Tender Value
₹3.6 Cr
EMD Value
₹1 L
Closing Date
8 Jul 2023, 3:00 pmClosed
Deputy Vice President (Projects)
Projects Division, HLL Bhavan, HLL Lifecare Ltd, Poojappura, 695012
Balance Works for the Supply, Erection, Commissioning and Validation of HVAC System (Low Side) for Manufacturing facility at Kerala State Homeopathic Co-operative Pharmacy Ltd (HOMCO) at Valiyakalavoor, Alappuzha
2023_HLL_580346_2
HLL/CHO/PROJ/EXT/HOMCO/HVAC
Open Tender
Miscellaneous Works
Item Rate
196 days
Valyakalavoor
Please refer Tender documents.
10 documents required · 10 mandatory
₹8,850
Yes
₹1 L
Yes
27 Oct 2023
22 Jun 2023
10 Jul 2023
22 Jun 2023
8 Jul 2023
22 Jun 2023
Amount
ITC of AHU Units
od8960/2023_2024 : Mechanical completion and commissioning of AIR HANDLING UNITS. AHU - 03 : 3000 CFM @ 100 MM WC static pressure (OINTMENT MFG.) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od8961/2023_2024 : Mechanical completion and commissioning of AIR HANDLING UNITS. AHU - 02 : 2000 CFM @ 125 MM WC static pressure (SAMPLING) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od8962/2023_2024 : Mechanical completion and commissioning of AIR HANDLING UNITS. <br>AHU - 01 : 2500 CFM @ 125 MM WC static pressure (DISPENSING) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system.
od9103/2023_2024 : Mechanical completion and commissioning of AIR HANDLING UNITS. AHU - 05 : 2500 CFM @ 75 MM WC static pressure (PACKING) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system.
od9070/2023_2024 : Mechanical completion and commissioning of AIR HANDLING UNITS AHU - 04 : 1500 CFM @ 100 MM WC static pressure (FILL SEAL) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9142/2023_2024 : Mechanical completion and commissioning of AIR HANDLING UNITS AHU -09 : 7000 CFM @ 75 MM WC static pressure (FG STORE) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, cooling coils, dampers, blowers, electrical panel for control, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9143/2023_2024 : Mechanical completion and commissioning of AIR HANDLING UNITS. AHU - 08 : 8500 CFM @ 75 MM WC static pressure (PMS) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9144/2023_2024 : Mechanical completion and commissioning of AIR HANDLING UNITS. AHU - 07 : 5000 CFM @ 75 MM WC static pressure (DISPENSED MATERIAL STORE) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, cooling coils, dampers,blowers, electrical panel for control, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9609/2023_2024 : AHU -16 : 3500 CFM @ 125 MM WC static pressure (AL) To shift the AHU to first floor sterility lab area mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system <br>
od9606/2023_2024 : AHU -15 : 1500 CFM @ 125 MM WC static pressure (AL) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system <br>
od9607/2023_2024 : AHU -14 : 1000 CFM @ 125 MM WC static pressure (ASSAY TEST) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9608/2023_2024 : Mechanical completion and commissioning of AIR HANDLING UNITS AHU -13 : 1000 CFM @ 125 MM WC static pressure (LIMIT TEST) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9659/2023_2024 : AHU - 20 : 1500 CFM @ 75 MM WC static pressure (1.5 M WIDE PASSAGE(P8)) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9660/2023_2024 : AHU - 19 : 4000 CFM @ 75 MM WC static pressure (PACKING) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9661/2023_2024 : AHU - 18 : 2500 CFM @100 MM WC static pressure (CONTACT PARTS PREPERATION) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9662/2023_2024 : AHU -17 : 2500 CFM @ 125 MM WC static pressure (COMPOUNDING) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9663/2023_2024 : AHU - 25 : 3000 CFM @ 100 MM WC static pressure (BLENDER) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9664/2023_2024 : AHU - 24 : 4500 CFM @ 100 MM WC static pressure (GRANULATION) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9665/2023_2024 : AHU - 22 : 3000 CFM @ 75 MM WC static pressure (PACKING MATERIAL STORE) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9666/2023_2024 : AHU - 21 : 2500 CFM @ 75 MM WC static pressure (1.5 M WIDE PASSAGE(P10)) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9667/2023_2024 : AHU - 35 : 5000 CFM @ 100 MM WC static pressure (MACERATION) (FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9668/2023_2024 : AHU - 34 : 4000 CFM @ 75 MM WC static pressure (QUARANTINE) (FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9669/2023_2024 : AHU - 33 : 6500 CFM @ 100 MM WC static pressure (DILUTION MFG) (FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9670/2023_2024 : AHU - 32 : 3000 CFM @ 100 MM WC static pressure (BACK POTENCY MFG) (FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9671/2023_2024 : AHU - 31 : 2500 CFM @ 75 MM WC static pressure (PACKING HALL) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9672/2023_2024 : AHU - 30 : 1000 CFM @ 100 MM WC static pressure (BULK PACKING) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, cooling coils, dampers,blowers, electrical panel for control, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9673/2023_2024 : AHU - 29 : 2000 CFM @ 100 MM WC static pressure (BLISTER) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9674/2023_2024 : AHU - 28 : 1500 CFM @ 100 MM WC static pressure (INSPECTION QTR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9675/2023_2024 : AHU - 27 : 2500 CFM @ 100 MM WC static pressure (COMP-II) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9676/2023_2024 : AHU - 26 : 2000 CFM @ 100 MM WC static pressure (COMP-1) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9679/2023_2024 : AHU-44 : 1000 CFM @100 MM WC static pressure (Multi mill) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9680/2023_2024 : AHU-43 : 2000 CFM @100 MM WC static pressure (Filling -2) ( FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9681/2023_2024 : AHU-42 : 3000 CFM @100 MM WC static pressure (Filling -1) ( FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9682/2023_2024 : AHU-41 : 1000 CFM @ 100 MM WC static pressure (Filling - Odour liquid) ( FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9683/2023_2024 : AHU - 39 : 5500 CFM @ 75 MM WC static pressure (SECONDARY PACKING HALL) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9684/2023_2024 : AHU - 38 : 2000 CFM @ 75 MM WC static pressure (MOTHER TINCTURE SECONDARY PKG.) (FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9685/2023_2024 : AHU - 37 : 3000 CFM @ 100 MM WC static pressure (FILLING & LABELLING) (FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9686/2023_2024 : AHU - 36 : 3000 CFM @ 100 MM WC static pressure (PERCOLATION) (FLP MOTOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od9688/2023_2024 : Fabrication, Supply, Installation, Testing and commissioning of following Air Handling Units (AHU) with double skin construction fabricated from Al extruded section frame structure with internal coving and in Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI constrution with 43 mm thick Puff insulation panel, with G4 fresh air filter, Prefilter section with G4 filters, cooling coil section with 6 row deep chilled water cooling coil , insulated SS 304 drain Pan,blower section with backward curve DIDW centrifugal fan along with KRUGER /NICOTRA make TEFC squirral case induction motor (IE- 2) with IP 55 protection with base frame, Drive set consisting of taper lock pulleys & V-belts and complete with anti vibration mounts, Double skin rexin flexible connection for fan outlet Inspection window, limit switch, light, Fine Filter section with 3micron filters in supply air discharge section. GI damper for Supply, Return, fresh & exhaust air and bypass damper. Service doors wherever applicable. provision Differential pressure guage across 10,3micron filters.<br>AHU - 23 : 4000 CFM @ 100 MM WC static pressure (TRITURATION)
od9689/2023_2024 : Fabrication, Supply, Installation, Testing and commissioning of following Air Handling Units (AHU) with double skin construction fabricated from Al extruded section frame structure with internal coving and in Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI constrution with 43 mm thick Puff insulation panel, with G4 fresh air filter, Prefilter section with G4 filters, cooling coil section with 6 row deep chilled water cooling coil , insulated SS 304 drain Pan,blower section with backward curve DIDW centrifugal fan along with KRUGER /NICOTRA make TEFC squirral case induction motor (IE- 2) with IP 55 protection with base frame, Drive set consisting of taper lock pulleys & V-belts and complete with anti vibration mounts, Double skin rexin flexible connection for fan outlet Inspection window, limit switch, light, Fine Filter section with 3micron filters in supply air discharge section. GI damper for Supply, Return, fresh & exhaust air and bypass damper. Service doors wherever applicable. provision Differential pressure guage across 10,3micron filters.<br>AHU -16A : 7000 CFM @ 125 MM WC static pressure (ASEPTIC FILLING & CLOSING)
Ventilation Units and Exhaust
od9692/2023_2024 : Supply, Installation, Testing and Commissioning of Single Skin type Exhaust Unit (EAU) made out of 18G GI powder coated consisting of Pre filter section for fixing 10micron filter, Fan section with DIDW forward curved Belt driven centrifugal fan (Kruger/Nicotra) driven by suitable NON Flame proof TEFC squirrel cage induction motor (CG/ABB/Kirloskar) with drive set consisting of Taper lock pulleys and V-Belts and complete with anti vibration mounts, Inlet and outlet connections complete with service doors. <br>EXUT - 03 : 600 CFM @ 40 MM WC static pressure ( Supply + Exhaust ) This exhaust unit has to be supplied and installed as whole
od9693/2023_2024 : Supply, Installation, Testing and Commissioning of Single Skin type Exhaust Unit (EAU) made out of 18G GI powder coated consisting of Pre filter section for fixing 10micron filter, Fan section with DIDW forward curved Belt driven centrifugal fan (Kruger/Nicotra) driven by suitable NON Flame proof TEFC squirrel cage induction motor (CG/ABB/Kirloskar) with drive set consisting of Taper lock pulleys and V-Belts and complete with anti vibration mounts, Inlet and outlet connections complete with service doors. EXUT - 02 : 1100 CFM @ 40 MM WC static pressure ( Supply + Exhaust ) This exhaust unit has to be supplied and installed as whole.
od9695/2023_2024 : Supply, Installation, Testing, Commissioning and Validation of Air Handling units with double skin construction fabricated from Al extruded section frame structure with internal coving and in non Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI constrution with 25 mm thick puff insulation panel,consisting of Pre filter section for fixing 10micron filter, Fan section with DIDW farward curved Belt driven centrifugal fan (Kruger/Nicotra) driven by suitable NON Flame proof TEFC squirrel cage induction motor (CG/ABB/Kirloskar) with drive set consisting of Taper lock pulleys and V-Belts and complete with anti vibration mounts, Inspection window, limit switch, bulk head lamp, fine filter section suitable for fixing 5 micron filters, Fresh air Louver at inlet, Inlet and outlet connections complete with service doors. VENT - 02(SUPPLY+RETURN): 5000 CFM @ 60 MM WC static pressure(CHANGE ROOM) Supply and Installation of the whole VU at site. This VU is not at site and hence has to be supplied in whole
od9696/2023_2024 : Supply, Installation, Testing, Commissioning and Validation of Air Handling units with double skin construction fabricated from Al extruded section frame structure with internal coving and in non Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI constrution with 25 mm thick puff insulation panel,consisting of Pre filter section for fixing 10micron filter, Fan section with DIDW farward curved Belt driven centrifugal fan (Kruger/Nicotra) driven by suitable NON Flame proof TEFC squirrel cage induction motor (CG/ABB/Kirloskar) with drive set consisting of Taper lock pulleys and V-Belts and complete with anti vibration mounts, Inspection window, limit switch, bulk head lamp, fine filter section suitable for fixing 5 micron filters, Fresh air Louver at inlet, Inlet and outlet connections complete with service doors. <br>VENT - 01 (SUPPLY+RETURN): 5500 CFM @ 60 MM WC static pressure (HERBS PROCESSING) Supply and Installation of the whole VU at site. This VU is not at site and hence has to be supplied in whole
od9711/2023_2024 : Supply, Installation, Testing and Commissioning of Double skin precooling Unit with 43 mm thick pannel thermal break profile with 0.6mm precoated sheet outerside and 0.6mm thick plane sheet inside,compleat with 8 rowdeep cooling coil ,with G-4 filter at inlet and volume control damper at the out let . <br>AHU - 1,2,3,4,11,13,14,16,17,24,25,26,27,29,33,37,41,42,43 : 500 CFM
Ducting and Insulation
od9712/2023_2024 : Ducting works at varying stages to be completed as required. General terms are Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. (Approximate Quantity ) (Smoke Test/Leak Test) 20 G GI Sheet Erection, supporting, leveling, jointing, existing, available duct at site which is not erected
od9713/2023_2024 : Ducting works at varying stages to be completed as required. General terms are Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. (Approximate Quantity ) (Smoke Test/Leak Test)<br>20 G GI Sheet Leak Testing, Leak rectification and balancing of existing, installed Duct
od9714/2023_2024 : Ducting works at varying stages to be completed as required. General terms are Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. (Approximate Quantity ) (Smoke Test/Leak Test)<br>22 G GI Sheet<br>Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. As per existing drawings
od9715/2023_2024 : Ducting works at varying stages to be completed as required. General terms are Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. (Approximate Quantity ) (Smoke Test/Leak Test)<br>22 G GI Sheet<br>Erection, supporting, leveling, jointing, existing, available duct at site which is not erected
od9716/2023_2024 : Ducting works at varying stages to be completed as required. General terms are Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. (Approximate Quantity ) (Smoke Test/Leak Test)<br>22 G GI Sheet<br>Leak Testing, Leak rectification and balancing of existing, installed Duct
od9717/2023_2024 : Ducting works at varying stages to be completed as required. General terms are Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. (Approximate Quantity ) (Smoke Test/Leak Test)<br>24 G GI Sheet<br>Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. As per existing drawings
od9718/2023_2024 : Ducting works at varying stages to be completed as required. General terms are Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. (Approximate Quantity ) (Smoke Test/Leak Test)<br>24 G GI Sheet<br>Erection, supporting, leveling, jointing of existing available duct at site which is not erected
od9719/2023_2024 : Ducting works at varying stages to be completed as required. General terms are Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. (Approximate Quantity ) (Smoke Test/Leak Test)<br> 24 G GI Sheet<br>Leak Testing, Leak rectification and balancing of existing, installed Duct
od43927/2023_2024 : Ducting works at varying stages to be completed as required. General terms are Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. (Approximate Quantity ) (Smoke Test/Leak Test)<br>20 G GI Sheet<br>Supply, Installation, Testing and Commissioning of Factory fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct es,supports,suspended rods with complete paint with Silicon sealent for duct joints. As per existing drawings
od9722/2023_2024 : Duct insulation chemically Cross linked close cell Polyethyelve CLASS 1 insulation with metalic foil with tape and addicive. ( Approximate Quantity )<br>13 mm thick for return air duct
od9723/2023_2024 : Duct insulation chemically Cross linked close cell Polyethyelve CLASS 1 insulation with metalic foil with tape and addicive. ( Approximate Quantity )<br>19 mm thick for supply air duct <br>
HEPA Filters, Grills and Dampers
od9724/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA:-<br>SS 304 Perforated grill for the following HEPA Filters sizes<br>305 x 305 x 150 mm
od9725/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA:-<br>SS 304 Perforated grill for the following HEPA Filters sizes<br>610 x 305 x 150 mm
od9726/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA:-<br>SS 304 Perforated grill for the following HEPA Filters sizes<br>610 x 610 x 150 mm
od9727/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA:-<br>Gel Seal type latest and advanced technology HEPA filters having effeciency of 99.99 down to 0.3 micron.<br>305 x 305 x 150 mm
od9728/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA:-<br>Gel Seal type latest and advanced technology HEPA filters having effeciency of 99.99 down to 0.3 micron.<br>610 x 305 x 150 mm
od9729/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA:-<br>Gel Seal type latest and advanced technology HEPA filters having effeciency of 99.99 down to 0.3 micron.<br>610 x 610 x 150 mm
od9730/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA :-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Type -1 :- Side connection <br>305 x 305 x 150 mm
od9731/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA :-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Type -1 :- Side connection <br>610 x 305 x 150 mm
od9732/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA :-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Type -1 :- Side connection <br>610 x 610 x 150 mm
od9733/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA :-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Type -1 :- Top connection <br>305 x 305 x 150 mm
od9734/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA :-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Type -1 :- Top connection <br>610 x 305 x 150 mm
od9735/2023_2024 : TERMINAL HEPA MODULE (ISO -7) AREA :-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes<br>Type -1 :- Top connection <br>610 x 610 x 150 mm
od9737/2023_2024 : TERMINAL HEPA MODULE (ISO -6) AREA :-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>305 x 305 x 150 mm
od9738/2023_2024 : TERMINAL HEPA MODULE (ISO -6) AREA :-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>610 x 305 x 150 mm
od9739/2023_2024 : TERMINAL HEPA MODULE (ISO -6) AREA :-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>610 x 610 x 150 mm
od9740/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>SS 304 Perforated grill for the following HEPA Filters sizes<br>305 x 305 x 150 mm
od9741/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>SS 304 Perforated grill for the following HEPA Filters sizes<br>610 x 305 x 150 mm
od28278/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA\:-<br> SS 304 Perforated grill for the following HEPA Filters sizes<br>610 x 610 x 150 mm
od9743/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>Gel Seal type latest and advanced technology HEPA filters having effeciency of 99.97 down to 0.3 micron.<br>610 x 305 x 150 mm
od9744/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Side connection <br>305 x 305 x 150 mm
od9745/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Top connection<br>305 x 305 x 150 mm
od9746/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>Gel Seal type latest and advanced technology HEPA filters having effeciency of 99.97 down to 0.3 micron.<br>305 x 305 x 150 mm
od9747/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>Gel Seal type latest and advanced technology HEPA filters having effeciency of 99.97 down to 0.3 micron.<br>610 x 610 x 150 mm
od9748/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Type -1 :- Side connection <br>610 x 305 x 150 mm
od9749/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Type -1 :- Side connection<br>610 x 610 x 150 mm
od9750/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Type -1 :- Top connection <br>610 x 305 x 150 mm
od9751/2023_2024 : TERMINAL HEPA MODULE (ISO -8) AREA:-<br>False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes.<br>Type -1 :- Top connection <br>610 x 610 x 150 mm
od9758/2023_2024 : RISERS GRILL<br>GI powder coated coller damper to be fixed inside the partition raiser
od9759/2023_2024 : RISERS GRILL<br>SS 304 perforated grill suitable to fix in the panel riser<br>
od9760/2023_2024 : RISERS GRILL<br>Grill module made out of 18G GI with powder coated finish suitable to fix collar damper and grill.
od9761/2023_2024 : SUPPLY & RETURN AIR GRILL / DIFFUSER ( 3 MICRON & VENTILATION AREAS) <br>AL linear bar grill with VCD suitable to fix in Grill modules
od9762/2023_2024 : RETURN AIR PERFORATED GRILL (FOR ISO 8 AREA WITH 10 MICRON FILTER) <br>Slab / false ceiling Grill module made out of 18G GI with powder coated finish with 10 micron filter suitable to fix collar damper and AL perforated grill. <br>
od9763/2023_2024 : RETURN AIR PERFORATED GRILL (FOR ISO 8 AREA WITH 10 MICRON FILTER) <br>AL linear bar grill with VCD suitable to fix in Grill modules
od9764/2023_2024 : SUPPLY & RETURN AIR GRILL / DIFFUSER ( 3 MICRON & VENTILATION AREAS) <br>Slab / false ceiling Grill module made out of 18G GI with powder coated finish suitable to fix collar damper and AL perforated grill.
od9765/2023_2024 : TERMINAL HEPA MODULE (ISO -6) AREA\:-<br> SS 304 Perforated grill for the following HEPA Filters sizes<br>305 x 305 x 150 mm
od9766/2023_2024 : TERMINAL HEPA MODULE (ISO -6) AREA\:-<br> SS 304 Perforated grill for the following HEPA Filters sizes<br>610 x 610 x 150 mm
od9768/2023_2024 : TERMINAL HEPA MODULE (ISO -6) AREA:-<br>Gel Seal type latest and advanced technology HEPA filters having effeciency of 99.99 down to 0.3 micron.<br>305 x 305 x 150 mm
od9769/2023_2024 : TERMINAL HEPA MODULE (ISO -6) AREA:-<br>Gel Seal type latest and advanced technology HEPA filters having effeciency of 99.99 down to 0.3 micron.<br>610 x 305 x 150 mm <br>
od9770/2023_2024 : TERMINAL HEPA MODULE (ISO -6) AREA:-<br>Gel Seal type latest and advanced technology HEPA filters having effeciency of 99.99 down to 0.3 micron.<br>610 x 610 x 150 mm <br>
od14633/2023_2024 : DAMPERS<br>Automatic Fire Dampers, capable of opeating automatically on receiving signal from a fire alarm panel (equivalent to the surface area of the no of units), with induvidual control panels with 240V supply, including electrical actuators.
od14634/2023_2024 : DAMPERS<br>18 G GI fire dampers with Fusible Link type for fire rating of 90 minutes.
od14635/2023_2024 : DAMPERS<br>AL low leakage volume control damper suitable for supply and return ducts
od14636/2023_2024 : RISERS GRILL<br>EU-4 filter washable filter for return air raiser (10 micron)
od44795/2023_2024 : TERMINAL HEPA MODULE (ISO -6) AREA:-<br>SS 304 Perforated grill for the following HEPA Filters sizes<br>610 x 305 x 150 mm
Pressure Gauges
od14637/2023_2024 : Differential Pressure Gauges<br>Differential Pressure gauges for AHUs and ventilation across the pre / fine / semi HEPA filter ( Range 0-100mm wc )
od14638/2023_2024 : Differential Pressure Gauges<br>Differentical pressure gauges for rooms with 18G GI powder coated box with 18G SS 304 flush cover, nozzles and tubing. ( Range - 0-10mm wc )
MS Supports
od14642/2023_2024 : STEEL STRUCTURE<br>MS structural angle/ flat for duct works, for duct flanges at site / factory fabricated.
od14643/2023_2024 : STEEL STRUCTURE<br>I-BEAM/C-CHANNEL/ANGLES for ducting , false ceiling supports in void area SERVICE FLOOR(APPROX)
od14644/2023_2024 : STEEL STRUCTURE<br>MS Supports for AHU s and Condensing units ,with chequrred plate and ISMB beems(APPROX.)
od17474/2023_2024 : PVC drain piping with 9 mm nitrial rubber insulation for AHU'S drain<br>40 MM
od17475/2023_2024 : PVC drain piping with 9 mm nitrial rubber insulation for AHU'S drain<br>25 MM
Validation and Documentation
od14656/2023_2024 : Environmental condition validation. Viable particle count and testing has to be carried for a minimum of 21 days for sterile area and 7 days for non sterile area while the validation is done for the first time. Various viable particle testing for sterile and non sterile area has to be carried out including sterility establishment at least for the validation phase by hiring a suitable firm by the contractor.<br>Cleaning, decontamination, fumigation and ensuring sterlity at designated areas of the sterile areas and needed compliance of bioburden level at non sterile areas, by VHP fumigation method, or suitable method complying the sterile/non- sterile area standards
od14657/2023_2024 : Environmental condition validation. Viable particle count and testing has to be carried for a minimum of 21 days for sterile area and 7 days for non sterile area while the validation is done for the first time. Various viable particle testing for sterile and non sterile area has to be carried out including sterility establishment at least for the validation phase by hiring a suitable firm by the contractor.<br>Sterility testing of designated locations in sterile area using swab method, using SCDA/SDA plates in sterile petridishes with sterile SCDA (with tween 80 or polysorbate). Sterile swabs to be usedfor the sampling.The sampling should be done in the sterile area, by adhering to sterile environmental standards and entry-exit procedure. The transfer of samples and petridishes has to be done by using a mobile LAF, kept at Grade A conditions.
od14658/2023_2024 : Environmental condition validation. Viable particle count and testing has to be carried for a minimum of 21 days for sterile area and 7 days for non sterile area while the validation is done for the first time. Various viable particle testing for sterile and non sterile area has to be carried out including sterility establishment at least for the validation phase by hiring a suitable firm by the contractor.<br>Viable count testing of CNC areas, with settle plate method, using SCDA, plates in sterile petridishes of 90mm diameter with sterile SCDA (with tween 80 or polysorbate). The sampling should be done in the CNC area, by adhering to sterile environmental standards and entry-exit procedure.
od14659/2023_2024 : Environmental condition validation. Viable particle count and testing has to be carried for a minimum of 21 days for sterile area and 7 days for non sterile area while the validation is done for the first time. Various viable particle testing for sterile and non sterile area has to be carried out including sterility establishment at least for the validation phase by hiring a suitable firm by the contractor.<br>Viable count testing of non- sterile area, with settle plate method, using SCDA, plates in sterile petridishes of 90mm diameter with sterile SCDA (with tween 80 or polysorbate). The sampling should be done in the non-sterile area, by adhering to sterile environmental standards and entry-exit procedure. <br>
od14660/2023_2024 : VALIDATION & DOCUMENTATION<br>DQ/OQ documents, Maintenance manual,Test certificate for equipment ( IQ format shall be provided by us but filling will be done later).<br>1) Hydraulic Test of MS Pipe <br>2) Smoke Test/Leak Test<br>3) Air balancing and Velocity Profile Test<br>4) Pressure Balancing Test<br>5) Temperature & RH test<br>6) Filter Integrity Test <br>7) Air Flow Pattern<br>8) Particle Count Test
od14661/2023_2024 : Environmental condition validation. Viable particle count and testing has to be carried for a minimum of 21 days for sterile area and 7 days for non sterile area while the validation is done for the first time. Various viable particle testing for sterile and non sterile area has to be carried out including sterility establishment at least for the validation phase by hiring a suitable firm by the contractor.<br>Viable count testing of sterile area, with settle plate method, using SCDA, plates in sterile petridishes of 90mm diameter with sterile SCDA (with tween 80 or polysorbate). The sampling should be done in the sterile area, by adhering to sterile environmental standards and entry-exit procedure. The transfer of samples and petridishes has to be done by using a mobile LAF, kept at Grade A conditions.
$Electrical Works
od14672/2023_2024 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.<br>4C X 2.5 SQMM CU
od14673/2023_2024 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.<br>4C X 1.5 SQMM CU
od14674/2023_2024 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.<br>3C X 2.5 SQMM CU
od14675/2023_2024 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.<br>3C X 1.5 SQMM CU<br>
od14676/2023_2024 : Electrical Starter Panels<br>AHU/ VENTILATION UNIT/ EXHAUST UNIT - Panel with bypass STAR/DELTA STARTER with Overload,Single phasing, Under voltage and overvoltage, phase reverse protection with necessary internal wiring. Starter should be compatible with necessary inputs and outputs provisions, power and control wiring should be carried out as per IS standards suitable for current ranging Ampere. set of ON & OFF indication lights & START- STOP push buttons (Floor Mounted Panel)
od14677/2023_2024 : Electrical Starter Panels<br>AHU (Having VFD) - <br>'VFD provision' with bypass STAR/DELTA STARTER with Overload,Single phasing, Under voltage and overvoltage, phase reverse protection with necessary internal wiring. Starter should be compatible for BMS also with necessary inputs and outputs provisions, power and control wiring should be carried out as per IS standards suitable for current ranging Ampere set of ON & OFF indication lights & START- STOP push buttons.(Floor Mounted Panel)
90.12.7.14 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 3 core 10 sqmm with factory made clamp
90.12.7.39 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 6 sqmm with factory made clamp
90.12.7.40 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 10 sqmm with factory made clamp
90.12.7.41 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 16 sqmm with factory made clamp
90.12.7.29 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 3.5 core 50 sqmm with factory made clamp
90.12.7.36 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 3.5 core 300 sqmm with factory made clamp
90.12.7.42 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 25 sqmm with factory made clamp
90.12.41.31 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 4 sqmm with factory made clamp
90.6.5.4 : Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 2 core 1.50 sqmm with factory made clamp
90.6.5.18 : Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 4 core 1.50 sqmm with factory made clamp
90.6.5.19 : Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. 4 core 2.50 sqmm with factory made clamp
4.6.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100 mm width X 50 mm depth X 1.6 mm thickness Details of cost for 30 metres
4.6.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150 mm width X 50 mm depth X 1.6 mm thickness
4.6.3 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.225 mm width X 50 mm depth X 1.6 mm thickness
4.6.4 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.300 mm width X 50 mm depth X 1.6 mm thickness
4.6.6 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.450 mm width X 50 mm depth X 2.0 mm thickness
9.1.7 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 10 sq. mm (22mm)
9.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.30 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.34 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
od17194/2023_2024 : DOUBLE COMPRESSION GLANDS<br>32 MM
od17195/2023_2024 : DOUBLE COMPRESSION GLANDS<br>25 MM
od17196/2023_2024 : DOUBLE COMPRESSION GLANDS<br>50 MM
od17197/2023_2024 : DOUBLE COMPRESSION GLANDS<br>20 MM
od17080/2023_2024 : Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. <br>END TERMINALS Copper <br>4C X 4 SQMM CU<br>
od17081/2023_2024 : Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. <br>END TERMINALS Copper<br> 4C X 2.5 SQMM CU<br><br>
od17082/2023_2024 : Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.<br>END TERMINALS Copper<br>4C X 1.5 SQMM CU
od17083/2023_2024 : Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.<br>END TERMINALS Copper<br>3C X 2.5 SQMM CU<br>
od17084/2023_2024 : Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.<br>END TERMINALS Copper<br>3C X 1.5 SQMM CU<br><br>
od29508/2023_2024 : END TERMINALS Aluminium<br>4C X 6 SQMM AL<br>
od17116/2023_2024 : CABLE TRAYS - Factory fabricated GI perforated type cable tray made out of 14swg sheet steel. supporting angle frame at every 1.2 m, bottom angles, anchor fasteners, bolts and nuts etc. The tray shall be suspended from ceiling using anchor bolt and angle iron supports or threaded rods. The rate shall include all accessories like bends, elbows, tees, coupler plates, joints and fixing accessories etc., which will be measured as linear measurement.<br>50mm wide perforated type cable tray
od17117/2023_2024 : CABLE TRAYS - Factory fabricated GI perforated type cable tray made out of 14swg sheet steel. supporting angle frame at every 1.2 m, bottom angles, anchor fasteners, bolts and nuts etc. The tray shall be suspended from ceiling using anchor bolt and angle iron supports or threaded rods. The rate shall include all accessories like bends, elbows, tees, coupler plates, joints and fixing accessories etc., which will be measured as linear measurement.<br>150mm wide perforated type cable tray
od17118/2023_2024 : CABLE & CONDUIT - The following cables including end termination for below listed XLPE insulated armoured cable with copper lugs, brass/PVC cable glands, tapping, crimping,ferruling etc. complete, to be included.<br>6 Core 1.0 SQ. MM, Armoured ATC conductor multistranded, Shielded cable. (For RH sensor & valve control)
od17119/2023_2024 : CABLE & CONDUIT - The following cables including end termination for below listed XLPE insulated armoured cable with copper lugs, brass/PVC cable glands, tapping, crimping,ferruling etc. complete, to be included.<br>4 Core 1.0 SQ. MM, Armoured ATC conductor multistranded, Shielded cable. (For RH sensor & valve control)
od17120/2023_2024 : CABLE & CONDUIT - The following cables including end termination for below listed XLPE insulated armoured cable with copper lugs, brass/PVC cable glands, tapping, crimping,ferruling etc. complete, to be included. <br>2 Core 1.0 SQ. MM, Armoured ATC conductor multistranded, Shielded cable.
od29985/2023_2024 : Supply and Installation of Junction boxes
od17176/2023_2024 : EARTHING<br>Earthing with Cast Iron C.I. earth plate (1200 mm X 1200 mm X 12 mm) thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required
od17244/2023_2024 : Supplying and laying 32 mm X 6 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)<br>
od17245/2023_2024 : Providing and fixing 32 mm X 6 mm G.I. strip on surface or in recess for connections etc. as required
5.19 : Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
90.16.1.2 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required (12 SWG)
90.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required (10 SWG)
90.16.1.4 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required (8 SWG)
Building Management System
od17250/2023_2024 : III-BMS (BUILDING MANAGEMENT SYSTEM):-<br>DDC CONTROLLERS - Standalone DDC Controller: DDC Controller shall be 32 bit microprocessor based standalone and net workable type BACnet BTL tested with real time clock. The controller shall support trend log objects, program areas and PID loop objects. The DDC's shall store programs and program parameters in non volatile memory. The controller shall have provision to communicate to the central BMS software over LAN or RS-485 if required. DDC controller shall be housed in a suitable encloser made out of 14/16 Swg MS CRCA sheet which is derusted, degreased and phosphated sheet folded construction. The panel to be dust, vermin proof type(IP-54) with powder coated paint. The panel shall have suitable mounting arrangement including mounting plate, power supply unit, control transformer, MCB & power socket, relay and necessary mounting arrangement etc.<br>FOR CONTROLLED AREA AHU
od17270/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU-43-(Filling-2) 3.7 kw
od17271/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU-42-(Filling 1) 5.5 kw
od17272/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU-41-(Filling - Odour liquid) 2.2 kw
od17273/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -37 : (FILLING & LABELLING) 2.2 KW
od17274/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -33 : (DILUTION MFG) 5.5 KW<br>
od17275/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -29 : (BLISTER) 2.2 KW
od17276/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -27 : (COMPRESSION-II) 3.7 KW
od17277/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -26 : (COMPRESSION-I) 2.2 KW
od17278/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -25 : (BLENDER) 3.7 KW
od17279/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -24 : (GRANULATION) 5.5 KW
od17280/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -17 : (COMPOUNDING) 3.7 KW
od17281/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -16 : (IASEPTIC FILLING) 5.5 KW
od17282/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -14 : (ASSAY TEST) 2.2 KW
od17283/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -13 : (LIMIT TEST) 2.2 KW
od17284/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -11 : (STERILITY) 3.7 KW
od17285/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -04 : (FILL/SEAL) 2.2 KW
od17286/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -03 : (OINTMENT MFG.) 3.7 KW
od17287/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -02 : (SAMPLING) 3.7 KW
od17288/2023_2024 : VARIABLE FREQUENCY DRIVES (VFD) Supply, Installation, Testing and Commissioning of VFD of suitable rating including accessoreies for the following AHUs<br>AHU -01 : (DISPENSING) 3.7 KW
Central Monitoring Station
od17314/2023_2024 : Service Charges<br>Site Calibration certificate of all above sensors.
od17315/2023_2024 : Service Charges<br>Services shall include the following,<br># Engineering and Documentation<br># Testing & Commissioning.
od17316/2023_2024 : Central Monitoring Station<br>System interface unit for connecting PC to DDC controllers
od17317/2023_2024 : Central Monitoring Station<br>Central Software: Graphical interface software shall be on open platform and work on MS Windows platform. Supporting minimum 3 user license working in a LAN / WEB environment.
od17318/2023_2024 : Central Monitoring Station<br>A3 B/W laser printers, 10/100MB Ethernet card with 2 Lan ports, etc
od17319/2023_2024 : Central Monitoring Station<br>Central Desktop computer system: Windows 11, INTEL CORE i5 12th generation or greater, 3GHz, 8GB RAM, 500GB SSD, 23" LED monitor, Mouse, keyboard, Antivirus software
od17322/2023_2024 : Louvers<br>Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction. Static air inlet air louvers with bird screen, with rain and wind protection. Installation includes the demolishing existing walls, attaching the louvers and finishing of the wall.
od17323/2023_2024 : Temperature, humidity and pressure display with remote Temp, RH & Pressure sensors
od17324/2023_2024 : Smoke sensors
od17325/2023_2024 : Differential Pressure switch (0-500Pa), across the filter including all the Fixing accessories.
od17326/2023_2024 : Duct Type Temperature & Rh combo Sensors with all duct mounting accessories.<br>Range: 0% to 95%<br>Rh Sensing element: capacitive sensor<br>Temp sensing element: PT1000<br>Accuracy: For Temp:+/- 0.3°C For Rh:+/- 3%
od17327/2023_2024 : Duct Type Temperature Sensors with all duct mounting accessories.<br>Range: 0 °C to 100 °C<br>Sensing element: PT1000<br>Accuracy: +/- 0.3°C
od17476/2023_2024 : AHU - 12 : 2000 CFM @ 100 MM WC static pressure (INCUBATOR) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, cooling coils, dampers,blowers, electrical panel for control, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od17477/2023_2024 : AHU -11 : 2000 CFM @ 125 MM WC static pressure (STERILITY) To shift the AHU to second floor to bottle drying area, mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, cooling coils, dampers,blowers, electrical panel for control, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od17478/2023_2024 : AHU -10 : 1500 CFM @ 125 MM WC static pressure (MEDIA PREPERATION) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
od17479/2023_2024 : AHU - 06 : 6000 CFM @ 75 MM WC static pressure (RM UNDER STORE) To mechanically complete the AHU by fixing the AHUs at position with base support, connect the inlet and outlet ducts, connect to Fresh air unit, mount the motor and blower, electrically terminate, with supply of belts, pulleys, cooling coils, dampers,blowers, electrical panel for control, sealants and acoustic layering/lining. Commissioning of the mechanically completed AHU and balance the system
ASHRAE CLEAN ROOM PRESENTATIONS PVT.LTD
Bidder Name
ASHRAE CLEAN ROOM PRESENTATIONS PVT.LTD
SHES Air & Automation Pune
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .