ENHANCEMENT OF 11 KVA TRANSFORMER FROM 160KVA TO 300 KVA AT SITE I AND SITE II WITH ASSOCIATED WORKS AT AF STN KANHERI HILLS UNDER GE AF THANE
2025_MES_694571_1
82677/E8
Open Tender
Civil Works
Item Rate
180 days
GE AF THANE
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GE AF THANE
₹78,000
Yes
29 May 2025
23 Jan 2025
20 Feb 2025
23 Jan 2025
18 Feb 2025
6 Feb 2025
Amount
Supply, install, testing and commissioning of transformer as per IS : 1180 part - I 2014 level-II OR Latest notification issued by BEE as on date of acceptance of tender, step down, copper wound 11KV/433 Volts (at no load) AC 3 phase 50 Hz 300/315 KVA (as per Standard BIS Norms) capacity, core type, oil immersed naturally air cooled, oil natural air natural (ON/AN) , with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYn-11 with neutral brought out on secondary side (LV) and having taping at +5% to 10% in steps of 2.5% on HV side to be changed by means of hand operated off load tap changer gear. The maximum temperature rise should not exceed 50 degree Celsius in oil and 55 degree Celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temp of 40 degree Celsius transformer shall be of BOLTLESS core design. Transformer shall be double wound, core type with low loss, non ageing, high permeability prime grade CRGO with M4 grade or better, perfectly insulated and clamped to minimize noise and vibrations. The transformer shall be IS/IEC 60076and as per IS-1180 part - I of 2014 marked and shall comprise of the following :-
(a) One cable box on HT side (Primary side) consisting of three nos porcelain bushing with copper rods, complete with nuts and washer , with cable glands suitable for reception/taking out 3 core 120 Sqmm, HT 11000 volts grade, XLPE insulated and PVC sheathed, heavy duty , armoured cables including jointing materials complete. (b) One cable box on LT side(secondary side) consisting of four nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands suitable for reception/taking out 400 sqmm 3.5 core, LT 1100 volts grade, PVC/XLPE insulated and PVC sheathed, heavy duty, armoured cables including jointing materials complete. (c ) conservator with filter type drain valve and oil level gauge. (d) De-hydrating breather with first fill of dehydrating agent (Silica Gel). (e) Explosive vent, Thermometer pocket on tank cover, oil level gauge, Oil drain filter valve, Lifting ligs,oil filling hole with cap/plug with connection plate complete, Air releasevalve plug and four nos plain solid cast steel detachable rollers. (f) One no 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree Celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device. (g) Two earthing terminals on tank cover to facilitate fixing of 50x6mm galvanised iron earth strip for earthing of body. (h) Rating plate and terminal marking plate. (j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral.
(k) First fill of new and unused transformer oil, IS-335 of 1986 marked, filtered and tested up to 50 KV dielectric strength at 2.5 mm air gap between testing electrodes, specific resistance at 27 Degree Celsius Ohm-om 500 x 10 the power12, water content 50 PPM, Dielectric dissipation factor (tan Deta at 90 degree Celsius) 0.005, Neutralisation value mg of KOH/gm of oil 0.03, Inter facial tension N/M at 27 Degree Celsius - 0.04, flash point 140 Degree Celsius and sluge 0.1 % by weight. (l) Providing adequate size and nos of channels, embedded in floor, for movement of transformer. (m) Transformer losses shall not exceed the loses mentioned in IS: 1180 part-Iof 2014 Part - I with energy Efficiency level –IIOR Latest notification issued by BEE as on date of acceptance of tender. (n) Oil temperature indicator. Note: (a) OEM should be BIS and BEE certified for all the ratings of the transformer that are to be submitted. (b) Rate quoted includes the cost of making and Testing of control wiring connection at the Transformer and RMU/VCB for the Temperature alarm/Trip, Gas alarm/Trip. And the Control cable shall be measured and paid separately under relevant item (c) Expenses / cost for FAT as nominated by the accepting Officer for FAT shall be included in the rate quoted. (d) The contractor should obtain warranty from OEM for minimum period of 5 years for all the transformer supplied.
Supply, install, testing and commissioning of transformer as per IS : 1180 part - I 2014 level-IIOR Latest notification issued by BEE as on date of acceptance of tender, step up, copper wound 433Volts/11KV Volts (at no load) AC 3 phase 50 Hz 300/315 KVA (as per Standard BIS Norms)capacity, core type, oil immersed naturally air cooled, oil natural air natural (ON/AN) , with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYn-11 with neutral brought out on secondary side (LV) and having taping at +5% to 10% in steps of 2.5% on HV side to be changed by means of hand operated off load tap changer gear. The maximum temperature rise should not exceed 50 degree Celsius in oil and 55 degree Celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temp of 40 degree Celsius transformer shall be of BOLTLESS core design. Transformer shall be double wound, core type with low loss, non ageing, high permeability prime grade CRGO with M4 grade or better, perfectly insulated and clamped to minimize noise and vibrations. The transformer shall be IS/IEC 60076and as per IS-1180 part - I of 2014 marked and shall comprise of the following :-
(a) One cable box on HT side (Primary side) consisting of three nos porcelain bushing with copper rods, complete with nuts and washer , with cable glands suitable for reception/taking out 3 core 120 Sqmm, HT 11000 volts grade, XLPE insulated and PVC sheathed, heavy duty , armoured cables including jointing materials complete. (b) One cable box on LT side(secondary side) consisting of four nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands suitable for reception/taking out 400 sqmm 3.5 core, LT 1100 volts grade, PVC/XLPE insulated and PVC sheathed, heavy duty, armoured cables including jointing materials complete. (c ) conservator with filter type drain valve and oil level gauge. (d) De-hydrating breather with first fill of dehydrating agent (Silica Gel). (e) Explosive vent, Thermometer pocket on tank cover, oil level gauge, Oil drain filter valve, Lifting ligs,oil filling hole with cap/plug with connection plate complete, Air releasevalve plug and four nos plain solid cast steel detachable rollers. (f) One no 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree Celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device. (g) Two earthing terminals on tank cover to facilitate fixing of 50x6mm galvanised iron earth strip for earthing of body. (h) Rating plate and terminal marking plate. (j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral.
(k) First fill of new and unused transformer oil, IS-335 of 1986 marked, filtered and tested up to 50 KV dielectric strength at 2.5 mm air gap between testing electrodes, specific resistance at 27 Degree Celsius Ohm-om 500 x 10 the power12, water content 50 PPM, Dielectric dissipation factor (tan Deta at 90 degree Celsius) 0.005, Neutralisation value mg of KOH/gm of oil 0.03, Inter facial tension N/M at 27 Degree Celsius - 0.04, flash point 140 Degree Celsius and sluge 0.1 % by weight. (l) Providing adequate size and nos of channels, embedded in floor, for movement of transformer. (m) Transformer losses shall not exceed the loses mentioned in IS: 1180 part-Iof 2014 Part - I with energy Efficiency level –II OR Latest notification issued by BEE as on date of acceptance of tender. (n) Oil temperature indicator. Note:(a) OEM should be BIS and BEE certified for all the ratings of the transformer that are to be submitted. (b) Rate quoted includes the cost of making and Testing of control wiring connection at the Transformer and RMU/VCB for the Temperature alarm/Trip, Gas alarm/Trip. And the Control cable shall be measured and paid separately under relevant item (c) Expenses / cost for FAT as nominated by the accepting Officer for FAT shall be included in the rate quoted. (d) The contractor should obtain warranty from OEM for minimum period of 5 years for all the transformer supplied.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm.
Supply and fix cable jointing kit for 11 KV grade cable for in door termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 70 to 120 sq mm.
Supply and fix cable jointing kit for 11 KV grade cable for Out door termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 70 to 120 sq mm.
Material and labour in repairs for earthing complete with copper earth plate electrode 600mmX 600mmX 3.15 mm thick buried directly in ground vertically ( earth pit not less than 2.25 metres deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including copper strip of size 20 X 3 mm from earth electrode to test point or up-to 7.5mtr whichever is less by means of GI bolts, nuts, check nuts and washers all as per electrical plate no 3 of SSR Part-I provision of G I Pipe 40mm bore eight grade for protection of GI strip and GI watering pipe of 20 mm bore medium grade,GI funnel with wire mesh,including char-coal, salt packed all around the earth electrode plate in layers,PCC earth pit chamber 1:3:6 type C1,RCC cover 1:2:4 type B1,excavation,earth work in any strata and returning filling, removal of surplus soil and testing for required value complete all as specified and directed.
DARSHAN CONSTRUCTION Co. (BID ID -3237390)
sapana enterprises (BID ID -3237088)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .