Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.5 LAccepted-Finance | ₹38.5 L | L1 | Accepted-Finance Being lowest bidder |
| 2 | L2₹43.0 L+₹4.5 L (11.8%)Rejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | ₹43.0 L+₹4.5 L (11.8%) | L2 | Rejected-Finance Other than lowest bidder |
| 3 | L3₹44.7 L+₹6.3 L (16.3%)Rejected-Finance | ₹44.7 L+₹6.3 L (16.3%) | L3 | Rejected-Finance Other than lowest bidder |
| Sl No | Description | Qty | Unit | GOODWILL ENGINEERS L3 | Bharat Enterprises L1 | Vijaypower Generators Limited L2 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning silent diesel Engine driven generating set, fully wired alternator AC to give an output of 125 KVA/ 100 KW continuously rating at a PF of 0.8 lagging, 415 Volts AC 3 phase 4 wire 50 Hz +/-1% supply, 1500 RPM, directly coupled with diesel engine specification complying BS 5514, ISO 3046, IS 1460, ISO 9001, ISO 8528 & IS 13018. DG Set shall be water cooled mounted on Channel section iron common base frame with AC Alternator complete with fuel tank provided within canopy on base frame (Service tank) of adequate capacity with fuel line and accessories, including PCC /RCC foundation work as per manufacturer instructions, vibration and damper pads (AVM), control panel with necessary meter and sound proof canopy as per CPCB-IV norms and other accessories etc comprising of the following:- | 1 | Each Job | 16,50,000 ₹16,50,000 | 15,79,000 ₹15,79,000 | 15,00,000 ₹15,00,000 Lowest |
| 1.01(I) Engine :- (a) Diesel driven 4 cylinder, in-line 4 stroke, radiator cooled with blower fan engine and fully controlled by Electronic Engine control module. (b) Air handling system with dry type, Replaceable paper element air cleaner with restriction indicator & Air to air aftercooler (c) Turbocharger, electrical lift pump for faster response (d) Fuel injection pump system with electronic governing (e) Dual fuel filter system: Pre & main filter including water separator and Water in Fuel sensor. (f) Integral set-mounted radiator system, designed for 50°C ambient temperature (g) Full flow spin on lube oil filter with plate type lube oil cooler. (h) 1 No of 12 V, 105 AH DC lead acid batteries having 4 year warranty with terminals and spare cables. (j) Electrical starter motor with soft start engagement feature (k) Bty charging alternator , 12 V DC Self starter, Fuel pipe C Class STIC of suitable size. (l) Emergency stop button | ||||||
| 1.02(II) Alternator :- (a) Brushless Excitation type, Screen protected, Revolving field, Self excited alternator conforming to IS4722, IS 13364 Suitable rated at 0.8 PF, 415 V- 440 V, 3 Phase, 4 wire 50 Hz, at 1500 RPM, self excited and self regulated with AVR, screen protected, drip proof, suitable Insulation class, self ventilated for engine as mentioned here in before. (b) 3 Phase reconnectable copper winding with terminals brought out for connection (c) Sealed bearings for alternator (d) Having IP 23 Enclosure, H Class of insulation, voltage regulation ±1% (e) unbalance load capability :- 25 % of rated current. | ||||||
| 1.03(III) DG Control Panel :- (a) Control panel is made up of 14/16 gauge CRCA sheet and is powder coated for weather-proof consists of the following parts :- (b) Micro processor based DG Controller module system to set monitoring, metering and control system with LCD display such as the following parameters:- Control System : Digital AVR, Digital electronic governing & Remote start-stop Engine metering: Oil pressure, Coolant temperature, Battery voltage, Engine speed Alternator metering : Line to Line Voltage and Line to Neutral Voltage, Current (single and 3 phase), Volt-Amperes (phase and total) and Frequency. (c) Aluminum bus bars with suitable capacity with incoming/ outgoing terminals (d) Indicating lamps for ‘Load ON’ and ‘Set Running’ . (e) Instrument fuses duly wired and ferruled . (f) MCCB of suitable rating with overload and short circuit protections. (g) CT of suitable ratio-03 Nos (h) One set of instruments MCBs | ||||||
| 1.04Engine protection: Low lube oil pressure, High/Low coolant temperature, Over speed, Bty Over/Under/Weak Volts, Fail to crank/ start, Sensor failure. AC Alternator protection : Over/Under voltage, Over/ Under frequency, Over current, Short circuit and Loss of AC sensing. Data logging: Engine hours, Control hours, Engine starts and upto 10 recent fault codes, 12 /24 Volt DC operation Sleep mode. | ||||||
| 1.05(IV) Silencer :- Silencer suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB(IV) as per latest global pollution standard. Mounting Arrangement and Fuel tank :- Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. Base frame with integral fuel tank having storage capacity not less than 8 hrs factory made HR/MS Sheet of suitable thickness is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning. | ||||||
| 1.06(V) Accoustic Enclosure :- (i) Designed to meet stringent MoEF/ CPCB norms of 75 dBA @ 1 Mtr at 75% load under free field conditions. (ii) The acoustic enclosure is made of CRCA sheets as per OEM shade and a structural/ sheet metal base frame painted in black. (iii) High quality noise absorbant and fire-retardant grade acoustic insulation material (PU Foam) complying to IS 8183 (iv) Two point / base lifting for easy handling at site (v) Air inlet louvers designed to operate at rated load (vi) UV resistant powder coating of all parts to withstand extreme environment (vii) Fluid drains for lube oil and fuel (viii) Fuel filling arrangement inside the enclosure (ix) Inside illumination - 01 No - LED fitting of 10 watt | ||||||
| 1.07(VI) First fill of Lubricants, Coolant & Fuel :- (i) First fill of oil, coolant as per OEM recommendations and diesel during testing for 12 hrs as per CA provn. Note : (i) The following items are deemed to be included in the rate quoted for all DG sets:- (a) DHPP for testing purpose shall be supplied by the contractor without any extra cost to Department. (b) PCC foundation for DG Set as per OEM instruction (ii) The contractor shall arrange for artificial load (water load/Electrical load) for testing for final testing of DG Set at site and the cost is deemed to be included in above offer. (iii) Testing of sound level should carried out at the site in presence of Engineer-in-Charge (iv) One set of latest Spare part catalogue with price, exploded view of parts and user's manual are deemed to be included in the offer. (v) All civil works including foundation for DG Set as per manufacturer's drawing/ specification. (vi) The rate quoted is deemed to be included for initial filling of radiator coolant and lubricating oil upto level (vii) The components i.e engine, alternator, panel etc of all the DG sets shall be procured from the OEM. (viii) Before delivery of DG set the inspection of the DG set shall be carried out at the workshop of OEM be the rep of the accepting officer, necessary arrangement for inspection shall be done by contractor. (ix) Engine and alternator of same make shall be preferred in case both are being manufactured by the same manufacturer or alternator as recommended to use by the manufacturer shall be allowed. No price adjustment on this accout shall be made and No misunderstanding on this account shall be entertained at later stage. Contractor quoted rate shall be deemed to be included for this aspect. (x) The emmision standard parameters of DG set should meet as per specified in "The Gazatte of India" bearing No 11 Dec 2013. (xi) Rates quoted are deemed to be included for foundation of DG set as approved by OEM. No extra payment for foundation will be paid to contractor. (xii) The BHP of DG set 125 KVA shall not be less than 480. The alternator efficiency shall not be less than 94%. | ||||||
| 2.00 | Supply, installation, testing and commissioning silent diesel Engine driven generating set, fully wired alternator AC to give an output of 75 KVA/ 60 KW continuously rating at a PF of 0.8 lagging, 415 Volts AC 3 phase 4 wire 50 Hz +/-1% supply, 1500 RPM, directly coupled with diesel engine specification complying BS 5514, ISO 3046 , IS 1460 , ISO 9001 , ISO 8528 & IS 13018.DG Set shall be water cooled mounted on Channel section iron common base frame with AC Alternator complete with fuel tank provided within canopy on base frame (Service tank) of adequate capacity with fuel line and accessories, including PCC /RCC foundation work as per manufacturer instructions, vibration and damper pads (AVM), control panel with necessary meter and sound proof canopy as per CPCB-IV norms and other accessories etc comprising of the following:- | 1 | Each Job | 12,40,000 ₹12,40,000 | 11,34,000 ₹11,34,000 Lowest | 12,90,000 ₹12,90,000 |
| 2.01(I) Engine :- (a) Diesel driven 4 cylinder, in-line 4 stroke, radiator cooled with blower fan engine and fully controlled by Electronic Engine control module (b) Air handling system with dry type, Replaceable paper element air cleaner with restriction indicator & Air to air aftercooler (c) Turbocharger, electrical lift pump for faster response (d) Fuel injection pump system with electronic governing (e) Dual fuel filter system: Pre & main filter including water separator and Water in Fuel sensor. (f) Integral set-mounted radiator system, designed for 50°C ambient temperature (g) Full flow spin on lube oil filter with plate type lube oil cooler. (h) 1 No of 12 V, 105 AH DC lead acid batteries having 4 year warranty with terminals and spare cables. (j) Electrical starter motor with soft start engagement feature (k) Bty charging alternator , 12 V DC Self starter, Fuel pipe C Class STIC of suitable size. (l) Emergency stop button | ||||||
Tender Value
₹34.0 L
EMD Value
₹67,980
Closing Date
8 Aug 2026, 6:00 pmClosed
GE UTILITY AMBALA
GE UTILITY AMBALA CANTT 133001
SPECIAL REPAIR TO DG SETS FOR WATER SUPPLY INSTALLATIONS AGAINST BER AND ALLIED WORKS AT SECTOR B AND SPECIAL REPAIR TO CHEMICAL DOSING SYSTEM FOR SYL FILTRATION PLANT UNDER GE UTILITY AMBALA CANTT
2026_MES_762719_3
CA NO GE U AMB 36 OF 2026-27
Open Tender
Civil Works
Item Rate
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹67,980
9 Sept 2026
17 Jul 2026
10 Aug 2026
17 Jul 2026
8 Aug 2026
25 Jul 2026
17 Jul 2026 - 20 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning silent diesel Engine driven generating set, fully wired alternator AC to give an output of 125 KVA/ 100 KW continuously rating at a PF of 0.8 lagging, 415 Volts AC 3 phase 4 wire 50 Hz +/-1% supply, 1500 RPM, directly coupled with diesel engine specification complying BS 5514, ISO 3046, IS 1460, ISO 9001, ISO 8528 & IS 13018. DG Set shall be water cooled mounted on Channel section iron common base frame with AC Alternator complete with fuel tank provided within canopy on base frame (Service tank) of adequate capacity with fuel line and accessories, including PCC /RCC foundation work as per manufacturer instructions, vibration and damper pads (AVM), control panel with necessary meter and sound proof canopy as per CPCB-IV norms and other accessories etc comprising of the following:- | 1 | Each Job | - | - |
| 1.01 | (I) Engine :-
(a) Diesel driven 4 cylinder, in-line 4 stroke, radiator cooled with blower fan engine and fully controlled by Electronic Engine control module.
(b) Air handling system with dry type, Replaceable paper element air cleaner with restriction indicator & Air to air aftercooler
(c) Turbocharger, electrical lift pump for faster response
(d) Fuel injection pump system with electronic governing
(e) Dual fuel filter system: Pre & main filter including water separator and Water in Fuel sensor.
(f) Integral set-mounted radiator system, designed for 50°C ambient temperature
(g) Full flow spin on lube oil filter with plate type lube oil cooler.
(h) 1 No of 12 V, 105 AH DC lead acid batteries having 4 year warranty with terminals and spare cables.
(j) Electrical starter motor with soft start engagement feature
(k) Bty charging alternator , 12 V DC Self starter, Fuel pipe C Class STIC of suitable size.
(l) Emergency stop button | - | - | - | - |
| 1.02 | (II) Alternator :-
(a) Brushless Excitation type, Screen protected, Revolving field, Self excited alternator conforming to IS4722, IS 13364 Suitable rated at 0.8 PF, 415 V- 440 V, 3 Phase, 4 wire 50 Hz, at 1500 RPM, self excited and self regulated with AVR, screen protected, drip proof, suitable Insulation class, self ventilated for engine as mentioned here in before.
(b) 3 Phase reconnectable copper winding with terminals brought out for connection
(c) Sealed bearings for alternator
(d) Having IP 23 Enclosure, H Class of insulation, voltage regulation ±1%
(e) unbalance load capability :- 25 % of rated current. | - | - | - | - |
| 1.03 | (III) DG Control Panel :-
(a) Control panel is made up of 14/16 gauge CRCA sheet and is powder coated for weather-proof consists of the following parts :-
(b) Micro processor based DG Controller module system to set monitoring, metering and control system with LCD display such as the following parameters:-
Control System : Digital AVR, Digital electronic governing & Remote start-stop
Engine metering: Oil pressure, Coolant temperature, Battery voltage, Engine speed
Alternator metering : Line to Line Voltage and Line to Neutral Voltage, Current (single and 3 phase), Volt-Amperes (phase and total) and Frequency.
(c) Aluminum bus bars with suitable capacity with incoming/ outgoing terminals
(d) Indicating lamps for ‘Load ON’ and ‘Set Running’ .
(e) Instrument fuses duly wired and ferruled .
(f) MCCB of suitable rating with overload and short circuit protections.
(g) CT of suitable ratio-03 Nos
(h) One set of instruments MCBs | - | - | - | - |
| 1.04 | Engine protection:
Low lube oil pressure, High/Low coolant temperature, Over speed, Bty Over/Under/Weak Volts, Fail to crank/ start, Sensor failure.
AC Alternator protection : Over/Under voltage, Over/ Under frequency, Over current, Short circuit and Loss of AC sensing.
Data logging: Engine hours, Control hours, Engine starts and upto 10 recent fault codes, 12 /24 Volt DC operation Sleep mode. | - | - | - | - |
| 1.05 | (IV) Silencer :-
Silencer suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB(IV) as per latest global pollution standard. Mounting Arrangement and Fuel tank :- Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. Base frame with integral fuel tank having storage capacity not less than 8 hrs factory made HR/MS Sheet of suitable thickness is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning. | - | - | - | - |
| 1.06 | (V) Accoustic Enclosure :-
(i) Designed to meet stringent MoEF/ CPCB norms of 75 dBA @ 1 Mtr at 75% load under free field conditions.
(ii) The acoustic enclosure is made of CRCA sheets as per OEM shade and a structural/ sheet metal base frame painted in black.
(iii) High quality noise absorbant and fire-retardant grade acoustic insulation material (PU Foam) complying to IS 8183
(iv) Two point / base lifting for easy handling at site
(v) Air inlet louvers designed to operate at rated load
(vi) UV resistant powder coating of all parts to withstand extreme environment
(vii) Fluid drains for lube oil and fuel
(viii) Fuel filling arrangement inside the enclosure
(ix) Inside illumination - 01 No - LED fitting of 10 watt | - | - | - | - |
| 1.07 | (VI) First fill of Lubricants, Coolant & Fuel :-
(i) First fill of oil, coolant as per OEM recommendations and diesel during testing for 12 hrs as per CA provn.
Note :
(i) The following items are deemed to be included in the rate quoted for all DG sets:-
(a) DHPP for testing purpose shall be supplied by the contractor without any extra cost to Department.
(b) PCC foundation for DG Set as per OEM instruction
(ii) The contractor shall arrange for artificial load (water load/Electrical load) for testing for final testing of DG Set at site and the cost is deemed to be included in above offer.
(iii) Testing of sound level should carried out at the site in presence of Engineer-in-Charge
(iv) One set of latest Spare part catalogue with price, exploded view of parts and user's manual are deemed to be included in the offer.
(v) All civil works including foundation for DG Set as per manufacturer's drawing/ specification.
(vi) The rate quoted is deemed to be included for initial filling of radiator coolant and lubricating oil upto level
(vii) The components i.e engine, alternator, panel etc of all the DG sets shall be procured from the OEM.
(viii) Before delivery of DG set the inspection of the DG set shall be carried out at the workshop of OEM be the rep of the accepting officer, necessary arrangement for inspection shall be done by contractor.
(ix) Engine and alternator of same make shall be preferred in case both are being manufactured by the same manufacturer or alternator as recommended to use by the manufacturer shall be allowed. No price adjustment on this accout shall be made and No misunderstanding on this account shall be entertained at later stage. Contractor quoted rate shall be deemed to be included for this aspect.
(x) The emmision standard parameters of DG set should meet as per specified in "The Gazatte of India" bearing No 11 Dec 2013.
(xi) Rates quoted are deemed to be included for foundation of DG set as approved by OEM. No extra payment for foundation will be paid to contractor.
(xii) The BHP of DG set 125 KVA shall not be less than 480. The alternator efficiency shall not be less than 94%. | - | - | - | - |
| 2 | Supply, installation, testing and commissioning silent diesel Engine driven generating set, fully wired alternator AC to give an output of 75 KVA/ 60 KW continuously rating at a PF of 0.8 lagging, 415 Volts AC 3 phase 4 wire 50 Hz +/-1% supply, 1500 RPM, directly coupled with diesel engine specification complying BS 5514, ISO 3046 , IS 1460 , ISO 9001 , ISO 8528 & IS 13018.DG Set shall be water cooled mounted on Channel section iron common base frame with AC Alternator complete with fuel tank provided within canopy on base frame (Service tank) of adequate capacity with fuel line and accessories, including PCC /RCC foundation work as per manufacturer instructions, vibration and damper pads (AVM), control panel with necessary meter and sound proof canopy as per CPCB-IV norms and other accessories etc comprising of the following:- | 1 | Each Job | - | - |
| 2.01 | (I) Engine :-
(a) Diesel driven 4 cylinder, in-line 4 stroke, radiator cooled with blower fan engine and fully controlled by Electronic Engine control module
(b) Air handling system with dry type, Replaceable paper element air cleaner with restriction indicator & Air to air aftercooler
(c) Turbocharger, electrical lift pump for faster response
(d) Fuel injection pump system with electronic governing
(e) Dual fuel filter system: Pre & main filter including water separator and Water in Fuel sensor.
(f) Integral set-mounted radiator system, designed for 50°C ambient temperature
(g) Full flow spin on lube oil filter with plate type lube oil cooler.
(h) 1 No of 12 V, 105 AH DC lead acid batteries having 4 year warranty with terminals and spare cables.
(j) Electrical starter motor with soft start engagement feature
(k) Bty charging alternator , 12 V DC Self starter, Fuel pipe C Class STIC of suitable size.
(l) Emergency stop button | - | - | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.96 MB
Tender2.pdf
Tender Documents • 0.82 MB
BOQ_872738.xls
BOQ • 0.91 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .