Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.5 LAccepted-AOC | ₹5.5 L Quoted ₹5.7 L | L1 | Accepted-AOC Accepted due to lowest |
| 2 | L2₹7.3 L+₹1.6 L (28.3%)Rejected-Finance | ₹7.3 L+₹1.6 L (28.3%) | L2 | Rejected-Finance Other than lowest |
Tender Value
Refer Docs
EMD Value
₹16,000
Closing Date
24 Feb 2021, 6:00 pmClosed
GE Ludhiana
Garrison Engineer Military Engineer Services Near Jagraon Bridge PIN-141001
Repair / Maint of sewage pump and misc E/M works at Dholewal and CG Complex under GE Ludhiana.
2021_MES_409635_2
GE/LDH-58/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Dholewal and CG Complex Under GE Ludhiana
Refer NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE Ludhiana
₹16,000
Yes
4 Mar 2021
6 Feb 2021
25 Feb 2021
6 Feb 2021
24 Feb 2021
9 Feb 2021
6 Feb 2021 - 8 Feb 2021
Amount
Taking out of submersible pump (sewage) of capacity 5/7.5/10 HP from the sewage well using chain pully block, transportation to civil workshop for repair and re-fixing in original position complete all as specified and directed by Engineer-in-charge.
M & L, strip opening submerssible pumping set 7.5 HP capacity, repairing the same by remetaling of shaft, turning of lathe to bring into original size, polishing, re-assembling including replacement of impeller bearing set, oil seal, worn out nuts, bolts, gasket etc, complete all as specified and directed by Engineer-in-charge.
M & L, Strip opening submerssible electric motor 7.5 HP 3 phase 415 volt, cutting existing burnt winding, rewinding the same with super enamel copper wire of gauge and number of turns as per original including replacement of bearings, re-fixing the motor with pump, bringing back to its original location connecting with sewage system and testing complete all as specified and directed by Engineer-in-charge.
Disconnecting non clog pumping set of capacity 5 HP transportation to civil workshop for repair, bringing back after repairs and re-fixing in original position complete all as specified and directed by Engineer-in-charge.
M & L, Strip opening of non clog pumping set of capacity 5 HP, repairing the same by re-assembling including replacement of impeller, bearing set, oil seal worn out nuts, bolts, gasket etc complete all as specified and directed by Engineer-in-charge.
Bailing out sludge water from sludge tank by using pumping set and disposing off the same not less than 50 metres away from site.complete all as specified and directed by Engineer-in-charge.
Bailing out mud/sludge (approx 10 cum) from sewage tank by using buckets and disposing off the sludge as specified and directed including cleaning of sludge tank complete all as specified and directed by Engineer-in-charge.
S & F in replacement direct online starter (DOL) in S/S housing with overload relay range 10 to 16 Amp complete suitable for electric motor 10 HP. Make : Siemen/L&T/Havells/ C & S/ Indo Asian
S & F in replacement direct online starter (DOL) in S/S housing with overload relay range 10 to 16 Amp complete suitable for electric motor 7.5 H P Make : Siemen/L&T/Havells/ C & S/ Indo Asian
S & F in replacement of cast iron sluice valve 80mm dia heavy duty including replacement of worn out nuts, bolts, gasket etc complete. Make: MINAR/BIR/ARCO/ Kirloskar/L & T/ Upadhaya
Supply and replacement of 1100 volts grade heavy duty PVC insulated flat submerssible cable 10 sqmm, 3 core with copper conductor complete. Make:- Havells, Finolex,KEI, Polycab
Supply and replacement of 1100 volts grade heavy duty PVC insulated flat submerssible cable 6 sqmm, 3 core with copper conductor complete. Make:- Havells, Finolex,KEI, Polycab
Supply and filling hypochloride solution Gde I conforming to IS 11673-1992 having 10 to 15% active liquid chlorine complete all as specified and directed by Engineer-in-charge.
S & F in replacement air termination rod single pointed aluminium of dia 12mm and 300 mm long.
Dismantling existing aluminium strip of size 25mm x 3 mm and re-fixing with new saddle and fixing screw for roof conductor/down conductors above ground.complete all as specified and directed by Engineer-in-charge.
S & F in replacement aluminium strip of size 25mm x 3 mm with new saddle and fixing screw for roof conductor/down conductor above ground.complete all as specified and directed by Engineer-in-charge.
S & F in replacement test point terminal block made of gun metal or phosphorus size 75mm x 75mm x25mm duly drilled and screwed including provision of nuts, bolts etc complete all as specified and directed by Engineer-in-charge.
Supply, laying, testing and commissioning in replacement of cable XLPE insulated PVC sheathed armoured 1100 volt grade heavy duty ISI marked with copper conductor of 35 Sqmm 3.5 core laid in trenches, fixed by means of MS saddles on or fixed on poles including connection with proper lugs. Note : Excavation, returning & filling of soil, sand and bricks will be measured and paid separately.
Excavation in trenches in soft/loose soil not exceeding 1.5 m wide and not exc. 1.5 mtr deep for laying of cables and getting out soft/loose soil complete all as specified and directed by Engineer-in-charge.
M & L, sand cushioning for laying of under ground cable complete all as specified and directed by Engineer-in-charge. ( Note:- Thicness of 18cm after punning shall be considered for payment.)
Supplying and laying bricks common brunt clay building bricks sub class B incl removing of old bricks complete all as specified and directed by Engineer-in-charge.
Returning filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cms thick in trenches complete all as specified and directed by Engineer-in-charge.
Removal of surplus soil obtained from excavation to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point.complete all as specified and directed by Engineer-in-charge.
Supply and fixing LED Bulb 10 watt complete all as specified and directed by Engineer-in-charge. Make : Bajaj/Phillips/Havells.
Supply and fixing LED Bulb 15 watt complete all as specified and directed by Engineer-in-charge. Make : Bajaj/Phillips/Havells.
Supply and fixing in replacement 3 metre long column pipe 80mm dia made out of heavy grade GI pipe with two number flanges welded at both ends having drilled hole and cut for submersible cable complete all as specified and directed by Engineer-in-charge.
Supply and fixing , GI fitting heavy grade 80mm bore such as bends (any type, radius and angle), tapers any type (straight, bend, increasing, decreasing etc incl fabrication work as per site requirement), flange, caps and plugs etc. suitable for 80 mm GI pipe heavy grade and socketed pipes including taking out the defective one form the trenches or ground/sumps complete all as specified and directed by Engineer-in-charge.
S&F, polycarbonate thermoplastic outdoor distribution board with flap cover operate with IEC 61439-3 which should be shock proof, protection class-II, earthed , IP 65 in accordance with IEC 60529(EN60529) weather proof , corrision free , acid and chemical resistant , impact resistant, , ultra voilet resustant according to IEC61439-I, made of halogen & silicone free recyclable mtrl, internally embedded gasket with provision for cable entry through integrated flanges top and bottom, Impact strength IK 08 (5 joule) in accoradance with IEC 62 262, The manufacturer of board shell submit a copy of CPRI test report in polycarbonate, The gasket should be internally embedded made of polycarbonate the box should have glow wire test 960 degree centigrate in accordance with 60695-2-11 (flame retardent and self exinguishing) UL subject 94,V-2, colour- gray , RAL-7035, distrubution board with the provision of 1 No modular switch and socket. Make:- Hensel/Siemens/GE power/Rittal
PARDEEP CONSTRUCTION COMPANY
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .