SE, EDC, Rampur
Office of the SE, EDC, Rampur
43/2022-23/EDC Releasing 1000 KVA connection (Industrial connection) of M/S Swati Campor and specialty chemical Pvt Ltd. under Jurisdiction of EDD-Milak, Rampur
2022_PVVNL_755021_2
43/2022-23(EDCR)
Open Tender
Electrical Works
Lump-sum
45 days
Office of the SE, EDC
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,180
SE, EDC, Rampur
₹9,000
28 Dec 2022
20 Dec 2022
27 Dec 2022
20 Dec 2022
27 Dec 2022
20 Dec 2022
Amount
Carriage of the following material from Store Centre, Rampur to work site including loading & unloading.
11 Mtr Long ST pole
33 KV XLPE Cable 3*300 sqmm (Double Ckt)
other line material such as X-arm, Cable Jointing kit etc.
ACSR Dog conductor
AB Cable (3x95+1x70+1x16) sqmm
old & used ACSR weasel Conductor
LT Distribution box 3 phase
33 KV Pilfer proof metering cubical
CT-PT Unit 20/1 Amp
3 PH-4 W Static TVM 33 KV
33 KV able Jointing kit 3*300 sqm mm (outdoor)
Excavation of foundation pit in size of 75x45cm having depth of 1/6th of the full length of the support(pole)Erection of support(pole) complete with providing and fixing of all clamps made of MS flat of size 75x8 mm. an other accessories . The work includes fabrication work and fixing of cross bracing sets 3.5 Mtr from MS Angle 65x65x6 mm/50x50x6 mm. The work includes cutting holes and providing MS Bolts of 16x40 mm size in the middle of the cross bracing with 1 No. sparing washer of proper size.
a) single support structure
11 Mtr long ST pole
b) Four Pole structure
11 Mtr long ST pole
Grouting of support in CC 1:4:8(cement, sand & 40 mm. brick ballast) Grouting will be done in the block of size 45x45cmx1/6th of full length of the support upto ground level, 30 cm plinth above the ground level with CC 1:3:6 (cement, course sand and stone grit) with muffing. The work includes back filling and proper ramming etc.
a) single support structure
11 Mtr long ST pole
b) Four Pole structure
11 Mtr long ST pole
Grouting of Stay Rods(20x1800)mm including all work of excavation, cement concrete in size of (0.60x0.60x0.30)M in the ratio of 1:4:8(cement, sand, 40mm brick ballast) including back filling of soil and proper ramming etc.
Fixing, tightening and nozelling of stay wire with stay rod with the pole of required tension by providing stay clamps.
Earthing of support with MS Earth Rod of (20x2500)mm long including excavation of pit and driving MS Rod 3.0 M apart from support and 0.5 M below the ground level and connecting below the earth electrodes with the help of GI wire No. 8SWG and earthing lugs
Water level Earthing (Chemical) complete as per RESPO Norms and as per direction of Supervising Engineer(all accessories for Water level earthing will be provide by the contractor)
Fixing of 33 KV Pin Insulator with Pin as per direction of Supervising Engineer.
Cartage and fixing of Disc Insulator B&S type 700 kg as per direction of Supervising Engineer.
Cartage and fixing of Disc fitting Dog/Racoon 700 kg as per direction of Supervising Engineer.
Make tranch for XLPE Cable CT/PT to meter Cubical as per RESPO Norms and as per direction of Supervising Engineer.
Digging and laying, sagging, 33 KV XLPE Cable (underground) (Double ckt cable) cable 3*300 sqmm with the help of cable jointing kit etc. as per RESPO Norms and as per direction of Supervising Engineer.
Laying, sagging, stringing and binding etc AB Cable (3x95+1x70+1x16) sqmm as per RESPO Norms and as per direction of Supervising Engineer.
Laying, sagging, stringing and binding etc of 33 KV XLPE Cable 3*300 sqmm (Double Ckt) as per RESPO Norms and as per direction of Supervising Engineer.
Laying, sagging, stringing and binding etc of ACSR Dog Conductor as per RESPO Norms and as per direction of Supervising Engineer.
Installation of LT Distribution box 3 Phase complete as per direction of Supervising Engineer.
Installation and connection of 33 KV Pilfer Proof metering cubical as per direction of Supervising Engineer.
Installation and connection of 3 Ph-4 W Static TVM 33 KV as per direction of Supervising Engineer.
Installation and connection of CT-PT Unit 30/1 Amp as per direction of Supervising Engineer.
Providing of Aluminium Paint and Painting of ST Pole as per direction of Supervising Engineer.
Providing of Red Oxide Paint and Painting of ST Pole as per direction of Supervising Engineer.
Providing and laying of HDPE pipe 6" Dia for underground 33 KV cable (Double Ckt) as per direction of Supervising Engineer.
Providing and fixing of Danger board with clampas per direction of Supervising Engineer.
Providing and fixing of number plate per direction of Supervising Engineer.
Providing and fixing Clamp with Bolts & nuts
Providing and fixing G.I. Pipe 6" dia
Providing and fixing ABC Suspension Clamp with nut & bolts
Providing and fixing Barbed wire GI
Providing and fixing Aluminium Binding Wire-6 Swg
Providing and fixing J Hook
Providing and fixing Piercing Clamp
Providing and fixing Stone pad(300X300X75MM)
Providing and fixing earth wire clamp with bolts and nut
Providing and fixing PG Clamp
Providing and fixing F bracket for 33 KV
Providing and fixing number plate
M/s Charley Enterprises
munfad electricals
HARSH ELECTRICALS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .