Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹13.9 LAccepted-AOC | L-1 | Accepted-AOC Being the lowest bidder | |
| 2 | L-2₹16.7 L+₹2.8 L (20.1%)Rejected-AOC | L-2 | Rejected-AOC Being other than the lowest bidder | |
| 3 | L-3₹16.7 L+₹2.8 L (20.4%)Rejected-AOC | L-3 | Rejected-AOC Being other than the lowest bidder |
Tender Value
₹19.9 L
EMD Value
₹39,800
Closing Date
29 May 2020, 6:00 pmClosed
Commander Works Engineer, MES, Bareilly
HEADQUARTERS, COMMANDER WORKS ENGINEER, MILITARY ENGINEER SERVICES, STATION ROAD, BAREILLY CANTT, PIN 243001
REPAIR AND REPLACEMENT OF RUNWAY LIGHTS, TAXI TRACK, DISPERSAL LIGHT, APPROACH LIGHT AND CONNECTED WORKS UNDER GE (EAST) BAREILLY
2020_MES_335230_1
8200/B/619/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BAREILLY
As Per NIT
6 documents required · 6 mandatory
₹500
GE East Bareilly
₹39,800
Yes
19 Jun 2020
19 Mar 2020
3 Jun 2020
19 Mar 2020
29 May 2020
4 May 2020
19 Mar 2020 - 11 May 2020
Amount
Periodical maintenance of complete runway lighting system and repair by dismantling of air field/taxi track light fitting , AFL cable & connection of any description and segregatting to servicable and unserviceable parts and make it in serviceable condition by deploying person who have knowledge about Air field light system, Constant current regulator and Beacon light complete all as specified and directed. Note -(i) Replacement of spare parts will be measure and paid separately under respective item of schedule. (ii) T&P and HT insulation tape required for repair will be arrange by the contractor with his own cost. (iii) Day of maintanence/ repairs intimate by the Dept prior to flying twice in a month. (iv) Failed to maintaining Runway light system for flying will be penalty of Rs 2000/- borne per job by the contractor.
Supply only bipin halogen lamp 200 watt 6.6 Amp complete all as specified and directed.
Supply only bipin halogen lamp 45 watt 6.6 Amp complete all as specified and directed.
Supply only BIpin halogen holder for 200/45 watt lamps complete with chord complete all as specified and directed.
Supply only isolating transformer 200W, 6.6 Amp, 50 HZ complete all as specified and directed.
Supply only isolating transformer 45W, 6.6 Amp, 50 HZ complete all as specified and directed.
Supply only Protection Glass cover with washer for 200 watt runway light (Clear white) complete all as specified and directed.
Supply only Protection Glass coverwith washer for 200 watt runway light (Yellow) complete all as specified and directed.
Supply only Protection Glass cover with washer for 45 watt Taxi track light (Blue) complete all as specified and directed.
Servicing, Oiling, greasing and testing of Beacon light complete all as specified and directed.
Supply and fixing 6 Sqmm AFL cable connector (male female) kit complete all as specified and directed.
Taking down old unserviceable Aviation light/ flood light/ post top fitting/ runway fitting of any make/capacity from pole complete all as specified and directed.
S&F LED aviation obstruction light 12 Watt with fitting complete and making electric connections complete all as specified and directed. Note :- Obstruction lights are to be replaced/fixed at Hangers/ATC/OH water tank.
S&F garden/path way LED Bollard light 8 watt in cylindrical shape with opal acrylic diffuser and IP65 protection complete all as specified and directed.
S&F light fitting hanging at roof of hanger with GI Tubing light grade Size 25/20 mm apporox 3.5 mtr long ENDURA HIGHBRITE Energy saving environmental friendly, and robust open type vertical Highbay 150 WATT 6500K LED luminaire with high power COB LED. Lamp type complete all as specified and directed.
S&F rectangular flood light luminaire 120W LED fitting with innovative thermal management with IP66 protection complete all as specified and directed.
S&F decorative LED post top lanterns with diffuser and painted spun aluminium deflector 40/35 watt LED fitting with IP66 protection fixing the fitting on steel pole/brick pillar and making good the disturbed surfaces complete all as specified and directed.
S&F in replacement PVC insulated and PVC round sheathed, copper conductor (flexible) industrial cable, 2.5 Sqmm 2 core, 1100 volts conforming to IS: 694 complete all as specified and directed. Note :- Cable to be replaced/fixed at Hangers/ATC//OH water tank/ Search Tower.
Excavation in trenches exc. 1.5 mtr wide and not exc.1.5 mtr wide for foundation for fixing pole/stay assembly and laying and taking out cables etc in soft/loose soil complete all as specified and directed.
Removing excavated material/soil to a distance not exc 50 mtr and above the starting point complete all as specified and directed.
Retruning filling including spreading, levelling watering and well ramming in layers not exceeding 25 CM in any type of soil complete all as specified and directed.
M&L for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc complete all as specified and directed.
M&L for Brick protection with sub class 'B' bricks old size, laid dry, flat over cable, perpendicular across the cable in trenches complete all as specified and directed.
Laying olny old bricks, laid dry, flat over cable, perpendicular across the cable in trenches complete all as specified and directed.
Dismantling and taking out old unserviceable electric cables and taking out old bricks and stacking complete bricks outside for re-use complete all as specified and directed.
Supply and laying LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoure, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 120 Sqmm 3.5 core complete all as specified and directed.
Supply and laying LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoure, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 Sqmm 3.5 core complete all as specified and directed.
Supply and laying LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoure, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core complete all as specified and directed.
Supply and laying LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoure, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 Sqmm 3.5 core complete all as specified and directed.
S&F in repair HT tropodome PVC insulated sheathed, AFL cable 6.6 Amps 5000 volts, with copper conductor 16sqmm multistranded complete all as specified and directed.
M&L for boring of holes under road /pavement/hard standing or any other situation by mannual means for 80/50mm bore for crossing the cable and making good both the ends complete all as specified and directed. Note :- GI pipe shall be measure and paid separately under respective item.
S&F in repair G I tube 80mm bore light grade galvanised with all fittings and fixed complete for road crossing /on wall/floor and crossing culvert or laid in floor complete all as specified and directed.
M&L in repair for MS cage for protection for Run way light and Taxi light, made out from steel framed bracket, nosing to steps including embeding in concrete and screwing etc. posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire,wire mesh etc, flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc.and similar work conforming to Fe-290 Gde E-165, as per sample complete all as specified and directed.
S&F in repair cable jointing kit for 1100 V grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5/ 4 core XLPE, armoured, Al conductor cable of size 25 to 50 mm indoor/Outdoor type complete all as specified and directed.
S&F in repair cable jointing kit for 1100 V grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5/ 4 core XLPE, armoured, Al conductor cable of size 70 to 150 sqmm Indoor/Outdoor type complete all as specified and directed.
M&L Scraping of old paint from the steel tubular pole with out removing accessories and preparation of old steel surfaces and applying one coat of alternative White and Red strips of 30 cm each upto 1.5 mtr height using synthetic enamel paint including numbering of pole by lettring height 40mm of black paint on 180mm black bordered luminious yellow circle. Repainting the remaining pole and clamps GI bkt etc above 1.5 mtr height by applying one coat of synthetic enamel aluminium paint complete all as specified and directed.
Trimming of tree branches along the LT/HT overhead line up to 3 mtr from OH conductor to tree and clearence the site complete all as specified and directed.
M&L in repair Earthing complete with galvanized steel plate electrode 60cm x 60cm x 6mm thick buried directly in ground earth pit not less than 2.25 meter deep below normal ground level with top edge of the plate not less than 1.5m below normal ground level connected to galvanized earth lead GI strip 32x6mm dia by means of bolts, nuts, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 3 of SSR Part-I connected to continuous earth wire/lead on DG set/ LT panel board. all as specified and testing on completion, including provision of earth wire protected by 15 mm dia GI light grade protection pipe from test point to main board and 40mm GI medium grade watering pipe funnel, PCC earth pit and RCC cover charcoal, salt and GI wire including excavation and earth work etc complete all as specified and directed.
Dismantling and taking down of street light of any cap any size any make from the pole complete all as specified and directed.
S&F of energy saving and environemntal friendly long life versatile pressure die-cast aluminium IP-65 roadway luminaire 60 W LED fitting with high power LEDs light source and electronic driver complete all as specified and directed.
Re-stretching of existing ACSR conductor and earth wire including cradles of any description any size and shape and in new position as in LT/HT over head lines, on existing poles including opening of connections and binding wires, Restringing and tightening of conductors/earth wires in position, removing sag, binding to insulators with new aluminium wires, making and connecting jumpers connections etc including commsiiioning and testing complete all as specified and directed. The quoted rates, shall deemed to be included the following provisions also :- (a) Seting/adjusting etc in position of cradles (b) Adjusting and tightning of stay assembly wherever required (c) Trimming/cutting of all trees barnches upto 03M distance from nearest conductors/earth wire as directed at site. Note: one RM length will be measured for 03 phase and one neutral one street light and one earth wire.
Dismantling earth wire of any type and size complete all as specified and directed.
M&L for 8 SWG GI continuous earth wire of size 3.15 mm or 4.00 dia for cradles, gurading and earth continuity on LT OH pole including suitable, binding wires etc compelte all as specifeid and directed
Dismantling of ACSR conductors of any type and size complete all as specified and directed.
M&L aluminium conductor steel reinforcd (ACSR) of any size over head conductor on poles including stringing, tightening binding to insulators with aluminium wire making and connecting commissioning and testing complete all as specified and directed.
S&F in repair shackle type insulator, porcelain, white brown, or green insulator of size 100x115mm (Height 100 mm and 115 mm dia) with section strip 31/5 mm and 14 mm bolt complete all as specified and directed.
S&F in repair 1100 volts grade heavy duty cable PVC insulated aluminum conductor screenedserved with inner sheathing of PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4mm GI suspension wire , one twin core cables flat or circular of size 10 Sqmm complete all as specified and directed.
S&F in repair switch fuse unit rewireable with side handle 100 Amp TPN 415 Volt, complete all as specified and directed.
S&F in repair Off load change over switch 200 Amp 4pole 415 Volt, complete all as specified and directed.
Supply and laying LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoure, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 Sqmm 3.5 core complete all as specified and directed.
S&F of energy saving and environemntal friendly long life versatile pressure die-cast aluminium IP-65 roadway luminaire 72 W LED fitting with high power LEDs light source and electronic driver complete all as specified and directed.
Note : Tenderers may note that amount of credit Rs 25,090.00 will be deducted from the total amount arrived, at the time of Acceptance of contract.
NOORI ENTERPRISSES
v v associates
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .