mark to be visible even after
fixing, including fixing in manholes with 30x20x15 cm cement
concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms,
depth upto 1.5 m, including getting out the excavated soil, and then
2.10 returning the soil as required, in layers not exceeding 20 cm in depth,
including consolidating each deposited layer by ramming, watering,
etc. and disposing of surplus excavated soil as directed, within a lead
2.10.1 All kinds of soil
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm
Constructing brick masonry water tight grease trap (with three
chambers , each of 0.4 M X 0.6 M in plan) with 75 class designation
bricks in cement mortar 1 : 5 ( 1 cement : 5 fine sand ) earth work,
excavation in all kinds of soil, foundation concrete 1 : 4 : 8 mix (1
cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal
size) inside and outside plastering 12 mm thick with cement mortar 1
NSRW-25 : 3 (1 cement : 3 coarse sand) finished with a floating coat of neat
cement including constructing baffle wall, stainless steel angles on
corners, stainless steel perforated plates with stainless steel lifting
handles in each chamber, inlet and outlet fittings in UPVC, double
seal C.I. covers complete as per standard design:
Inside size 2.0m x 1.5m and 1.0m deep including two nos. 60x60 cm.
NSRW-25 C.I. Cover and frame (double seal weight of cover and frame not less Each 4.00 62372.59 249490.38
TOTAL PLUMBING 10921214.13 2844320.38
FIRE PUMP & PIPE & ACESSERIES
Supplying, installation, testing and commissioning of electric driven
terrace pump suitable for automatic operation and consisting of
following, complete in all respects, as required: (Terrace Pump)
(a) Horizontal type, multistage, centrifugal, split casing pump of cast
iron body & bronze impeller with stainless steel shaft, mechanical
confirming to IS : 1520
b) Suitable HP squirell cage induction motor TEFC type suitable for
operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of
protection for enclosure, horiziontal foot mounted type with Class-'F'
insulation, conforming to IS-325.
(c) M.S.fabricated common base plate, coupling, coupling guard,
foundation bolts etc.as required.
(d) Suitable cement concrete foundation duly plastered and with anti
vibration pads.
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS
sheet, 1200 mm in height with air release valve on top and flanged
connection to riser, drain arrangement with 25 mm dia gun metal
wheel valve with required accessories, pressure gauge and
paintingwith synthetic enamel paint of approved shade as required.
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Note:Contractor shall include in his rates for providing level
controllers, pressure switches, wiring, cabling from level controller /
pressure switch to panel etc. complete as required to operate the
system automatic/manual. Pump shall be protected against running
Providing, laying, testing & commissioning of 'C' class heavy duty
MS pipe conforming to IS 3589/IS 1239 including Welding, fittings
like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing
7 the pipe on the wall/ceiling with suitable clamp/support frame and
painting with two or more coats of synthetic enamel paint of required
shade complete as required :
Supplying, fixing, testing and commissioning of butterfly valve of PN
1.6 rating with bronze/gunmetal seat dulyISI marked complete with
11 nuts, bolts, washers, gaskets conforming to IS 13095 of following
sizes as required :
Providing, installation, testing and commissioning of non-return valve
14 of following sizes confirming to IS: 5312 complete with rubber gasket,
GI bolts, nuts, washers etc.as required
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63
16 mm dia male and female couplings duly bound with GI wire, rivets
etc. conforming to IS 636 (type-A) as required
Supplying and fixing first-aid Hose Reel with MS construction spray
painted in post office red, conforming to IS 884 complete with the
following asrequired.20 mm nominal internal dia water hose
17.1 thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm
nominal internal dia gun metal globe valve & nozzle.Drum and
brackets for fixing the equipmets on wall.Connections from riser with
25 mm dia stop gun metal valve & M.S. Pipe and socket.
Providing & fixing indoor type hose lockable cabinet frames
fabricated from 40mm x 40mm x 5mm angle iron sections and 16
gauge MS sheet with full front glass door and locking arrangement,
suitable to accommodate landing valves, 15 m long hoses, first-aid
NSRFP-3 hose reel and branch pipe nozzle & fire mans’ axe. The cabinet No. 56.00 2500 140000.00
frame shall be painted with one coat of primer and two or more coats
of synthetic enamel paint of approved make and shade, as required
(Approx 2.1 m (high) x 0.9 m (wide). The item shall be complete of
MS housing with front door.
NSRFP-2 Providing and fixing standard firemans axe with heavy rubber handle. No. 56.00 750 42000.00
Cost shall be inclusive of providing break glass box containing key
for the cabinet along with hamer)
Providing and fixing heavy duty SS Floor grating with frame of
approved design including setting in floor with cement motor to match
with floor finish as per architect requirement. (for FHC drain pipe)
Digitally signed by ANUJ
ITEM No. AMOUNT (in Rs.) AMOUNT (in
Description of Items Unit QUANTITY RATE (in Rs.)
(DSR/MR) (DSR) Rs.) (NON- DSR)
Supply, Installation, Fixing of CO2 type Fire Extinguisher of capacity
4.5 kg confirms to IS 15683, bearing ISI mark, consisting of High
Pressure seamless steel cylinder (IS 7285) and duly approved by
NSRFP-7 Chief controller of Explosive Nagpur, fitted with wheel type valve, fully Each 56.00 5000 280000.00
charged with CO2 gas (IS 15222), with non-conductor of electricity
discharge PVC horn along with Bend Pipe, internally siphon tube &
mounting brackets having fire rating.
Supply, Installation, Fixing of Stored Pressure (ABC Dry Chemical
Powder) type Fire Extinguisher of Capacity 9 kg Confirms to IS
15683, bearing ISI mark complete with brass forged squeeze grip
type valve fitted with pressure gauge , pressurize with dry Nitrogen
gas filled, with discharge nozzle with wall mounting bracket, having
fire rating of 3A & 21B.
Mechanical Foam type Fire Extinguisher. In HP Mild Steel Cylinders
ISI marked TAC approved fitted with pressure indicating gauge,
internal tube, squeeze lever type valve fully charged complete in all
respects including wall suspension bracket / trolley mounted and
confoming to IS:910
NSRFP-10 50 Litres (trolley mounted) No. 4.00 15000 60000.00
TOTAL (DSR/NON-DSR) 423487960.25 70836614.29
GRAND TOTAL 494324575.00
GRAND TOTAL 494324575.00
Digitally signed by ANUJ
aoc.pdf
Download all tender documents and submit your bid