Loading…
Loading…
Tender Value
₹50 L
EMD Value
₹50,000
Closing Date
2 Jul 2026, 6:00 pm
Similar tender results from the same govt authority in the past 3 years.
The Executive Engineer (O&M), DGVCL Piplod Division Office, Surat.
Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable end termination & straight through jointing kit (to be supplied by contractor) on ARC basis under all scheme under Althan sub division under Piplod Division as well as all Sub-division in jurisdiction under Piplod Division or within the jurisdiction of Surat City Circle.
315329
DGVCLDPPL/0098/06/2026 Approved Date: 03-06-2026
Open
Electrical
Surat
₹1,180
SURAT DGVCL
₹50,000
18 Jun 2026
18 Jun 2026
18 Jun 2026
2 Jul 2026
18 Jun 2026
Sub:-Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with
cable end termination & straight through jointing kit (to be supplied by contractor) on ARC basis under all scheme under CFC under Piplod Division as
well as in jurisdiction of Althan sub division under Piplod Division or within the jurisdiction of Surat City Circle.
Item Code DETAILS OF WORKS Qty Unit Rate Amount
1 9925000001 Labour charge for excavation of cable trench of 400mm Meter
width x 1200mm depth, in any type of soil for laying of
cable of size up to 240 mm2 (For additional cable 200 mm
additional width shall be considered i.e. half trench
length is to be considered)
2 9925000002 Labour charge for excavation of cable trench of 600mm Meter
width x 1200mm depth, in any type of soil for laying of
cable of size up to 240 mm2 (For additional cable 200 mm
additional width shall be considered i.e. half trench
length is to be considered)
3 9925000003 Labour charge for excavation of cable trench of 400mm Meter
width x 1500mm depth, in any type of soil for laying of
cable of size up to 240 mm2 (For additional cable 200 mm
additional width shall be considered i.e. half trench
length is to be considered)
4 9925000004 Labour charge for laying of 11kV / 22 kV XLPE Cable of Meter
size up to 240 mm2 & preparation of sand layer 100mm
thick, in the cable trench & covering the cable with
mm dia (Inner), thickness 25 mm, 1.0 meter long RCC
half round muffs and providing and fixing of 4inch width
yellow colour polyethylene tape with printing "CAUTION
ELECTRIC CABLE BELOW" at 0.75 m depth from ground
surface after laying cable in trench. This will provide
indication that electric cable is passing underground so as
to protect cable from mechnical injuries, refilling the
same, as per Instruction of Engineer in Charge (EIC).
5 9925000005 Labour charge for horizontal drilling using Auger machine Meter
without damage to surface road at max 2.0 mtrs depth &
putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D.
, 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-
1987(3rd revision) and BIS certification and laying of
11KV/22KV XLPE cable of size up to 300 mm2 in HDPE
pipe, as per Site Condition (excluding cost of pipe). The
detail map obtained from HDD machine and excell
sheet(hard and soft copy) indicating the respective depth
and distance from adjacent landmark for each segment
for HDD is must required to be submitted. HDD to be
carried out at depth 1.5 mtrs to 2.0 mtrs as per site
conditions and as per instruction of EIC.
6 9925000006 Labour charge for horizontal drilling manually without Meter
damage to surface road at max 2.0 mtrs depth & putting
of 6.11 kg/cm2 , class-4,Green color, 110mm O.D., 8.5mm
thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd
revision) and BIS certification and laying of 11KV/22KV
XLPE cable of size up to 300 mm2 size, as per Site
Condition (excluding cost of pipe). The detail map and
excell sheet(hard and soft copy) indicating the respective
depth and distance from adjacent landmark for each
segment of cable to be submitted. Drilling to be carried
out at depth Minimum 1.2 mtrs to 2.0 mtrs as per site
conditions as per instruction of EIC.
7 9925000007 Supply of 6.11kg/cm2, class-4,Green color, 110mm O.D., Meter
8.5 mm thickness H.D.P.E. pipe confirms to IS 4984 and
BIS certification for laying of underground 11KV / 22KV
XLPE cable up to 300 mm2 size.
8 9925000008 Labour work for RCC concreting on disputed location and CMT
repairing of damage portion of road crossing for the work
carried out for roads crossing as well as concreting &
muffing of ploes including all materials (1:2:4)
9 9925000009 Providing & fixing concrete stone route marker of 300 No
mm width x 150 mm thick x 650 mm height embedded in
earth at least 300 mm below & 350 mm above ground
level respectively at distance approx 50 meters along the
length of cable. The RCC concreting (1:2:4)(all necessary
maeterials will be in bidder's scope) of route marker is to
be carried out 300 mm width x 150 mm thick x 300 mm
below ground level as per instruction of EIC. The route
marker should be with name of company with approved
yellow colour-DGVCL. The distance from marker to cable
and cable depth with feeder name etc., marked with
arrow sign is to be painted on it.The route marker is to be
fixed at location near to any fixed permanent location
(not necessary to fix exact on top of cable) as per
instruction of EIC.
10 9925000014 Labour charge for erecting of 11kV / 22 kV XLPE cable of Per Job
size up to 300 mm 2 on DP Structure with fixing of 02 Nos
polymer cleats on top and middle part. Polymer cleats,
nut bolts etc. fixing material to be provided by contractor.
11 9925000015 Providing & fixing of 6.11kg/cm2, class-4,Green color, Per Job
110mm O.D., 8.5mm thickness H.D.P.E. pipe confirms to
IS 4984 and BIS certification on the erected DP structure
for the mechanical protection of cable by inserting the
cable inside HDPE pipe. The HDPE pipe shall be erected in
such a way that 300mm shall be below the ground level
and the rest 2700 mm shall be supported on the DP
Structure with 01 No Polymer cleat. All materials
including polymer cleat and Nut bolt to be provided by
12 contractor.and fixing of pipe type earthing from 80 mm
9925000016 Providing No
dia class-B GI pipe with pit to be filled with salt & coke
and construction of chamber as per DGVCL Drg. No. dg
/100 for DP and cable. The earthing pit should be joined
with cable by G.I. strip of size 1” width & 2 mm thick. All
material GI pipe, Coke, Salt etc will be supplied by bidder.
13 9925000017 Supply & fixing of heat shrink type end terminations No
(outdoor) for upto 11kV 3C x 185 mm 2 size XLPE cable as
per DGVCL technical specification.
14 9925000018 Supply & fixing of heat & shrinkable end terminations No
(outdoor) for upto 22 kV 3C x 185 mm2 size XLPE cable as
per DGVCL technical specification.
15 9925000019 Supply & fixing of heat shrink type end terminations No
(indoor) for upto 11kV 3C x 185 mm 2 size XLPE cable as
per DGVCL technical specification.
16 9925000020 Supply & fixing of heat & shrinkable end terminations No
(indoor) for upto 22 kV 3C x 185 mm 2 size XLPE cable as
per DGVCL technical specification.
17 9925000021 Supply & fixing of heat shrinkable straight through joint No
for upto 11kV 3C x 185 mm2 size XLPE cableas per DGVCL
technical specification.
18 9925000022 Supply & fixing of heat shrinkable straight through joint No
type for upto 22kV 3C x 185 mm 2 size XLPE cable as per
DGVCL technical specification.
19 9925000023 Labour charge for excavation of 2100mm long x 1200mm No
wide x 1200 mm deep joint pits for installation of
11kV/22kV Straight through joints as per instruction of
engineer-in-charge & covering the cable with 150 mm dia
(Outer), thickness 25 mm, 1.0 meter long RCC half round
muffs & refilling same as per instruction of EIC .
20 9925000024 Providing and fixing of insulating bus bar , made from No
11KV/22KV XLPE cable after removal of semi conducting
layer and applying of PVC heat shrinkable anti-tracking
core insulating tubing (1.1KV), on both end terminal using
Aluminium long barrel heavy duty up to 240 sq mm lugs,
Aluminium bus connector. Taping with PG- clamp for bus
conductor as per drawing and as per instruction of EIC.
The Alluminium lugs and PG clamp shall be covered with
11KV/22KV HT insulating tapes.(11KV/22KV XLPE cable will
be in scope of DGVCL while all other materials will be in
bidder's scope)
21 9925000025 Testing of cable at various points and commissioning the No
feeder as per instruction of engineer-in-charge. Test
result shall be submitted by contractor with bill.
22 9925000026 Preparation and submission of 6 (six) copies, of complete Set
layout drawings with GIS mapping as per actual cable
routing showing road crossing, HDPE pipe sleeving,
jointing locations, markers etc.
23 9925000027 Providing and fixing of Sign Board at junction point Made No
out of 2 mm aluminium sheet size 750x300 mm (2.5 x 1ft)
rectangle, as per design, pre treated with phosphate
process and acid etching coated with one coat of epoxy
primer and two coats of best quality paints, refloctrorised
with Hi-Intensity retro – reflective sheeting as per the
latest and frame fabricated from suitable size iron angle.
The Sign Board is to be fixed on the base prepared from
channel and bracing angles which is grouted by means of
cement concreting of 1:2:4 for size of 300 mm dia x
mm height (500 mm to be grouted in ground). The details
to be displayed on sign board will be given by In-charge
(a) Hi intensity Micro prismatic Grade
24 9925000028 Providing and fixing of Sign Board (Danger Board) on No
Distribution Transformer Centers
Made out of 2mm aluminium sheet size 300x300mm
(1x1ft) as per design, pre treated with phosphate process
and acid etching coated with one coat of epoxy primer
and two coats of best quality paints, refloctrorised with Hi-
Intensity retro-reflective sheeting as per the latest and
frame fabricated from suitable size iron angle. The Sign
Board (Danger Board is to be fixed at the location as per
instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
25 9925000029 Providing & fixing of aluminium tag of size 250 mm (L) x No
75 mm (W) from 3 mm aluminium sheet along with
mm dia aluminium binding wire for fixing of aluminium
tag near end termination joint at DP structure for
identifyng the cable. The details of feeder i.e. 11 / 22 KV
with feeder name shound be punched on the tag by letter
punch of size 16 mm as per instruction of In-charge
26 9925000030 Supply & fixing of heat shrink type end terminations Nos
(outdoor) for 11kV 3C x 240 mm2 size XLPE cable as per
DGVCL technical specification.
27 9925000031 Supply & fixing of heat & shrinkable end terminations Nos
(outdoor) for 22 kV 3C x 240 mm2 size XLPE cable as per
DGVCL technical specification.
28 9925000032 Supply & fixing of heat shrink type end terminations Nos
(indoor) for 11kV 3C x 240 mm2 size XLPE cable as per
DGVCL technical specification.
29 9925000033 Supply & fixing of heat & shrinkable end terminations Nos
(indoor) for 22 kV 3C x 240 mm2 size XLPE cable as per
DGVCL technical specification.
30 9925000034 Supply & fixing of heat shrinkable straight through joint Nos
for 11kV 3C x 240 mm2 size XLPE cableas per DGVCL
technical specification.
31 9925000035 Supply & fixing of heat shrinkable straight through joint Nos
type for 22kV 3C x 240 mm2 size XLPE cable as per DGVCL
technical specification.
32 9925000047 Laying of any size of 11/ 22 KV XLPE /PILC Cable in per cable
redaymade trench or in open space per mtr
Labour charges for Lying of O/H XLPE cable pole to pole
34 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 NO.
meter long RCC half round pipe
Erection of D.P. (double pole) structure using 9 / 11 Mtr.
RSJ pole with cable connection arrangement along with
fitting of necessary fabrication for 11KV cable including
excavation of pit & refilling of earth as per instruction of
EIC. (Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 9 / 11 Mtr RSJ pole
with cable connection arrangement along with fitting
ofnecessary fabrication for 11KV/22 KV cable including
excavation of pit & refilling of earth as per instruction of
EIC. (Exclusive of concreting & muffing of poles)
Erection of D.P. (double pole) structure using 8.0 Mtr. PSC
pole with cable connection arrangement along with fitting
of necessary fabrication for 11KV cable including
excavation of pit & refilling of earth as per instruction of
EIC. (Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 8.0 Mtr PSC pole
with cable connection arrangement along with fitting
ofnecessary fabrication for 11KV/22 KV cable including
excavation of pit & refilling of earth as per instruction of
EIC. (Exclusive of concreting & muffing of poles)
40 Laying (including installation, testing and commissioning) mtr 335 as per rate derived by UGVCL letter no
of various size of ugvcl/r&c/ug/Cost Data-2022-23/816 Date:-27-
Single circuit 11 KV 300 sq mm XLPE insulated Aluminium 01-2023
armoured Cable in ground 1200 mm deep and 300 mm
wide trench, providing sand cushioning below (75 mm
thick layer of sand) and above (75 mm thick layer of sand)
of the cable and covering it with RCC half round hume
pipe (150 mm inner
diameter with thickness of 30 mm and One meter in
length) before refilling
pre-bonding tap/warning tap should provide below
(including installation, testing and commissioning) mtr 468 as per rate derived by UGVCL letter no
size of back filling the same to make ground ugvcl/r&c/ug/Cost Data-2022-23/816 Date:-27-
Doubleas circuit
11 KV 300 sq mm XLPE insulated 01-2023
As per specification
Aluminium armoured and drawing
Cable of DGVCL.
in ground 1200(mm
wide trench, providing sand cushioning
below (75 throughout
mm thick on cable
of sand) andgap).
thick layer of sand) of the cable and covering it with RCC
half round hume pipe (150 mm inner diameter with
thickness of 30 mm and One meter in length) before
refilling pre-bonding tap/warning tap should provide
below 700 mm from the ground level and back filling the
same to make ground level as per original. As per
specification and drawing of DGVCL. ( RCC half round pipe
should be provide throughout on cable without gap).
42 Supply & fixing of heat shrink type end terminations No 5549 as per rate derived by UGVCL letter no
(indoor) for 11kV 3C x 300 mm 2 size XLPE cable as per ugvcl/r&c/ug/Cost Data-2022-23/816 Date:-27-
technical specification. 01-2023
43 Supply & fixing of heat shrink type end terminations No 6676 as per rate derived by UGVCL letter no
(outdoor) for upto 11kV 3C x 300 mm2 size XLPE cable as ugvcl/r&c/ug/Cost Data-2022-23/816 Date:-27-
per technical specification. 01-2023
44 Supply & fixing of heat shrinkable straight through joint No 8040 as per rate derived by UGVCL letter no
for 11kV 3C x 300 mm 2 size XLPE cableas per L technical ugvcl/r&c/ug/Cost Data-2022-23/816 Date:-27-
specification. 01-2023
Rate as per SOR 50,00,000/-
Executive Engineer (O&M)
DGVCL, Division Office,
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
50 LACS ALTHAN SDN UG WORK TENDER.pdf
2. BID DOCUMENT.pdf
3. Detail Technical Specification.pdf
SCHEDULE B UG ALTHAN.pdf
Download all tender documents and submit your bid