Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.7 LAccepted-AOC | L1 | Accepted-AOC As per Quoted and Negotiated value |
Tender Value
Refer Docs
EMD Value
₹45,000
Closing Date
14 Oct 2024, 3:00 pmClosed
Managing Director
No 4 Rajiv Gandhi salai Taramani Chennai 60013
E-TENDER FOR PROVISION OF ADDITIONAL ELECTRICAL IBMS WORKS AT TIDEL NEO VILLUPURAM, THIRUCHITRAMBALAM VILLAGE, VANUR TALUK IN VILLUPURAM DISTRICT
2024_TIDEC_489021_1
TIDEL/2024-25/20
Open Tender
Electrical Works
Works
45 days
THIRUCHITRAMBALAM VILLAGE, VANUR TALUK VILLUPURAM
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹45,000
Tidel Park Ltd Chennai
23 Nov 2024
27 Sept 2024
15 Oct 2024
27 Sept 2024
14 Oct 2024
9 Oct 2024
28 Sept 2024 - 4 Oct 2024
4 Oct 2024
Amount
Ceiling Fan Points: Supply,installation,testing and commissioning of ceiling fan points same as Primary Light Point Wiring but for ceiling fan points including supplying and fixing concealed type fan hook box and supply and fixing of electronic type 300W fan step regulator with moulded front plate in GI anodised manufacturer's mounting box fixed flush with the wall complete with all accessories as required as per the site conditions. (BOQ 18.79)
Ex Fan Points: Supply,installation,testing and commissioning of Ex-fan points same as Primary Light Point Wiring but for exhaust fan points including supplying and fixing one no 6A switch with indicator in switch board and one no 6A socket near Ex fan location in wall with moulded front plate in GI anodised manufacturer's mounting box fixed flush with the wall complete with all accessories as required as per the site conditions. in MS conduits. (BOQ 18.80)
Supply and fixing of 450mm (18") sweep (Heavy duty) AC exhaust fan complete with necessary wall opening and making good of the wall. (Data-A )
Supply and fixing of louvers shutters arrangements for 300mm (12") sweep AC exhaust fan (SD-120)
Supply and fixing of louvers shutters arrangements for 450 mm (18") sweep AC exhaust fan. (Data-B )
STP indoor panel: supply & fixing all weather proof enclosure for the existing STP panel with re erection of panel with necessary Connection. Quotation (Data- C)
Supply , fixing, testing and commissioning of Street light Outdoor Fixture IP65 of LED street light luminaire Model no: 70W LED light fixture Philips make BRP 062(or) Havells make (or) Crompton make and supply and fixing of The pole shall be grouted inside ground pit (cross section 600 x 600 mm) with cement concrete 1:2:4 with necessary GI ‘A’ class pipes (not less than 38 mm dia, NB) to facilitate pulling of cables. Separate pipes shall be provided for incoming and outgoing cables. The cement concrete shall be protected from premature drying by curing for at least seven days after pouring. All concrete surfaces from 150 mm below ground level to top shall be finished smooth with cement mortar 1:4.-pole height above ground 6-m-top 70mm,bottom 130mm,thickness 3mm,with base plate size220x220x16mm-4nos foundation bolts,700 mm length 24mm dia. (Data-D)
Supply , fixing, testing and commissioning of Street light Outdoor Fixture IP65 of LED street light luminaire Model no: 70W LED light fixture Philips make BRP 062(or) Havells make (or) Crompton make 2 Nos, with Double arm Arrangements and supply and fixing of The pole shall be grouted inside ground pit (cross section 600 x 600 mm) with cement concrete 1:2:4 with necessary GI ‘A’ class pipes (not less than 38 mm dia, NB) to facilitate pulling of cables. Separate pipes shall be provided for incoming and outgoing cables. The cement concrete shall be protected from premature drying by curing for at least seven days after pouring. All concrete surfaces from 150 mm below ground level to top shall be finished smooth with cement mortar 1:4.-pole height above ground 6-m-top 70mm,bottom 130mm,thickness 3mm,with base plate size220x220x16mm-4nos foundation bolts,700 mm length 24mm dia. (Data-E)
Supply and fixing 32A 3pin Industrial Socket with 32A Tempra Plug on wall with necessary Connection. MV Panel ROOM (Data-F)
Supply and fixing of 1400mm sweep (56") AC ceiling fan complete with stepped electronic 300W regulator with 1 metre down rod including fan clamp with side plates and cross arm of size 450mm. (SD-108 )
Supply and fixing of“Havells” Dura Batten 40W–WW DURA-BS-40W-LED-865SP-CSS 9with conduit pipe suspension with PVC unsheathed copper leads from the terminals to the fittings with fluorescent tubes. (Data-G)
Supply and run of 3 Core 2.5 sq.mm. PVC insulated SC unsheathed copper cable of 1100V grade in suitable gauge MS conduit pipe on wall and ceiling with continuous earth wire connection of 14 SWG TC wire with painting of suitable colour. (Data- H)
Supply and run of 2 of 4 sq.mm. (56 / 0.3) PVC insulated SC unsheathed copper conductor of 1100V grade in suitable heavy gauge MS coundit pipe on wall and ceiling with continous earth wire connection of 14 SWG TC wire with painting of suitable colour. (for Tempra Plug) (SD-44)
Supply installation, testing and commissioning of VFD Starter panel Supply of 3.7 kw VFD Bypass DOL Starter Panel with 16A Three Pole MCB, Power Contactor, OLR, Relay, Indication lamp, Temp sensor, Controller and BMS compatibility Suitable for Indoor Installation. VFD Make : SCHNEIDER ATV310. (Data-I)
Supply installation, testing and commissioning of VFD Starter panel Supply of 5.5 kw VFD Bypass DOL Starter Panel with 25A Three Pole MCB, Power Contactor, OLR, Relay, Indication lamp, Temp sensor, Controller and BMS compatibility Suitable for Indoor Installation. VFD Make : SCHNEIDER ATV310. (Data-J)
Supply and fixing of Vertical type Hager IP43 Double Door DB 4 way, 12 +12 modules VYV06DM-P MCCB DB with IP 54 Protection, with Four Pole 125A, 25KA MCCB HHA126U as incoming with 3 Nos 32A SP MCBs and 3 Nos 32A TP MCbs are outgoing with1 Nos of Cable Adopter Box with Section Plates and 1 No of CEB for Vertical TPN DD DB Hager VYV00E for fixing one No Selec MFD meter with RS -485 Comm protocol MFM-384-C-CE l with earth connection..The MCB DB and MCB’s should be with ISI mark (Data-K)
Supply and fixing of Vertical type Hager IP43 Double Door DB 6 way, 12 +12 modules VYV06DM-P MCCB DB with IP 54 Protection, with Four Pole 125A, 25KA MCCB HHA126U as incoming with 6 Nos 32A TP MCbs are outgoing with1 Nos of Cable Adopter Box with Section Plates and 1 No of CEB for Vertical TPN DD DB Hager VYV00E for fixing one No Selec MFD meter with RS -485 Comm protocol MFM-384- C-CE l with earth connection..The MCB DB and MCB’s should be with ISI mark (Data-L)
Supply and run of 4 of 4 sq.mm. (56 / 0.3) PVC insulated SC unsheathed copper conductor of 1100V grade in suitable heavy gauge MS conduit pipe on wall and ceiling with continuous earth wire connection of 14 SWG TC wire with painting of suitable colour. (SD-49)
Supply and Laying of 4 Core 10 Sq.mm XLPE Copper armoured Cable PVC/XLPE (FR-LS) insulated outer sheathed partly laid in cable tray and partly laid in wall/ ceiling with suitable individual clamps at every 1 mtr interval . Cable tray will be measured and paid separately. Cable Tags to be provided at every 50mtr interval and at either side of the bends.Only for Lighting cables cable tie will be permitted other cables clamps to be provided. (BOQ 18.40)
Re fabrication of existing panel by providing Bus extension for adopting additional 63A TP MCBs Chamber 2 Nos with 2 Nos 200A MCCB Motorized for IBMS connectivity with all bus connection and Termination etc. (Data- M)
Supply , Erection Testing and commissioning of 415V/50 HZ 400 A Cubicle panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet 2750(L)x 1850(H) x 550(W) in MM with 1”x 1/4 ” tinned copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on rear side of the panel board for earth buses and Selec MFD meter with RS -485 Comm protocol MFM-384- C-CE with suitable CT coil -6 Nos, with Two set of LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. With the following Switches. Incoming: 400 Amps Four Pole MCCB (ABB) – 1 No. Outgoing: 1. 125 Amps Four Pole MCCB(ABB) -6 Nos. 2. 63 Amps Triple Pole MCCB --12 Nos with 6 mm thick hylem sheet separation for switches to bus bar interconnection. and Control wiring using 4.0 sqmm Copper wire for automation and painting with One coat of red oxide and 2 coats of synthetic spray paint and Superscribing with suitable colour paint, the name of the location of feeding, size of the cable, capacity of the switches and bus bar chamber including Transport Charges. HVAC Panel No:1 (Data-N)
Supply , Erection Testing and commissioning of 415V/50 HZ 630 A Cubicle panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet 2750(L)x 2250(H) x 550(W) in MM with 1”x 1/4” tinned copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 2”x 1/4” copper flat on rear side of the panel board for earth buses and Selec MFD meter with RS -485 Comm protocol MFM-384-C-CE with suitable CT coil -7 Nos, with Two set of LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. With the following Switches. Incoming: 630 Amps Four Pole MCCB (ABB) – 1 No. Outgoing: 1. 125 Amps Four Pole MCCB(ABB) -7Nos. 2. 63 Amps Triple Pole MCCB -- 14 Nos with 6 mm thick hylem sheet separation for switches to bus bar interconnection. and Control wiring using 4.0 sqmm Copper wire for automation and painting with One coat of red oxide and 2 coats of synthetic spray paint and Superscribing with suitable colour paint, the name of the location of feeding, size of the cable, capacity of the switches and bus bar chamber including Transport Charges. HVAC Panel No:2 (Data-O)
Supply & fixing of Acoustic insulation for supply air duct with 20mm Thick Class 1 rating Open Cell nitrile rubber insulation material with density of 140 to 180 kg /m³. Insulation shall have built-in Anti-Microbial protection and should pass Fungi Resistance as per EN ISO 846 Method A and Bacterial Resistance as per EN ISO 846 Method C. Insulation shall have noise absorption proprieties as per ISO 354, ISO 11654 & ASTM C 423. Thermal conductivity of the insulation material shall not exceed 0.047 W/m K at an average temperature of 20 Deg C as per EN 12667. Insulation should withstand maximum surface temperature of +85 Deg C and minimum surface temperature of -20 Deg C as per EN 14706 & EN 14304. The material should conform to Class 1 rating for surface spread of flame in accordance to BS 476 Part 7 & HB, V0 rating as per UL 94. Adhesive to adhere insulation to the walls & ceilings shall be from the Insulation manufacturer only. (BOQ-15.48)
Supply testing ,installation and Commissioning of of Ravel make 4 zone conventional panel (RE2554) with batteries have the capacity of 12V,7aH with all Connection. (Data- P)
Supply and fixing of Ravel Make Manual Call Point RE716 with connection. (Data- Q)
Supply and fixing of Ravel Make HooterRE:24CS with connection. (Data- R)
Supply and fixing of Ravel make multi sensor smoke detector with base:(RE316SH2L) with MS powder coated junction box 100x100x40mm on ceiling with Necessary Connection. (Data- S)
Supply and laying of FRLS PVC insulated 2 core 1.5 sq.mm. Armoured Copper Cable on ceiling / wall using fixing accessories like screws, plug, clamps, etc., as per standard methods and as directed by the Departmental Officers. (BOQ-28-11)
Supply of 200Litres Barrel -3 Nos with 1No loading Carriage (Data-T)
supply and Installation of Toshiba Make 1.0 Tr Inverter AC Unit 3 Star Value. Blue Coated Evaporated Coil, with Aqua Clear protection outdoor Unit With temperature Display on the Indoor Unit. Hi–Wall mounting energy efficient Split type AC unit consisting of outdoor condensing unit complete with compressor and air cooled condenser with fan motor & Fully remote control operation etc., including initial charge of gas and suitable for single phase AC, ( 230V, 50Hz, AC ) Model Make: Toshiba ( 3Star rated ) (MR) (Data U)
Supply, installetion, testing and commissioning of Toshiba Make Bacnet Controller, Model BMS- IFBN1280U-IN for IBMS Connectivity for all AHUs and Outdoor Units of HVAC system. Rate adjusted to add 18% GST (QUO)
Renewal by supply and fixing of 4KVA double boost wall mounting type Automatic voltage stabilizer with time delay, low & high cut off arrangements suitable for operation on 230V/ 50C/S, AC supply. V-Guard. (SR)
Supply and fixing of MS stand for fixing outdoor unit M-1991
Supply and laying of 5/8" and 3/8" copper pipe (Extra beyond 3 metres supplied with AC unit) M-1990
Supply and laying of 20Mm PVc Drain Pipe with suitable gradient on wall.
Supply and fixing of Timer for dual alternative operation of Ac Unit in IBMS room. (Quo)
supplying & fixing Aspen mini blanc Automatic condensate drain pump for Split AC Unit in IBMS room. (Quo)
supplying & installation of 12.0 TR ductable unit Aspen max Hi flow automatic condensate drain pump for CSU Type AHU Unit (Quo)
Hire and Labour Charges for fixing Hanging scaffolding Charges for fixing the Louvers for Exhaust fan from Ist Floor to Fourth floor. (Data-V)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .