Loading…
Loading…
Tender Value
₹75.5 L
EMD Value
₹1.5 L
Closing Date
8 Oct 2026, 2:00 pm
Executive Engineer STD Sopore
amargarh sopore
Replacement of 11kV VCB panels for various Receiving Stations of KPDCL - STD Sopore under UT Capex
2026_PDD_324778_1
STDS/13 of 2026-27
Open Tender
Electrical Works
Turn-key
120 days
Baramulla/Kupwara/Sopore
Please refer Tender documents.
5 documents required · 5 mandatory
₹2,002
Executive Engineer STD Sopore
₹1.5 L
16 Sept 2026
16 Sept 2026
10 Oct 2026
16 Sept 2026
8 Oct 2026
18 Sept 2026
16 Sept 2026 - 18 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Outgoing SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Two Core(0.5,5P10) Epoxy Casted CT with CTR :400-200/5-5A,TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape. (KPDCL approved make/vendor)
To be Installed in following Receiving Stations:
1. R/Stn Tangdhar = 4 No.
2. R/Stn Keran = 01 No.
3. R/Stn Tangmarg = 03 No.
4. R/Stn Kralpora = 02 No. | 10 | No. | 1 | ₹10 |
| 2 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Incommer SCADA Compatible VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with Numerical O/C, E/F relays confirming to IEC61850, Master Trip Relay, Mimic Diagram, Digital Voltmeter with VSS, Digital Ammeter with ASS, PF Meter, Annunciation Windows with annunciation relays(6-Windows), 3-phase Tri-vector meter -5 Amps DLMS Compliant with RS-485 port ,Double Ratio; Two Core(0.5,5P10) Epoxy Casted CT with CTR :600-300/5-5A,TNC Switch, LR switch, Indication Lamps & other equipments as per approved Technical Specifications, of reputed make alongwith 11kV/ 110 V, Three phase epoxy resin cast Voltage Transformer with rated burden 15VA per phase and accuracy class 0.5 including Fixing of Earthing & Feeder Name Plate with Name of feeder written on it by using high intensity reflective Tape (KPDCL approved make/vendor) to be Installed in Receiving Station Tangdhar | 2 | No. | 2 | ₹4 |
| 3 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 120 mm² XLPE LT Cable 4 Core, armoured, FRLS ( Polycab, Havells, KIE, Anchor or equivalent) as per approved drawings/standards | 45 | Mtr | 1 | ₹45 |
| 4 | Dismantalling of Existing Outdated 11 KV VCB Panels including their carriage from site to divisional stores at Sopore | 12 | No. | 1 | ₹12 |
| 5 | CONTENGENCIES /T&P | - | - | - | - |
| 6 | Supply of A4 Paper Rims | 2 | No. | 1 | ₹2 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.22 MB
SBD13.pdf
Tender Documents • 1.63 MB
Drawing-Panel1_merged.pdf
Other Document • 23.17 MB
BOQ_1095843.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .