Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.8 LAccepted-Finance | L1 | Accepted-Finance valid to be received. | |
| 2 | L2₹10.0 L+₹18,900 (1.92%)Accepted-Finance DADRA AND NAGER HAVELI DN | DADRA AND NAGAR HAVELI | THE DADRA AND NAGAR HAVELI AND DAMAN AND DIU | 396193 | L2 | Accepted-Finance valid to be received. |
| Sl No | Description | Qty | Unit | Hitendra A Patel | ACCURATE INFRA |
|---|---|---|---|---|---|
| 1.00Items | |||||
| 1.01 | Providing and erecting Approved make Three pole moulded case circuit breaker having breaking capacity/strength ICU of 35 K.A. and above at 415 V. having Normal current rating 200A.with variable Thermal & magnetic release suitable to work on A.C.supply 50 c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. housing. ICS=100% of ICU only | 3 | Ea | 60,000 ₹60,000 Lowest | 60,000 ₹60,000 Lowest |
| 1.02 | Supply of Approved make Iron Clad or metal clad four pole change over switch 415V. confirming to IS of following capacity (A) 200 A / 250 A | 2 | Ea | 44,000 ₹44,000 | 43,000 ₹43,000 Lowest |
| 1.03 | Providing and erecting busbar chamber confirming to IS-375 fabricated from 16 G.M.S. sheet, dust & vermin proof having hinged door with rubber gasket and necessary busbar supports with COPPER busbar having current density not more than 1.6 Amp. / sq.mm (Rated current / cross section area) duly wrapped with colour insulation tape for phase sequence, three phase & neutral each suitable for following current capacity with necessary painting mounted on wall or pedestal frame of required size with necessary connections. (B) Suitable for 200 Amp. capacity | 4 | Rn.Mtr | 28,000 ₹28,000 | 26,000 ₹26,000 Lowest |
| 1.04 | Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for (B) three phase incoming and single phase horizontal type outgoing Per phase isolation type (PPI) (b) sheet steel double door (iii)8 way | 5 | Ea | 22,500 ₹22,500 | 20,750 ₹20,750 Lowest |
| 1.05 | providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240 V A.C. system and having breaking capacity 10 KA to be erected in existing box. confirming to IS 8828/1996 with ISI Mark | 102 | Ea | 14,280 ₹14,280 | 13,770 ₹13,770 Lowest |
| 1.06 | Providing & erecting 240 V MCB double pole switch for motor & inductive load (C Curve) having 10 KA breaking capacity & confirms to IS : 8828 in existing box having following capacity (A) 6 to 32 Amp. | 10 | Ea | 3,700 ₹3,700 | 3,640 ₹3,640 Lowest |
| 1.07 | providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for control panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts and bolts if required. (e) One wire 6.00 sq. mm | 230 | Mtr | 15,410 ₹15,410 | 14,950 ₹14,950 Lowest |
| 1.08 | (g) One wire 16.00 sq. mm | 140 | Mtr | 22,400 ₹22,400 Lowest | 28,000 ₹28,000 |
| 1.09 | Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (C) 3 1/2 core 50 Sq. mm ( 25 Sq.1/2 mm core) | 200 | Mtr | 80,000 ₹80,000 | 70,000 ₹70,000 Lowest |
Tender Value
₹9.5 L
EMD Value
₹18,967
Closing Date
25 Aug 2025, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, PWD, WD-I, Daman
O/o. the Ex. Eng., P.W.D., 2nd floor Multi office complex, near Veg. Market, Moti Daman.
Regarding requirement of Electrical works for compliances of Electrical Audit at PHC, Dabhel and PHC, Fort Area, Daman. (E-47586)
2025_DAMAN_4399_1
67/2025-26
Open Tender
Civil Works - Others
Works
60 days
Daman District
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
The Executive Engineer, PWD, WD-I, Daman
₹18,967
28 Aug 2025
18 Aug 2025
25 Aug 2025
18 Aug 2025
25 Aug 2025
18 Aug 2025
Items
Providing and erecting Approved make Three pole moulded case circuit breaker having breaking capacity/strength ICU of 35 K.A. and above at 415 V. having Normal current rating 200A.with variable Thermal & magnetic release suitable to work on A.C.supply 50 c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. housing. ICS=100% of ICU only
Supply of Approved make Iron Clad or metal clad four pole change over switch 415V. confirming to IS of following capacity (A) 200 A / 250 A
Providing and erecting busbar chamber confirming to IS-375 fabricated from 16 G.M.S. sheet, dust & vermin proof having hinged door with rubber gasket and necessary busbar supports with COPPER busbar having current density not more than 1.6 Amp. / sq.mm (Rated current / cross section area) duly wrapped with colour insulation tape for phase sequence, three phase & neutral each suitable for following current capacity with necessary painting mounted on wall or pedestal frame of required size with necessary connections. (B) Suitable for 200 Amp. capacity
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for (B) three phase incoming and single phase horizontal type outgoing Per phase isolation type (PPI) (b) sheet steel double door (iii)8 way
providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240 V A.C. system and having breaking capacity 10 KA to be erected in existing box. confirming to IS 8828/1996 with ISI Mark
Providing & erecting 240 V MCB double pole switch for motor & inductive load (C Curve) having 10 KA breaking capacity & confirms to IS : 8828 in existing box having following capacity (A) 6 to 32 Amp.
providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for control panel, relays, power switchgears, motor starters & control wiring) with required size of copper lugs, nuts and bolts if required. (e) One wire 6.00 sq. mm
(g) One wire 16.00 sq. mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (C) 3 1/2 core 50 Sq. mm ( 25 Sq.1/2 mm core)
Solder less crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. (D) 35/50 Sq.mm.
Solder less crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner. (C) 16 Sq.mm.
Providing & erecting 415 V MCB three Pole for Motor & Inductive Load (C Curve) having 10KA breaking capacity & confirms to IS :8828 in existing box having following capacity (c)63 Amp.
Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of 50mm having 80-200 Micron galvanising, Inner pipe dia of 25 mm having 200-250 Micron galvanising, connection terminal dia of 12mm with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for following type of applications with chamber and heavy duty cover.(approved make OEM has to submit test certificate) & having back filling compound of (B) Inner chemical (CCM Compound)- Resistivity:- 0.2 / meter testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no load & dry form, Sulphar content:- <2%(C) Back fill Compound :- Earthing compound should be capable to retain moisture for long time Necessary test report must be submitted. (b)For Electrical installation up to 11 KV in normal soil. Length of Pipe : 2.00 mtrs Back filling Compound :1 no. Bag of 25 Kg.
(B) Flood Light (IP-65), Surge protection -4KV integral and ,Light must have 440VAC line supply with over-voltage protection. (iv) above 90 to 120 watts
Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (E) 3 core 2.5 Sq. mm
Providing & erecting PVC Corrugated Flexible Conduit with required nos. of coupling, PVC bushes, Check-nuts etc. complete of following sizes. (2) 25 mm
Providing and erecting required size HOT deep Galvanised iron strip for earthing of H.T. , OCB/ ACB/ Transformer LT panel board, Motors etc. using proper clamp.
Providing & erecting weather proof, dust & vermin proof, floor mounted front operated indoor type cubical panel board necessary IP-42 and above protection as per approval from engineer incharge made from 14 SWG thick CRC M.S. sheet for outer body & doors, 16 SWG thick CRC M.S.sheet for internal partitions with necessary accesories , supporting angles/ flats channel including cutting, bending, drilling, welding, riveting with internal partitions & cable alley as per requirements & instruction of engineer-in-charge with erection of supplied switch gears, BUSBARS, suitable size of inter connecting PVC copper wire / copper-aluminium strips, rubber grommets, rib, bakelite control fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange - bolts-base Plates, sufficient nos. of hinged doors, handles with locking arrangement and rubber gasket,heavy duty end terminal connection,danger notice board,necessary ventilation,earthing strip complete. The Panel shall be painted with epoxy powder coating. (The rates excludes the cost of switchgears, bus bars, inter connecting mains & Copper Aluminium strips, meters, Fuses etc. The dimension shall be measured excluding base beams) The panel shall be supplied with following approved manufacturers with following size. (A) locally fabricated panel board (i) with 350 mm depth
Providing and erecting Approved make Three pole moulded case circuit breaker having breaking capacity ICU of 25 K.A. at 415 V having normal current rating up to 25 A to 100A. with Fixed thermal & magnetic release suitable to work on A.C. supply 50 c/s. with all internal connections, spreader tinned copper & complete erected in existing 16 G.M.S. housing. ICS=100% of ICU only
Providing and erecting ,Fabricating the box type items made from M.S. Sheet with A.I. supports, wings, doors, handles other hardware materials as per requirement design with finishing by three tank powder coating processed inside and outside painted, erected as directed including minor civil work.
Supplying and erecting approved make GRP / FRP Perforated type Cable Tray Material – Corrosion Resistant Polyester Flame Retardant U.V. Stabilized Resin System - Manufactured from Pultruded Sections- Polyester Resin System, Glass Content : 55 – 60 % - - Standard Length : 3000mm- Support Span – 1500mm, Deflection L/200 - Specification NEMA FG1 1993- UV Resistant - Flame Retardant – IS 6746 - Appendix K/UL 94, Very Low Flammability - Specification Followed NEMA FG1 1993 Oxygen Index – Minimum 30% as per ASTM D 2863 - Flame Spread (Extent of Burning) – 20mm as per Standard ASTM D 635 - Tensile Strength – 4000 – 8000 Kg/Cm2 as per Standard ASTM D 638 - Flexural Strength – 2500 – 10000 Kg/Cm2 as per Standard ASTM D 790- Izod Impact Strength – 130 Kg/Cm2 as per Standard ASTM D 256- Compressive Strength – 2500 – 5000 Kg/Cm2 as per Standard ASTM D 695- Barcol Hardness – 50 – 65 (F) Width - 300mm, Pultruded “C” Channel with 50mm Sides 4mm Thickness, Loading 30 Kg./Mtr.
Disconnecting the cable connection and Providing straight joint with PVC mould using heat shrink /cast resin type epoxy compound Insulating material and making the joint complete using necessary in line connectors, hardener, earth continuity connection, spacers etc. and reconnecting the same & ensure the joint resistance within the limits as per IS. (A) up to 25 Sq mm Cable
Supply & fixing of 4.5KG GAS type Co2 (ISI marked) extinguisher including all accessories with wall bracket & raw plug conforming to IS:15683 as directed by Engineer in Charge
Supply & fixing of 6 Kg ABC type dry power extinguisher consisting of welded MS cylindrical body with discharge valve, nozzle and hanging arrangement complete conforming to IS:15683 as directed by Engineer in Charge.
Supplying FIRE bucket round bottom of 9 litres capacity made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and Red out side with FIRE mark, filled with dry-sand and kept on existing stand provided or hung on wall hook.
Supplying and erecting floor mounting stand for keeping four nos. of FIRE buckets comprising 1500 mm in length, 900 mm height frame made out of 30mm X30 mm X 4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of approved enamelled silver paint.
Supply & Erecting 18/20 Watt LED Emergency Inverter Light.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .