Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.1 LAccepted-AOC | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹44.4 L+₹1.9 L (4.41%)Rejected-Finance 3082 SECTOR 20D CHANDIGARH 160 020 | CHANDIGARH | CHANDIGARH | 160020 | L2 | Rejected-Finance Other Than Lowest Bidder | |
| 3 | L3₹46.5 L+₹4.0 L (9.39%)Rejected-Finance | L3 | Rejected-Finance Other Than Lowest Bidder | |
| 4 | L4₹48.7 L+₹6.2 L (14.6%)Rejected-Finance SECTOR 10 PANCHKULA | PANCHKULA | PANCHKULA | HARYANA | L4 | Rejected-Finance Other Than Lowest Bidder | |
| 5 | L5₹51.5 L+₹9.0 L (21.2%)Rejected-Finance NOT FOUND | L5 | Rejected-Finance Other Than Lowest Bidder |
Tender Value
₹43 L
EMD Value
₹86,000
Closing Date
9 Aug 2023, 6:00 pmClosed
GE Chandigarh
GE Chandigarh N Area Pin-160003
SPL REPAIR/REPLACEMENT OF EXISTING UNSV LT PANELS TO UPGRADE NEW LT PANEL AND EXISTING OLD VINTAGE ELECTRICAL LT/STREET LIGHT RCC POLES CONVERT TO NEW STEEL POLE AT N AREA AND HALLOMAJRA AREA UNDER GE CHANDIGARH
2023_MES_608561_1
GE/CHD-41/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Chandigarh
Class D category b(i) for contractor enlisted in MES
7 documents required · 7 mandatory
₹500
GE Chandigarh
₹86,000
Yes
16 Sept 2023
13 Jul 2023
11 Aug 2023
13 Jul 2023
9 Aug 2023
28 Jul 2023
13 Jul 2023 - 23 Jul 2023
Amount
In coming:- 1. MCCB - 400 Amps, 415V, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos Out going:- 1. MCCB - 315 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 No. 2. MCCB - 200 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-02 Nos. 3. MCCB - 125 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 25 KA-02 Nos. 4. Spare place for fixing any switch gear in future-01 No and Necessary foundation with bolts to be grouted in PCC foundation as recommended by the manufacturer shall deemend to be included in overall quoted rates Note :-Panel shall be front and back openable, double door system lockable/openable by key from both sides and shall have louvers and air vent gasket for natural flow of air 'U' type gasket shall be used to make the panel completely vermin proof. The bottom of the panel shall contain a detachable plate having provision of entry of amroured cable of adequate size with MS glands.
In coming:- 1. MCCB - 400 Amps, 415V, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos Front operatd changeover switch 315 Amps - 01 Nos , Out going:- 1. MCCB - 250 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 25 KA-02No. 2. MCCB - 160 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos. 3. Spare place for fixing any switch gear in future-01 No and Necessary foundation with bolts to be grouted in PCC foundation shall deemend to be included in overall quoted rates Note :-Panel shall be front and back openable, double door system lockable/openable by key from both sides and shall have louvers and air vent gasket for natural flow of air 'U' type gasket shall be used to make the panel completely vermin proof. The bottom of the panel shall contain a detachable plate having provision of entry of amroured cable of adequate size with MS glands
In coming:- 1. MCCB - 200 Amps, 415V, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos , Out going:- 1. MCCB - 160 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-02 Nos. 3. Spare place for fixing any switch gear in future-01 No and Necessary foundation with bolts to be grouted in PCC foundation shall deemend to be included in overall quoted rates Note :-Panel shall be front and back openable, double door system lockable/openable by key from both sides and shall have louvers and air vent gasket for natural flow of air 'U' type gasket shall be used to make the panel completely vermin proof. The bottom of the panel shall contain a detachable plate having provision of entry of amroured cable of adequate size with MS glands
In coming:- 1. MCCB - 315 Amps, 415V, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos Out going:- 1. MCCB - 160 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-02 Nos. 3. Spare place for fixing any switch gear in future-01 No and Necessary foundation with bolts to be grouted in PCC foundation shall deemend to be included in overall quoted rates Note :-Panel shall be front and back openable, double door system lockable/openable by key from both sides and shall have louvers and air vent gasket for natural flow of air 'U' type gasket shall be used to make the panel completely vermin proof. The bottom of the panel shall contain a detachable plate having provision of entry of amroured cable of adequate size with MS glands
In coming:- 1. MCCB - 250 Amps, 415V, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos Out going:- 1. Triple pole and neutral - 100 Amps, AC with thermal setting 70% to 100% and breaking capacity 35 KA-10 Nos. 3. Spare place for fixing any switch gear in future-01 No and Necessary foundation with bolts to be grouted in PCC foundation shall deemend to be included in overall quoted rates Note :-Panel shall be front and back openable, double door system lockable/openable by key from both sides and shall have louvers and air vent gasket for natural flow of air 'U' type gasket shall be used to make the panel completely vermin proof. The bottom of the panel shall contain a detachable plate having provision of entry of amroured cable of adequate size with MS glands
In coming:- 1. MCCB - 250 Amps, 415V, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos Front operatd changeover switch 250 Amps - 01 Nos , Out going:- 1. MCCB - 250 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 25 KA-01 No. 2. MCCB - 200 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos. 3. Spare place for fixing any switch gear in future-01 No and Necessary foundation with bolts to be grouted in PCC foundation shall deemend to be included in overall quoted rates Note :-Panel shall be front and back openable, double door system lockable/openable by key from both sides and shall have louvers and air vent gasket for natural flow of air 'U' type gasket shall be used to make the panel completely vermin proof. The bottom of the panel shall contain a detachable plate having provision of entry of amroured cable of adequate size with MS glands
In coming:- 1. MCCB - 315 Amps, 415V, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos Front operatd changeover switch 250 Amps - 01 Nos , Out going:- 1. MCCB - 250 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 25 KA-03 No. 2. MCCB - 160 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos. 3. Spare place for fixing any switch gear in future-01 No and Necessary foundation with bolts to be grouted in PCC foundation shall deemend to be included in overall quoted rates Note :-Panel shall be front and back openable, double door system lockable/openable by key from both sides and shall have louvers and air vent gasket for natural flow of air 'U' type gasket shall be used to make the panel completely vermin proof. The bottom of the panel shall contain a detachable plate having provision of entry of amroured cable of adequate size with MS glands
Supply, installation, commissioning and testing of LT indoor cubical compartment type feeder pillar box of size 2000 x 1500 x 450 mm, CPRI approved Company made, made out of 2.0 mm thick CR CA sheet, duly painted with 7 tank process powder coating modular construction and with PU gasket having temperture withstand -40 deg to +120 Deg, both side openable, front side with double shutter, with side locking arrangement, mounted on MS stand of suitable size made out of MS Angle iron of size 75x75x6 mm, frame fixed in PCC block 1:3:6 of size 450x450x450mm,legs of MS stand shall be 600 mm above ground level and 300 mm below ground, vermin proofs, making necessary cable connection with cable thimble, glands, including Aluminium TPN bus bar of capacity 300 Amp minimum size 32 x10 mm thick and minimum length not less then 900 mm each duly PVC/epoxy coated, mounted on PVC/epoxy insulator etc complete 1 Set and all MCCB's connection shall be with aluminum bus strip of suitable rating from main bus bar, MCCB's mounting arrangent shall be adjustable type, comprising of following :-
In coming:- 1. RCCB 400 Amp sensitivity 30 KA-01 2. MCCB - 400 Amps, 415V, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 35 KA-01 Nos Front operatd changeover switch 315 Amps - 01 Nos , Out going:- 1. MCCB - 250 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 25 KA-04No. 2. MCCB - 160 Amps, 4 Pole, AC with thermal setting 70% to 100% and breaking capacity 25 KA-06 Nos. 3. Spare place for fixing any switch gear in future-01 No and Necessary foundation with bolts to be grouted in PCC foundation shall deemend to be included in overall quoted rates Note :-Panel shall be front and back openable, double door system lockable/openable by key from both sides and shall have louvers and air vent gasket for natural flow of air 'U' type gasket shall be used to make the panel completely vermin proof. The bottom of the panel shall contain a detachable plate having provision of entry of amroured cable of adequate size with MS glands.
Excavation in trenches in soft/loose soil not exceeding 1.50 meter wide and not exceeding 1.5 meter in depth and not exceeding 10sqmm on plan and getting out complete all as specified.
Returning,filling in including spreding, levelling, watering and well ramming in layers not exceeding 25 cm thick each excavated soil in trenches after the pipes have been laid and tested completed as in soft/loose soil, complete all as specified.
Removing of surplus soil/excavated material to a distance not exceeding 50meter and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified.
Sand cushioning with clean dry sand to cables with layer of sand 8cm before laying of cable and 15cm thick after laying of cable complete all as specified. Note : For payment purpose punned thickness of 18cm shall be measured against spread thickness of 23cm as mentioned in para 19.75 of SSR part-I
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 95 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 25 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. Note for item no 15 to 18 : Exacavation/earthwork, brick protection and sand cushioning will be measured and paid separately.
Earthing complete with galvanized steel earth plate electrode 600x600x6mm surrounded by mixture of charcoal and salt in alternate layers burried directly in ground vertically in a pit of depth not less 2.25mtr below ground level with top edge of earth plate at a depth of not less than 1.50mtrs below ground level connected with and including 32x6mm galvanized iron strip as earthing lead by means of bolts, nuts, check nuts and washers made out of galvanized iron, 20mm dia medium grade GI pipes for watering with funnel, wire mesh and 40mm GI light grade protection pipe for GI strip and including necessary excavation, earth work, PCC 1:3:6 type C-2 concrete pit and RCC pit cover charcoal and common salt filling in alternate layers complete all as specified and directed by Engineer-in-Charge on electrical plate no-3 of SSR Par-I of 2009. Note:(i) If desirable earthing result not found re done earthing without any extra charge until get required earth resistance. (ii) The result sheet of earthing may submit to sub division level by contractor.
Taking down old unsv LT Panel complete all as specified and directed by Engr-in-Charge.
Excavation in trenchs exc. 1.5 mtr in depth but not exceeding 3 mtr in depth and getting out in any type of soil complete all as specified.
Supply and fixing on LT pole danger notice plate for LT of size 20 cm x 15 cm , 1.6mm thick mild steel sheet vitreous enameled white with letters, figure and conventional skull & bones “DANGER” etc. in signal red colour and fixed with MS clamps made out of 25mmx3mm MS flat iron, nut, bolts complete all as specified and directed.
Disconnection and removing the unserviceable broken PCC LT pole and Supply & install steel tublar pole swaged welded with MS base plate size 30cm x 30cm x 6mm thick final taper plug bolts nuts & washers as per IS: 2713 (part-I) 1980 made out of MS tubing including painting of two coats of aluminium paint of approved quality over one coat of red oxide primer length 9.00 mtr long 410 SP -31 using for any description of external electric work all as specified and directed by Engr-in-charge. NOTE : (i) Earth work and PCC work will be measured and paid separately under respective item of the schedule.
M & L PCC (1:4:8) type D-1 (using 40 mm graded stone aggregate) for foundation of the pole complete all as specified and directed.
M & L PCC (1:3:6) type C-1 (using 20 mm graded black trap/granite/basalt stone aggregate) for coping of the pole including necessary form work complete all as specified and directed.
Material, fabrication and labour for cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections inclidng nuts, bolts, washers , welding, bending cold or hot, driling holes for bolts, in and shape or size as indicated or directed and inclusive of one primer coat and two under coat of synthetic enamel paint and incl removing rusted cross arm complete all as specified.
M&L for stay assembly for LT poles comprising of 20mm dia, 2.15 mtr long galvanized stay rod , having 7 / 2.25 mm GI stay wire stranded and 300mm X 500mm X 6mm thick MS stay plate, complete all as shown on electrical plate No 1 of SSR, Part-I with and including all necessary fittings/accessories like loop type insulator overall dimensions 90mmx140mm, clearance of hole 25.5mm, shackle & stay clamps made out of 50x6mm MS flat iron, necessary excavation and earth work in soft/loose soil and PCC works in (1:3:6) type C-2 (using 40mm graded stone aggregate) including taking out and dismantling old unserviceable stay assembly complete all as specified and directed by Engineer-in-Charge.
S&F street light bracket made out of 32mm dia, 1.50 mtr long (both side fancy type )GI tubing, "medium grade" ISI marked, bent to required shape and angle as per site requirement with and including MS clamps size 30X6mm, with nuts, bolts, washers etc for fixing street light fittings and bracket, duly painted with two coats of aluminium paint over a coat of red oxide primer including taking out existing unserviceable rusted GI bracket complete all as specified and as directed.
Supply & Laying of PVC insulated,armoured heavy duty, electric cable with stranded aluminum conductor of size 2 core 16 sqmm 1100 volts grade, laying in trenches, passing through pipes, fixed along walls and/or poles complete all as specified .
All as per item No 29 above but cable of size 25 Sq.mm,4 core
Supply and laying of class B bricks laid along direction of cable for under ground cable protection as directed by Engineer- in - charge
Supply and fix street light sunken box of PVC including MCB 16Amp with clamps, nuts & bolts and making connection complete as directed by Engineer- in - charge
S & F in repair 25 mm bore Tubes ‘light grade’, galvanized , laid in trenches or fixed along poles with mild steel clamps, as protection to cable, complete all as specified .
S & F in repair 50 mm bore Tubes ‘light grade’, galvanized , laid in trenches or fixed along poles with mild steel clamps, as protection to cable, complete all as specified .
LONGIA ENGINEERS
M/s Shiksha Enterprises
M/s Friends Engineering Works
shiv shanker enterprises
M/S SURINDER KUMAR MAHAJAN
Alpha Engineers and Builders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .