Loading…
Loading…
Tender Value
₹98.8 L
EMD Value
₹98,810
Closing Date
18 May 2026, 6:00 pmClosed
Similar tender results from the same govt authority in the past 3 years.
Municipal Commissioner
Augmentation work with SITC of Pumping Machinery with related Mechanical, Electrical, Instrumentation and Miscellaneous works for Gomtipur water Distribution Station Besides Gomtipur Drainage in Gomtipur Ward of East Zone of AMC.
302080
2026-27
Open
Miscellaneous Works
Ahmedabad
2 documents required · 2 mandatory
₹2,400
Municipal Commissioner, Ahmedabad
₹98,810
6 May 2026
6 May 2026
6 May 2026
18 May 2026
6 May 2026
estimated cost, as mentioned above. Amount of my / our tender works out for Rs. ________________ (in figures)
Estimated amount put to tender Rs. Estimated amount put to tender Rs.
2) Amount Quoted for Buy Back Items Minimum Rs. 4,48,000/- OR more (as per Annexure-1) in Scope of Work (Section A-4, A.4.7), Rs.
3) Final Tender Amount (Without GST) = 1 - 2 = Rs. ____________________
Signature of Contractor
Company’s seal :
1. Bidder has to quote % Above (Premium) or % Below (Discount) or as par of total Job, Rs. 98,80,451/- (i.e. Total Estimated Project Cost
w/o buyback value) and has to carry out work at Ordered Value with any Excess -Less Qty. mentioned in above items as per site
requirement and instruction of Engineer-in-charge.
2. Bidder must quote Minimum Rs. 4,48,000/- OR more for buyback items as per Annexure-1 in Scope of Work, Section A-4(A.4.7)
separately online at Sr. 2 as indicated above. Bidder to note that net amount quoted by the bidder shall be determined by deducting
the total amount of buyback quoted by bidder from the amount quoted for works as above at Sr. No. 1 and the net amount so derived
the total amount of buyback quoted by bidder from the amount quoted for works as above at Sr. No. 1 and the net amount so derived
shall be considered for Price Evaluation purpose to determine lowest bid.
SUMMARY OF COST
Name Augmentation work with SITC of Pumping Machinery with related
of Mechanical, Electrical, Instrumentation and Miscellaneous works for
Work Gomtipur water Distribution Station Besides Gomtipur Drainage in
Gomtipur Ward of East Zone of AMC.
A. MECHANICAL WORK
B. INSTRUMENTATION WORK
C. ELECTRICAL WORK
TOTAL OF CAPITAL COST (A + B + C)
(EXCLUDING GST)
E BUY BACK AMOUNT IN RS. (AS PER ANNEXURE-1)
TOTAL AMOUNT AFTER DEDUCTION OF BUY
TOTAL AMOUNT AFTER DEDUCTION OF BUY
BACK VALUE IN RS. (D-E)
Name Augmentation work with SITC of Pumping Machinery with related Mechanical, Electrical, Instrumentation and
of Miscellaneous works for Gomtipur water Distribution Station Besides Gomtipur Drainage in Gomtipur Ward of
Work East Zone of AMC.
MECHANICAL WORK
SUPPLY LABOUR AMOUNT TOTAL
SR. NO. ITEM QTY UNIT RATE (S) RATE (L) (In Rs.) AMOUNT
1.1.1 HORIZONTAL SPLIT CASING CENTRIFUGAL 3 Nos. 615,450.00 12,500.00 627,950.00
PUMP WITH MOTOR
Supply, installation, testing and commissioning of
horizontal mounted, side suction & side delivery type
Horizontal Split Casing Centrifugal Pump having CI
Casing, CF 8 M impeller & wear rings, SS410 Shaft & shaft
sleeves, gland packed and suitable to couple with TEFC
squirrel cage IE3 efficiency class Induction Motor, 3 Phase,
415 V, 50 Hz., AC supply, max. 1500 RPM synchronous
speed. The scope shall also include all required accessories
viz. CI drain rim type base plate, Flex. coupling, coupling
guard, foundation bolts, min 25 mm dia. G.I. Class-B drain
pipe upto drain channel, etc. as per specification.
Capacity : 550 m³/hr
Motor Rating : 75 KW or as per Manfactuer Standard
The scope also includes chipping, grouting, altering the
civil foundation to suit the new pumpset as required and
removal of debries and cleaning the dry well.
INDUCTION MOTOR FOR ABOVE HSCF PUMPS:
Supply Installation Testing and Commissioning (SITC) of
approved make, energy efficient, Efficiency Class-IE3,
horizontal foot mounting, solid shaft, squirrel case,
Induction Motor rating mini 75 kW or higher as per IS,
3Phase, 415V, 50Hz., AC supply, maxi.1500 RPM
synchronous speed and having TEFC enclosure with Class
F insulation (temp. rise limited to Class B) with RTD/BTD.
Supply, installation, testing and commissioning of
Manually gear operated CI/DI Double Flanged, Rising
Spindle type, Sluice Valve conforming to IS 14846 PN
with SS 304 seat rings and SS spindle with hot dipped
galvanised hardware's, bolts, nuts & washers, gaskets, etc.
as per data sheet.
Size : 250 mm NB (Manually Operated - On suction pipe)
2.2.1 Supply, installation, testing and commissioning of 3 Nos. 137,063.00 742.00 137,805.00
Electrically gear operated CI/DI Double Flanged, Rising
Spindle type, Sluice Valve with actuator, integral
starter,etc. conforming to IS 14846 PN 1.0 with SS 304 seat
rings and SS spindle with all hot dipped galvanised
hardware's, bolts, nuts & washers, gaskets, etc. as per data
Size:200 mm NB (Electrically Operated - On Delivery Pipe
of Each HSCF Pump)
2.3.1 Supply, installation, testing and commissioning of double 3 Nos. 16,571.00 742.00 17,313.00
flanged CI/DI Dual Plate Check Valve conforming to API
594 Class 300 / PN 1.6 with CS dual door, hinge pin & stop
pin of SS 410 , springs of AISI 304 and seat rings of SS
( renewable ), along with all required accessories, gaskets
and hardwares,etc. and as per specification.
Size : 200 mm NB (On Delivery Pipe of Each HSCF Pump)
3.1.1 Supply, installation, testing and commissioning of double 3 Nos. 6,216.00 0.00 6,216.00
flanged Expansion Bellows confirming to EJMA/IS
standard with PN 1.0 rating & all necessary St.St.
Size : 200 mm NBx 300 mm ( L )(On Delivery Pipe of Each
4.1.1 C.I. PIPES, FITTINGS & SPECIALS 20 MTR. 4,094.80 776.60 4,871.40
Manufacture, Supply and delivery and Instllation of CI
flange ended Pipes & Fitting complete as per IS 1536 /
1537, Class B or its latest revision for various dia meter and
classes The delivery of pipes to be made to Pump house/site
including all taxes , loading carting, unloading, stacking,
insurance, octroi, inspection charges etc. complete as per IS
and as per specifications.
Size : 200 mm NB and Above ( For HSCF Pump Pipe )
5.1.1 Flanged Joints of Pipes, Fittings and Specials: 12 Nos. 0.00 1,007.00 1,007.00
Supply, Installation, Making of Flanged CI & GI Pipes,
Fittings and Specials Joints with all jointing materials,
rubber packing, nut bolts, labour etc.for complete
Size: 250 mm dia
6.1.1 M.S. PIPES & SPECIALS 6 RMT 2,663.00 - 2,663.00
Supply, Gas cutting of pipe, Fabrication, welding,
Installation, testing and commissioning of MS pipe &
Specials conforming to IS 3589 & flanges confirming to IS
6392-PN-1.0, fabricated from MS. plate with necessary
supports & anchoring. Pipe fabricated from MS plate.
(Excluding supply of flange)
Size: 250 mm NB X 5 mm Thk
6.2.1 Providing Painting to inside and outside pipe line with two 12 Sq.m 332.00 - 332.00
parts of Solvent free high build liquid Paint as per AWWA
C210-07 Suitable for potable water application & shall be
approved by CFTRI- India/BS 6920-UK/international
standard /NSF/ANSI/-61 2004 to be fit for contact with
potable water for human consumption with 406 micron
thickness. inclusive of necessary materials , labour
,Equipment ,Contractor's overhead charges and profit and
including all taxes.
Size: 200 mm NB
6.2.2 As per Above Item Specification 24 Sq.m 332.00 - 332.00
Size: 250 mm NB
6.3.1 Supply, welding , Installation, testing & commissioning of 15 Nos. 2,509.78 0.00 2,509.78
MS flat machined faced flanges confirming to IS 6392 &
drilled as per IS-1538 with drilling off centre bolt holes and
flange thickness as per PN 1.0 including cutting & welding.
Size : 200 mm NB Drilled
7.1.1 G.I. PIPES & FITTINGS: 18 RMT 864.00 34.00 898.00
Supply, installation, connection with equipments as
required, testing and commissioning of GI pipe conforming
to IS-1239 , Medium Duty with coupling, tee, bend, union,
elbow, flanges , etc as all required fittings for connection
complete with gaskets, hardware, and required accessories
as per IS & Specifications
Size: 100 mm NB(For Air valve and Dewatering Pump)
8.1.1 DEWATERING PUMPS 1 Nos. 146,348.00 - 146,348.00
Supply, erection, testing and commissioning of Non Clog
Submersible Pump with C.I. casing & CF8M impeller,
including necessary accessories and hadrwares, etc., 25m
cable as required suitable for 3 phase, 415 V, 50 Hz AC
supply with min. 3 HP motor and necessary safety futures
along with pump monitoring unit for auto stop facilities,
cable termination / juction box of required terminal size,
supporting arrangement for pump and other required
accessories to be installed in dry well drain pit.
Capacity: 30 m3/hr
Head: 15 m. Motor Rating: Mini. 2.2 kw (or higher rating
as reco. by pump manufacturer)
9.1.1 MONORAIL EOT WITH ELECTRIC CHAIN HOIST 1 Nos. 166,000.00 8,300.00 174,300.00
Supply, installation, testing & commissioning of
Electrically Operated Chain Hoist & Electrically operated
Trolley, suitable to operate on Mono Rail Girder having
motorised motion, manufactured as per IS:6547-1972-
Class-II & IS-3177- Class-II, complete with brake, chain-
gear, motors, safety device, pendant push button, starter
panel, cables from motor to starter panel and all other
required accessories like limit switches, power supply
system (Fastoon cable type), fasteners, epoxy painting, etc.
tested for over load as per IS and as per specifications,
complete in all respect.
Capacity : min. 2.0 Ton. Min.
Lift : 10.00 m as mini. or as per site req.
Bay Length : 12 m (w/o MONORAIL GIRDER & MS
supporting structure)
Note: Minimum as specified capacity or higher as per
requirement such that EOT with ECH capacity is min.1.25
times of the pump /motor OR single heaviest component to
be lifted within pump house.
10.1.1 Providing and Supplying at site of work with M.S. 1200 kg 72.92 - 72.92
anchor bolts, channels, angles, chequered plates, all
other type of inserts, ladder, ISMB etc. in concrete
members during concreting as per instructions in all
positions and at any level including keeping them in
correct position and alignment, including adjustment of
reinforcement and shuttering, etc. complete and
including two coats of approved oil paint over one coat
of zinc-rich primer over exposed surfaces of above
mentioned inserts after embedment, etc. all as
specified."Providing and Supplying at site of work with
M.S. anchor bolts, channels, angles, chequered plates
(12mm thick), all other type of inserts, ladder, ISMB
etc. in concrete members during concreting as per
instructions in all positions and at any level including
keeping them in correct position and alignment,
including adjustment of reinforcement and shuttering,
etc. complete and including two coats of approved oil
paint over one coat of zinc-rich primer over exposed
surfaces of above mentioned inserts after
embedment, etc. all as specified. (min. 250 mm I-
Beam gireder for Vertical & Horinzontal column, for
Monorail etc. as required to complete the work in all
respects & satisfactory operation of Electric Chain
Hoist)For Construction of monorail girder for
Chain Pulley Block with all required accessories
and hardware and as per instruction given by
Engineer In-Charge.Size : 350 x
10.1.2 Labor Charges for lowering,laying,fixing with 1200 kg - 11.37 11.37
fabrication at site with M.S. anchor bolts, channels,
angles, chequered plates, all other type of inserts,
ladder, ISMB etc. in concrete members during
concreting as per instructions in all positions and at
any level including keeping them in correct position
and alignment, including adjustment of reinforcement
and shuttering, etc. complete and including two coats
of approved oil paint over one coat of zinc-rich primer
over exposed surfaces of above mentioned inserts
after embedment, etc. all as specified. (min. 250 mm
I-Beam gireder for Vertical & Horinzontal column, for
Monorail etc. as required to complete the work in all
respects & satisfactory operation of Electric Chain
For Construction of monorail girder for Chain
Pulley Block with all required accessories and
hardware and as per instruction given by Engineer
11.1.1 Supplying & Fixing SMC Chequered plate having 7 mm 7 Sq. 3,390.00 204.00 3,594.00
thickness, made out of SMC Confirming to IS 13410 & by Mtr.
Hot press Compression Moulding technique Suitable cut &
fixed with MS Angle Frame to Fit Trench Widths as per site
requirement approved by engineer incharge.
Provide as per Actual Site Requirements.
12.1.1 Miscellaneous Civil Work including Demolition/ 1 Job 357,400.00 - 357,400.00
modification, providing cut-outs (core cutting) of Required
size, minor repairing / finishing works etc. Required civil
works including Pump Foundations, Valve Foundations,
pipe & fittings foundations/support etc. and incl. grouting
PCC / RCC Support including cement, sand, grit, kapachi,
water, steel bars, scafolding materials, curing,finishing,
plastering, painting complete in all respect.and any other
unforeseen / emergency work during Installation of pump
in running Dry well etc. Necessary Inside and Outside
plastering, Painting, Kota Stone, Brick Work and all other
as required to complete the work in all respects and as
required for installation and satisfactory operation of all
electro-mech. equipment’s as per the tender scope / BOQ.
and any other work required at site as per instruction of
Engineer- In-Charge of AMC and as per the tender scope /
12.1.2 Miscellaneous Civil Work for Door, Window, Ventilation 1 Job 254,300.00 - 254,300.00
and Rolling Shutter including Demolition/Dismentaling
modification incl. Providing, Supplying, jointing and fixing
MS Door, Ventilation, Alluminium frame section Windows
with three track horizontal sliding sliding incl glass & grill
or as per instrcted by engineer in-charge. Providing
supplying and fixing Rolling shutter and any other work
required at site as per instruction of Engineer- In-Charge of
AMC and as per the tender scope / BOQ.
12.1.3 Civil Work For Transformer Foundation incl. Excavation, 1 Job 86,200.00 - 86,200.00
filling PCC, RCC work, Plaster, painting, brick work and
all other as required to complete the work in all respects and
as required for installation and satisfactory operation of
transformer as per the tender scope / BOQ. and any other
work required at site as per instruction of Engineer- In-
Charge of AMC and as per the tender scope / BOQ.
13.1.1 DISMANTLING, CARTING AND STACKING 1 Job - 40,000.00 40,000.00
(Mechanical Items)
Dismantling of all Existing HSCF Pump-Motor set, existing
Valves, NRV, Drain Pumps, Pipes and Specials (Tees, Band
etc) etc. of Existing HSCF Pump House covering with
Plastic and packing in wooden box with all required
accessories and transportation & stacking at AMC store /
site or as per instruction given by the engineer In-Charge.
13.1.2 DISMANTLING, CARTING AND STACKING 1 Job - 30,000.00 30,000.00
(Electrical Items)Dismantling of all existing APFC Panel,
All Cubicle panels, Cables, Cable Trays, lighting fixtures,
existing lighting wiring including loading, shifting &
unloading at location in plant compound as directed by
Enng. in charge of AMC.
14.1.1 Office Table 1 Nos. 2,000.00 - 2,000.00
Office Table of size 1200 mm length X 600 mm width with
min. three nos. drawers.
14.1.2 Steel Office Chair with arm rest 3 Nos. 1,000.00 - 1,000.00
14.1.3 Steel Cupboard (min. W x H x D: 900 mm x 1800 mm x 1 Nos. 25,000.00 - 25,000.00
430 mm) with min. 20 guage steel
TOTAL ESTIMATE OF MECHANICAL WORK (WITHOUT GST)
Name Augmentation work with SITC of Pumping Machinery with related Mechanical, Electrical, Instrumentation and
of Miscellaneous works for Gomtipur water Distribution Station Besides Gomtipur Drainage in Gomtipur Ward of
Work East Zone of AMC.
INSTRUMENTATION WORK
ITEM QTY UNIT (In Rs.) AMOUNT
1.1.1 PRESSURE MEASURING SYSTEM 3 Nos. 950.00 79.00 1,029.00
Supply, installation, testing & commissioning of Bourden type
Pressure Gauge glycerene filled having 100 mm dial with necessary
fittings/accessories (Manifold valve, nipples, etc. shall be in SS 316 only)
as per specifications & complete in all respects.
Range : 0 - 6 kg / sq.cm.
(On Each pump Delivery Pipe)
1.1.2 Supply, installation, testing and commissioning of Digital Pressure 3 Nos. 26,903.00 2,244.00 29,147.00
Transmitter along with, manifold valve, required fittings, tubing (all
valves, fittings, tubings, etc. shall be in SS 316 only) all accessories,
hardware, etc. complete in all respects as per specifications and having
following measurement ranges:
Range : 0 - 6 Kg/cm2
(On Each Pump delivery-)
2.1.1 LEVEL MEASURING SYSTEM 1 Nos. 54,860.00 4,576.00 59,436.00
Supply, installation, testing and commissioning of Ultrasonic type
Level Transmitter along with all required accessories, hardware,
hardware, etc. complete in all respects with local and remote display, as
per specification. The scope also includes providing 4" flanged , puddle
pipe approximate 300 mm long including fixing of the same in civil
structure slabe of pump house for mounting of level Transmitter.The
work also include all necessary work like make hole,repair /
modificationin existing slab, etc.Level Transmitter having following
measurement ranges for liquid (Water) application:
Meas. Range: upto 6 m (at any one compartment of sump)
2.1.3 Supply, installation, testing & commissioning of Float & Board type 1 Nos. 16,353.00 1,365.00 17,718.00
level indicator along with all accessories, hardware, etc.
complete in all respects as per specifications and having following
measurement ranges:
Meas. Range: upto 6 m (at any one compartment of sump)
3.1.1 INSTRUMENT CABLE & ACCESSORIES 300 MTR 118.00 23.00 141.00
'Supply, Laying, Installation, Connection, Termination, Testing &
Commissioning of Instrument Cables, along with cable glands, lugs,
cable trays, required junction boxes, fittings and accessores as per specs.
The unit rate shall include
a. Supply, loading & unloading of the cable at site from store.
B. Shifitng of cable from site store to place of installation.
c. Fixing of cable clamps, brackets, supports, route markers etc. where
ever required to fix the cables safely.
d. Excavation, back filling and levelling of ground alongwith laying of
fine sand, protection bricks and other necessary civil material for laying
cables outside the building.
e Testing and submission of sketches & reports of all the cables laid.
Cable Length is Approx. Provide as per Actual Site Requirements.
3.1.2 CONTROL CABLE2C x 1.5sq.mm.Cable Length is Approx. Provide 150 MTR 100.00 23.00 123.00
as per Actual Site Requirements.
3.1.3 SIGNAL CABLE 300 MTR 120.00 30.00 150.00
Cable Length is Approx. Provide as per Actual Site Requirements.
4.1.1 INSTRUMENT CABLE TRAY 100 MTR 272.00 30.00 302.00
GI Perorated type cable tray shall be made out of galvanized MS sheets
of 1.6 mm thickness with required asccessories . All material shall be Hot
dip galvanised (816 g/m2) as per IS 2629 as mentioned in specification
and tray hardware shall be in GI.
50 x 50 mm - Perforated type
Cable Length is Approx. Provide as per Actual Site Requirements.
5.1.1 CABLE END TERMINATION AND CONNECTION 20 Nos. 43.00 14.00 57.00
'Supply, fixing, connection, testing and commissioning of double
compression brass cable glands and crimping type Bimetalic lugs /
sockets with necessary tools and equipments as specified in
specifications and IS complete in all respects. The glands and lugs /
sockets shall be suitable for cable size and type mentioned above. The
job also includes earthing the glands and armour of the cable with
common earth bar or flexible copper mesh as applicable.
5.1.2 CONTROL CABLE 20 Nos. 36.00 13.00 49.00
5.1.3 SIGNAL CABLE 20 Nos. 29.00 12.00 41.00
TOTAL ESTIMATE OF INSTRUMENTATION WORK (WITHOUT GST)
Name Augmentation work with SITC of Pumping Machinery with related Mechanical, Electrical, Instrumentation and
of Miscellaneous works for Gomtipur water Distribution Station Besides Gomtipur Drainage in Gomtipur Ward of East
work Zone of AMC.
ELECTRICAL WORK
SUPPLY LABOUR AMOUNT TOTAL
ITEM QTY UNIT RATE (S) RATE (L) (In Rs.) AMOUNT
Supply, laying, testing & commissioning of 11 kV, 3C x
sq.mm.XLPE (UE) armoured H.V Cable stranded Aluminium
conductor, galvanised steel flat strip/ round wire armoured,
extruded PVC type ST2 sheathed, heavy duty cable conforming
to IS:7098 (Part-2) & IEC:60502(Part-2).
1.2.1 Supply, Installation, Testing and Commissioning of the Heat 3 Nos. 6,060.00 925.00 6,985.00
shrinkable type Indoor H.T.cable end terminations suitable for
11 kV, 3C x 240 sq.mm. XLPE (UE) armoured cable
including necessary earth connectivity connection, material &
consummables making the termination/ joint complete ensuring
the joint resistance is within the permissble limit as per IS.
1.2.2 Supply, Installation, Testing and Commissioning of the Heat 1 Nos. 10,562.00 925.00 11,487.00
shrinkable type outdoor H.T.cable end terminations suitable
for 11 kV, 3C x 240 sq.mm. XLPE (UE) armoured cable
including necessary earth connectivity connection, material &
consummables making the termination/ joint complete ensuring
the joint resistance is within the permissble limit as per IS.
2.1.1 DISTRIBUTION TRANSFORMER 1 No 1,815,000.00 90,750.00 1,905,750.00
SITC of Outdoor type, Three phase, oil immerged, 11 /
KV, Energy Efficiency Level -2, Distribution transformer of
315 KVA & voltage ratio, copper double wound, vector group -
Dyn11, HV delta connected & LV star connected with neutral
brought out connected to provide separate earthing terminals,
bushing / cable box on HV side and cable box on LV side suitable
for cables or bus duct as per requirement with standard fittings,
conforming to IS: 1180 (Part-1) / 2021 with its latest
amendment including first fill of transformer oil & following
(a) Oil conservator with filling holes with cap and prismatic oil
level gauge, (b) Silica Gel dehydrating breather charged with
silica gel, (c) Oil drain cum sampling valve with plug (d) Oil filter
valve, (e) Lifting Eyes / Hooks / Lugs, (f) Two earthing terminal,
(g) Diagram and rating plate, (h) Air release plug, (i) Explosion
vent with diaphragm OR PRV (j) Thermometer pocket, (k) Four
bi-directional plain roller with base channel with hauling holes,
(l) Fixed / Separate type radiator banks , (m) Off circuit
externally operated tapping switch (For rating < 1000 kVA), (n)
100 mm stem type oil temperature indicator (For rating <
kVA), (o) Bucholtz relay with shut off valve (p) 150 mm dial
type oil temperature indicator with Alarm / Trip contact (For
rating ≥ 500 kVA), (q) 150 mm dial type winding temperature
indicator with Alarm / Tip contact (r) Marshalling box (s)
mm dia. magnetic type oil gauge (For rating ≥ 1600 kVA) (t)
Inspection cover & Jacking lugs (For rating ≥ 1600 kVA). With
off circuit tap changer as per standard IS.
Maximum Total Losses (kW) @ 50% / @ 100% / % Imp
2.1.1.1 Transformer temp. rise/Heat run test charges @manufacturers 1 No. - 25,000.00 25,000.00
2.1.1.2 Transformer Total Losses(W) Testing at ERDA Laboratory to 1 No. - 55,000.00 55,000.00
confirm Guarantted losses as per energy efficiency level-2 of IS:
2.1.2 Supply and levelling of transformer yard using gravel, fine sand 75 Sq.m. 400.00 - 400.00
and other required filing material, enmarked for the switchyard
including removing of trees or boulders if any etc. The general
level of the yard shall be at a convenient level for movement of
man and material and it should match with FGL and as per
Specification and Drg.
2.1.3 Supply and Installation of Chain link fencing around switch yard 20 RMT 1,250.00 - 1,250.00
etc. as per Specification and Drg.
2.1.4 SITC of 2.5 mtr wide gate with required material as per 2 Nos. 12,500.00 - 12,500.00
Specification.and as per Specification and Drg.
3.1.1 LOW VOLTAGE (LT) PANEL BOARD (PMCC): 1 Nos. 1,733,019.00 86,651.00 1,819,670.00
SITC of PMCC Panel (50kA), compartmentalised, floor mounted
/ stand mounted as per site, Extensible on both ends,suitable for
Manual & Auto operation -Local & through PLC/SCADA
operation as per site conditions complete in all respects as per
Tender SLD / Specification / IS and including following as
(1) One Nos. FP 630 A Microprocessor EDO ACB for I/C with
Digital Voltmeter with Voltmeter Selector Switch, Digital Power
Factor Meter, Digital Ammeter with Ammeter selector switch,
KWh Meter, MFM with RS-485, R, Y, B, on, off, trip Indicating
lamps & ON, E-STOP,TNC Switch, Reset Pushbutton, etc.
(2) 630 A TPN Main busbars. (Main & Auxilary bus-bars size
with current density 0.8A/Sq.mm)
(3) Three Nos. (2W + 1S) Soft starter for min. 75 kW Motor or
higher as per pump Manufacturer reco. with suitable derating and
with 250A TPN Motor Duty MCCB, 150A AC3 Inbuilt/ External
bypass contactor, Ten channel temperature scanner with potential
free contacts, fast acting fuse, MFM with RS-485, door display
key pad & digital MPR+SPP with CBCT, on, off, trip Indicating
lamps & ON, E-STOP, Local/Remote, Auto/ Manual selector
switch & LCS for Pump- MOV Actuator with Indication & push
(4) One nos. 160 A TPN Microprocessor MCCB feeder for APFC
(5) Two Nos. 320 A TPN microprocessor MCCB feeder for
Nos Borewell Feeder and 1 No Spare.
(6) Three nos. 63ATPN MCCB feeders (for PDB - Auxiliary
accessories load & 1 No. Spare)
(7) Tr. losses comp. fixed capacitor bank with one no. 10 kVAR
& two nos. 5 kVAR, Two nos. 2 kVAR,One nos.1 kVAR
capacitors bank each with capacitor duty contactor, timer & 'D'
curve MCB, etc. for each transformer.
(8) One no. Outdoor lighting LDB feeder with 32ATPN 'C' curve
MCB with 32A contactor & Time switch.
(9) 6 nos. 32A 'C' curve MCB feeders (for Indoor and Outdoor
LDB, 1 nos. Dewatering Pump & 3 Nos. spare feeders)
(10) 6 nos. 16A DP MCB feeders (for single phase supply for
nos. X'mer marshaling box, 5 Spare.)
(11) 2 Nos. MOV Actuator 16A FP MCB feeder for Inlet side
Valve and Spare.
(12) 3 nos. 630A/5A, Cl.-0.5 metering CT
(13) 1 nos. 630A/5A, Cl.-1 CT for 1nos. APFC
(14) 2nos. Multiplication relay for dry run protection of pumps.
3.1.2 AUTOMATIC POWER FACTOR CORRECTION (APFC) 1 Set 180,116.00 7,954.00 188,070.00
SITC of 90 kVAR APFC Panel complete in all respects as per
SLD / Specification / IS and including following as minimum:
(1) 160 A FP Microprocessor MCCB I/C.
(2) 10 Steps Microprocessor APFC Relay with sensitivity 10mA.
(3) 1 no. 30 kVAR capacitor bank with 63A 'D' curve MCB &
kVAR Capacitor duty contactor with timer.
(4) 1 nos. 20 kVAR capacitor bank with 40A 'D' curve MCB &
20 kVAR Capacitor duty contactor with timer.
(5) 2 nos. 10 kVAR capacitor bank with 20A 'D' curve MCB &
10 kVAR Capacitor duty contactor with timer.
(6) 3 nos. 5 kVAR capacitor bank with 16A 'D' curve MCB &
kVAR Capacitor duty contactor with timer.
(7) 2 nos. 2 kVAR capacitor bank with 16A 'D' curve MCB &
kVAR Capacitor duty contactor with timer.
(8) 1 nos. 1 kVAR capacitor bank with 16A 'D' curve MCB &
kVAR Capacitor duty contactor with timer.
(9) All capacitors shall be Gas Filled type with dielectric losses
≤ 0.2w/kVAR. (Suitable for 0.95 or better Correction).
3.2.1 SITC of Lighting Distribution Board (LDB) as under: 1 Nos. 7,125.00 369.00 7,494.00
3 Phase 4 Wire TPN, 6 way Prewired LDB (One for Indoor &
Outdoor Lighting) Suitable to house :
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB 'C' curve (9 nos.) & 16A SP MCB
'C' curve (9 nos.)
(At Panel Room)
3.2.2 SITC of Power Distribution Board (PDB) for MOV as under: 1 Nos. 9,620.00 389.00 10,009.00
3 Phase 4 Wire TPN, 8 way Prewired MOV-PDB for Actuator of
valves power supply (For MOV Pump delivery valves, valve at
Header & spare):
Incoming: 63A TPN, MCB 'C' Curve
Outgoing: 10 nos. 32A TP MCB 'C' Curve
3.3.1 LOCAL CONTROL STATION 3 Nos. 4,000.00 840.00 4,840.00
SITC of Pendant type ON_OFF LCS with pushbutton set
complete with Enclosure, necessary mounting/ fixing
arrangement on wall / pipe support etc. to be installed near
motors for remote operation, etc. as per IS and specifications.
(including structural steel) (For 3 nos.Pump )
3.3.2 SITC of Local Control Station with pendant type 3 Nos. 4,000.00 500.00 4,500.00
Open_Stop_Close pushbutton set and with Open, Close, Trip &
Local / Remote Indicating Lamps complete with Enclouser,
necessary mounting/ fixing arrangement on wall / pipe support
etc. to be installed near motors for remote operation, etc. as per
IS and specifications (including structural steel)(For Delievery
Valve of Each Pumps )
4.1.1 LOW VOLTAGE (LT) CABLES 200 Mtr 753.00 31.00 784.00
Supply and unloading & delivery at site, storage & security at
site of 1.1 kV, A2XFY/2XWY XLPE insulated (IS 7098) / PVC
insulated (IS 1554) AL / Cu conductor cables as per specification
& IS. The cable when laid outside the building shall be laid
underground in excavated trench, as per specified method and
shall be laid in prepared trench on cable tray when laid inside the
3.5C x 240 sq. mm. A2XFY Cable (2 Runs for Tr. 1 to PMCC
Cable Length is Approx. Provide as per Actual Site
4.1.2 3.5C x 95 sq. mm. A2XFY Cable (1 Runs for each APFC 25 Mtr 325.00 18.00 343.00
Panel)Cable Length is Approx. Provide as per Actual Site
4.1.3 3C x 150 sq. mm. A2XFY Cable (1 Runs for Each Main Pump 150 Mtr 421.00 13.00 434.00
Cable Length is Approx. Provide as per Actual Site
4.1.4 4C x 6 sq. mm. A2XFY Cable (For WR-DB with TPN MCB at 250 Mtr 72.00 6.00 78.00
Sump & Pump House, Outdoor LDB, Indoor LDB, 1nos.
Cable Length is Approx. Provide as per Actual Site
4.1.5 4C x 2.5 sq. mm. 2XWY/2XFY Cable (For TPN MCB at PMCC 300 Mtr 75.00 6.00 81.00
room & Pump house maintenance floor & Pump House floor,
Motor Operated Valves,)
Cable Length is Approx. Provide as per Actual Site
4.1.6 3C x 2.5 sq. mm. 2XWY/2XFY Cable (For Outdoor light) 200 Mtr 80.00 6.00 86.00
Cable Length is Approx. Provide as per Actual Site
4.1.7 2C x 2.5 sq. mm. 2XWY/2XFY Cable ( for 1nos. APFC CT & 300 Mtr 165.00 10.00 175.00
X'mer marshaling box Single Phase Supply, for level switch)
Cable Length is Approx. Provide as per Actual Site
4.1.8 5C x 1.5 sq. mm. 2XWY/2XFY Cable (For 1 Nos. Dewatering 150 Mtr 120.00 10.00 130.00
Cable Length is Approx. Provide as per Actual Site
4.1.9 7C x 1.5 sq.mm. 2XWY/2XFY Cable (For Each Motor LCS with 250 Mtr 101.00 12.00 113.00
Cable Length is Approx. Provide as per Actual Site
Cable Length is Approx. Provide as per Actual Site
4.1.11 12C x 2.5 sq.mm. 2XWY/2XFY Cable (For Actuator LCS of 100 Mtr 373.00 17.00 390.00
Each Main Pump )
Cable Length is Approx. Provide as per Actual Site
4.1.12 10Tride x 1.0 sq.mm. individual triad and overall shielded with 250 Mtr 430.00 30.00 460.00
aluminum mylar tape Signal Cable for RTD & BTD of motor
(1Run Motor to S/S Panel)
Cable Length is Approx. Provide as per Actual Site
4.2.1 CABLE END TERMINATION AND CONNECTION: 4 Nos. 860.00 - 860.00
SITC of Double compression Weather proof type Ni-Plated brass
cable glands and crimping type Bimetalic lugs / sockets with
necessary tools and equipments as specified in specifications and
The glands and lugs / sockets shall be suitable for cable size and
type mentioned below & as per specificaitons.
1) Earthing the glands and armouring with earthing clamp and
jumper and also connecting to common earth bar.
2) The job also includes, if necessary, supply & fixing of
extension busbar of same material on MCCB or panel board
terminal / connector to connect more than one no. of parallel
cables or to connect higher size cable to lower size unit. The job
also includes earthing the glands and armour of the cable with
common earth bar or flexible copper mesh.(Cable termination
qty. shall be as per site requirement)
3.5C x 240 sq. mm. A2XFY Cable (2 Runs for Tr. 1to PMCC
4.2.2 3.5C x 95 sq. mm. A2XFY Cable (1 Run for each APFC Panel) 2 Nos. 428.00 - 428.00
4.2.3 3C x 150 sq. mm. A2XFY Cable (1 Runs for each Pump-Motor) 6 Nos. 496.00 - 496.00
4.2.4 4C x 6 sq. mm. A2XFY Cable (For WR-DB with TPN MCB at 10 Nos. 111.00 - 111.00
Sump & Pump House, Outdoor LDB, Indoor LDB, 1nos.
4.2.5 4C x 2.5 sq. mm. 2XWY/2XFY Cable (For TPN MCB at PMCC 30 Nos. 77.00 - 77.00
room & Pump house maintenance floor & Pump House floor,
Motor Operated Valves)
4.2.6 3C x 2.5 sq. mm. 2XWY/2XFY Cable (For Outdoor light ) 60 Nos. 76.00 - 76.00
4.2.7 2C x 2.5 sq. mm. 2XWY/2XFY Cable (For Each Motor space 32 Nos. 75.00 - 75.00
heater(as required), for 1nos. APFC CT & X'mer marshaling box
Single Phase Supply, for level switch)
4.2.8 5C x 1.5 sq. mm. 2XWY/2XFY Cable (For 1 Nos. Dewatering 6 Nos. 150.00 - 150.00
4.2.9 7C x 1.5 sq.mm. 2XWY/2XFY Cable (For 3Nos. Each Motor 16 Nos. 89.00 - 89.00
LCS with Ameter)
4.2.10 10C x 1.5 sq.mm. 2XWY/2XFY Cable 8 Nos. 185.00 - 185.00
4.2.11 12C x 2.5 sq.mm. 2XWY/2XFY Cable (For Actuator LCS of 3 16 Nos. 129.00 - 129.00
4.2.12 10Tride x 1.0 sq.mm. individual triad and overall shielded with 18 Nos. 185.00 - 185.00
aluminum mylar tape Signal Cable for RTD & BTD of motor
(1Run Motor to S/S Panel)
SITC of GI ladder type cable trays with side channels of size -
x 15 x 15 mm/ 100 x 15 x 15 mm & rungs of size - 35 x15 x
mm spaced at 250 mm apart, fabricated from 2 mm thick sheet
steel in standard length of 2.5 meter, duly hot dipped galvanized
after fabrication as per IS 2629- 1989/ IS 4759-1984 including
accessories such as coupler plates/ fish plates, bends, tees,
reducers, elbows, covers and electro- galvanized hardware etc,
erected on existing support as per specification and instruction of
engineer in charge.
300 x 100 mm - Ladder type ( Tray RMT is Approx. Provide
as per Actual Site Requirements.)
5.1.2 150 x 100 mm - Ladder type ( Tray RMT is Approx. Provide 100 Mtr 365.00 37.00 402.00
as per Actual Site Requirements.)
5.2.1 Supply & laying GI perforated type cable trays with returned 100 Mtr. 269.00 27.00 296.00
edge/ flange, fabricated from 2.0 mm thk sheet steel in the
standard length of 2.5 mtrs, duly hot dipped galvanized after
fabrication as per IS 2629-1989 / IS 4759-1984 including
accessories such as coupler plates/ fish plates, bends, tees,
reducers, elbows, covers and electro-galvanized hardware etc,
erected on existing support as per specification and instruction of
engineer in charge.
150 x 35 mm x 2.0 mm thick ( Tray RMT is Approx. Provide
as per Actual Site Requirements.)
5.2.2 100 x 35 mm x 2.0 mm thick ( Tray RMT is Approx. Provide 100 Mtr 207.00 21.00 228.00
as per Actual Site Requirements.)
5.3.1 Cable Trench, Laying & Installation of Cable: Making cable 50 Mtr - 46.00 46.00
trench in soft soil of suitable width of 90cms deep for laying
cable all over the run and back filling the same and making the
surface as normal ground as per IS & Specification. (For laying
HT & LT cable in ground)
5.3.2 Cable Covering in Trench: Cable Covering with second class 50 Mtr. 102.00 31.00 133.00
bricks or cement tiles laid cover the cable crosswise & also on
both side with covering of 7.5cms. Layer of sand above & below
cable (16 bricks per meter.) as per IS & Specification. (For HT
& LT cable trench)
5.4.1 Supply, laying and erection of 120 mm approved make Double 100 Mtr 127.00 9.00 136.00
Walled Corrugated pipes (DWC) of polyethelene (confirming to
IS 14930 II) with necessary connecting accessoies of same
material at required depth for laying of cable below ground / road
surface for enclosing cable and back filling the same to make
ground as per original. (For HT & LT cable).
5.4.2 Supply, laying and erection of 90 mm approved make Double 100 Mtr 86.00 9.00 95.00
Walled Corrugated pipes (DWC) of polyethelene (confirming to
IS 14930 II) with necessary connecting accessoies of same
material at required depth for laying of cable below ground / road
surface for enclosing cable and back filling the same to make
ground as per original. (For Pump cable)
5.4.3 Supply, laying and erection of 50 mm approved make Double 100 Mtr 53.00 9.00 62.00
Walled Corrugated pipes (DWC) of polyethelene (confirming to
IS 14930 II) with necessary connecting accessoies of same
material at required depth for laying of cable below ground / road
surface for enclosing cable and back filling the same to make
ground as per original. (For LT cable).
6.1.1 CHEMICAL EARTHING SYSTEM 2 Nos 9,916.00 573.00 10,489.00
SITC of Maintenance free chemical earthing (copper) with
earthpit of minimum bore size dia. 225mm Safe Earthing
Electrode consisting Pipe-in-Pipe Technology as per IS-
3043:1987 /Tech spec. made of corrosion free Pipes having Outer
pipe dia of 48 mm having (plating thickness as per IS) copper
plating, Inner corrosion free Hot dip galvanised (plating
thickness as per IS) pipe dia of 26 mm with copper flat strip type
connection terminal 14mm dia with constant ohmic value
surrounded by highly conductive corrosion resistant chemical
compound with high charge dissipation suitable for electrical
installation & of 3Mtr. length of Pipe with two nos. 25Kg. bag of
Back filling compound.NOTE: Earthing Resistance value & date
shall be painted on the chamber cover.(2 nos.Each for neutral of
6.1.2 SITC of chemical earthing with earthpit of minimum bore size 6 Nos 6,643.00 382.00 7,025.00
dia. 225 mm Safe Earthing Electrode consisting Pipe-in-Pipe
Technology as per IS-3043:1987 made of corrosion free G.I.
Pipes having Outer pipe dia of 80 mm having 80-200 Micron
galvanising, Inner pipe dia of 40 mm having 200-250 Micron
galvanising or copper coated solid steel road / flat strip type
connection terminal 14mm dia with constant ohmic value
surrounded by highly conductive corrosion resistant chemical
compound with high charge dissipation suitable for electrical
installation of 11 kV & 440V of 2 Mtr. length of Pipe with one
no. 25Kg. bag of Back filling compound.
(2nos. Each for body of Tr.1 , PMCC And Motor and other
Electrical Equipments )
6.2.1 SITC of 50mm(w) x 6mm(T) etc. sizes as required, HOT deep 250 Kg 60.00 17.00 77.00
GI Strip including supply & fixing using GI spacers, saddles
when laid inside the building and inclusive of excavation &
refilling of earth when laid outside the building &
interconnection with earth pit & all electro-mechanical
(50X6 G.I Strip wt.2.3 kg/m, 2.3x Mt.=Ans kg.)
( Transformer, LT PaneL etc.)
6.2.2 Supply, laying and erection of 25 mm(w) x 6mm(T) etc. sizes as 90 Kg 60.00 17.00 77.00
required, HOT dip galvanized GI Strip including supply &
fixing using GI spacers, saddles when laid inside the building
and inclusive of excavation & refilling of earth when laid outside
the building & interconnection with earth pit & all electro-
mechanical equipments.
(25X6 G.I Strip wt.0.6 kg/m, 0.6x 150 Mt.=90kg.)
6.2.3 Supply, laying and erection of 40mm(w) x 6mm(T) etc. sizes 112 Kg 753.00 34.00 787.00
Copper Strip including supply & fixing of bolts, saddles when
laid inside the building and inclusive of excavation & refilling of
earth when laid outside the building & interconnection with earth
pit & Tr. nutral.
6.2.4 Supply, laying and erection of 40 mm(w) x 6 mm(T) etc. sizes as 188 Kg 60.00 17.00 77.00
required, HOT dip galvanized GI Strip including supply &
fixing using GI spacers, saddles when laid inside the building
and inclusive of excavation & refilling of earth when laid outside
the building & interconnection with earth pit & all electro-
mechanical equipments.
(40X6 G.I Strip wt1.88 Kg/m, 1.88 x 100=188Kg.)
6.2.5 SITC of HOT Dip Galvanized iron strip wire 8 SWG (For LDB, 21 Kg 60.00 17.00 77.00
PDB, LCS, St.Light Pole, etc.)
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 200Mt.=21)
7.1.1 INTERNAL WIRING 200 Mtr 98.00 12.00 110.00
SITC of Mains & outlet points wiring with 1.1 kV grade FRLS
PVC insulated ISI marked flexible stranded copper conductor
wires with medium class min. 25mm. dia. Rigid PVC pipe
and accessories to be erected concealed in / to be run on surface
/ wall / ceiling with following sizes as mentioned below. The unit
rate wirings shall be with connector, PVC junction box, wires,
holder, ceiling rose, angle holder, switch, sockets, switch
board, brass chromium / cadmium plated machine screws, phase
and neutral wires, green Earth continuity wires etc. as required to
complete wiring from LDB panel to the final outlet termination
points. The wiring shall be as per IS:732, IS:4648 and as
per tender specification / IS.
(a) SITC of Mains wiring with 3 wire 1.5 sq.mm .
7.1.2 (b) SITC of Mains wiring with 3 wire 2.5 sq.mm as per tender 200 Mtr 116.00 12.00 128.00
specification & IS.
7.1.3 (c) SITC of Mains wiring with 4 wire 1.5 sq.mm as per tender 200 Mtr 106.00 12.00 118.00
specification & IS.
7.1.4 (d) SITC of Mains wiring with 4 wire 2.5 sq.mm as per tender 200 Mtr 139.00 12.00 151.00
specification & IS.
7.2.1 SITC of Point wiring for Light / fan / Bell / Primary Point with 50 Nos. 356.00 59.00 415.00
2nos. 1.5 sq. mm & earth wire of 1.5 sq. mm (green) both are of
ISI marked 1.1 kv grade FRLS PVC insulated multistrand copper
wires, pipe to be erected concealed in flushed on wall /
ceiling, complete with 6A Tissino Type ISI marked flush type
switch / bell push & accessories erected on metal / PVC Box
covered with 3 mm thick PC (Polycarbonate) / Acrylic sheet
with necessary lamp holder / ceiling Rose / H. D. connector as
directed with medium class Rigid PVC pipe & accessories.
7.2.2 SITC of 6A independent Plug with 2 nos. 1.5 sq.mm Cu. Mains 4 Nos 534.00 59.00 593.00
size wiring & earthwire of 1.5 sq.mm (green) both are of .ISI
marked 1.1 KV Grade FRLS PVC insulated multi strand copper
wiress with medium class rigid pvc pipe erected with ISI
marked 3 / 5 Pin socket and 6A Modular type switch and
accessories with earth continuity of following type erected on
PVC / Metallic/Wooden box, single mounting base frame
covered with textured/metallic/white front plate modules erected
on / in wall / ceiling as per pipe erected. with necessary ceiling
rose / H.D.Connector as directed.( 4 nos. at Pump House cum LT
7.2.3 SITC of One 300/380 mm dia. Ex fan 16A independent Plug 4 Nos 732.00 50.00 782.00
point near Ex. Fan with 2nos. 4 sq.mm Cu. Mains size
wiring & earthwire of 1.5 sq.mm (green) both are of ISI marked
1.1 KV grade FRLS PVC insulated multistrand copper wires with
medium class Rigid PVC pipe and accessories to be erected
complete with Modular type switch & 5 pin Plug erected on PVC
/ Metallic/Wooden box covered with appropriate front plate
modules erected on / in wall / ceiling as per pipe erected with
following type of accessories. Plug point shall be near Ex.Fan.
(For 4 Nos. Pump House Room )
7.2.4 SITC of 5/15A independent Plug with 2nos. 4 sq.mm Cu. Mains 4 Nos 732.00 50.00 782.00
size wiring & earthwire of 1.5 sq.mm (green) both are of ISI
marked 1.1 KV grade FRLS PVC insulated multistrand copper
wires with medium class Rigid PVC pipe and accessories to be
erected on wall / ceiling, complete withModular type switch &
pin Plug erected on PVC / Metallic/Wooden box covered with
appropriate front plate modules erected on / in wall / ceiling as
per pipe erected with following type of accessories.
(For Pump House cum LT Room)
7.2.5 SITC of Single Phase 20A 3 Pin Metal clad Industrial Type 3 Nos. 800.00 45.00 845.00
Socket with plug top and 20A SPMCB, suitable for flush
mounting, in 16 SWG MS box of suitable size and covered with
3 mm thick electrical grade hylam sheet or eqivalent ISI marked
Electrical grade bakelite sheet and earthing with 2.5 sq.mm
insulated copper wire run inside the conduit including
interconnections etc. complete as required.
(For Pump House cum LT Room)
7.2.6 SITC of 415V Four Pole MCB Switch (C Curve) having 10KA 3 Nos 564.00 26.00 590.00
breaking capacity & confirms to IS:8828 having capacity, 32A,
(For Pump House / LT Room / Elect. Hoist at Pump House)
7.2.7 SITC of 3 watts LED Lamps integral type,cool white with PC 2 Nos. 50.00 19.00 69.00
diffuser suitable for LAMP holder.
(For Panel room/ Pump house )
7.3.1 1200 mm sweep ceiling fan, capacitor type, having double 2 Set 1,530.00 51.00 1,581.00
ball bearing 450mm down rod, canopies, shackle, rubber bush,
blades, electronic speed regulator, suitable to operate on
230V,50Hz AC supply conforming to IS: 374/1979.Fan shall be
painted with white colour.
(For LT Panel Room)
7.3.2 380 mm sweep 1400 R.P.M exhaust fan, capacitor type, 4 Nos. 3,005.00 47.00 3,052.00
having double ball bearing, M.S.blades, mounting frame,
forearms, suitable to operate on 230V,50 HZ AC supply
conforming to IS: 2312.Fan shall be painted with epoxy grey
colour controlled by one 6 A flush type switch on board and 6A
plug point near Ex. fan. With Bird Net
(For Pump House Room )
8.1.1 LED LIGHT FIXTURES: 10 Nos 504.00 26.00 530.00
SITC of Indoor wall mounting LED indoor fittings with LEDs
of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB,
with housing used as a heat sink shall be made of thick sheet Steel
conforming to IS: 513/CRCA polyester powder coated and high
U.V. & corrosion resistance with diffuser and/or Polycarbonate
optics with company mark/name 120 to 300 V,Power Factor
more than 0.9, THD < 10 %, CCT 4000 K to 6500K, Uniformity
ratio >0.7, Luminaire efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80 Certificates)
36 Watt or up to 25% higher wattage Tube Light with
integral / non-integral driver, Surge-4KV, IP-20, 4 feet, Cat-
(For LT Room / Pump House)
8.2.1 SITC of Surface mounted LED Flood light fittings with High 10 Nos. 5,015.00 128.00 5,143.00
power White LEDs wattage of 1Watt and above assembled on
single MCPCB, efficiency more than 130 lm/w and corrosion
free High pressure die cast aluminum housing with smooth finish
powder coated and heat sink extruded aluminium with diffuser
and Polycarbonate optics/ lenses with company mark/name
engraved or embossed120 to 300 V,Power Factor more than 0.95,
THD < 10 %, CCT5000 K to 5700K,Uniformity ratio >0.45,
Luminaire efficacy> 85 lumens/watt . LEDdriver efficiency >
%.( Each fittings required LM-79 & LM-80 certificates)40 Watt
Flood Light (IP-65), Surge -4KV Cat-III(for pump house cum
8.2.2 SITC of 'B' class galvanised iron pipe 32 mm outside dia 45 10 Nos. 297.00 43.00 340.00
cmslong duly welded on 20 cms x 20 cms x 3 mm thick M.S.
base plate, erected on wall or corner for mounting luminaire with
necessary hardware materials duly painted for wall mounting
indoor flood light fixtures on Wall of Buildings.
8.3.1 EXTERNAL LED LIGHT FIXTURES & LIGHTING: 12 Nos. 5,858.00 170.00 6,028.00
SITC of Wall mounted 80W LED Outdoor Flood Light
fittings with High power White LEDs wattage of 1Watt and
above assembled on single MCPCB, efficiency more than
lm/w and corrosion free High pressure die cast aluminum
housing with smooth finish powder coated and heat sink extruded
aluminium with diffuser and Polycarbonate optics/ lenses with
company mark/name engraved or embossed 120 to 300 V,Power
Factor more than 0.95, THD < 10 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaire efficacy> 85 lumens/watt .
LED driver efficiency > 85 %. ( Each fittings required LM-79 &
LM-80 certificates)
Flood Light (IP-65), Surge -4KV, 80 watt Cat-III
(12 Nos for Area Lighting)
8.3.2 SITC of 'B' class galvanised iron pipe 32 mm outside dia 45 12 Nos 297.00 43.00 340.00
cms long duly welded on 20 cms x 20 cms x 3 mm thick M.S.
base plate, erected on wall or corner for mounting luminaire with
necessary hardware materials duly painted for wall mounting
indoor & outdoor flood light fixtures on Wall of Buildings.
9.1.1 SAFETY ACCESSORIES 4 Nos 8,560.00 26.00 8,586.00
SITC of following safety accessories complete with necessary
fixing brackets, other accessories and tools etc. as required
to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher of
6.5 kg capacity with necessary clamps made from 50 x 6 mm
M.S. Flat with nut & bolts grouted in wall complete.
9.2.1 Supplying stand first AID box with anticeptic cream, medicine 2 Nos. 297.00 - 297.00
for use on wounds due burn, crepe bandage, guage bandage,
medicated ready to use bandage (Band-aid) adhesive tape for
medicinal user, scissors, anticeptic solution (Savlon or similar)
(All above contents shall be of standard makes)
(For Pump house / LT Room)
9.3.1 Supply & fixing of printed instruction (First Aid) Chart both in 2 Nos. 123.00 6.00 129.00
English and Gujarati and duly framed with front glasses, for
treatment of person suffering from electric shock.
9.4.1 Supplying & fixing of FIRE bucket round bottom of 9 litres 4 Set 212.00 - 212.00
capacity made out of 24 guage G.I. sheet with extra handle at
bottom duly painted white inside and Red outside with FIRE
mark, filled with dry sand and kept on stand provided or hung on
9.5.1 Supplying and erecting floor mounting stand for keeping four 1 Nos. 890.00 43.00 933.00
nos. of FIRE buckets comprising 1500 mm in length, 900 mm
height frame made out of 30mm X 30 mm X 4 mm angle iron
with cross supports for legs, welded with 4 hooks and duly
painted with one coat of red lead and two coats of approved
enamelled silver paint.
9.6.1 Supply and fixing of 30 W fluorescent lamp operated emergency 1 Nos. 6,234.00 85.00 6,319.00
light with maintenance free battery for 3 hours operation during
mains power failure.LED Portable/Rechargeable flood light
having die - cast aluminium enclosure designed for maximum
thermal efficiency of 130lm luminous efficiency at voltage
supply between 140-270V AV/12V DC at operating temperature
of -20 degree to 60degree celcius with battery back up 3-4hrs
9.7.1 Supply and laying of Synthetic Insulating Mat of Class - A of 12 Mtr 763.00 - 763.00
min. thickness 2 mm as per IS:15652 and with good electrical
insulation property for 1.1KV/3.3KV as per site requirement. .
(for PMCC & APFC etc. Panels)
9.8.1 Providing pair of rubber hand gloves ISI make suitable for 2 Nos. 212.00 - 212.00
working on 22 KV supply
10.1.1 MISCELLANEOUS: 500 kg 64.84 - 64.84
Providing, Supply of Structure Steel at site of work with freight,
loading, unloading carting, etc. including all taxes and duties
complete such as joints, channels, angles, Iron Rails,
ISA/ISMC/ISMB/MS flat, Plates, Chequered plates (below
10mm thickness) etc. required for support structure of Elecrto-
Mechanical equipments etc. for support on floor / wall / beam /
brackets etc. as per tender and IS.
10.1.2 Labour Charges for lowering, laying, Fixing with fabrication 500 kg - 11.36 11.36
various size section of MS such as joints, channels, angles, Iron
Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered plates etc
Complete with two coats of red oxide and two coats of approved
colour shade of epoxy paint as per relevant IS and as per
11.1.1 LIASONING CHARGES FOR OBTAINING POWER / 1 Ls 15,000.00 - 15,000.00
Liasoning Charges for obtaining N.O.C from Electrical Inspector
/ Statutory authority for Power / Ele. Installation. (Fees shall be
paid by tenderer for obtaining N.O.C. from Electrical Inspector /
Statutory authority on behalf of client and shall be reimbursed on
submission of orignial receipt to Client). Liasoning Charges shall
include preparing required attasted documents & drawing for
obtaining NOC on behalf of client (Applicable Fees / deposits
shall be reimburse by Client).
12.1.1 Ladder: Ladder shall be made out of light aluminium allow 1 Nos. 6,000.00 - 6,000.00
of good strength. They shall be of step ladder, foldable, self
supportig type with sperader of metalic angles or high
Ladder: As per S.R. No.2.(i) 3 Meter long
12.1.2 Ladder: As per S.R. No.2.(ii) 6 Meter long 1 Nos. 10,000.00 - 10,000.00
TOTAL ESTIMATE OF ELECTRICAL WORK (WITHOUT GST)
Name Augmentation work with SITC of Pumping Machinery with related Mechanical, Electrical,
of Instrumentation and Miscellaneous works for Gomtipur water Distribution Station Besides
Work Gomtipur Drainage in Gomtipur Ward of East Zone of AMC.
Sr. Unit Rate Total Amount
Sr. Unit Rate Total Amount
Existing 550 m3/hr. HSCF Pump Motor set with All 3 Nos. -
1 Pumping Machinery Like Valves, Pipes, NRV,
Expansion Bellow etc.
2 Existing All Switch Gear Panel and MCC Panel 1 Lots -
3 Existing APFC Panel. 1 Nos. -
4 Existing Manual chain Hoist 1 No. -
5 Removed L.T Cables as per Site Availability 1 Lot. -
TOTAL OF BUYBACK AMOUNT (In Rs.) -
Notes: The rate of the items shall be deducted from the capital cost of the tender and contractor shall
carryout all items.
AMC will take final decision whether to sell item or not. If AMC does not sell particular item, the
bidder will not get rebate amount of that item.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01 Volume-I_Technical Bid-Part-1 Gomtipur drainage WDS (1).pdf
ALL DRAWING.pdf
Financial Bid- Gomtipur Drainage WDS.pdf
Download all tender documents and submit your bid