| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 4 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 5 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹53,000
Closing Date
16 Nov 2023, 2:00 pmClosed
EE, ECWD SAHARANPUR
EE, ECWD SAHARANPUR
Construction work of Underground Cable from 33/11 KV Sub-Station AVAS VIKAS (SAHARANPUR).
2023_PVVNL_849628_2
34/ECWD/SRE/2023-24
Open Tender
Electrical Works
Lump-sum
45 days
SAHARANPUR
PLEASE REFER TENDER DOCUMENTS
2 documents required · 2 mandatory
₹3,540
EE, ECWD SAHARANPUR
₹53,000
30 Nov 2023
18 Oct 2023
16 Nov 2023
18 Oct 2023
16 Nov 2023
19 Oct 2023
18 Oct 2023 - 18 Oct 2023
1. Supply of following material G.I. Channel (125×65)mm
M.S. Earthing Rod
Top Channel Holding Clamp for PCC Pole 9 M + S.T. Pole 11 M long & 13M long
E Bracket for 33 KV
Danger Board with clamp for PCC Pole 9 M + S.T. Pole 11 M long & 13M long
Number Plate with clamp for PCC Pole 9 M + S.T. Pole 11 M long & 13M long
Aluminum Binding wire
Barbed wire
Read Oxide Paint
Aluminium paint
M.S. Bolts Nuts & Washers
Earth wire clamp with Nut & Bolts
Concreting of support
Stone pad (300×300×75)mm
P.G. clamp for Dog to Dog conductor
Outdoor type cable jointing kit for 33 kv XLPE cable
G.I pipe 150mm dia 3 mtr long .
Laying of HDPE 80 PN 150mm Pipe
Route Marker
2. Safe carriage of with loading & unloading at both ends respectively. (under jurisdiction of PVVNL) a) Steel Tublar Pole SP-55 11M (Bottom Portion Galvanized)
d) 33 KV Pin Isulators (Polymer)
h) 33KV, 3×300mm² XLPE Cable
Erection of Following material A- Erection of support after excavation of foundation pit in mix soil/normal soil/soft & hard rock and its back filling and leveling etc. The size of the pit will be (900×600)mm and having depth of 1/6th of the full length of the support & Erection of support. The work includes carriage and handling of supports from site store to pit site. (i) 11 M Long STP, SP-55 Round Pole
B- Fixing of all clamps, Cross Bracing Sets 3.5 Mtr. from M.S. Angle 65×65×6mm/50×50×6mm & other accessories on the supports as per drawing. Work includes cutting of holes and providing M.S. Bolts of 16×40mm size in the middle of cross bracing with 1 no. spring washer. The work also includes carriage & handling of accessories from sectional store to pit site as well as any fabrication work if required. (i) ouble Pole Structures (a) 11 M Long STP, SP-55 Round Pole
Grouting of supports in CC 1:4:8 (Cement, sand & 40 mm brick ballast) Grouting will be done in the block of size (450×450)mm ×1/6th of full length of the support, up to ground level, 300 mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grit) with muffing as per drawing, work includes back filling and proper ramming. (i) 13 M Long STP, SP-72 Round Pole
Earthing of supports with MS earth Rod of (20×2500)mm long including excavation of pit and driving M.S. Rod 3.0 M apart from support and 0.5m below the ground level and connecting below the earth electrodes with the help of G.I. wire no. 8 SWG and earthing lugs.
Providing & fixing of danger board at each location as per specification of the drawing with clamps etc.
Making H.T. Connections of the proposed line, on to the existing 33 KV bay/line from where line is eminating and another at the end of line to the terminal gantry at proposed 33 KV Sub-station. The work consists of fixing of tension fitting, insulators, jumpering, clamping and binding etc. at the end as per site conditions.
Painting of following supports/structures with 2 coats of synthetic enamel paint after one coat of ready mix primer including cost of all material, as well as rubbing/cleaning of surface as required for proper completion of work. Painting will be done by post office red paint from top to cross arm and remaining by Aluminium paint. (a) 13 Mtr, SP-72 Poles including all channels/X-Arms/Clamps etc (i) Double supports
Wrapping of barbed wire on 33 KV PCC Poles/SP-55 ST & SP-72 ST Poles as anti-climbing device for a length of 0.9 Mtr., wire pitch/gap 13mm and fixing upper and lower end keeping lower end at a height of 2.75 Mtr. from the ground complete with supply and fixing of lower end & upper end clamps made of M.S. Flat 40×5mm complete with nuts & bolts & all other required material.
Numbering of each supports by preparing background with dark yellow paint in the size of 150mm dia and writing support number 100mm high with black paint.
Supply & Fixing of Stone Pad (300×300×75)mm
12. H.T. Power Cable Laying : i) Digging of trench of size 900x1050 mm for laying of 33KV cable including loops.
ii) Safely laying of 33KV 3x300mmsq XLPE cable in cable trench by laying 2 No. Cables in each trench. (single circuit laying)
iii) Safe laying of 33KV XLPE cable in Air on D/P / F/P.
iv) Laying of Ist class bricks along the length on both sides and stone slab 650x450x40 as a top cover over the XLPE cable in trench. (Single circuit laying) (as per RESPO Norms)
g) safely laying of HDPE 80 PN 150mm Pipe by trienchless methode in double layer tunnel under railway track for laying 33 KV XLPE cable
Laying of 33 KV 3x300 sqmm AL Cable in HDPE Pipe
v) Filling river sand in side beneath & around cable in the trench.
v) Back filling of excavated earth in the cable trench up to the ground level and remming properly.
vi) Making of 33KV outdoor type Heat shrink XLPE Cable Box of size 3x185mmsq and crimping of proper size Aluminium lugs. Work includes providing insulating tapes etc.
vii) Fixing 150mm dia 3 mtr long G.I pipe over 33KV 3x300 mm2 XLPE cable before mounting the cable on double pole structure. This work includes supply & fixing of clamps, Nut bolt, sealing of top and bottom of pipe and one end of pipe is to be buried under earth about 500mm including laying of cable in Pipe.
Fixing Cable Route Marker
BALA JI ELECTRICAL AND CONTRACTOR
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .