| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.7 LAccepted-Finance | L1 | Accepted-Finance L1 Contractor | |
| 2 | L2₹1.8 L+₹9,710 (5.72%)Rejected-Finance | L2 | Rejected-Finance Not L1 Contractor | |
| 3 | Rejected-Technical NOT FOUND | - | Rejected-Technical No documents were uploaded by the bidder. | |
| 4 | Rejected-Technical | - | Rejected-Technical Registration not as per tender notice clause no. 1.10, Experience Certificate not as per tender notice clause no. 1.13 |
Tender Value
₹2.2 L
EMD Value
₹4,500
Closing Date
24 May 2024, 6:00 pmClosed
Director
NIT Calicut, NIT Calicut Campus PO, Kerala, 673601
CSED Research room wiring
2024_NITC_805981_1
Engg/EMU/JE1/011/CSEDResRmWrng
Open Tender
Civil Works
Item Rate
12 days
NIT Calicut, NIT Calicut Campus PO, 673601
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹4,500
Yes
26 Jun 2024
3 May 2024
27 May 2024
3 May 2024
24 May 2024
3 May 2024
Amount
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
4 way (8 + 12), Double door
Supplying and fixing 63 amps rating, Four pole (Three phase and neutral) 415 Volts, residual current circuit breaker (RCCB), having a sensitivity current up to 100 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Double pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing 63A rating, Four pole, Three phase, 415 Volts, 10kA, "C" curve, miniature circuit breaker suitable for inductive load of four pole in the existing MCB DB complete with connections, testing and commissioning etc as required.
Supplying and fixing 40 to 63A rating, Three pole (Three phase ) 415 Volts, 10kA, "C" curve, miniature circuit breaker suitable for inductive load of triple pole in the existing MCB DB complete with connections, testing and commissioning etc as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
DP Switch
Supplying and fixing 20/25 A modular DP switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Modular Socket
Supplying and fixing 3 pin 25 A modular socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75mmX75mm)
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Metal box removal
Charges for removing the old Distribution board with MCB, RCCB, outgoing cable& other accessories without any damage and transporting to the store, clearing damages of the wall including painting, etc. as required.
Supplying and fixing of 4 way double door, single pole and neutral, sheet steel, MCB distribution board,240V, on surface/ recess, complete with tinned copper bus bar, earth bar, din bar, detached gland plate, interconnection, phosphetized and powder painted including earthing etc. as required.(But without MCB/RCCB/Isolator)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 2.5 sq. mm
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 4 sq. mm
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 1.5 sq. mm
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supply and fixing of box type tube fittings (Batten & T8 LED Tube), complete with side holders and 18/20 watt 4 feet T8 LED tube including 25x3mm or suitable GI clamp for fixing at an angle of 45 degree etc, as required.(T8 LED-Bajaj BLRB 18W CW LED or or compatible, Batten- Bajaj BLRB-DB 118 I or compatible)
Supply of 28W 1200 mm sweep 5 Star rated BLDC ceiling fan with input voltage range (140-285V), 380 rpm, Air delivery 235 m3/min, regulator supported type, Aluminium Blade material ,white colour,with 3 years onsite warranty, conforming to IS:374:2019 latest
Sivaprathapan KB
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .