Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.1 LAccepted-AOC 131 NILMONI BHATTACHARJEE LANE KADAL BERHAMPORE MURSHIDABAD W B PIN 742102 | BERHAMPORE | MURSHIDABAD | WEST BENGAL | 742102 | L1 | Accepted-AOC LOWEST BID | |
| 2 | L2₹22.6 L+₹1.4 L (6.80%)Rejected-Finance | L2 | Rejected-Finance SECOND LOWEST | |
| 3 | L3₹24.3 L+₹3.2 L (15.0%)Rejected-Finance 10 6 NABIN SENAPATI LANE HOWRAH 711 101 | HOWRAH | HOWRAH | WEST BENGAL | 711101 | L3 | Rejected-Finance THIRD LOWEST | |
| 4 | L4₹25.7 L+₹4.6 L (21.8%)Rejected-Finance VILL CHHOTO CHAND GHAR PO BARA CHAND GHAR DIST NADIA PIN 741196 | 741196 | L4 | Rejected-Finance FOURTH LOWEST |
Tender Value
Refer Docs
EMD Value
₹56,000
Closing Date
15 Jan 2021, 5:00 pmClosed
SE PWD CEC
184 C R Das Road Berhampore Murshidabad PIN 742101 TEL NO 03482261581 6292121856 M
Construction of composite Court Building at Domkol, Murshidabad. Supply, Installation, Testing and Commissioning of 200 KVA Silent DG sets
2020_WBPWD_307174_1
WBPWD/CEC/NIT/08/Q/20-21
Open Tender
ELECTRICAL WORKS ORG
Item Rate
60 days
DOMKOL
Please refer Tender documents.
4 documents required · 4 mandatory
₹56,000
Yes
on virtual platform
18 Mar 2021
2 Dec 2020
18 Jan 2021
3 Dec 2020
15 Jan 2021
10 Dec 2020
8 Dec 2020
Amount
Supply , delivery at site on foundation , commissioning of 200KVA, 415V, 50Hz, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-II approved Engine & Acoustic Enclosure having following specifications :- Engine:- Make : KOEL GREEN /Crompton Greaves/ CUMMINS/Volvo/Parkins/Eicher/ Ashok Leyaland Engine Type : 4 Stroke Diesel Engine RPM : 1500 Power : 248 BHP or Higher Duty : PRIME Cooling : Liquid cooled with radiator Cylinder : 6 Aspiration : Turbo Charged Type of Governor : Electronic Fuel Tank Capacity : Minimum capacity 350 Ltrs. Fuel Consumption at 75% rated Load with Radiator or Fan : 35 Ltr./ Hr. or Less Fuel Consumption at 100% rated Load with Radiator or Fan : 46 Ltr./ Hr. or Less Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
Exhaust Silencer : Residential Type Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
Alternator Make : KOEL GREEN /Stamford/ Leroy Somer/ Crompton Greaves Rating : 415 V., 3Ph. 50 Hz., 200 KVA, 1500 rpm Type : Brushless, self excited and self regulated Insulation : Class H Protection : screen-protected drip proof with Min.IP-23 degree of protection RPM : 1500 Voltage Regulation (max) : ±1% Winding connection : Star with Neutral Total Distortion factor : Less than 3% Total Harmonic distortion in output waveform : < 5%
AMF Panel Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 250 KVA DG set having following specification/features.
Generator voltage/AC Mains voltage. Generator Current in all phases Frequency Power Factor Energy Indication for alternator supply Running time indications number of hours of operation and service intervals, service due indications The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
Acoustic Enclosure The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-II norms. Base Frame Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
Terms & Conditions (i) Rate should be quoted inclusive of all applicable taxes and Duty etc. (ii) All materials, equipments & accessories must conform to relevant IS specifications. The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer. (iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to submit in triplicate copy during delivery of the equipment. (iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from competent Authority (As per CPCB-II). (v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer/OEM. (vi) The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier.
INSTALLATION OF DG SET Providing cement concrete foundation for the DG set with 1:2:4 (1 cement : 2 course sand : 4 graded stone aggregate 20 mm nominal size)[M20 grade ] including excavation, providing base concrete with 1:5:10 cement concrete, required centering/ shuttering, finishing the exposed portion etc. as reqd. ( Item will be paid based on measurements for 1:2:4 CC, but excluding the 1 : 5: 10 leveling course of base concrete) as per direction of E-in-Charge and manufacturer recommendation.
Supply & fixing of exhaust gas piping of 125 mm dia MS black class B pipe welded incl. all necessary bend supports and clamps anti vibration mounting insulation of exhaust system with 50 mm thick mineral wool covered with wire mesh and aluminium cladding ( from DG sets to top of the building plus 3mtr or as per CPCB) for 200 KVA DG set as per direction of EIC.
S&F special type MS angle iron bracket support made of 40x40x6 mm. MS angle with flat iron clamp with nuts, bolts & washers etc. for 125 mm. dia
S&F rain protection canopy for 125 mm exhaust pipe
Hire charges for scaffolding by bamboo required rope of square type arrangement for smooth working & carriage of MS black pipe by vertical run & dismantling at the end of work.
S& delivery of 400 ltrs. Capacity heavy gauge MS sheet barrel with MS angle made support stand.
Supply & delivery of best quality oil hand pump with 1" dia PVC flexible pipe (12' ft. approx.)
S &D of HSD for testing & immediate run of DG set incl. carrying charge
S &D of Mobile Oil for testing & immediate run of DG set incl. carrying charge
Supply & laying of 1.1 KV grade 10 core 1.5 sq.mm. PVC copper conductor control cable partly recessed and partly by shaddle on wall to interconnect DG set with AMF panel.
S& laying 120 sq. mm. single core multistrand PVC insulated flexible Cu wire in suitable size of PVC flexible pipe (reinforced) from nutral earth busbar to transformer point as required (for Transformer /Generator neutral earthing) including Socketing both sides by Cu Socket.
Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 65 mm x 8 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 80 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe
Extra treatment of soil by using salt & charcoal for plate electrode as to G.S.
Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc.
Making connection of Power cables between AMF & DG & DG Panel after necessary finishing ends & proper Glanding.
Supply & Delivery of 1.1 KV grade XLPE/PVC insulated. PVC sheathed, steel Armoured Al. conductor Cable of the following size, and conforming to IS: 7098(Part-I):1988/1554(Part-I):1988/ 5831:1984/ 3961(Part-I):1967/ 3975:1970/ 10810:1984 / 3975:1970 /8130:1984/ 3961:1967/ 10418:1982 / 10810:1984 as amended upto date, in respect of component materials and tests, and as per the approved makes list attached herewith. 4 Core 240 Sq.mm [From Main panel to DGAMF Panel]
Laying through Floor/ Pavement/Wall Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish Above 95 sqmm at an average depth of 100 mm in floor/pavement/wall etc.
Laying on Wall / surface with Saddles / clamps. Laying of following cable on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting Cable size 3/3½/4 core 240 sqmm and upto 3/3½/4 core 300 sqmm
Laying through Underground Trech Laying of one No. cable above 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed
Laying through Masonry Trench Laying of one cable above 150 sqmm and upto 300 sqmm through existing covered masonry trench incl. taking out RCcovers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : 4 Core 240 Sq.mm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : 4 Core 240 Sq.mm
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required 80 mm dia
DG Room Electrical Work Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire in 20mm size PVC rigid conduit 'FR' , with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish Ave Run 5 Mtr
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box and mending good the damages to original finish Average run 1.5 mtr
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board complete with 3 nos suitable size copper bar with holes (for Ph,N & E) fixied on bakelite/Hard rubber insulator over the MS welded chairs and bakelite/ perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required
S&D of 240V Single industrial box (thick ness of box should not be less than 22 SWG) type luminaire with CRCA body (Make :- Philips -TMC 501P 1xT-LED22W P3241/ Equivalent product of Crompton/Wipro having similar specification in all respect). incl S&D 1x 18 watts 4 ft LED tube lamp (Make:- Philips, Cat - Mas LED tube 1200 mm 18W865 T8 I 2100 Lumen PC Body/ Equivalent product of Crompton/Wipro having similar specification in all respect)
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with Special type MS clamp whose one side fixed with roof iron structure and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type 125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Supply & delivery of 250 volt. 48" (1200 mm) sweep A.C. Ceiling fan having safety wire , P2 type capacitor incl. down rod, canopy & fan blades etc. complete with all accessories (without regulator) & having Double Ball Bearing & Low Noise. [Make - Crompton HB+ or HS+/Orient Energy star/Usha Striker/Make of Similar specification As per Approved Make List]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.
Supply & Fixing 240 V 9 Watt LED Bulb . (Make - Philips/Crompton/Wipro)
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. 2 + 4 Way Legrand Make
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection 6-32A SP MCB Legrand Make
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. 32 A DP Isolator Legrand Make
Supply & Delivery of 1.1 KV grade XLPE/PVC insulated. PVC sheathed, steel Armoured Al. conductor Cable of the following size, and conforming to IS: 7098(Part-I):1988/1554(Part-I):1988/ 5831:1984/ 3961(Part-I):1967/ 3975:1970/ 10810:1984 / 3975:1970 /8130:1984/ 3961:1967/ 10418:1982 / 10810:1984 as amended upto date, in respect of component materials and tests, and as per the approved makes list attached herewith. 2 Core 10 Sq.mm
Laying through Floor/ Pavement/Wall Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/wall etc.
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : 2 Core 10 Sq.mm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : 2 Core 10 Sq.mm
Distribution wiring by S&L of following 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire in 20mm size PVC rigid conduit 'FR' incl. necy. fittings as required 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
Finishing of the PVC insulated Cu wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. 1.5 sqmm cu wire
2.5 sqmm cu wire
Terms and condition The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
SHANKAR BHATTACHARJEE
SREEKRISHNA ENGINEERING ENTERPRISE
ASIM KRISHNA MODAK
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .