Improvement and Development of E.I and Fans in AAM-SC at Dr. Sahib Singh Verma Polyclinic ,Jharoda Burari in Ward no- 10 Under Civil Line Zone.
2025_MCD_254210_1
EEE-II/TC/2025-26/33.2
Open Tender
Electrical Works
Percentage
60 days
EEE/CLZ
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
₹7,400
3 Nov 2025
3 Nov 2025
11 Nov 2025
3 Nov 2025
11 Nov 2025
3 Nov 2025
Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. (a) 5/6 Amp Switch
(b) 15/16 A switch
(c) 3 pin 5/6 A socket outlet
(d) 6 pin 15/16 A socket outlet
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required. (a) 3 x4 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 25 mm
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissionino etc. as required. (a) Single pole
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required. (a) 3 X 2.5 sq.mm
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioninq etc. as required. (a) 63A
Earthing with GI earth pipe 4.5Mx40mm dia i/c accessories and providing masnary enclosure with cover plate having locking arrangement and watering pipe etc(but without charcoal or coke and salt complete as required.
Providing and fixing 25 mm X 5 mm G. I. strip on surface or in recess for connections etc. as required.
Brush Less Direct Current (BLDC) Motor Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req. (a) 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required.
LED Batten light (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency > 85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range - 15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/ 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing / Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer -in- Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminum Body (Thickness ≥ 1.20 mm) (a) 18- 22 watt
SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPM with desired color
S/I/T/C of stand for split AC
S/I/T/C of copper pipe for split AC
S/I/T/C of Drain Pipe
S/I/T/C of 3 Core, 4 Sqmm. Electrical wire for Air Conditioner
Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R- 407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). (a) 1.5 TR with 5 Star BEE Rating
Supplying, lowering, testing and commissioning of vertical type, multistage, totally enclosed water filled deep well submersible pumping set complete i/c connection etc. as reqd Single Phase 1.5 HP having discharge of 72 LPM Approx. at 49 M Head.
Supply, Installation, testing and commissioning of cubical type control panel board for single phase & Three Phase submersible pumping set of following rating complete with contactor, relay , MCB ,condenser ,voltmeter, ammeter and indication lamp etc including connections etc as reqd. 1.5 HP (Single Phase)
P&F following sizes of PVC insulated & PVC sheathed copper conductor 3 core submersible cable confirming to IS.694/1990 etc. as reqd.3x 2.5 sq.mm
Supplying and fixing following sizes of insulated steel flexible safety rope for holding submersible pump set i/c clips etc complete as reqd.6 mm
Development of tube well with suitable capacity of air compressor i/c lowering of the necessary induction pipe or line i/c cost of fuel, hire charges of compressor etc as reqd. The development shall be considered complete when Gravel stop sinking, Discharge ceased to improve and the sand contents are not more than 10 PPM after 20 minutes of starting the pump complete as reqd.
Supply, lowering and fixing following size of G.I. Pipe (M-Class) i/c cutting threading on both sides etc. ISI marked etc as reqd.a) 25mm(Nominal Bore)
Supply, lowering and fixing following size of G.I. Pipe (M-Class) i/c cutting threading on both sides etc. ISI marked etc as reqd.a) 36mm(Nominal Bore)
SITC of single phase monoblock pump set complete with all accessories workable on 415/240 volt, 50 HZ AC supply (a) 1 H.P(0.75 Kw) single phase pump set, head from 12-30 mtr section and delivery 25x 25 mm
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
GeneralConditions2025.pdf
Tender Documents • 0.12 MB
MCD_GCC_Circulars_2025.pdf
Tender Documents • 12.97 MB
BOQ_292534.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .