Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.7 LAccepted-AOC P O SASINDA VILL KASHIYA P S BELDA WEST MEDINIPUR PIN 721445 | BELDA | PASCHIM MEDINIPUR | WEST BENGAL | 721445 | ₹7.7 L | L1 | Accepted-AOC AOC |
| 2 | L2₹7.9 LRejected-Finance | ₹7.9 L | L2 | Rejected-Finance L2 |
| 3 | L3₹10.3 LRejected-Finance 2ND FLOOR KAMARHATI 1 GRAHAM ROAD KAMARHATI KAMARHATI KOLKATTA WEST BENGAL 700058 | 24 PARAGANAS NORTH | WEST BENGAL | 700058 | ₹10.3 L | L3 | Rejected-Finance L3 |
Tender Value
Refer Docs
EMD Value
₹21,157
Closing Date
16 Jan 2026, 12:00 pmClosed
Room No. 108, Purta Bhawan, Salt Lake
Room No. 108, Purta Bhawan, Salt Lake
Construction of a G plus 5 storied Academic Building for the Open Campus-cum-Regional Centre of NSOU--- EI for Fire Pump room, chiller plant room with starter, different plug points Etc
2025_WBPWD_979348_1
WBPWD/EE/BED/e-NIQ-129/2025-26
Open Tender
ELECTRICAL WORKS ORG
14 days
NSOU
Please refer Tender documents.
5 documents required · 5 mandatory
₹21,157
29 Jan 2026
24 Dec 2025
19 Jan 2026
2 Jan 2026
16 Jan 2026
2 Jan 2026
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (BrandapprovedbyEIC) in20mmsizePVCrigidconduit 'FR' (Precisionmake), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate and 2no. suitable size“Ph&N”copper bar&earthing attachment fixedonwall incl.mendinggood damages to original finish. Average run 6 mtr
Distribution wiring in 1.1 KV grade 22/0.3 (1.5sqmm) single corestranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20 mm size PVC rigid conduit 'FR' (Precision make),with 1.1 KV grade 1x22/0.3(1.5sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 6A 3 pin Modular type plug socket & switch (Brand approved by EIC)on 4 Module GI switch board with 3/4 Module top cover plate on wall incl. necy. connection making earthing attachment, painting and mending good damages to building works. On Board
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required. 2x80/0.4 (10 sqmm) + 1x84/0.3 (6 sqmm) as ECC
Supplying and fixing polythene pipe complete with fittings as necy. under ceiling/beam, bound with 22 SWG GI binding wire incl. supplying and drawing 1x18 SWG GI Wire as fish wire inside the pipes and fittings and providing 50 mm dia disc of MS sheet (20 SWG) having colour paint at one face fastened at the load point end of the polythene pipe with fish wire (synchronizing with roof/beam casting work of building construction) 25mm dia 3mm thick Polythene Pipe
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 25 mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. i) 2 x 84/0.3 (6 Sq mm)
ii) 4 x 56/0.3 (4 sqmm) + 2 x 36/0.3 (2.5 sqmm) ECC
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required i) 2x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC
ii) 2 x 36/0.3 (2.5 Sq mm) + 1 x 22/0.3 (1.5 Sq mm) ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. 10 Sq mm
S & D of 1.1 KV. Gr. armored XLPE/A Al. LT cable of following rating for connection from main panel at gr. Fl to VTPN DB at different floor. [Make: Gloster/Polycab/Havells/RR Kable] a) 4 core X 120 sq.mm. [From Main Panel to Sub Dist.Panel]
b) 4 core X 50 sq.mm. [ From Main LT Panel to VTPN]
c) 4 core X 25 sq.mm [From VTPN to Starter]
d) 4 core X 10 sqmm [For Area Lighting]
S & laying of 1.1 KV. Gr. armored XLPE/Un armoured Al. LT cable of following rating for connection from main panel at gr. Fl to VTPN DB at different floor. [Make: Gloster/Polycab/Havells/RR] 1 core X 50 sq.mm.
Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed a) 4 core X 120 sq.mm.
Laying of cable of following sizes on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting a) 4 core X 300 sq.mm.
a) 4 core X 50 sq.mm.
i) 4 core X 25 sqmm
ii) 4 core X 10 sqmm
Supplying and fixing 4 core compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : i) 4 core X 300 sqmm
i) 4 core X 120 sqmm
i) 4 core X 50 sqmm
i) 4 core X 25 sqmm
ii) 4 core X 10 sqmm
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. i) 4 core 300 sqmm
i) 4 core 120 sqmm
i) 4 core 50 sqmm
i) 4 core 25 sqmm
ii) 4 core 10 sqmm
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required. (c) 80 mm Dia
Supplying and fixing double door 4-Way Vertical TPN MCB Distribution board for lsolator incomer with IP-42/43 protection, on angte iron frame on wall & mending good the damages to original finish incl. lnter connection with suitable size of copper wire and neutral link & provision for earthing attactment (Mk. L & T,Cat No DBVTM004DD /equivalent of Legrand / ABB/ HAVELLS) a) 100 A FP MCB Isolator (Make- L&T, cat no- BF410000/Legrand/ABB/Havells) b) 63 A TP MCB (make- L&T , cat No-BB30630C/ Legrand/ABB/Havells)-4 Nos.
Supplying and fixing double door Vertical TPNMCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Interconnection with suitable size of copper wire and neutral link & provision for earthing attachment.
Supplying and fixing 415V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic /adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection (Make- L&T,/Legrand/ABB/Havells) 125 A FP MCCB (Make- L&T / Legrand/ABB/Havells)
Supplying and fixing 240V MCB of Breaking apacity 10kA & C characteristics on din rail of existing DBs and necessary connection. (Make-Legrand/ Seimens/ Schneider/ L&T/ ABB) i) 6-32 A SP
Supplying and fixing 240/415 V TP/FP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection.(Make-Legrand/ Seimens/ Schneider/ L&T/ ABB) i) 63 A (TP) [VTPN ]
Supply & Fixing 240 V, 2 nos 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 2 nos 6A Modular type switch, without plug top on 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. (Make- Legrand Myrius/Crabtree/ Siemens)
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. (Make- Legrand Myrius/Crabtree/ Siemens)( for electrical room cooler/aquaguard/ other amenities for entire building)
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Supply & Delivery double LED Fittings with LED tube ( Philips Make, Cat No.TMC 502 2 x T-LED 22W with MAS LEDTube 1200mm 18W 865 T8I-21001m) Or Equivalent product of Crompton/Wipro/Havells having similar specification in all respect)
Fixing only outdoor / street light type fluorescent light fitting complete with all accessories to be fixed/projected from the wall of the building incl. making holes to building, S&F 40 mm dia GI pipe (ISI-Medium) 1.50 mts. average length, with GI socket at one endand thread at the other end & suitable bend to house the fitting & making necy. connections with S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall and painting.
Supply & Delivery of LED Flood light luminarie IP 66,made up of pressure die cast aluminium housing with Toughened glass/ PC cover provided with high power LEDs and secondary optics PCIPMMA lens and Silicon filled BIS registered Potted Vibration proof Driver with built in 4 KV surge protection and 10KV extemal SPD with EIlicacy>l3s lumen/watt or better, Impact resistance-IK10/IKO8,CRI >70, CCT > 5700K. Make:- Wipro Ranger LED/Crompton, PLUTO NEO/ Philips Tango LED/Jaquar) Driver Mk.- Philips Sig:nify/Wipro / Xitanium/ Inventronics. LED Chip mk.-Nichia,Cree,Osram, Lumiled. (a) 200 watt
Lowering and refixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. making necessary disconnection and connection as required.
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.
Supply and Delivery of 415 volt, 20 HP Star Delta submersible Pump Controller, Coil Voltage-380 V--415 V. [Make- Lauritz Knudsen (cat No--MU-G30 20-33A)]
Supply and delivery of 12 Volt,12 AH SMF battery, recharged with constant current and constant voltage mode only. (Make- Exide power safe plus Model- EP 12-12)
Supply and Delivery of 22 ft height bamboo ladder.
Suppling and Fixing of 3 Ph, 4 Way, 415 Volt, 10/40 Amp, C.L-1.0 Energy meter. (Make- L&T (Cat No- WR301BC6D20) / Siemens/ABB)
Suppling and Fixing of 1 Ph, 240 Volt, 24 hrs digital time switch. (Make- GIC)
Suppling and Fixing of 1/2 HP, 1 Ph, 240 volt centrifugal Pump, on the base made by brick and mending good the damages.
Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation, per storey of building per vertical run
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1x4 SWG GI (HotDip) wire (4Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S& F 15mm dia GI pipe protection (1Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65Mts. below the ground level By TATA Medium GI Pipe
Connecting the equipments to earth busbar including S&F GI (HotDip) wire of size as below on wall /floor with staples buried inside wall /floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. No 10 SWG GI
Excavation of soil for installation of Earth Electrode and filling & ramming as to GS. (For Soft soil)
Note:- Rate should be quoted inclusive of all taxes and duties including GST.
Please Enable Macros to View BoQ information
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.89 MB
2911_ii.pdf
Tender Documents • 0.50 MB
BOQ_2387086.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid