Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.0 LAccepted-AOC SHOP NO 10 ASHRAM MANDIR NAKATIA P O P A C SHAHJAHANPUR ROAD BAREILLY 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | L1 | Accepted-AOC Acceptance of tender | |
| 2 | L2₹17.2 L+₹64,110 (3.87%)Rejected-Finance | L2 | Rejected-Finance Being Higher Bid | |
| 3 | L3₹18.9 L+₹2.4 L (14.2%)Rejected-Finance VILL KASHNI NEAR AANCHAL DAIRY PO BIN PITHORAGARH UTTARAKHAND PIN 262508 | PITHORAGARH | PITHORAGARH | UTTARAKHAND | 262508 | L3 | Rejected-Finance Being Higher Bid | |
| 4 | L4₹20.8 L+₹4.3 L (25.9%)Rejected-Finance 38 BHARKATIYA JOSHI NEAR POST OFFICE JHULAGHAT ROAD PITHORAGARH UTTARAKHAND 262520 | PITHORAGARH | PITHORAGARH | UTTARAKHAND | 262520 | L4 | Rejected-Finance Being Higher Bid |
Tender Value
₹18.8 L
EMD Value
₹37,600
Closing Date
29 Dec 2021, 6:00 pmClosed
GE Pithoragarh
GE Pithoragarh Post Bharkatia Pithoragarh ( UK)PIN-262520
DAY TO DAY MAINTANENCE E/M SERVICES OF BLDGS AND INTERNAL WIRING OF CERTAIN BLDGS AND CONNECTED WORKS AT MIL STN DHARCHULA UNDER GE MES PITHORAGARH
2021_MES_481181_3
8405/DHR/E8
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Dharchula
Please refer Tender documents.
5 documents required · 5 mandatory
₹500
GE Pithoragarh
₹37,600
Yes
19 Jan 2022
10 Dec 2021
31 Dec 2021
10 Dec 2021
29 Dec 2021
17 Dec 2021
10 Dec 2021 - 17 Dec 2021
Amount
DESCRIPTION OF ITEMS
Taking down carefully copper/aluminium point wiring (light ,fan, socket or power ) complete (fittings such as switches, ceiling roses, pendants, regulators, sockets etc and making good disturbed surfaces of walls, floors etc complete all as specified and directed.
M & L for point wiring with 1.5 Sqmm (Nominal cross sectional area) single core PVC insulated with PVC unsheathed multi stranded copper conductor FRLS cable in open/surface PVC casing and caping of suitable size , complete with all accessories /fitting and PVC terminal switch board of suitable size with plastic surface sheet top cover open recessed on all and brass screw and washer including unsheathed single core PVC insulated cable green in colour 1.5 Sqmm multistranded copper conductor as contineous earth wire and connecting to earth dolly for as following:
(a) One light point/Fan point/bell point controlled by one way switch of 5/6 Amps
(b) One 3/5 pin socket outlet point on same board controlled by one way switch of 5 Amps but with cables 1.5 sqmm size
(c) One 3/5 pin socket outlet point on independent board controlled by one way switch of 5 Amps but with cables 2.5 Sqmm size
M & L for point wiring with 2.5 Sqmm (Nominal cross sectional area) single core PVC insulated with PVC unsheathed multi stranded copper conductor cable in PVC casing and caping of suitable size, in open surface type complete with all accessories /fitting and PVC terminal switch board of suitable size with PVC surface sheet top cover open recessed on all and brass screw and washer including unsheathed single core PVC insulated cable green in colour 2.5 Sqmm multistranded copper conductor cable as earth wire and connecting to earth dolly complete all as specified and directed for 3/5 pin , 15/16 Amps power socket controlled by one , one way switch of 15/16 Amps complete all as specified
M & L point wiring with 1.5 Sqmm (Nominal cross sectional area) single core PVC insulated with PVC unsheathed multi stranded copper conductor cable in PVC concealed conduit 20mm or higher dia , complete with all accessories /fitting and sunken terminal boxes, switch board of suitable size with 3 mm thick plastic laminated hard gloosy surface sheet top cover open recessed on all and brass screw and washer including unsheathed single core PVC insulated cable green in colour 1.5 Sqmm multistranded copper conductor as contineous earth wire and connecting to earth dolly including making good disturbed surfaces to same as previous existing complete all as specified and directed
(a) One light point/Fan point/bell point controlled by one way switch of 5/6 Amps
(b) One 3/5 pin socket outlet point on same board controlled by one way switch of 5 Amps but with cables 1.5 sqmm size
(c) One 3/5 pin socket outlet point on independent board controlled by one way switch of 5 Amps but with cables 2.5 Sqmm size
M & L point wiring with 2.5 Sqmm (Nominal cross sectional area) single core PVC insulated with PVC unsheathed multi stranded copper conductor cable in PVC concealed conduit not less than 20mm dia , in concealed type complete with all accessories /fitting and sunken terminal boxes, switch board of suitable size with 3 mm thick plastic laminated hard gloosy surface sheet top cover open recessed on all and brass screw and washer including unsheathed single core PVC insulated cable green in colour 2.5 Sqmm multistranded copper conductor cable as earth wire and connecting to earth dolly including making good disturbed surfaces complete all as specified and directed for 3/5 pin , 15/16 Amps power socket controlled by one , one way switch of 15/16 Amps complete all as specified
S & F switch piano flush button single pole one way 5Amps complete all as specified and directed
S & F switch piano flush button single pole two way 5/6 Amps complete all as specified and directed
S & F bell push flush button single pole one way 5Amps complete all as specified and directed
S & F switch piano flush button single pole one way 15Amps complete all as specified and directed
S & F socket out let 3 pin 5/6 Amps flush type complete all as specified and directed
S & F socket out let two in one 3 pin 5/6 Amps and 3 pin 15/16 Amps, flush type, non shutters, non interlocking complete all as specified and directed.
S & F Ceiling rose , surface bakelite, AC, 60x30mm, 3 terminals complete all as specified and directed.
S & F lamp holder PVC /poly carbonated type with back plate suitable for pendants /angular /batten fittings complete all as specified and directed.
S & F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet complete all as specified and directed
S & F in repair Bell multi music type complete all as specified and directed
S & F in repair sheet metal enclosure for DB SPN 4 way with 200 Amps rating bus bar 240 Volts, double door suitable for housing MCBs and isolators complete all as specified and directed
S & F in repair sheet metal enclosure for DB SPN 8 way with 200 Amps rating bus bar 240 Volts, double door suitable for housing MCBs and isolators complete all as specified and directed
S & F in repair MCB SP 6 to 40 Amps ,240volts 10KA complete all as specified and directed
S & F in repair MCB SPN 40 Amps ,240volts 10KA complete all as specified and directed
M & L for replacement of sub main wiring with 2 runs of 6 Sqmm and one runs of 4 Sqmm Copper cable multistranded drawn through existing surface /recessed steel/PVC conduit providing necessary clamp ,screw, thimble and connected to MCB/DB box /main switches etc all as specified and directed.
Supply & fix in replacement LED tube light 4' long along with all fixtures and fittings ,internally pre wired and including connecting up to ceiling rose with twin core twisted flexible copper conductor cable with suitable size ,18W complete all as specified and directed.
Supply & fix in replacement LED tube light 2' long along with all fixtures and fittings ,internally pre wired and including connecting up to ceiling rose with twin core twisted flexible copper conductor cable with suitable size ,9/10W complete all as specified and directed
S & F in replacement LED retrofit 'T' bulb 12 watts, complete all as reqd site and directed.
S & F in replacement of Electronic choke 28W / 36 watts suitable for fulorescent tube light fitting complete all as specified and directed.
S & F in replacement fluorescent tube light lamp of 28/36watts, 240volts suitable for fulorescent tube light fitting complete all as specified and directed.
M & L for replacement of 1100 Volts grade heavy duty cable PVC insulated aluminium conductor served with an inner sheathing of PVC tape and over all PVC sheathed in service connection suspended by insulating hangers not more than 1 M apart including 4mm dia GI suspension wire one twin core flat or circular stranded conductor of size 10 Sqmm complete all as specified and directed .
M & L for replacement of house service bracket (hook type complete with 3.0 mtr long GI Pipe 40mm dia med grade ,two nos 90 degree bend,clamps , nuts and bolts,washers,MS hooks and stay or guy all as reqd at site and directed.
Supply and Fix in replacement of 1x20 watt LED building security light fitting, with and including GI bracket made out of 1.5 mtr GI pipe bent to shape light grade of 40mm dia, bracket clamps nut bolts etc and making electric connection with 3 core 2.5 sq mm PVC insulated copper conductore cable complete all as specified and directed.
Material and Labour for replacement of earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly in ground (earth pit not less then 2.25 metres deep below ground level) with top edge of the plate not less then 1.5 metres below normal ground level, conneted to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, cheek nuts and washers of galvanised or iron protected by 15 mm bore GI pipe (light grade) and connected to main switch board as directed including concrete pit in PCC (1:3:6) type C1 precast RCC (1:2:4) type B1 cover slab 40x40 Cm x 6Cm reinforced with 8 mm dia deformed bar @ 5 cm c/c with one handle for lifitting made out of 8 mm dia MS bar, funnle, wire mesh, 20 mm bore GI pipe (medium grade) for watering including charcoal and salt in alternative layers necessary excavation and earth work in any type of soil and testing complete all as shown on electrical plate No-3 of SSR part-I, 2009.
Dismantling existing U/S energy meter by disconnecting electrical connections from board and depositing the same in AGE office store yard, S & F two wire tampar proof Electronic energy meter in polycarbonated body with LCD display in class 1.0 as per IS 13779/IEC 61036, IP-54 ,50Hz,240Volts,AC,2.5 - 30 Amps, single phase , 240 V on and including suitable size teakwood board complete all as specified and directed.
Dismantling existing U/S energy meter by disconnecting electrical connections from board and depositing the same in AGE office store yard, S & F 4 - wire tampar proof Electronic energy meter in polycarbonated body with LCD display in class 1.0 as per IS 13779/IEC 61036,IP-54 ,50Hz,240Volts,AC,10 - 60 Amps, three phase , 415 V on and including suitable size teakwood board complete all as reqd at site,specified and directed.
Supply only tape roll insulation (25Mtr long)suitable for 1.1KV grade best quality, good adhesive as sample held with AGE office all as directed
Disconnecting / taking down carefully ceiling fan from existing position, dismantling, overhauling and cleaning throughly, oiling /greasing and rehanging at same or new locations after replacing split pins , check nuts, rubber seal etc and re- assemble duly connected with new PVC three core flexible copper conductor cable of size 23/.0076, complete testing & specified all as directed. Note: Spare parts will be measured and paid separately under respective items as supply only as mentioned below.
M&L for taking out burnt copper winding from Ceiling Fan of 1200 mm size and rewinding with existing /same guage of super enammeled copper winding wire complete and refixing at same or new location all as specified and directed.
Supply only Ball bearing for Ceiling fan after and including taking down old ball bearing complete all as reqd at site , specified and directed.
Supply only Capacitor 2.5 Mfd +- 5% 440 Volt AC 50 Hz after removing old defective condensor complete all as specified and directed.
M & L for painting with one coat of spray paint with white enamelled paint on external surface of ceiling Fan of any size complete after duly prepared the surfaces by rubbing with wire mesh,washing with soap water including filling cavities with filler, one complete including writing of MES Number all as specified and directed
Disconnecting /taking down carefully Exhaust Fan of any size from existing position, dismantling, overhauling and cleaning throughly, oiling /greasing and rehanging after replacing split pins , check nuts, rubber seal bushes etc and re- assemble duly connected with new PVC three core flexible copper conductor cable of size 23/.0076, complete testing & specified all as directed.
M & L for taking out burnt copper winding from exhaust Fan of any size/type and rewinding with existing /same guage of super enammeled copper wire complete all as specified and directed
Supply only Capacitor 4 Mfd +/- 5% 440 Volt AC 50 Hz or suitable one after removing old defective condensor complete in exhaust fan all as specified and directed
M & L for painting with one coat of spray paint with grey/blue enamelled paint on external surface of exhaust Fan of any size complete after duly prepared the surfaces by rubbing with wire mesh,washing with soap water complete including writing of MES Number all as specified and directed
Taking down carefully storage water heater of capacity up to 25/35/50 ltr dismantling inner tank and outer tank , pipe assembly, cleaning throughly with descalling liquid compound , overhauling complete to ensure free and constant flow of water through outlet , welding of inner tank if required at site rethreading of inlet/outlet pipe 15 mm dia , reassembling the same at existing /new location including necessary fasteners to ensure proper safety as reqd at site , testing and commissioning after re-installation at site complete all as specified and directed. Note:Spare parts will be measured and paid separately under respective items as supply only as mentioned below.
Supply only thermostate fitting fitment varying capacity for 25/35/50ltrs capacity geysers
Supply only PVC connection pipe nylon threaded15mm size with brass nuts copping in both end of length 450mm for geysers complete all as specified and directed.
Supply only heating element of 1.5/2.0 KW for geyser (as per sample ISI brand) including taking down old heating element complete all as specified and directed.
Taking down carefully flate-plate solar collector storage solar water heater of capacity up to 100 ltr dismantling inner tank and outer tank , pipe assembly, cleaning throughly with descalling liquid compound , overhauling complete to ensure free and constant flow of water through outlet , welding of inner tank if required at site,laser/ultrasonic welding for bonding fin and raiser tube, repair of copper bracing for bonding of header and raiser making leak proof, repair & repalcement of back and side insulation material, rethreading of inlet/outlet pipe 20 mm dia , reassembling the same at existing location including necessary fasteners to ensure proper safety as reqd at site ,repair/ welding of MS structure for collector stand, testing and commissioning after re-installation at site complete all as specified and directed. Note:Spare parts will be measured and paid separately under respective items as supply only as mentioned below.
(a) Supply only heating element of 3.0 KW for solar water heater (as per sample ISI brand) including taking down old heating element complete all as specified and directed.
(b) Supply only Thermostat for solar water heater 100 Ltr
(c) Supply only flate-plate solar collector transparent cover to prevent heat loss and made with ironpoor solar safety toughened glass, 4 mm thick with low iron, transmissivity upto 92% at near normal incidence glass as same as existing
(d) Supply only Heavy duty nylon threaded flexible PVC/CPVC connection pipe 25 mm dia suitable for both hot & cold watrer supply of solar water heater complete all as specified and directed.
(e) Supply only GI/brass adjustable scew clamp as per sample
(f) Supply only Elbow 15mm
(g) Supply only Tee 15mm
(h) Supply only Socket 15 mm
(j) Supply only Union 15mm
(k) Supply only Reducer Socket 20 mm
(l) Supply only Tank nipple 15 mm
(m) Supply only Nipple 15 mm
(n) Supply only of M-Seal
(o) Supply only Butterfly valve 15mm
(p) Supply only GI pipe medium grade 15 mm, ISI marked all as speficied and directed
(q) Supply only GI pipe medium grade 20 mm, ISI marked all as speficied and directed
M & L for replacement of sub main wiring with 2 runs of 4 Sqmm and one runs of 4 Sqmm Copper cable FRLS multistranded drawn in and including PVC conduit in walls / surface providing necessary clamps ,screws, thimbles and connected to MCB of solar water heater/DB box etc all as reqd at site , specified and directed.
Taking down carefully self container drinking water cooler storage capacity upto 150 Lts dismantling inner tank and outer tank , pipe assembly, cleaning throughly with descalling liquid compound , overhauling complete to ensure free and constant flow of water through outlet , welding of inner tank if required at site rethreading of inlet/outlet pipe 15 mm dia , through checking/ rectification of fault in electrical circuits and refrigeration system, oiling & graesing of blower motor, replacement of compressor/ blower or other necessary parts as required, reassembling the same at existing /new location including necessary fasteners to ensure proper safety as reqd at site , testing and commissioning after re-installation at site complete all as specified and directed. Note:Spare parts will be measured and paid separately under respective items as supply only as mentioned below.
(a) Supply only in replacement of Compressor unit with all connected accessories of existing size/rating for self container drinking water cooler storage capacity upto 150 Ltrs
(b) Supply only starting Capacitor suitable for water cooler capacity upto 150ltrs (As per sample) including taking down old defective running Capacitor complete all as specified and directed
(c) Supply only running Capacitor suitable for water cooler capacity upto 150ltrs (As per sample) including taking down old defective running Capacitor complete all as specified and directed
(d) Supply only Relay assy for water cooler storage type , storage Capacity upto 150 Ltr(As per sample) including taking down old defective running Capacitor complete all as specified and directed
(e) Supply only thermostate unit for storage type water cooler of capacity upto 150ltrs (As per sample) including taking down old defective thermostate unit complete all as specified and directed
(f) Supply only over load protection for water cooler storage type , storage Capacity upto 150 Ltr (As per sample) including taking down old defective assy complete all as specified and directed
M&L for Taking down Fan/blower motor of storage type water cooler Capacity upto 150 Ltr and refixing after rewinding blower motor, fan blade of suitable size, testing after complete all as reqd at site, specified and directed
Cutting suction and discharge gas pipeline and taking out unserviceable compressor unit from refrigerator of 165/175/195 ltrs capacity and S&F new sealed compressor unit of same model or approved model of same capacity complete including commissioning and testing after installation at site complete all as specified and directed
S & F Relay assy and OLP for Refrigerator , storage Capacity 165/285/310 Ltr (As per sample) including taking down old defective one complete all as specified and directed
S & F thermostate unit for Refrigerator suitable for capacity 165/195/285/310 Ltr (As per sample) including taking down old defective thermostate unit complete all as specified and directed
M&L for Charging with suitable Refrigerant Gas R-134a after cutting opening sealed unit (compressor) of water Cooler /Refrigerator of any size/capacity/type including replacement of capliary pipe and moisture driver filter etc including crimping and re soldering to charging line complete all as reqd at site,specified and directed
Disconnecting all electrical and copper pipe connection and taking down carefully AC of any type/ rating (window/split) from existing position , dismantling , servicing, overhauling and cleaning of filters, fans, indoor and outdoor units through washing or air pressure throughly, checking cooling coil, compressor, gas level, oiling and greasing of fan & motor etc and re install at same locations after replacing defective parts duly connected with existing AC supply complete all as reqd at site,specified and directed Note:Spare parts will be measured and paid separately under respective items as supply only as mentioned below.
(a) Supply only in repair starting relay for 1.5 TR capacity AC of any make/Type
(b) Supply only in repair starting capacitor 80-100Mfd for 1.5 TR capacity AC of any make/Type
(c) Supply only in repair running capacitor 36 Mfd for 1.5 TR capacity AC of any make/Type
(d) Supply only in repair thermostate unit including electronic relay eqpt and electronic plate for 1.5 TR capacity AC including taking down old thermostate unit omplete all as reqd at site,specified and directed
M&L for Charging with suitable Refrigerant Gas R-32/R-410A after cutting opening sealed unit (compressor) of AC of any type and capacity upto 1.5 TR including replacement of capliary pipe and moisture driver filter etc including crimping and re soldering to charging line complete all as reqd at site,specified and directed
URBANS CONSTRUCTIONS
M/s J P Traders
SK Traders Sons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .