CWE AF SECUNDERABAD
MAINTENANCE AND REPAIRS OF EOT AND HOT CRANES, FIRE FIGHTING LINES, CONTROL VALVES, HYDRANTS, HOSE REELS AND FIRE ALARM SYSTEM AND CONNECTED ITEMS AT AFS BIDAR UNDER GE (AF) BIDAR
2024_MES_664265_2
85622/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF BIDAR
As per NIT
9 documents required · 9 mandatory
₹500
GE AF BIDAR
₹69,000
Yes
4 Nov 2024
9 Sept 2024
2 Oct 2024
9 Sept 2024
30 Sept 2024
16 Sept 2024
9 Sept 2024 - 13 Sept 2024
Amount
Comprehensive maintenance of EOT Crane, of 5 ton capacity of bay length 30.0 metres, span 7.0 metres and height of lift 4.0 metres from floor level including monthly maintenance, load test (verticality test and deflection test) and maintenance of crane panel, thrusher brakes, electric motors, steel ropes, crane cabin, limit switches, all electrical and control cables, bus bars, gear oil, pendants along with push buttons etc., once in a month complete all as specified and as directed.
Comprehensive maintenance of EOT Crane, of 2 ton capacity of bay length 12.0 metres, span 4.0 metres and height of lift 4.0 metres from floor level including monthly maintenance, load test (verticality test and deflection test ) and maintenance of crane panel, thrusher brakes, electric motors, steel ropes, crane cabin, limit switches, all electrical and control cables, bus bars, gear oil, pendants along with push buttons etc, once in a month complete all as specified and as directed.
Comprehensive Maintenance of EOT Crane, of 1.5 ton capacity of bay lenth 15.0 metres, span 4.0 metres and height of lift 4.0 metres from floor level including monthly maintenance, load test (verticality test and deflection test ) and maintenance of crane panel, thrusher brakes, electric motors, steel ropes, crane cabin, limit switches, all electrical and control cables, bus bars, gear oil, pendants along with push buttons etc., once in a month complete all as specified and as directed.
NOTE FOR ITEM Nos : 1,2 & 3 Cost of bearings, fixed/finger contacts, spare kits for starters, renewal of unserviceable gears, greasing to wheel drum and the ropes, renewal of push buttons, limit switch, control panel fuse, thermal relay, under voltage relay, power contactors, internal wiring of LT panel board, interconnections of other miscellaneous spares not covered under the scope of work but required for complete satisfactory comprehensive maintenance of the crane shall be deemed to include in the unit rate quoted.
Labour element of spares listed below as SUPPLY ONLY also deemed to be included in the unit rate quoted. The contractor has to employ minimum one experienced and trained electrician having full knowledge on cranes and one helper to carry out the regular maintenance once in a month or as required for smooth and effective functioning of Cranes and the cost is deemed to be included in the unit rate quoted by the contractor.
Any complaints regarding breakdown will be attended with in 24 hours failing which an amount of Rs.522/per day for Electrician and Rs.370/per day for Helper as per rates circulated by Labour Commissioner will be deducted from the RAR due to the contractor. Technician is responsible for cleaning and maintenance for EOT/HOT cranes under monthly maintenance. Necessary tools & plants like ladder etc., required to attend the break down if any, shall be provided by the contractor and the cost is deemed to include in the unit rate quoted. The contractor should submit the identity proof of Technician/Person visiting the site and also responsible for the integrity of the personnel attending the break down and monthly visits. Full load test with 10% over load to be carried out once in the currency of the contract and the rates will be measured and paid under respective item accordingly. Make : Balaji Engineering Works / Tojym Steel Products / S K Cranes
M & L for carrying out full load test (with 10% extra load) of EOT Crane, of 5 ton capacity including carrying out verticality test and deflection test in the presence of the user complete all as specified and as directed.
M & L for carrying out full load test (with 10% extra load) of EOT Crane, of 2 ton capacity including carrying out verticality test and deflection test in the presence of the user complete all as specified and as directed.
M & L for carrying out full load test (with 10% extra load) of EOT Crane, of 1.5 ton capacity including carrying out verticality test and deflection test in the presence of the user complete all as specified and as directed. NOTE FOR ITEM NOS: 4 ,5 & 6 (i) Cost of T&P required is deemed to be included in the unit rate quoted. (ii) Loads required for testing shall be arranged by the contractor and cost for the same is deemed to be included in the unit rate quoted. (iii) The contractor shall arrange the sealing with "O" ring and "D" shackles for connecting the loads and the cost deemed to be included in the unit rate quoted. Make : Balaji Engineering Works / Tojym Steel Products / S K Cranes
Supply only gear oil, grade 140 complete all as specified and as directed
Taking up or down MS ERW steel tubing of 150 mm dia with fittings complete including cutting the pipe complete all as specified and as directed. Note : 1. Excavation and RFR will be measured and paid seprately under the respective items.
Supply and fix MS ERW pipe line suitable for existing fire fighting system of dia 150 mm bore , bearing ISI Mark , along with the fittings in trenches complete all as specified and as directed. Make : Jindal /Tata / BST / Advance Steel Tubes
Supply and fix MS ERW pipe line suitable for existing fire fighting system of dia 200 mm bore , bearing ISI Marke , along with the fittings in trenches complete all as specified and as directed. Make : Jindal /Tata / BST / Advance Steel Tubes
Supply and fix MS ERW pipe line suitable for existing fire fighting system of dia 300mm bore , bearing ISI Marke , along with the fittings in trenches complete all as specified and as directed. Make : Jindal /Tata / BST / Advance Steel Tubes
M&L painting with enamelled paint of postal red colour on iron/steel surface of any description over 10 cm in width or girth, not other wise described including preparation of old painted surface for free from dust and deposits complete all as specified and as directed. Make- Asian/Nerolac/Berger.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for and taking out / for laying underground pipes extra and getting out in soft / loose soil, complete all as specified and as directed.
Returning filling, incl spreading, levelling, watering & well ramming in layers n.exc 25 cm in soft/loose soil, complete all as specified and as directed.
Removing excavated soil to a distance not exc 50 m & depositing where directed at a level not .exc 1.5 m above the starting point complete all as specified and as directed.
Disconnection and removing the unservicable analogue Addressable flame detector and Supply, Installation, Testing & Commissioning of Analogue Addressable flame detector with UV/IR detection. LPCB approved,FM,CE complaince,complete all as specified and as directed. Make : Honey well,Siemens,Hochiki,Notifier,Ceasefire,Morley,AGNI
Disconnection and removing the unservicable Addressable manual call point and Supply and fixing of Addressable manual call point resettable type including transparent safety cover with back box complete all as specified and as directed. Make :Notifier
Disconnection and removing the unservicable Addressable electronic sounder cum strobe and Supply and fixing of Addressable electronic sounder cum strobe with back box,32 tone selction, EN 54 complete all as specified and as directed. Make: Notifier
Disconnection and removing the unservicable Siren and Supply, Installation, testing & commissioning of Siren 2.0 KM Range Single Honeywell stage complete all as specified and as directed. Make :Khaitan
Disconnection of duracell Lithium CR 123A batteries from the Sensor and Supply 3 Volt lithium battery complete all as specified and as directed. Make :DURACELL
Disconnection and removing the pipe line connections connected to the Diesel Engine of Capacity 125 KW /167 HP (at Parachute Building), Type 4R 1040, Make :- KOEL unit carefully for finding out the defects and Servicing/ repairing the same and including Replacement of unserviceable Fuel Filters, Air filters, Oil filters, Fan belt, Hose Pipe sets, Engine Oil, Coolant, Bearings complete and refixing the same in its original position couple with the pumpset and connecting the pipe line testing and commisioning complete all as specified and as directed. Note : (i) All the misc items and Fuel Filters, Air filters, Oil filters, Fan belt, Hose Pipe sets, Engine Oil, Coolant, Bearings not covered under the scope of work but required for satisfactory completion of job is deemed to be included in the unit rate.
All as per Item No 22 here-in-above but of capacity 58 KW/79 HP (at New ATC Building) complete all as specified and as directed.
All as per Item No 22 here-in-above but of capacity 44.2KW/60 HP (at Air Field FF Pump house) complete all as specified and as directed.
Disconnection and removing the Fire Fighting Pumps of Capacity 167 to 170 HP, Head 90 Mtr, Discharge 4590 LPM connected to the Diesel Engine of Capacity 125 KW /167 HP (at Parachute Building) alongwith connections and overhauling the same complete including reneuwal of worn out bearings, metalling & Polishing the shaft, Coupling Unit, Oil Seal, Gland, Impeller Sleeves, Impeller lock nuts, complete and re-fixing the pump in its original postion after completion of repairs and overhauling connecting the pipelines testing and commisioning complete all as specified and as directed. Note : (1) All the misc items not covered under the scope of work but required for satisfactory completion of job is deemed to be included in the unit rate.
All as per Item No 25 here-in-above but of capacity 50 to 60 HP (at Air Field FF Pump house) complete all as specified and as directed.
All as per Item No 25 here-in-above but of capacity 79 HP (at New ATC Bldg) complete all as specified and as directed.
Disconnection and removing the Fire Fighting Jockey Pumpset of Capacity 10 to 15 HP, 440V connected to the Fire Fighting system (at Parachute Building, Air Field FF Pump house & New ATC Bldg) alongwith connections and overhauling the same complete including reneuwal of worn out bearings, metalling & Polishing the shaft, Coupling Unit, Oil Seal, Gland, Impeller Sleeves, Impeller lock nuts complete and re-fixing the pump in its original postion after completion of repairs and overhauling connecting the pipelines testing and commisioning complete all as specified and as directed. Note : (1) All the misc items not covered under the scope of work but required for satisfactory completion of job is deemed to be included in the unit rate.
Disconnection and taking down unserviceable double headed yard hydrant valve 63mm and replacing the unserviceable End Cap, Lugs Grip and Rubber Washer, checknut and Polishing the hydrant carefully and refixing the same after repairs in its original position complete all as specified and as directed. Make :- Getec/Newage/Padmini
All as per Item No 29 here-in-above but Single headed yard hydrant valve 63mm dia complete all as specified and as directed.
Disconnection and taking down unserviceable double headed yard hydrant valve 63mm and S&F New Double headed yard hydrant valve 63mm instantatenous with operating wheels, end caps and securing chains ISI Marked complete alongwith necessary fixing materials requried for completion of job complete all as specified and as directed. Make :- Getec/Newage/Padmini
All as per Item No 31 here-in-above but Single headed yard hydrant valve 63mm dia complete all as specified and as directed.
Taking down unserviceable hose reel drum alongwith hose including S&F new hose reel drum with 19mm dia 36.0 Mtr long re-inforced rubberised fabric hose including 6.35mm dia nozzle with a ball valve swing type, recessed as per sample complete, hose (BIS mark) conforming to IS : 636, type II and complying to IS : 903 as replacement at requirement basis of fire fighting area complete all as specified and as directed. Make :- Getec/Newage/Padmini
Taking down unserviceable corroded/broken Hose Box and S&F new Hose Box made of 18 gauge MS Sheet 800 x 600 x 250mm with double door with 4mm thick glass and door frame made of 16 gauge MS Sheet painted with fire red oxide and brilliant white inside the box complete all as specified and as directed. Make :- Getec/Newage/Padmini
Disconnection and removing unserviceable sprinklers from any height of the building carefully and S&F New Sprinkler universal type, quick/ early response type as per IS : 15105/TAC guidelines, 68 degree temperature rating complete in Hangers and other technical buildings complete all as specified and as directed. Make :- 7 Star/Tyco/Getech
Disconnection and removing the AFPP Oscillating type system Foam Monitor of capacity not less than 1800 LPM and servicing/repairing of the Foam Monitoring unit complete including renewal of unserviceable Parts, check nuts, monitoring system, cover, proposing devicer by specialist and dual jet and re-fixing the same in its original position complete all as specified and as directed. Make :- Getec/Newage/Padmini
Disconnection and removing the unserviceable AFPP Oscillating type Foam Monitor system S&F New AFPP Oscillating type foam monitor system unit of capacity not less than 1800 LPM complete all as specified and as directed. Make :- Getec/Newage/Padmini
Disconnection and removing the AFPP Oscillating type system Water Monitor of capacity not less than 1800 LPM and servicing/repairing of the Water Monitoring unit complete including reneuval of unserviceable Parts, check nuts, monitoring system and cover and re-fixing the same in its original position complete all as specified and as directed. Make :- Getec/Newage/Padmini
Disconnection and removing the unserviceable AFPP Oscillating type Water Monitor system S&F New AFPP Oscillating type Water monitor system unit of capacity not less than 1800 LPM complete all as specified and as directed. Make :- Getec/Newage/Padmini
Disconnection and removing the unserviceable/ broken Stainless Steel Spindle along with the check nuts & gate from the Sluice valve of Size 80mm dia and M&L for New Spindle of same size & capacity with Brass/Stainless Steel Check nuts including polishing, mechining, threading & necessary lathe work complete all as specified and as directed.
All as per item No 40 here-in-above but of capacity 100mm dia sluice valve complete all as specified and as directed.
All as per item No 40 here-in-above but of capacity 150mm dia sluice valve complete all as specified and as directed.
Disconnection and removing the unservicable Sluice Valve 80mm dia and S & F Sluice Valve 80mm dia, IS-14846, PN 1.6 brass/stainless steel spindle with hand wheel head, screwed both ends for GI Pipe 80 mm dia complete all as specified and as directed. Make: Kirlosker/Upadhyaya/RMCO/Kartar
All as per item No 43 here-in-above but of capacity 100mm dia sluice valve complete all as specified and as directed.
All as per item No 43 here-in-above but of capacity 150mm dia sluice valve complete all as specified and as directed.
Disconnection and removing the unservicable Non Return Valve 150mm dia and S & F Non Return Valve 150mm dia, both end flanged including provn of new gasket and nuts, bolts and washers and fixed complete all as specified and directed. Make: Kirlosker/Upadhyaya/RMCO/Kartar
Disconnection and removing the unservicable CI Foot Valve and S & F CI Foot valve 100mm dia with all fittings including flanges, leather washer, fasteners for fitting such as necessary size nut bolt and washer, rubber packings / joining materials complete including taking down the old unsv one complete all as specified and as directed. Make: Kirlosker/Upadhyaya/RMCO/Kartar
All as per item No 47 here-in-above but of capacity 150 mm dia CI Foot valve complete all as specified and as directed.
All as per item No 47 here-in-above but of capacity 200 mm dia CI foot valve complete all as specified and as directed.
Disconnection and removing the unservicable CI Butterfly Valve 80mm dia and S & F CI Butterfly Valve 80mm dia, (Wafer Type) PN 1.6 brass/stainless steel spindle with hand wheel head, screwed both ends, ISI Marked complete all as specified and directed. Make: Kirlosker/Upadhyaya/RMCO/Kartar/Audco
All as per item No 50 here-in-above but of capacity 100mm dia complete all as specified and directed.
All as per item No 50 here-in-above but of capacity 150mm dia complete all as specified and directed.
All as per item No 50 here-in-above but of capacity 200mm dia complete all as specified and directed.
Disconnection and removing the U/S gate valve 50 mm dia and S & F Gun metal globe or gate valve 50 mm dia with iron wheel head, screwed both ends for GI Pipe complete all as specified and directed.
Disconnection and removing the unservicable power contactor carefully from Panel board and S&F new power contactor 160 Amp Capacity , 440 V comprising of all accessories type MNX-110 complete all as specified and as directed. Make : GE /Seimens/L&T.
Disconnection and removing the unservicable power contactor carefully from Panel board and S&F new 3 pole power contactor series CK75CA311 of capacity 185Amp , 440 V comprising of all accessories complete all as specified and as directed. Make : GE /Seimens/L&T.
Disconnection and removing the unservicable power contactor carefully from Panel board and S&F new 3 pole power contactor series CL12A311M of capacity 160Amp , 440 V comprising of all accessories complete all as specified and as directed. Make : GE /Seimens/L&T.
Disconnection and removing the unservicable power contactor carefully from Panel board and S&F new power contactor 25 to 32 Amp Capacity , 440 V comprising of all accessories complete all as specified and as directed. Make : GE /Seimens/L&T.
Disconnection and removing the unservicable Lead Acid Battery and S&F Lead Acid Battery, 12Volt, 180 AH with Initial fully charged alongwith electrolyte and other accessories complete all as specified and as directed. Make :- Exide/Amco/Amron
Disconnection and removing the unserviceable MCCB 63 Amps capacity and supply and fix MCCB 3 pole 16 KA 63 Amps 440 volts MCCB along with fixing arrangements complete all as specified and as directed. Make : L&T or its equivalent in Legrand/ABB
Disconnection and removing the unserviceable MCCB 200 Amps capacity and supply and fix MCCB 3 pole 36 KA 200 Amps 440 volts MCCB along with fixing arrangements complete all as specified and as directed. Make : L&T or its equivalent in Legrand / ABB
Disconnection and removing the unserviceable pressure guage and S&F Pressure gauge 8"dial 0-21 kgs rating ISI Marked complete all as specified and as directed.
Disconnection and removing the unserviceable pressure guage and S&F Pressure gauge 4"dial 0-21 kgs rating ISI Marked complete all as specified and as directed.
Disconnection and removing the unserviceable battery lead connection and M&L for battery connected leads made out of PVC Single core 1100 volts grade bunched copper conductor upto 1.5m long including one end soldered with a copper lug and the other end soldered with a brass terminal along with nut, bolt and washer complete all as specified and as directed.
Disconnection and removing the unserviceable battery lead connection and M&L for battery connected leads made out of PVC Single core 1100 volts grade bunched copper conductor upto 0.6 m long including both end soldered with a brass terminal along with nut, bolt and washer for interconnection of batteries complete all as specified and as directed.
Disconnection and removing the unservicable self starter unit 24 volts capacity carefully from the Diesel engine for 125 KW/58KW finding out the defects and to replace the u/s items such as field coils, bentex, armature solenoid switch etc and refixing the same in its original postion after completion repairs including testing and commissioning complete all as specified and as directed. Make : TVS Lucas/Fenner or as approved by the OEM. Note : Armature and bentex will be measured and paid unde respective item of the BOQ
Disconnection and removing the unservicable self starter unit 12 volts capacity carefully from the Disel engine for 44.2 KW finding out the defects and to replace the u/s items such as field coils, bentex, armature etc and refixing the same in its original postion after completion of repairs including testing and commissioning complete all as specified and as directed. Make : TVS Lucas/Fenner or as approved by the Engr in-charge. Note : Armature and bentex will be measured and paid under respective item of the BOQ
Supply only bentex unit made with brass suitable for 12 volts self starter unit complete all as specified and as directed.
Supply only bentex unit made with brass suitable for 24 volts self starter unit complete all as specified and as directed.
Supply only Armature unit with copper winding suitable for 12 volts self starter unit complete all as specified and as directed.
Supply only Armature unit with copper winding suitable for 24 volts self starter unit complete all as specified and as directed.
Disconnection,Supply and fixing in existing LT panel on load switch fuse unit 200 A 4 pole AC,415 Volt with HRC Fuses without enclosure complete all as specified and as directed . Make :GE/Havells/L&T
Disconnection,Supply and fixing in existing LT panel on load switch fuse unit 400 A 4 pole AC,415 Volt with HRC Fuses without enclosure complete all as specified and as directed. Make :GE/Havells/L&T
Supply and fixing battery charging unit of capacity suitable for 12/24 volts battery and fixing in inside the AMF panel enclosure including taking down U/s battery charging unit complete all as specified and as directed.
Taking down radiators by unscrewing carefully nut bolts, and transporting to workshop for cleaning washing of blocked water cooling pipe and repair and soldeing/ welding if any including necessery hard ware material like rubber bush and taking back to site. Fixing in original portion of the Diesel engine set for capacities of 125 KW to 44.2 KW complete all as specified and as directed. Make :- Kirloskar
Supply and fixing oil pressure guage as per existing sample & capacity including removing old oil pressure gauge complete all as specified and as directed. Make: Yankey/ Pricol
Supply & fixing temprature gauge oil/water in the diesel engine including taking down old temp guage complete all as specified and as directed. Make :- Yankey / Pricol)
Taking down old fuel / Oil pipe line with benjo bolt, supply and fixing new fuel/oil pipe lines (High pressure ruber pipe covered with steel armoured complete all as specified and as directed.
Dismantling the fuel tank and fuel line/pipe complete clean ,replace the broken pipe lines and reconnect the fuel line and refixing the fuel tank in same position complete all as specified and as directed.
Taking down dynamo assembly from engine for repair/replacement of worn out parts and refixing the same including cheking of proper charging of batteries complete all as specified and as directed.
Disconnection and removing the unservicable PCB carefully from Panel board and S&F new PCB 24V DC W305 suitable for Make Kirloskar Diesl enginet or its equivalent complete all as specified and as directed.
Disconnection and removing the unservicable Air vessel and S&F Air Vessel , 300 mm dia, 1 Mtr height, alongwith Auto air release valve spring loaded type complete all as specified and as directed. Make :- Getec / Newage / Padmini
RASI AND COMPANY (BID ID -3106345)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .