| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.8 LAccepted-Finance 101 VRAJ APARTMENT OPP POLICE HEAD QUARTERS SARU SECTION ROAD JAMNAGAR 381008 | JAMNAGAR | 381008 | ₹33.8 L | L1 | Accepted-Finance L1 |
| 2 | L2₹37.8 LRejected-Finance 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | ₹37.8 L | L2 | Rejected-Finance L2 |
| 3 | L3₹38.4 LRejected-Finance INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | ₹38.4 L | L3 | Rejected-Finance L3 |
| 4 | L4₹39.3 LRejected-Finance INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | ₹39.3 L | L4 | Rejected-Finance L4 |
| 5 | L5₹39.9 LRejected-Finance | ₹39.9 L | L5 | Rejected-Finance L5 |
| Sl No | Description | Qty | Unit | jagdish machinery stores L3 | JAYESH TRADING CORPORATION L4 | rajengineers L5 | SURESH ELECTRICALS L2 | M/s SK Traders L1 | MONA GENERATOR SEVICES PVT. LTD. L6 | JAMNAGAR ELECTRIC AND MACHINERY CO L7 | BHAVNA IMPERIAL ENTERPRISE L8 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95sq mm 3.5 core including taking down old cable and seperation of bricks for re-laying complete all as specified as directed by Engineer in Charge. | 1,519 | RUNNING METRE | 500 ₹7.6 L | 525 ₹8.0 L | 651 ₹9.9 L | 593 ₹9.0 L | 500 ₹7.6 L | 613 ₹9.3 L | 650 ₹9.9 L | 625 ₹9.5 L |
| 2.00 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50sq mm 3.5 core including taking down old cable and seperation of bricks for re-laying complete all as specified as directed by Engineer in Charge. | 950 | RUNNING METRE | 300 ₹2.9 L | 310 ₹2.9 L | 385 ₹3.7 L | 355 ₹3.4 L | 300 ₹2.9 L | 364 ₹3.5 L | 420 ₹4.0 L | 360 ₹3.4 L |
| 3.00 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25sq mm 4 core including taking down old cable and seperation of bricks for re-laying complete all as specified as directed by Engineer in Charge. | 650 | RUNNING METRE | 222 ₹1.4 L | 210 ₹1.4 L | 250 ₹1.6 L | 231 ₹1.5 L | 220 ₹1.4 L | 238 ₹1.5 L | 295 ₹1.9 L | 240 ₹1.6 L |
| 4.00 | Material and labour for provision of earthing complete with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to galvanised mild steel strip 32 x 6 mm by means of bolts, nuts, check nuts and washer of galvanized steel, watering pipe of 20 mm bore galvanised iron medium grade and 40 mm bore galvanised iron light grade for earth strip protection including all excavation, earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm), with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion.
Note :
(i)Earth result after installation completely should be less than 5 Ohm. (ii)Quoted rates shall be deemed to include for earth strip with protection pipe of 7.5 M length. | 36 | EACH JOB | 4,000 ₹1.4 L | 4,500 ₹1.6 L | 5,000 ₹1.8 L | 5,000 ₹1.8 L | 4,000 ₹1.4 L | 8,513 ₹3.1 L | 5,900 ₹2.1 L | 5,100 ₹1.8 L |
| 5.00 | M & L for Bus bar chamber box outdoor type made out of mild steel CRCA sheet 3.15mm thick duly painted with synthatic enamal paint (internally and externally) over a coat of red oxide primer size not less than 800mmx600mmx400mm including aluminum bus bar four nos of capacity 250A fixed with insulators and angle iron of size 40x40x5 mm of height 0.9 Mtr including PCC foundation complete all as specified and directed | 4 | EACJ JOB | 25,000 ₹1 L | 24,000 ₹96,000 | 27,520 ₹1.1 L | 18,750 ₹75,000 | 40,000 ₹1.6 L | 24,136 ₹96,544 | 40,000 ₹1.6 L | 35,000 ₹1.4 L |
| 6.00 | Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire out door type weather vermin, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet with double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc with angle iron frame 50x50x6 mm and height not less than 0.9 mtr with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with all accessories complete all as specified as directed by Engineer in Charge. comprising the following:- | 1 | EACH | 2,10,000 ₹2.1 L | 1,95,000 ₹1.9 L | 1,69,113 ₹1.7 L | 1,73,542 ₹1.7 L | 1,14,311 ₹1.1 L | 1,56,756 ₹1.6 L | 1,35,000 ₹1.4 L | 2,54,000 ₹2.5 L |
| 6.01(i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 800 Amps for phases and 400 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment. (ii) LED type indicating lamps (RYB). (iii) Digital Voltmeter (iv) Digital Ammeter with CTs. (v) Panel board internal wiring with suitable rated PVC insulated copper conductors. (vi) MCCB 630 Amps,415V, 4 Pole, 50 KA - 01 No (In coming) (vii) MCCB 200 Amps, 415V, 4 pole, 25 KA - 04 Nos (Out going) (vii) MCCB 100 Amps, 415V, 4 pole, 16 KA - 02 Nos (Out going) | |||||||||||
| 7.00 | Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire out door type weather vermin, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet with double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc, with angle iron frame 40x40x5 mm and height not less than 0.9 mtr duly fixed with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with all accessories as specified and as directed by Engineer in Charge comprising the following:- | 3 | EACH | 1,00,000 ₹3 L | 1,00,000 ₹3 L | 90,624 ₹2.7 L | 86,000 ₹2.6 L | 65,000 ₹1.9 L | 85,541 ₹2.6 L | 1,24,000 ₹3.7 L | 1,12,000 ₹3.4 L |
| 7.01(i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 400 Amps for phases and 200 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment. (ii) LED type indicating lamps (RYB) with holders controlled by fuzes and switches. (iii) Panel board internal wiring with suitable rated PVC insulated copper conductors (iv) MCCB 200 Amps,415V, 4 Pole, 25 KA - 01 No (In coming) (v) MCCB 100 Amps, 415V, 4 pole, 16 KA - 05Nos (Out going) | |||||||||||
| 8.00 | Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire out door type weather vermin, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet with double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc, with angle iron frame 50x50x6 mm and height not less than 0.9 mtr fixed with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with all accessories as specified and as directed by Engineer in Charge comprising the following:- | 2 | EACH | 1,25,000 ₹2.5 L | 1,35,000 ₹2.7 L | 1,14,739 ₹2.3 L | 1,07,000 ₹2.1 L | 1,05,000 ₹2.1 L | 1,07,454 ₹2.1 L | 1,35,000 ₹2.7 L | 1,58,000 ₹3.2 L |
Tender Value
₹42 L
EMD Value
₹84,000
Closing Date
2 Jan 2026, 6:00 pmClosed
Lt Col Sumukh Swaroop
Garrison Engineer (AF) No1 Military Engineer Services Air Force Station Jamnagar 361003
SPECIAL REPAIR REPLACEMENT OF LT PANEL, BUS BAR AND CABLES IN DOMESTIC AREA AT AF STN JAMNAGAR UNDER GE (AF) JAMNAGAR NO 1
2025_MES_744209_1
8393/E8
Open Tender
Miscellaneous Works
180 days
JAMNAGAR
6 documents required · 6 mandatory
₹500
GE (AF) Jamnagar No 1
₹84,000
Yes
30 Jan 2026
12 Dec 2025
3 Jan 2026
12 Dec 2025
2 Jan 2026
26 Dec 2025
Amount
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95sq mm 3.5 core including taking down old cable and seperation of bricks for re-laying complete all as specified as directed by Engineer in Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50sq mm 3.5 core including taking down old cable and seperation of bricks for re-laying complete all as specified as directed by Engineer in Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25sq mm 4 core including taking down old cable and seperation of bricks for re-laying complete all as specified as directed by Engineer in Charge.
M & L for Bus bar chamber box outdoor type made out of mild steel CRCA sheet 3.15mm thick duly painted with synthatic enamal paint (internally and externally) over a coat of red oxide primer size not less than 800mmx600mmx400mm including aluminum bus bar four nos of capacity 250A fixed with insulators and angle iron of size 40x40x5 mm of height 0.9 Mtr including PCC foundation complete all as specified and directed
Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire out door type weather vermin, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet with double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc with angle iron frame 50x50x6 mm and height not less than 0.9 mtr with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with all accessories complete all as specified as directed by Engineer in Charge. comprising the following:-
(i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 800 Amps for phases and 400 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment. (ii) LED type indicating lamps (RYB). (iii) Digital Voltmeter (iv) Digital Ammeter with CTs. (v) Panel board internal wiring with suitable rated PVC insulated copper conductors. (vi) MCCB 630 Amps,415V, 4 Pole, 50 KA - 01 No (In coming) (vii) MCCB 200 Amps, 415V, 4 pole, 25 KA - 04 Nos (Out going) (vii) MCCB 100 Amps, 415V, 4 pole, 16 KA - 02 Nos (Out going)
Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire out door type weather vermin, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet with double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc, with angle iron frame 40x40x5 mm and height not less than 0.9 mtr duly fixed with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with all accessories as specified and as directed by Engineer in Charge comprising the following:-
(i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 400 Amps for phases and 200 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment. (ii) LED type indicating lamps (RYB) with holders controlled by fuzes and switches. (iii) Panel board internal wiring with suitable rated PVC insulated copper conductors (iv) MCCB 200 Amps,415V, 4 Pole, 25 KA - 01 No (In coming) (v) MCCB 100 Amps, 415V, 4 pole, 16 KA - 05Nos (Out going)
Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire out door type weather vermin, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet with double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc, with angle iron frame 50x50x6 mm and height not less than 0.9 mtr fixed with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with all accessories as specified and as directed by Engineer in Charge comprising the following:-
(i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 600 Amps for phases and 300 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment. (ii) LED type indicating lamps (RYB) with holders controlled by fuzes and switches. (iii) Panel board internal wiring with suitable rated PVC insulated copper conductors. (iv) MCCB 350 Amps, 415V, 4 pole,35 KA - 01Nos (v) MCCB 160 Amps, 415V, 4 pole, 25 KA - 02 Nos (vi) MCCB 125 Amps, 415V, 4 pole, 16 KA - 02 Nos
Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire out door type weather vermin, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet with double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etcwith angle iron frame 50x50x6 mm and height not less than 0.9 mtr fixed with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with complete all as specified and as directed by Engineer in Charge comprising the following:-
(i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 200 Amps for phases and neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment. (ii) LED type indicating lamps (RYB) with holders controlled by fuzes and switches. (iii) Panel board internal wiring with suitable rated PVC insulated copper conductors. (iv) MCCB 100 Amps, 415V, 4 pole,16 KA - 01Nos (v) MCCB 63 Amps, 415V, 4 pole, 10 KA - 05 Nos
Supply, installing, testing and commissioining of LT cubical panel board, 440 Volts, 50 Hz, 3 phase, 4 wire out door type weather vermin, dust proof front operated with adequate air ventilation at sides and back fabricated out of 3.15 mm thick CRCA sheet with double door shutter and locking arrangements, cable trays cable lugs etc including provision for taking out incoming and outgoing cables duly marked with relevetted letter plates of appropriate size for each feeder cables danger boards etc with angle iron frame 50x50x6 mm and height not less than 0.9 mtr fixed with PCC 1:2:4 type B1 platform; nut,bolts, washers etc for grouting and painting with powder coated epoxy finish of approved colour over a coat of red oxide primer including taking down old unserviceable existing LT Panel board with as specified and as directed by Engineer in Charge comprising the following:-
(i) Bus bar chamber consisting of four Nos aluminium bus bar duly sleeved of capacity 600 Amps for phases and 300 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulation in separate compartment. (ii) LED type indicating lamps (RYB) with holders controlled by fuzes and switches. (iii) Panel board internal wiring with suitable rated PVC insulated copper conductors.(v) MCCB 400 Amps, 415V, 4 pole,50 KA - 01Nos (iv) MCCB 160 Amps, 415V, 4 pole, 25 KA - 04 Nos (v) MCCB 125 Amps, 415V, 4 pole, 16 KA - 02 Nos
Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out of cables and foundation of poles etc. and getting out complete all as specified and as directed by Engineer in Charge
Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed by Engineer in Charge
Removal of surplus excavated soil to a distance not exceeding 50metre and depositing where directed at a level not exceeding 1.5metre above the starting point complete all as specified and as directed by Engineer in Charge
Material and labour, sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts complete all as specified and as directed by Engineer in Charge. Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment.
Supplying and laying un-reinforced precast concrete cable cover, class LV,type 1 with peak, size 250mm x 150mm x 40mm complete all as specified and as directed by Engineer in Charge
Laying only old un-reinforced precast concrete cable cover, class LV,type 1 with peak, size 250mm x 150mm x 40mm complete all as specified and as directed by Engineer in Charge
M & L Hard core, broken to gauge n exc 63 mm complete all as specified and as directed by Engineer in Charge
M & L Cement concrete in foundations, filling and mass concrete Type C2 1:2:4 (40mm grade aggregate ) complete all as specified and as directed by Engineer in Charge
SURESH ELECTRICALS (BID ID -3513704)
jagdish machinery stores (BID ID -3511367)
JAYESH TRADING CORPORATION (BID ID -3513185)
rajengineers (BID ID -3513604)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3513952)
JAMNAGAR ELECTRIC AND MACHINERY CO (BID ID -3514384)
BHAVNA IMPERIAL ENTERPRISE (BID ID -3514366)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
PS.pdf
Tender Documents • 0.88 MB
BOQ_833326.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid