| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.7 LAccepted-AOC | L1 | Accepted-AOC lowest tender | |
| 2 | L2₹42.3 L+₹2.3 L (5.71%)Rejected-Finance KURUPPAMPARAMBIL PERUMPADAPPU PALLURURHY P O ERNAKULAM KERALA 682006 | ERNAKULAM | KERALA | 682006 | L2 | Rejected-Finance Other than lowest tender | |
| 3 | L3₹43.3 L+₹3.3 L (8.27%)Rejected-Finance | L3 | Rejected-Finance Other than lowest tender | |
| 4 | L4₹43.8 L+₹3.8 L (9.39%)Rejected-Finance | L4 | Rejected-Finance Other than lowest tender | |
| 5 | L5₹4.4 L−₹35.6 L (88.9%)Rejected-Finance | L5 | Rejected-Finance Other than lowest tender |
Tender Value
₹45.3 L
EMD Value
₹90,600
Closing Date
10 May 2021, 6:00 pmClosed
GE NS KOCHI
Military Engineer Services Garrison Engineer (Naval Services) Kataribagh, Naval Base Post Kochi, 682 004
FUNCTIONAL REQUIREMENT OF AC PLANTS AT JOC, ND SCHOOL, NSRY AREA INCLUDING PERIODICAL PREVENTIVE MAINTENANCE OF COLD STORAGE EQUIPMENT AT BV YARD INHS SANJIVANI HOSPITAL, REPAIR /MAINTENANCE OF ELECTRICAL CONTROL SYSTEMS OF CERTAIN CENTRAL AND PA
2021_MES_436197_1
8782/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
Kochi
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE NS KOCHI
₹90,600
Yes
17 Jun 2021
13 Apr 2021
12 May 2021
13 Apr 2021
10 May 2021
26 Apr 2021
14 Apr 2021 - 21 Apr 2021
Amount
Providing services of One AC mechanic per shift for central/package type AC Plants from 0600 hours to next day 0600 hours in three shifts per day and night (i.e. 8 hours per shift) including Sundays and holidays as per users requirement during summer/monsoon/winter and maintain the inside temperature and RH as per design and/or the requirement of users (where air conditioning have been provided) including carrying out of daily check up and cleaning complete all as specified and as directed by the EIC for the following plants installed at locations shown:-:- At JOINT OPERATION CENTRE(K) (i) 26 X2 =52 TR capacity (In operation) (ii) 26 X1=26 TR capacity (As Stand by)
Ditto All as per Item No 1, but for installation at FATS (SEAKING SIMULATOR): (i) 60X2 =120 TR capacity (In operation) (ii) 60X1=60 TR capacity (As Stand by) (iii) DG set 375 KVA as standby power supply (iv) Dehumidifier -(01 workng+1 Stand by)
Notes for Item No 1 and 2: (i) Minor complaints shall be done through Ac plant operator of respective central AC Plant Tripping i.e. strainer blockage, dries chock, solenoid failures, valves failure, water level maintain in CTs etc shall be included in above quoted rate. (ii) Operators employed for duties round the clock and the Shift operator having ITI/ITC pass in Refrigeration Mechanic trade from any Govt recognised college/institutions and having min 2 years experience in AC plant operations. (iii) Contractor shall be include the cost/expense in unit rate for providing the protecting cloths, tools, computer,& consumables and shift uniform for operator on deployed work. (iv) Certificate of Technical education qualification for the employing person shall be procured before assigning the job. (v) The operator should be filling of daily log sheets and deposit monthly, Log books shall be provided by contractor for entire duration of CA. (vi) Security of entire AC plants area shall be rest with contractor to ensure that no other person should be entered without permission of JE/EIC/GE. (vii) All necessary tools should be available with contractor, Contractor ensure cleaning of installation and Ac plant premises internal and external including roof top of building are deemed to be inclusive details of minimum staffs to be employed. (vii) Unit rate shall be deemed to be including all type of taxes, contribution towards social welfare of workers as per labour act i.e. EPF,ESIC,Insurance etc necessary documents shall be provide before claiming if any payments.
Providing services of one AC mechanic for central AC plants from 0800 hours to 1600 hours in one shifts per day as per users requirement during summer/ monsoon/ winter and maintain the inside temperature and RH as per design and/ or the requirement of users (where air conditioning have been provided) including carrying out of periodical check up and cleaning complete all as specified for the following plants:- Naval Ship Repairing Yard(excluding Sunday/holidays) (i) 75X2 =150 TR capacity (In operation) (ii) 75X1=75 TR capacity (As Stand by)
Notes for Item No 3: (i) Minor complaints shall be done through AC plant operator of respective central AC Plant Tripping i.e. strainer blockage, dries chock, solenoid failures, valves failure, water level maintain in CTs etc shall be included in above quoted rate. (ii) Operators employed for duties one shift per day (i.e 8 hours per shift) excluding Sundays and holidays and the Shift operator having ITI/ITC pass in Refrigeration Mechanic trade from any Govt recognised college/institutions and having min 2 years experience in AC plant operations. (iii) Contractor shall be include the cost/expense in unit rate for providing the protecting cloths, tools, computer & consumables and shift uniform for operator on deployed work. (iv) Certificate of Technical education qualification for the employing person shall be procured before assigning the job. (v) The operator should be filling of daily log sheets and deposit monthly, Log books shall be provided by contractor for entire duration of CA. (vi) Security of entire AC plants area shall be rest with contractor to ensure that no other person should be entered without permission of JE/EIC/GE. (vii) All necessary tools should be available with contractor, Contractor ensure cleaning of installation and Ac plant premises internal and external including roof top of building are deemed to be inclusive details of minimum staffs to be employed. (vii) Unit rate shall be deemed to be including all type of taxes, contribution towards social welfare of workers as per labour act i.e. EPF,ESIC,Insurance etc necessary documents shall be provide before claiming if any payments.
Preventive Maintenance of monthly and check up of Bitzer Blast cold storage 48000 BTU of 2 units including 2 ODU+ 2 IDU (-)30 °C operation with R- 404A Refrigerant gas two stage, semi hermetically sealed compressor consisting 4 cylinder, controlled with electronically operated solenoid valve for liquid system, complete all as specified and directed.
Preventive Maintenance monthly and check up of Danfoss cold room plant (-)18 °C with(50000 BTU) of 3 units including 3 ODU +3 IDU, R-404 A Refrigerant, The compressor hermetically sealed , equipped with electronically controlled solenoid valve system. The system have individual accumulated to verify and control the liquid gas flow including micro processor controlled electrical panel indoor blower unit controlled with fans and other electrical circuits with electronically operated solenoid valve for liquid system, complete all as specified and directed
Preventive Maintenance monthly and check up of Blue star cold room of capacity upto 30000 BTUof 4 units including 4 IDU+4ODU, R-22 Refrigerant temp to be stabled +4 °C equipped with electrically operated micro processor control panel including blower fans and other electrical circuits of the system to be checked complete all as specified and directed by Engineer-in-charge.
Preventive Maintenance monthly and check up of Blue star cold room at sanjivani Hospital plant (-) 18 °C with (10000 BTU) of 2 units including 2 IDU + 2 ODU,R-404 A Refrigerant. The compressor hermetically sealed. Equipped with electronically controlled solenoid valve system. The system have individual accumulated to verify and control the liquid gas flow including micro processor controlled electrical panel indoor blower unit controlled with fans and other electrical circuits of the entire system to be checked complete all as specified and directed by Engineer-in-charge.
Preventive Maintenance monthly and check up of Blue star cold room at sanjivani hospital temp to be stabled +4 °C with capacity upto 12000 BTU of 2 units including 1 IDU+1 ODU ,R-22 Refrigerant including in door blower unit equipped with electrically operated micro processor control panel including blower fans and other electrical circuits of the system to be checked complete all as specified and directed by Engineer-in-charge. Note for serial No 4 to 8 (a) All Major spares shall be measured and paid under relevant items Here in after. (b) Each servicing/checkup of cold storages by OEM/authorised dealers shall be carried out once in two months up to contact duration, and at any time of breakdown call by MES rep. (c)The job above quoted shall be included for all labour cost, except electrical control panels with parts
Supply and fix of digital temperature gauge of subzero model SZ7504 of working Temperature range -50°C to +99°Ccomplete all as specified and directed.
Supply only Catchall -sub cooling.
Supply only liquid line drier ( Model 604).
Supply only HP/LP Switch.
Supply only Oil Pressure Switch.
Supply only Solenoid Valve.
Supply only Expansion Valve.
Supply only Condenser fan motor capacity of 0.5 HP-0.75 HP along with leaf suitable for existing bracket of outdoor unit.
Supply only Evaporator Motor working capacity of 1.0 HP on 230 V for cold room suitable in existing indoor unit.
Supply only drain heater working on 230 V complete all as specified and directed.
Supply only Cold Room Defrost Heater working on 230 V complete all as specified and directed.
Supply and fixing in replacement of weather proof LED tube lights,230Volt,along with copper cable as required for connecting existing points at inside cold rooms complete all as specified and directed.
Supply only Compressor oil suitable working for existing R-134 and R-404 complete all as specified and directed.
Supply only Gas (404 A) in sealed cylinder Note: Empty cylinders to be returned to contractor after use.
Supply only Gas R-22 suitable for Cold storage outdoor units in sealed cylinder Note: Empty cylinders to be returned to contractor after use.
Supply and fixing in replacement of single core copper cable of size 6 Sqmm connection along with copper lugs in existing starter connections/pump/motor connections etc complete all as specified and directed
Material and Labour for servicing of chiller/condenser pump of capacity up to 5 HP including disconnecting & dismantling ,replacement of unserviceable bearings, water seal, gland bush, suitable gaskets/rubbers, nut bolts, terminal box and gland packing including reassembled and refixing the same location complete all as specified and directed by Engineer in charge.
Ditto All as per Item No 25 but for 7.5 HP to 10 HP.
Ditto All as per Item No 25 but for 12.5HP to 15 HP.
Ditto All as per Item No 25 but for Above 15 HP capacity.
Dismantling of electric motor 3 phase 415 V 15 HP to 25 HP transport to local work shop and taking out of bearing and re-metaling the bearing housing, including rewinding with same gauge super enameled copper insulated wire grinding, turning to the required size, cleaning of stator, varnishing, drying, re-assembling the motor to bring in original state including fixing on the foundation all as directed by Engineer-in charge.
Ditto All as per Item No 29 but upto 15 HP
M&L for Servicing/repairing of pump starter panel of capacity up to 5 HP (DOL) of chiller/condenser pump/CT motor/compressor motor in AC plants, including decarbonizing, tightening of control cable terminations, cable glands, and end termination crimping by attending with skilled Electricians and helper, with necessary T&P for checking and make functional at Various locations in Naval base Kochi. Notes: (i) Any major work identified while attending the above job shall be measured and paid separately under relevant item below as supply and fix. (ii) Minor spares up to 100 Rs per unit shall be included in the above quoted rate
M&L for Servicing/repairing of pump starter panel of capacity upto 5 HP Star delta type of chiller/condenser pump/CT motor/compressor motor in AC plants, including decarbonizing, tightening of control cable terminations, cable glands, and end termination crimping by attending with skilled Electricians and helper, with necessary T&P for checking and make functional at Various locations in Naval base Kochi. Notes: (i) Any major work identified while attending the above job shall be measured and paid separately under relevant item below as supply and fix (ii) Minor spares up to 100 Rs per unit shall be included in the above quoted rate
Ditto All as per Item No 32 but for capacity above 5 HP and upto 10 HP
Ditto All as per Item No 32 but for capacity above 10 HP and upto 25 HP
Ditto All as per Item No 32 but for capacity above 25 HP and upto 50 HP
Supply and replace power contactor MNX-18 to 22 Amp , 18 Amps, TP, 415V of coil voltage 220 V with aux contact 1 NO/1 NC including taking down the old unserviceable contractor all as specified and directed.
Supply and replace power contactor MNX-25, TP, 25 Amps, 415V of coil voltage 220 V with aux contact 1 NO/1 NC including taking down the old unserviceable contractor all as specified and directed.
Supply and replace power contactor MNX-32, 32 Amps TP 415V of coil voltage 220V with aux contact 1 NO+1NC.
Supply and replace power contactor ML Type/ MNX-40, 40 Amps, TP, 415V of coil voltage 220with aux contact 1 NO+1NC.
Supply and replace power contactor MNX-50, 50-70 Amps, TP, 415V of coil voltage 230 with aux contact 2 NO+ 2 NC.
Supply and replace power contactor ML/ MNX-95, 95 Amps, TP, 415V of coil voltage 230 with aux contact 2 NO+ 2 NC.
Supply and replace power contactor MO,up to capacity 18 Amp-20 Amp, 415V of coil voltage 220 V with aux contact 2 NO+2 NC including taking down the old unserviceable contractor all as specified and directed.
Supply and replace add -on Aux contact block front mounting of 2 NO + 2 NC suitable for MNX contactor 9-80A,3P,complete all as specified and directed.
Supply and replace power contactor MO ,25-45 Amps .
Supply and replace thermal overload relay for ML/MO/MNX contractors capacity up to 42 Amp all as specified and directed delay range 6 to 42 Amps.
Supply and replace Bolted fuse links Type HG offset staggered, F1, capacity of 2-32 Amps all as specified and directed
Supply and replace STAR DELTA timer with coil voltage 230/415V for 3-30 sec range all as specified and directed.
Supply and replace timer ET 100 electronic coil voltage 230/415V for 3-10 sec range all as specified and directed.
Supply and replace single phasing preventer, suitable for 380V-415V, AC all as specified and directed.
M&L for Attending breakdown call for Electric fault in AC plant LT panel for MCCBs/Electric LT panel bus bar reconditioning, cable gland and end termination crimping of 3 Ph elect supply LT cables, Any type of electrical complaint pertains to AC plants with skilled Electricians and helper , with necessary T&P for checking the equipment at Various locations in Naval base Kochi, find out the faults to the equipments (including replacement of minor parts such as lugs,fuses,wires,nuts,bolts,washers,etc,) complete and rectification of minor problems to make the plant functional , all as directed by the Engineer- in-Charge. Note: (i) Any major work identified while attending the above job shall be measured and paid seperatly under relevant item below as supply and fix (ii) Minor spares up to 100 Rs per unit shall be included in the above quoted rate
Supply and replace MCCB 415V, 36 KA, 4 pole DN 3, 400 Amp with spreader terminals, including taking down unserviceable MCCB all as specified and directed.
Ditto All as per Item No 51 but of DN 2,25KA,4 pole, capacity 200-250 Amp,415 Volt .
Ditto All as per Item No 51 but of DN 0,25 KA,100-125 Amp Amp,4 pole.
Supply and replace MCB, TPN 20-32Amp,C curve, 10 KA including taking out old unserviceable MCB, all as specified and directed.
Ditto All as per Item No 54 but of Capacity,TPN 63 Amps curve, 10 KA.
Ditto All as per Item No 54 but of Capacity, TP 20-32 Amps curve, 10 KA.
Ditto All as per Item No 54 but of Capacity, TP 40-63Amps, C curve, 10 KA.
Supply and fixing in replacement of fully automatic star-delta starter in sheet metal enclosure of type MK with capacity upto 12.5 HP/9.3KW suitable for Motor Rating AC-3,415V, 50H, and complete all as specified and directed.
Supply and replace digital Voltmeter 3 phase, Class 1 all as specified and directed.
Supply and replace digital Ammeter 1/5A, 3 phases, Class 1all as specified and directed.
Amount of Credit Schedule shall be deducted to arrive the Contract Sum.
Albert Rebello and Company
S. M. Enterprises
AISWARYA ENTERPRISES
SREENARAYANA ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .