BILL OF QUANTITY
S.No. Sub-Head DSR NDSR
A CIVIL WORK 18,17,495.90 -
B ELECTRICAL AND LIFT WORKS 4,00,820.00 1,92,22,322.37
D HVAC PLUMBING 4,84,970.80 1,47,109.40
E DUCTING AND GRILLS 20,70,368.00 19,20,491.80
F HVAC ELECTRICALS WORKS 2,57,536.00 17,42,466.43
Add Cost Index @7% on DSR 2021 6,54,992.01 -
Add GST @6.33% on DSR 2021 items 6,33,760.91 -
Grand Total (1+2) 3,88,27,816.62
Grand Total (1+2) 3,88,27,816.62
Digitally signed by
CHANDRESH KUMAR
MOTI LAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY, ALLAHABAD
Name of Work: Proposal of New Infrastucture Projects in the Institute Campus
TENDER BILL OF QUANTITY
S.No. Discription of items Qty. Unit Rate DSR Market MR Rate Amount DSR Amount MR
#REF! A2 CONSTRUCTION OF TRANSFORMER PLATFORM, TRENCH, MANHOLE ETC.
Earth work in excavation by mechanical means (Hydraulic excavator) / manual
means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm
a DSR2021-on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, 100.00 Cum 286.85 28,685.00 -
2.8.1 including getting out the excavated soil and disposal of surplus excavated soil as
directed, within a lead of 50 m. All kinds of soil.
Providing and laying in position cement concrete of specified grade excluding the
cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement :
4 coarse sand (zone-III) derived from natural sources : 8 graded stone
aggregate 40 mm nominal size derived from natural sources)
Centering and shuttering including strutting, propping etc. and removal of form
c DSR2021-for : Walls (any thickness) including attached pilasters, butteresses, plinth and 650.00 Sqm 669.55 4,35,207.50 -
4.3.2 string courses etc
Centering and shuttering including strutting, propping etc. and removal of form
for : Suspended floors, roofs, landings, balconies and access platform.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing
e DSR2021-in position and binding all complete upto plinth level. Thermo-Mechanically 2600.00 Kg 89.65 2,33,090.00 -
4.20.1.4 Treated bars of grade Fe-500D or more.
Providing and laying in position ready mixed or site batched design mix cement
concrete for reinforced cement concrete work; using coarse aggregate and fine
aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland
/Portland Slag cement, admixtures in recommended proportions as per IS: 9103
to accelerate / retard setting of concrete, to improve durability and workability
without impairing strength; including pumping of concrete to site of laying,
curing, carriage for all leads; but excluding the cost of centering, shuttering,
finishing and reinforcement as per direction of the engineer-in-charge; for the
following grades of concrete.
Note: Extra cement up to 10% of the minimum specified cement content in
design mix shall be payable separately. In case the cement content in design
mix is more than 110% of the specified minimum cement content, the
contractor shall have discretion to either re-design the mix or bear the cost of
All works upto plinth level
Concrete of M25 grade with minimum cement content of 300 kg /cum
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with
collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints etc. complete : 250 mm
diameter RCC pipe
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with
collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints etc. complete : 300 mm
diameter RCC pipe
Constructing brick masonry circular manhole 1.22m internal dia at bottom and
0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement
plaster 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished
with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3
coarse sand : 6 graded stone aggregate 40mm nominal size) and making
DSR2021-necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4
19.11.1. graded stone aggregate 20mm nominal size) finished with a floating coat of neat
1 cement, all complete as per standard design : 1.68 m deep with SFRC Cover and
frame (heavy duty HD-20 grade designation) 560mm internal diameter
conforming to I.S. 12592, total weight of cover and frame to be not less than
182kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate 20mm nominal size) including centering, shuttering all
Constructing brick masonry circular type manhole 0.91 m internal dia at bottom
and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand), in side
cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand)
finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1
cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size), and
making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand
: 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of
j DSR2021-neat cement, all complete as per standard design : 0.91 m deep with S.F.R.C. 12 Each 11886.45 1,42,637.40 -
19.9.1.1 cover and frame (heavy duty, HD-20 grade designation) 560 mm internal
diameter conforming to I.S. 12592, total weight of cover and frame to be not
less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4
graded stone aggregate 20 mm nominal size) including centering, shuttering all
complete. (Excavation, foot rests and 12mm thick cement plaster at the external
surface shall be paid for separately): With common burnt clay F.P.S. (non
modular) bricks of class designation 7.5
TOTAL of Subhead-A 18,17,495.90 -
B ELECTRICAL WORK
Supply, Installation, Testing & Commissioning of Outdoor type Package Sub- 2 Job 35,14,208.00 70,28,416.00
station as per following of 11/0.433KV, 630 KVA Transformer(Oil cooled), along
with RMU, connection between RMU & transformer with 11KV, 3 No. 3Cx95
Sq.mm XLPE amoured cable, Connection between Transformer & 1000A LT ACB
with 1200A Aluminium Busbar, padlocks etc as required. All HT termination shall
be 11 KV heat shrinkable type. Transformer shall be 630 KVA, 11 KV/433 V, Oil
Cooled type, core type,double wound with copper, oil immersed ONAN cooled
1 NS-B1 distribution transformer with hermetically sealed tank arrangement having a no
load voltage ratio of 11 kV/433V. Tapping +5% to -5% in steps of 2.5% shall be
provided at line end of HV winding. Chnging of taps shall be carried out by
means of OFF Load Tap Changer and making suitable size of Plinth, MS channel
etc. . The transformer shall be manufctured as per latest IS 1180 Level 1). All
the manufctured as per latest IS 1180 Level 1). All the above equipments should
be connected and installed in a prefabricated Enclosure as per following details.
Make-Schneider, ABB, Siemens or Equivalent make.
HT SWITCHGEAR / Ring Mains Unit
Three Way, 11kV, Indoor, Non Extensible, free standing, metal clad, SF6
a insulating, Ring Main Unit comprising of two numbers 630 A fault making/load
breaking switches and one number 200A tee-off circuit breakers complete with
all accessories as per followings:
Digitally signed by
CHANDRESH KUMAR
MOTI LAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY, ALLAHABAD
Name of Work: Proposal of New Infrastucture Projects in the Institute Campus
TENDER BILL OF QUANTITY
S.No. Discription of items Qty. Unit Rate DSR Market MR Rate Amount DSR Amount MR
i. IDMT Relay for Circuit Breakers - Self
The Ring Switches and Tee- Off Circuit Breaker are Provide with Intergrated
Earthing Switches with Making Cpacity.
iii. live cable indicator for ring switches.
iv. SF6 Gas pressure indicator.
Padlocking facility Powered 630Amps, 21kA for 3 sec., SF6 insulated Non-
Extensible Compact switchgear (Type CCT2 ) consisting of two No. of Fixed
Manual Load Break Switch & one No. fixed Manual Vacuum Circuit Breaker in
SF6 insulated Stainless steel enclosure with self-powered series trip
microprocessor base numerical over current & earth fault relay
(IDMTL+Instantenius) for protection.
RMU-NON-Extensible FBX-C /CCT2 (2 Nos. Isolators O, 1 No. Vacuum Circuit
b. Breaker - T2) with AL Busbar)-BIL 28/75kV function consisting of 2 No. of Load
Break Switch as per following details.
i. Operation of LBS- Manual.
ii. Cable Switch Rating- 12KV, 630A, 21KA/3 sec.
iii. Cable Bushing Rating- 630A,
iv. Cable Cover:- As per our standard
v. Fixed type Capacitive voltage indication.
vi ON/OFF/EARTH Switch via MIMIC.
Bottom Cable Termination- Suitable upto 300sqmm, T2 function Type:- 3
vii position Disconnector and Earthing switch equipped with separate drive unit. T2
equipped with over current time release for transformer protection.
viii Vacuum circuit breaker 12 kV, 630 A, 21 KA/3 sec.
ix. Operation of breaker — Manual
Self Powered Electronic numerjcal protection relay providing over-current &
earth fault protection — Schneider make DPX VS
xi. Ring core protection current transformers.
xii Capacitive voltage shall be indication fixed type.
xiii. ON, OFF, EARTH indication on the front mimic of the panel.
xiv. Cable box for termination of cable upto 300sqmm
xv Cable cover standard.
xvi Emergency trip push button.
xvii Shunt trip coil
RMU Accessories:- 1 No. operating Handle & Manometer for SF6 gas pressure
indication. Right Angled Cable Boots suitable for 1 Run x 3 C x 300 Sq mm
c TRANSFORMER (Make - Kotson/Danish/Equivalent)
i. Standard - As per IS 1180 level-2
ii Type - ONAN, Hermatically sealed corrugated tank
iii Ratio- 11 KV/433V,
iv Capacity:- 630 KVA,
v Vector Group- Dyn11,
vi Tapping - Off Load Tappings +5% to -5% in steps of 2.5%,
vii Winding- Double Wound Copper,
viii Class of Insulation - A,
ix Ambient Temperature- 50 Deg C,
x Temperature rise in oil over ambient - 40 Deg C
xi Temperature rise in winding over ambient- 45 Deg C
xii Losses at 50% loading - 1510 W (Max)
xiii Losses at 100% loading - 4300 W (Max)
xiv %lmpedance- 4.5% (IS TOL)
Transformer Accessories Oil Temperature Indicator, Winding Temperature
PSS enclosure shall be Outdoor Type 2mm thick Galvanized Enclosure shall have
lP54 degree of protection for HT & LT switchgear compartment & lP34 degree of
protection for Transformer Compartment. The enclosure exterior shall be
powder coated with Poly Prepelene based paint. HT & LT compartment will be
provided with the door and pad locking arrangement. Transformer Compartment
will be provided with Cover. The Compartment illumination lamp with door
operated switch shall be provided for HT,Transformer and LT compartment.
Lifting(Bucket) arrangement shall be provided with each PSS and internal
earthing connection shall be copper strips.
1200 Amp Aluminium LT Busbar shall be 4 Pole between Transformer Secondary
to 1000 Amp ACB. However copper flexible shall be provided between
Transformer & LT Incomer Connection alongwith Main Busbar.
Incomer: 1000 Amp 1000 Amp FP Electrically operated horizontal drawout type
Air Circuit Breaker microprocessor based releases for O/C, S/C & earth fault
f protection with instantaneous. (50 KA)
Outgoing: 6 Nos. 400 Amp, FP Moulded Case Circuit Breaker (50 KA).
Accessories: ON/OFF/TRIP Indication. RYB Indicating lamp
Package Substation described as above.
Supply, Installation, Testing & Commissioning of HT Cable 11 KV grade, 3C x
120 Sq.mm aluminum conductor XLPE (Cross linked polyethylene) insulated,
PVC bedded, Galvanized flat steel strip armoured cables confirming to I.S. 7098
(part -II with latest amendments) II KV grade at a depth of 900 mm below
ground level over a cushion of 100 mm thick fine river sand all around and
protected with well burnt bricks on sides and top / MS clamp on wall along the
cable & back filling after digging the soil/ trough cable laying machine, complete
in all respect as per direction of Engineer incharge. The armoring of cable shall
be properly connected with the earth terminal of the panel and as required lugs
and clamp etc. If cable crossing through road mail line then suitable boring of
road/ rail line may be done/ trough cable laying machine & suitable permission
obtained by contractor from Nagar Nigam/ Railway authority for laying of cable
and suitable size GI pipe to be fixed across the road/rail line.
Supply and making End Termination of 120 Sq mm indoor cable with heat
3 NS-B3 shrinkable jointing kit complete with all accessories including lugs suitable for 3 10 Nos. 2,398.00 23,980.00
core, XLPE aluminium conductor cable of 11 KV grade as required
Supply and making straight through 120 Sqmm cable jointing with heat
shrinkable jointing kit complete with all accessories including ferrules suitable
for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as
Digitally signed by
CHANDRESH KUMAR
MOTI LAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY, ALLAHABAD
Name of Work: Proposal of New Infrastucture Projects in the Institute Campus
TENDER BILL OF QUANTITY
S.No. Discription of items Qty. Unit Rate DSR Market MR Rate Amount DSR Amount MR
Supply, Installaion, Testing & Commissioning of aluminum conductor XLPE
armored served sheathed cable 1100 Volts grade at a suitable depth of 1000
mm below ground level over cushion of 75 mm thick sand all around and
protected with well burnt bricks on sides & on top along the cable & back filling
after digging the soil & its back filling/ On wall/ floor the cable run canceled
manner, with cutting and plastering in hard rock / soft rock after excavation,
5 NS-B5 complete in all respect as per direction of Engineer in charge. If crossing the
cable in road/ rail line suitable boring to be done across the road/Rail Line/ cable
trenching machine and also suitable size of GI pipe to be fixed across the
road/rail line and also in pole cable terminated in suitable size of GI pipe. The
armouring of cable shall be properly connected with the earth terminal of the
panell F P and as required lugs, Gland and clamp etc properly fixed. Make -
Havells, KEI, Kalinga, Gloster, Finolex, Rallison.
a NS-B5.1 3C x 240 sq mm.sqmm Al Armoured cable 500.00 Metre 1,570.85 7,85,427.00
b NS-B5.2 3.5C x 120 sq mm. Al Armoured cable 840.00 Metre 823.42 6,91,675.32
c NS-B5.3 3.5C 95 sq mm. Al Armoured cable 950.00 Metre 670.90 6,37,353.58
d NS-B5.4 3.5C x 50 sq mm. Al Armoured cable 675.00 Metre 396.78 2,67,829.54
Supplying and making End Termination with brass compression gland for
6 NS-B6 following size of PVC insulated and PVC sheathed / XLPE aluminium conductor
cable of 1.1 KV grade as required
a NS-B6.1 3C x 240 sq mm.sqmm Al Armoured cable 10 Nos. 355.00 3,550.00
b NS-B6.2 3.5C x 120 sq mm. Al Armoured cable 15 Nos. 198.00 2,970.00
c NS-B6.3 3.5C 95 sq mm. Al Armoured cable 30 Nos. 195.00 5,850.00
d NS-B6.4 3.5C x 50 sq mm. Al Armoured cable 40 Nos. 164.00 6,560.00
Supplying and making end termination with aluminium lugs for following size of
7 NS-B7 PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV
grade as required
a NS-B7.1 3C x 240 sq mm.sqmm Al Armoured cable 60 NOS. 372.00 22,320.00
b NS-B7.2 3.5C x 120 sq mm. Al Armoured cable 90 NOS. 150.00 13,500.00
c NS-B7.3 3.5C 95 sq mm. Al Armoured cable 180 NOS. 109.00 19,620.00
d NS-B7.4 3.5C x 50 sq mm. Al Armoured cable 240 NOS. 55.00 13,200.00
DSR_E& Supply, Installation, Testing & Commissioning of Earthing with copper earth
M plate 600 mm X 600mm X 6 mm thick including accessories, and providing
2022 masonry enclosure with cover plate having locking arrangement and watering
5.6 pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
DSR_E& Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground
M as strip earth electrode, including connection/terminating with nut, bolt, spring,
2022 washer etc. as required. (Jointing shall be done by overlapping and with 2 sets
5.8 of brass nut bolt & spring washer spaced at 50mm)
Supply, Installation, Testing and Commmmissioning of 11 KV non- extensible 1 Job 16,81,500.00 16,81,500.00
outdoor type RMU lP55 floor mounted with Motorizes Load Break switch 02 nos.
as incomer, fixed type Motorized Vacuum Circuit Breakers- 05 Nos. as outgoing.
All live parts, bus bars of RMU should be enclosed in tank to avoid multiple inter
connections & sealed for life robotically for three sides and one side manul
welded non magnetic/ non ferrite/ stainless steel tank Grade 304 of minimum
2.5 mm thick having IP 67 degreee of protection filled with SF6 gas to fulfill the
requirement as per IEC 60376,60376 B as insulation with leakage rate less than
0.1% per year tested as per IEC 62271-200. Suitable site replaceable Cable
bushings. The unit shall have front cable entry for ease of installation. RMU
should be complete with all accessories such as Terminal boots, VPIS, cable
supports, all front cable terminations, mechanical indications ON/OFF,
Manometer as per IEC standards 62271-200, 60056,060129, 60265, 60298,
60420, 60529 and 60694. Altitude of installation up to 1000 m as per IEC
60120. The unit shall include the following with all necessary standard fitting
required at site. RMU should be tested for an internal arc fault of 21 kA for 1 sec
as per IEC62271-200 and paint shade thickness should be as per AIS 632 IS- 5
complete all specified and directed. The outer enclouser shall cover the full
length of the switch gear, to ensure IP55 protection for full door covering of
complete switchgear etc.
The above unit shall include the following with all necessary standard fittings as
required at site and incorporating the following accessories:
a Incomer - 2 Nos. of followings.
(i) Manually operated 12 kV, 630A Load Break swich and Earthing switch with
making capacity
(ii) "Live Cable" LED Indicators through Capacitor Volatge Dividers mounted on
ii. (iii) Earth fault passage indicator one per LBS
iv. (iv) Mechanical ON/OFF/EARTH lndixation
(v) Cable boxes suitable for 1x3CX300 sq mm XLPE Cable with right angle Cable
Termination Protectors, situated towards side of RMU etc.
(vi) Cable Door should be arc proof and interlocked with respective Earthing
vi. Switches, For safety of operator it should not be possible to open the cable Door
unless the earth Switch is ON etc.
b Outgoing: 5 nos.of followings:
(i) 630A Vacuum Circuit Breaker module for
making and breaking of fault current alongwith Earth Switch
ii (ii) Short time breaking current - 21 KA/ 3 sec. Making Capcity - 52.5 KA
iii (iii) Internal Arc - 21 Kai 1 sec
iv (vi) Nominal operating gas pressure - 1.3 (minimum) Bar abs.
v (v) Power frequency withstand voltage- 28 KV
vi (vi) Impulse withstand voltage- 75 KV
vii (vii) Outdoor Enclosure - lP55
viii (viii) Front cover mechanism - IP2X
ix (ix) Cable covers- 3 X
x Stored Energy mechanism for Motor operation -24
(xi) Cable box for front termination of the cable suitable upto 3 core 300 sqmm,
11 KV XLPE cable.
xii (xii) Operation Counter
(xiii) Self-Powered Microprocessor based Relay ( 3 O/C & E/F) with RS485 port
and with standard settinas
xiv (xiv) Protection CT - 50 - 100I1A, Cl - 5P10, 2.5 VA burden
xv (w) Suitable site replaceable Cable bushings
(wi) Arc proff cvable covers with self Interlocking mechanism between doors,
earth switch, disconnector & VCB
xvii (xvii) Capacitive voltage indication fixed type system
(xviii) Mechanical Indications for breaker ON, OFF, EARTH, TRIP, Spring Charged-
c Capacitive voltage indication fixed type VPIS 9 -15
d. Necessary interlocking arrangement for seafty and operations
e Stored Energy mechanism for Motor operation- 24 \
f One No. Manometer
Digitally signed by
CHANDRESH KUMAR
MOTI LAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY, ALLAHABAD
Name of Work: Proposal of New Infrastucture Projects in the Institute Campus
TENDER BILL OF QUANTITY
S.No. Discription of items Qty. Unit Rate DSR Market MR Rate Amount DSR Amount MR
Safety lnerlocks shall be provideed as per relevant IEC/IS Standards and
Manufacturers directions.
h All cable bushing should be site replaceable type.
i Module should be accommodated as per manufacture's design
RMU cable box shall be front accessible type to have easy access to protection
Connection between cable riser panel & coupler VCB shall be cable connected
k using touch proof kits and same shall be done by OEM as per their
recommended guidelines.
Vacuum Interrupter should be of same make of RMU. Cable box should be arc
proof with bolted door and interlocked with respective erthing switches. Doors
should be removable for the ease
access to terminate cables.
11.0 NS-B11 PASSANGER LIFT (13 PASSENGER)
Supply, installation, testing, commissioning,and final testing of 13 Passenger 1 Job 44,78,998.93 44,78,998.93
(884 KG) automatic lift complete (including all the civil and electrical works
necessary for successful installation and commissioning of the Lift as per site
requirement) as per CPWD specification including automatic rescue device
(ARD), All standard equipments, accessories and control equipments as per
manufacturer's design and as per CPWD specification (Part III LIFTS) on turnkey
basis, Conforming to NBC/statutory norms and fulfilling following requirements.
Type : Passenger lift.
Load : As per specified elsewhere 13 Passenger (884 Kg) (for each person
standard weight 68 Kg.)
Speed : 1.00 Meter / second.
Control : ACV3F, 32 bit Microprocessor integrated serial communication control
system with RMS (Remote monitoring systema0 / BMS (Building Monitoring
system) supporting software.
Motor / Machine : Permanent magnetic synchronous gearless motor.
Operation : Simplex collective selective with / without lift attendant.
Total rise : About 12 meters (Approx) two stops only.
Landings :- All floors on same side.
G+ 4 floor (5 Stops/5 Landings)
Signals : Digital car position indicator, car travel direction indicator inside car &
at all landings, Voice annunciator with suitable music shall provide in the lift car.
Shaft size : As per manufacturer's design and as per CPWD specification (Part
III Lifts), shaft to be constructed separately.
Guide rail : As per manufacturer's specification.
Lift & Car size : As per manufacturer's design and as per CPWD specification
(Part-III Lifts)
Car entrance : As per manufacturer's design and as per CPWD specification
(Part-III Lifts)
Landing entrance :- As per manufacturer's design and as per CPWD
specification (Part-III Lifts)
Car Door : S.S. (Stainless steel) hairline finish centre / Telescopic opening door
with vision panel.
Landing door : Brushed S.S. finish (Stainless steel) hairline finish centre /
Telescopic opening door with vision panel.
Door operation : Automatic electric power operated door, full height infra red
curtain with multiple cross / cross light beams.
Car interior : S.S. (Stainless steel) panel with hair line finish on all sides.
Car floor : Anti skid PVC flooring on heavy duty MS (Mild Steel) platform.
Car ceiling & lighting : S.S. (Stainless steel) finishes with aesthetic appearance
with LED ceiling lights.
Car ventilation : Pressure fan / Blower fan (Car fan with automatic appearance
with LED ceiling lights.
Emergency lighting in car : Battery operated emergency lighting in the lift car.
Intercom system : Battery operated Intercom system in lift car, machine room
and ground floor / control room.
Emergency alarm : Battery operated alarm bell system in lift car & control room
/ ground floor.
Position of machine room : Directly above the hoist-way.
Electric power supply : AC 415V, 3 phase, 50 Hz & AC 230V, 1 Phase 50 Hz
terminated in machine room.
Fire man switch : Fire man switch at machine room / Terminal landing.
All car panel buttons and all floor switches must be with brail language as per lift
Audio visual indication in the lift car showing overloading shall be provided such
that doors kept open till excess load is removed.
Spring buffer / Hydraulic buffers shall be provided.
Mechanical over speed governor, door key holes in the floor doors shall be
Lift machine hoisting arrangement in the lift machine room and monkey ladder
for lift pit should be provided by the lift agency, along with the other steel
structure works, foundations for the machines etc.
In the hoist way facia plate shall be provided.
Permanent wiring in lift machine room and lift well with proper no. of light
points, with fixtures, exhaust fan, plug points and 3 phase 440 V power supply
shall be made available by the department in lift shaft, machine room or at
Car top safety barricade shall be provided.
ARD (Automatic rescue device) : Solid state inbuilt automatic rescue device
(ARD) for automatically rescues passengers trapped in the lift car in between
floors in the event of power failure. Automatic operation and immediate action
in the event of mains failure capable to move the lift to the nearest landing,
opens the automatic door of the lift car and floor. Sealed maintenance free
battery backup with automatic charging unit and auto changeover device on
13 Passenger (884Kg.)
TOTAL OF SUBHEAD B 4,00,820.00 1,92,22,322.37
Sub Head 'A'- Machinery
1) DSR 2019Variable Refrigerant Volume / Flow Air-conditioning System
Digitally signed by
CHANDRESH KUMAR
MOTI LAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY, ALLAHABAD
Name of Work: Proposal of New Infrastucture Projects in the Institute Campus
TENDER BILL OF QUANTITY
S.No. Discription of items Qty. Unit Rate DSR Market MR Rate Amount DSR Amount MR
Supply, Instalaltion, testing and commissioning of Variable Refrigerant Flow
/Volume (VRF/VRV) (with the latest technology/version) with All-Inverter driven
Compressor, modular type airconditioning system with stepless modulation
for both heating & cooling modes, complete with indoor and outdoor units,
individual remote controller and centralized controller, interconnected
refrigerant piping with insulation, Y joints, full charge of refrigerant gas including
additional top up and oil, control cabling etc. as per detail given in specifications
and having following items. The prices to be given in Indian rupees including
all taxes and duties and delievered at site. Refrigerant to be used shall be - R
It shall be complete as per specifications,with connectivity to automation for A/M
status, RUN status & Remote start/stop command.(Bacnet/IP) with multi
connection kits for each outdoor unit & First charge of refrigerant gas for the
VRF/VRV Units & required MS frame work or required foundation & anti vibration
pads for mounting the outdoor units. installation, testing & commissioning of air
cooled VRV/VRF system shall include pipe pressure testing & flushing with
nitrogen, charging of gas/oil etc. & will include all lifting/shifting etc.
1.1) Air Cooled VRV / VRF Outdoor Unit
Supply Installation, Testing & Commissioning of modular type Variable
Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable
for cooling and heating, having all hermetically sealed inverter type Scroll
Compressor(s), minimum two compressors for above 16 HP modules,
microprocessor based Controller, top discharge type condensing unit(s), with R
410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as
required. The unit shall deliver the rated capacity at AHRI Conditions and work
even at50°Cambient temperature without tripping. The unit shall be suitable to
work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled
with first charge of the refrigerant and ready for use as required. The COP at
AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 .
1.1.1) DSR 201914 H.P Cool / Heat Pump Unit 1 Nos. 229852.00 2,29,852.00 -
1.1.2) DSR 202016 H.P Cool / Heat Pump Unit 1 Nos. 262688.00 2,62,688.00 -
1.1.3) DSR 202132 H.P Cool / Heat Pump Unit 1 Nos. 525376.00 5,25,376.00 -
1.1.4) DSR 202242 H.P Cool / Heat Pump Unit 1 Nos. 689556.00 6,89,556.00 -
1.1.5) DSR 202344 H.P Cool / Heat Pump Unit 2 Nos. 722392.00 14,44,784.00 -
Indoor Units -
Supply, Instalaltion, testing and commissioning of Indoor units equipped
with pre-filter, fan section with suitable static fan to distribute the air as
per approved shop drawings, multispeed motor, coil section with DX coil, -
outer cabinet / cassette panel, drain pan, insulation, pipe connections etc. of
various capacities as per specifications and drawings.
1.2.1 Cassette Unit - Supply, installation, testing and commissioning of following
minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted
unit equipped with synthetic washable media pre-filter, fan section with low
noise fan/dynamically balanced blower, multispeed motor, coil section with DX
DSR Copper coil, electronic expansion valve, outer cabinet, drain pump, grill,
2019 necessary supports, vibration isolation, cord less remote control etc., suitable
for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as
required. The unit shall have automatic force shut down provision in case of fire
on receiving signal from BMS System. The cooling capacity of indoor unit will be
at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
1.2.3) Ductable Unit - Supply, installation, testing and commissioning of following
minimum capacity and external static pressure VRF/VRV ceiling mounted
ductable type Indoor unit equipped with washable synthetic media pre-filter,
fan section with low noise fan/dynamically balanced blower, multispeed
motor, coil section with DX copper coil, electronic expansion valve, corded
remote control, outer cabinet, vibration isolators, drain pan, other necessary -
supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50
Hz complete as required. The unit shall have automatic force shut down
provision in case of fire on receiveing signal from BMS System. The cooling
capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19
Degree C WB temperature.
1.2.3.6 DSR High Static Ductable units (minimum 110 pascal external static
2019 pressure)
2.3) Y-joints For Indoor Unit -
Supply,installation,testing and commissioning of Imported Y/T refnet Joints with
insulation to connect indoor units with main header as per drawing. It should be
MR complete as per manufacturing standards & as per directions of Engineer-in- 40 SET 7,904.00 3,16,160.00
(1 Set will comprise of 2 Y/T Refnet Joints each for sution & discharge side)
2.4) Self Diagnostic Type Individual Remote Controllers (Corded Type) -
Supply, Installation, Testing & Commissioning of Corded Wall Mounted Type Self
MR Diagnostic Type Digital Programmable Individual Remote Controllers of latest 35 SET 4,114.00 1,43,990.00
generation for setting required temperature for various Indoor Unit.
2.5) Self Diagnostic Type Individual Remote Controllers (Cordless Type) -
Supply, Installation, Testing & Commissioning of Cordless Type Self Diagnostic
MR Type Digital Programmable Individual Remote Controllers of latest generation 2 SET 2,815.00 5,630.00
for setting required temperature for various Indoor Unit.
2.6) Main Intelligent Programmable Central Controller (Corded Type) -
Supply, installation, testing and commissioning of Main centralized controller /
manager digital type of latest generation for VRV/VRF system for controlling all
the indoor & outdoor units installed in building with adapters (for connecting
additional indoor units, cost for the same is deemed to be included in this item)
MR with On / Off, touch screen and Temparature Controls, fan speed, scheduling, 1 SET 1,03,290.00 1,03,290.00
air flow direction setting, operation history etc. The controller should be
compatible with automation system (Bacnet/IP) with all accessories. It should
be complete as per manufacturing standards & as per directions of Engineer-in-
2.7) Expansion Kit, Communication PCB & Thermostat -
Digitally signed by
CHANDRESH KUMAR
MOTI LAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY, ALLAHABAD
Name of Work: Proposal of New Infrastucture Projects in the Institute Campus
TENDER BILL OF QUANTITY
S.No. Discription of items Qty. Unit Rate DSR Market MR Rate Amount DSR Amount MR
Supply, Installation, Testing & Commissioning of Electronic Type Expansion Kit,
Communication PCB with Sensors, Corded Self Diagnostic Type Digital
Thermostat, Controller, control box with internal wiring, AHU kit for each DX
MR Type Units and other related accessories etc with connectivity to automation -
system for A/M status, RUN status & Remote start / stop command (Bacnet/IP).
It should be complete as per manufacturing standards & as per directions of
Engineer-in-charge.
2.7.1) MR For 12000 CFM F/M AHU with 1 x 42.0 HP VRV ODU 1 SET 1,53,095.00 1,53,095.00
2.7.2) MR For 13000 CFM F/M AHU with 2 x 44.0 HP VRV ODU 1 SET 1,64,030.00 1,64,030.00
2.7.3) MR For 15000 CFM F/M AHU with 1 x 52.0 HP VRV ODU 1 SET 1,99,023.00 1,99,023.00
3) MR Double Skin Floor Mounted VRV DX AHU (AHRI / Eurovent Certified) -
Supply, installation, testing and commissioning of factory fabricated Double
Skinned VRV DX Air-handling unit Floor mounted type fabricated out of extruded
aluminium section with 0.8 mm pre-plasticized / pre-coated Galvanised steel
sheet outside & 0.8 mm plain Galvanised steel sheet inside with backward
curved plug fan, fan section and fan motor TEFC type suitable for operation on
415 volts ± 10%, 50 Hz ± 5% AC supply, VFD with harmonic filters, 6 Row
cooling coil made of Aluminium finned Copper tube with coil section, Coilotron -
UV section only of 600 mm in length in floor mounted AHU, pre-filter (MERV 8)
section with filters of non woven synthetic media of 10 micron particle size
with an efficiency of 90%, fine filter (MERV 13) section with filters of non
woven synthetic media of 5 micron particle size with an efficiency of 95% in
supply after fan, polished stainless steel drain pan made out of 22 G sheet
duly insulated.
The AHU panels shall be insulated with 23mm thick & 36 Kg/m³ density PU
foam & shall have thermal break. The motor & blower assembly shall be
mounted on Aluminium extruded section only. These AHUs shall have air
inlet / outlet connection made of 20 G GI sheet. The complete AHU shall -
conform to specication & face velocity across cooling coil shall be limited to
152 MPM maxm. Static pressure given below is for guideline & actual to be
AHU DX coils shall be in tune with the requirement of VRV Outdoor Unit capacity
and no divisions shall be made in cross sectional area of the coil. If multiple ins
and outs of refrigerant pipe are required then coils shall be grouped into -
required rows keeping the cross sectional area of the coil constant. The capacity
of Air-handlers shall be as follows:
3.1) MR VRF/AHU - 12,000 CFM Capacity, 6 Row CC, 70 mm St. Pr., 1 Nos. 6,94,550.00 6,94,550.00
3.2) MR VRF/AHU - 13,000 CFM Capacity, 6 Row CC, 70 mm St. Pr. 1 Nos. 7,43,290.00 7,43,290.00
3.3) MR VRF/AHU - 15,000 CFM Capacity, 6 Row CC, 75 mm St. Pr. 1 Nos. 8,83,419.00 8,83,419.00
4) MR Accoustically Insulated Box Type Inline Fans -
Supplying, installing, testing and commissioning of INLINE FANS suitable for
installing in any position in vertical or horizontal ducts. The casing shall be
double skin, internally acoustically lined and constructed of galvanised steel.
with efficient motor, fire retardent double layer canvass connection etc complete
in all respect & of following capacities. The casing shall be selected for lower
noise level. Fan motor shall have inbuilt speed controller.
4.1) MR 100 to 300 CFM (12mm static pressure, single phase) 2 Nos. 10,518.00 21,036.00
4.2) MR 400 to 700 CFM (15mm static pressure, single phase) 2 Nos. 12,374.00 24,748.00
4.3) MR 800 to 1000 CFM (15mm static pressure, single phase) 2 Nos. 15,467.00 30,934.00
4.4) MR 1100 to 1500 CFM (15mm static pressure, single phase) 2 Nos. 22,025.00 44,050.00
5) NS-C5 Plastic Propeller Fans -
Supplying, installing, testing and commissioning of direct driven PROPELLER
FANS. Each fan shall be complete with permanent split capacitor or shaded pole
motor, mounting plate with light weight type PVC impellers with aerofoil
contours for high efficiency & low noise & gravity louvers for weather protection
as required. Fan selection arrangement and Electrical characteristics shall be as
6) NS-C6 GI Propeller Fans -
Supplying, installing, testing and commissioning of direct driven PROPELLER
FANS. Each fan shall be complete with permanent split capacitor or shaded pole
motor, mounting plate with light weight type GI impellers with aerofoil contours -
for high efficiency & low noise & gravity louvers for weather protection as
required. Fan capacity shall be as follows :
7) Axial Flow Fan -
Supply, installation, testing and commissioning of ceiling mounted Tube Axial
flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to
800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above
1300 mm dia) , cast aluminium alloy impeller complete with TEFC Sq. Cage
Induction motor IE-3 suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase
A.C supply with support, mountings, vibration isolators, fire retardant
flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird -
screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan
along with motor shall be high efficient one with fire rated (class H) suitable for
withstanding 250 °C temperature rated for 2 hours. Fan outlet velocity shall be
limited to maximum of 16 m/sec. Fan & Fan motor KW given below are for
guideline & actual Dia / KW shall be as per manufacturer selection based on
maximum 16 m/sec outlet velocity.
Axial Fan shall be AMCA certified for Air and Sound performance in accordance
to AMCA 210 and AMCA 300. Complete Fan shall be tested and approved by CE /
UL / EN in accordance with "Power Ventilators for Smoke Control Systems" for
250 °C for 2 hours. Manufacturer shall furnish AMCA Test Certificate for air &
sound performance along with UL / EN fire test certificate (Latest) for each fan -
sourced from that particular factory. The noise level of axial fan shall be less
than 80 dBa at a distance of 3.0 mt from the fan. The fan shall be low RPM (less
than or equal to 1000 RPM) and capacities shall be as follows. Wattage of motor
shall be as per actual selection meeting other technical parameters
NS-C7.1 15000 CFM (25mm static pressure, Axial Fan, 960 / 1450 RPM, 5.5 Kw Fan
Motor or as required, 800 MM Fan Dia)
NS-C7.2 11000 CFM (25mm static pressure, Axial Fan, 960 / 1450 RPM, 3.7 Kw Fan
Motor or as required, 700 MM Fan Dia)
NS-C7.3 8000 CFM (18mm static pressure, Axial Fan, 960 / 1450 RPM, 3.7 Kw Fan Motor
or as required, 600 MM Fan Dia)
8) NS-C8 AHU Mounted Coilotron UV System For Floor Mounted AHU -
Digitally signed by
CHANDRESH KUMAR
MOTI LAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY, ALLAHABAD
Name of Work: Proposal of New Infrastucture Projects in the Institute Campus
TENDER BILL OF QUANTITY
S.No. Discription of items Qty. Unit Rate DSR Market MR Rate Amount DSR Amount MR
Supply, installation, testing and commissioning of AHU mountable self
contained and factory assembled Coilotron UV System with UL 1995 ABQK
listed and UL 2043 certified, UV lamp of 800 mA & life of UV lamp shall not be
less than 11000 hours. Coilotron shall be installed in all floor mounted AHUs as -
specified herein. All the component / parts shall comply with the specification
given in the tender. AHU supplier and coilotron supplier shall co-ordinate with
each other regarding the fixing of the same in the AHU.
TOTAL OF SUBHEAD C 43,25,838.00 51,49,645.00
Sub Head 'D' - HVAC Plumbing
1) Condensate Drain Piping With Nitrile Rubber Insulation
Supply, installation, testing and commissioning of UPVC condensate drain
water piping of density 10 Kg/m³ complete with fittings like elbows, tees,
reducers, bends, flanges, supports & duly insulated with "O" class Closed Cell
Elastomeric Nitrile Rubber of specified pipe section of specified thickness etc.
as required and of following sizes.
1.1) 25 mm dia pipe, 13 mm Insulation 250 RMT 227.00 56,750.00
1.2) 32 mm dia pipe , 13 mm Insulation 190 RMT 288.00 54,720.00
1.3) 40 mm dia pipe , 13 mm Insulation 50.1 RMT 394.00 19,739.40
1.4) 50 mm dia pipe , 13 mm Insulation 30 RMT 530.00 15,900.00
2) NS-D2 Insulated Refrigerant Piping for VRV / VRF System -
Supply, installation, testing and commissioning of interconnecting high
pressure copper refrigerant piping work including vaccumiazation and
Nitrogen testing suitable for refrigerant R 410A duly insulated with FACTORY
PREFORMED TUBULAR EPDM RUBBER FOAM SECTIONS with completely closed
cell structure as per specifications - Density 40-60 kg /cum , Class A as per
ASTM E 84 , Class V-0 as per UL 94 and Mu value > 7000 between indoor & -
outdoor units as per specifications. External refrigerant piping shall be laid on 16
G GI covered perforated cable trays. Piping inside occupied area & vertical shaft
inside the AHU Room shall be supported using 16 G GI hangers. All exposed
pipe shall have UV coating on insulation & cost to be included in the piping.
Cable tray is quantified seperately.
6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick
9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick
15.9 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick
19.1 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick
22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick
28.6 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick
34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick
41.30 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm
thick insulation
TOTAL OF SUBHEAD D 4,84,970.80 1,47,109.40
Sub Head 'E' - Ducting & Grilles
1) 16.12.1 Rectangular GI Ducting (Factory Made - L Shape)
Supply, installation, balancing and commissioning of factory fabricated GSS
sheet metal rectangular/round ducting complete with neoprene rubber gaskets,
elbows, splitter dampers, vanes, hangers, supports etc. as per approved
drawings and specifications of following sheet thickness complete as required.
2) 16.12.2 Site Fabricated GI Ducting -
Supply, installation, balancing and commissioning of site fabricated GSS sheet
metal rectangular/round ducting complete with neoprene rubber gaskets,
elbows, splitter dampers, vanes, hangers, supports etc. as per approved
drawings and specifications of following sheet thickness complete as required.
3) 16.21 Duct Accoustic Lining -
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm
thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm
GI section of 1.25 mm thick, at 600 mm centre to centre covered with
Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet
fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX
compound etc. complete as required and as per specifications.
Digitally signed by
CHANDRESH KUMAR
MOTI LAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY, ALLAHABAD
Name of Work: Proposal of New Infrastucture Projects in the Institute Campus
TENDER BILL OF QUANTITY
S.No. Discription of items Qty. Unit Rate DSR Market MR Rate Amount DSR Amount MR
4) 16.23 Duct Insulation -
Supplying and fixing of following thickness duly laminated aluminum foil of mat
finish closed cell Nitrile rubber (Class "O") insulation on existing duct after
applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 -
mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as
per specifications and as required.
5) 16.20 Fire Dampers & Actuator -
Supplying, Fixing, testing and commissioning of fire dampers in supply air
duct/main branch and return air path as and where required of required sizes i/c
control wiring,the damper shall be motorized and spring return so as to close
the damper in the event of power failure automatically and open the same in -
case of power being restored. The spring return action shall be inbuilt
mechanism and not externally mounted. The damper shall also be closed in the
event of fire signal complete as required and as per specifications.
6) NS-E6 Grilles, Diffusers, VCD
Supply, installtion and testing of Powder coated Aluminium extruded
grills / diffusers as per specifications given in tender and of following sizes.
M Supplying & fixing of powder coated extruded aluminium Supply Air Grills with
2022 aluminium volume control dampers as per specifications.
M Supplying & fixing of powder coated extruded aluminium Return Air Grills with
2022 louvers without volume control dampers complete as required.
Supplying, fixing testing commissioning of supply air diffusers of powder coated
6.3) aluminium with aluminium volume control dampers with anti smudge ring & 5 Sqmt. 12,184.00 60,920.00 -
removable core.
Supplying, fixing testing commissioning of Return air diffusers of powder coated
6.4) aluminium without volume control dampers with anti smudge ring & removable 5 Sqmt. 8,121.00 40,605.00 -
Supplying, fixing testing commissioning of Fresh / Exhaust air louvers with bird
screen & damper
Supplying, fixing testing commissioning of Volume control GI Dampers to be
provided in Supply / Exhaust air registers / terminals.
Supplying, fixing testing commissioning of Fixed bar linear air register of
following sizes
7) NS-E7 GSS Duct Damper -
Supply, installation and testing of multiblade box type Galvanized Sheet Steel
construction damper for ducts to be provided with suitable links and 10 SMT 7,046.00 70,460.00
quadrants for control of volume of air.
8) NS-E8 Under Deck Insulation of Exposed Roof -
Supplying and fixing of thermal insulation on exposed roof (underdeck) with
19mm thick EPDM Rubber foam with completely closed cell structure as per
specifications - Density 40-60 kg /cum , Class A as per ASTM E 84 , Class V-0
as per UL 94 and Mu value > 7000, tape & adhesive (pidilite SR -998) with
adhesive (pidilite SR -998) etc. as required & finally fixed with the help of rawl
plug & dash fasteners in ceiling.
Sub Head 'F' - HVAC Electric Work
1) NS-F1 Electrical Sub Panel
Supply, installation, testing and commissioning of cubical floor / wall mounted
type switch board as detailed below & switch gears suitable for AC-23 duty
with digital energy meter on incoming feeders of all Sub-Panels covered under
this Item, including making interconnection etc as required. BMS compitable
dual source energy meter with maximum demand shall be taken in main
incomer of HVAC Panels.
1.1) NS-F1.1 M.C.C. For VRV Outdoor Units (Panel Suitable For Outdoor Type - IP54) 1 Set 7,65,786.00 7,65,786.00
Supply, installation, testing and commissioning of Cubical type sectinalised
floor standing switch board by CPRI apprved firms of 31 MVA fault
capacity at 415 V complete with 4 strip, 600 A capacity Aluminium Bus - -
Bar Electrolytic grade E-91, cable alley, switchgears suitable for AC-23 duty
& of following capacity & as per specification given in the tender.
630 A TPN MCCB with with overload, short ckt., earth fault, protection
release, with 144 mm (0 - 630 A) ammeter with 3 CT and selector switch, 144
mm (0 - 500 V) Voltmeter with selector switch, phase indication light with -
protection fuse, on / off / trip indicating light with protection fuse.
b) Bus Coupler -
Bus Coupler for section A & B of 800 A capacity, four pole MCCB.
Incomer and bus coupler shall be mechanically & electrically interlocked to
avoid paralleling of the two supplies. -
c) OUTGOINGS -
i) For VRV ODU -
40/63 A TPN MCB (2W+1S) SET 3 -
125/160 A TPN MCCB (6W+2S) SET 8 -
Controls & interlocking accessories as required. LOT -
1.2) NS-F1.2 Isolator Switch With Metal Enclosure For ODU (IP-65) 8 No. 7,717.00 61,736.00
40 A 4 pole RCBO for VRV Outdoor Units with sheet metal enclosure, rain
protection etc. as required to suit the site condition.
For AHU Fan Motor VFD Driven + Fire Damper + Coilotron in AHU &
Germitron UVGI in Duct etc. up to 12 KW
Digitally signed by
CHANDRESH KUMAR
MOTI LAL NEHRU NATIONAL INSTITUTE OF TECHNOLOGY, ALLAHABAD
Name of Work: Proposal of New Infrastucture Projects in the Institute Campus
TENDER BILL OF QUANTITY
S.No. Discription of items Qty. Unit Rate DSR Market MR Rate Amount DSR Amount MR
Supply, installation, testing and commissioning of Cubical type sectinalised
floor standing switch board by CPRI apprved firms of 18 MVA fault
capacity at 415 V complete with 4 strip, 100 A capacity Aluminium Bus - -
Bar Electrolytic grade E-91, cable alley, switchgears suitable for AC-23 duty
& of following capacity & as per specification given in the tender.
Sub Head 'D' - HVAC Electric Work -
40 A TPN MCB with (0-30/40A) ammeter with three CT and selector switch,
(0 - 500 V) voltmeter with selector switch, phase indication light with protection -
a) For AHU Fan Motor up to 11 Kw -
32 / 40 A TPN MCB & Suitable Space for accomodating VFD (VFD quantified
separately with AHU) SET-01
b) For Fire Damper & Actuator, Coilotron, Germitron etc. -
6 A SP MCB, SET-4 -
Controls & interlocking accessories as required. Lot -
1.4) NS-F1.4 Axial Fan Motor Up to 3.7 KW 4 No. 22,439.00 89,756.00
40 A TPN MCB with 16 A DOL starter, overload relay, start / stop push
buttons, phase indication lights with protection fuse, on / off / trip indication
lights with protection fuse, single phase preventer & auto / manual mode
selector switch. Set - 01
Controls & interlocking accessories as required. Lot -
1.5) NS-F1.5 Axial Fan Motor Up to 5.5 KW 2 No. 25,645.00 51,290.00
40 A TPN MCB with 25 A DOL starter, overload relay, start / stop push
buttons, phase indication lights with protection fuse, on / off / trip indication
lights with protection fuse, single phase preventer & auto / manual mode
selector switch. Set - 01
Controls & interlocking accessories as required. Lot -
1.6) NS-F1.6 Single Phase MCB for VRV Indoor Units / Inline Fan / Propeller Fan -
Supply, Installation, Testing & Commissioning of suitable size PVC / G.I. Box
with 6A / 10A / 16A SP MCB, loop in loop out connector and box cover etc as 15 Set 1,128.00 16,920.00
required at site.
1.7 NS-F1.7 Starter for Propeller / Inline fan (Single Phase) -
Supply, Installation, Testing & Commissioning of modular type single phase
motor starter up to 6 A / 10 A / 16 A (Rating shall be as per motor) including
suitable size G.I. Box with modular, modular cover plate, conduiting and wiring
from starter to fan etc as required at site.
2) NS-F2 Power & Control Cabling -
Supply, laying, testing and commissioning of power and control cabling as
per specification given in the tender. Power cabling of XLPE insulated Aluminium
/ Copper conductor armoured cables of 1.1 KV Grade including cable -
end termination with brass compression glands & aluminium lugs etc as per
Note:- Copper cable upto 16 Sq. mm & above shall be Aluminium Cable -
2.1) NS-F2.1 For Motor Up to 3.73 Kw -
1 x 3C x 4 Sq. mm Copper 55 RMT 386.00 21,230.00
2.2) NS-F2.2 For Motor of 5.5 Kw -
1 x 3C x 6 Sq. mm Copper 35 RMT 497.00 17,395.00
2.3) NS-F2.3 For Motor of 7.5 / 9.3 / 11 Kw -
2 x 3C x 6 Sq. mm (Rate for Single Run) Copper 20 RMT 497.00 9,940.00
2.4) NS-F2.4 For VRV ODU Unit (From AC Panel to Isolators near ODU) -
2.4.3) NS-F2.4.31 x 4C x 25 Sq. mm Aluminium 80 RMT 369.00 29,520.00
2.5) NS-F2.5 For VRV Outdoor / HW ODU (From Isolators to Unit) -
2.5.1) NS-F2.5.11 x 4C x 4.0 Sq. mm Copper Flexible Cable 65 RMT 265.00 17,225.00
2.5.2) NS-F2.5.21 x 4C x 6.0 Sq. mm Copper Flexible Cable 55 RMT 387.00 21,285.00
2.5.3) NS-F2.5.31 x 4C x 10.0 Sq. mm Copper Flexible Cable 45 RMT 663.00 29,835.00
2.6) NS-F2.6 For VRV Indoor Unit Inline Fan / Propeller Fan (From MCB to Unit) -
NS-F2.6.11 x 3C x 2.5 Sq. mm Copper Flexible Cable 230 RMT 175.00 40,250.00
Control cabling (PVC insulated Copper conductor of 1.1 KV Grade
armoured cable)
4) NS-F4 Transmission & Control Wiring For VRV System -
Providing & fixing of control cum trans-mission wiring of copper between
indoor and out door unit in 25 mm PVC Conduit.
5) NS-F5 Earthing Strip / Wires as per specs. -
5.1) NS-F5.1 Supply & laying of 6 SWG GI wire or in recess for loop earthing as required. 479.93 RMT 51.00 24,476.43
Supply & laying of Rubber mat 1000 mm. Wide to withstand 1.1 KV dielectric
strength as per latest IS 15652-2006.
6) NS-F6 Cable Tray
Supplying and installing following size of perforated GI cable trays including
bends. tee, reducers etc with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling with GI suspenders
including bolts & nuts, suspenders etc as required.
6.1) 2 100 mm wide x 50 mm depth x 1.6 mm thickness. 48 RMT 669.00 32,112.00 -
6.2) 2 150 mm wide x 50 mm depth x 1.6 mm thickness. 38 RMT 716.00 27,208.00 -
6.3) 2 300 mm wide x 50 mm depth x 1.6 mm thickness. 72 RMT 963.00 69,336.00 -
6.4) 2 600 mm wide x 50 mm depth x2 mm thickness. 72 RMT 1,790.00 1,28,880.00 -
Digitally signed by
CHANDRESH KUMAR
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT Revised.pdf
Tender Document
SCC.pdf
Tender Document
GCC 2022 PMC.pdf
Tender Document
List of Makes Final.pdf
Tender Document
Integrity pact.pdf
Tender Document
Drawings.pdf
Tender Document
Technical Specification.pdf
Tender Document
Revised BoQ.pdf
Tender Document
corrigendum-2503-Corrigendum 05.pdf
pdf • 0.09 MB
corrigendum-2426-Corrigendum 04.pdf
pdf • 0.11 MB
addendum-c37b0329a3b4-Corrigendum 04.pdf
pdf • 0.11 MB
corrigendum-2418-Corrigendum03.pdf
pdf • 0.26 MB
corrigendum-2417-Corrigendum_02.pdf
pdf • 0.10 MB
corrigendum-2357-Corrigendum01.pdf
pdf • 0.08 MB
addendum-cf90e629ec1a-Adendum01.pdf
pdf • 0.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .