| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.7 LAccepted-AOC H NO 01 MADINA BAGH MEHJOOR NAGAR NEAR HOTEL RAFADA SRINAGAR 190015 J K | BUDGAM | JAMMU AND KASHMIR | 190015 | L1 | Accepted-AOC Being L1 bidder | |
| 2 | L2₹16.3 L+₹49,649.30 (3.13%)Rejected-Finance WARD NO 16 HOUSE NO 66 SALLIAN TALAB UDHAMPUR 182 101 J K | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L2 | Rejected-Finance Not Being L1 Bidder | |
| 3 | L2₹16.3 L+₹49,649.30 (3.13%)Rejected-Finance | L2 | Rejected-Finance Not Being L1 Bidder | |
| 4 | L3₹16.5 L+₹64,049.30 (4.04%)Rejected-Finance NEAR INDUSTRIAL ESTATE THANDA PADDAR UDHAMPUR J K 182101 | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L3 | Rejected-Finance Not Being L1 Bidder | |
| 5 | L4₹16.9 L+₹1.0 L (6.39%)Rejected-Finance 15A 9 CHOWBHAGA ROAD KOLKATA KOLKATA 700039 | KOLKATA | WEST BENGAL | 700039 | L4 | Rejected-Finance Not Being L1 Bidder |
Tender Value
₹15.5 L
EMD Value
₹31,000
Closing Date
20 Sept 2021, 6:00 pmClosed
GE KARGIL
GE KARGIL LADAKH 194103
REPAIR AND MAINT OF STREET LIGHTS, GATE LIGHT AND GARDEN LIGHTS OF VARIOUS UNITS AT KARGIL, KAKSAR, HINSKUT, BUDHKHARBU, APATI, CHANIGUND AND HARDAS ETC UNDER GE KARGIL
2021_MES_471268_1
GE/K-31/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KARGIL
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE KARGIL
₹31,000
Yes
27 Nov 2021
30 Aug 2021
22 Sept 2021
30 Aug 2021
20 Sept 2021
14 Sept 2021
Amount
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. nexc 10 sq m on plan and n exc 1.5 m in depth and getting out hard and dense soil for pipe lines complete all as specified.
Returning filling in (soil) including spreading, leveling, watering and well ramming in layers not exceeding 25mm thick all as specified and directed by Engr-in-Charge
Removing excavated materials (soil) to a distance not exceeding 50m away from the starting point and depositing where directed at a level not exceeding 1.5m above all as specified and directed by Engr-in-Charge
Sand cushioning of the underground cable complete as per SSR Part-I clause 19.75 all as specified and directed by Engr-in-Charge
Supplying and laying un-reinforced pre-cast concrete cable cover of mix 1:1:5:3 (Type A-1), conferming to class IV, flat size 250mmx150mmx40mm
Supply and laying of XLPE insulated heavy duty under ground electric cable with aluminium conductor 1100 volt grade laid in trenches ducts drown through GI pipes, across the road / path / drain / along poles / walls / floors / eqpt etc including jointing testing complete of cable of above description :-
(a) Corss sectional area 25 Sqmm 4 core
(b) Cross sectional area 16 Sqmm 2 core
(c) Cross sectional area 10 Sqmm 2 core
(d) Cross sectional area 70 sq mm 3½ core
Dismantling of unsv item and S&F of Sheet metal enclosure(Factory made)for distribution board single door, single pole and neutral, 240 Volt, 2 way with 200 Amp rated bus bar including blanking plates where required
Dismantling of unsv MCBs and S&F of MCB single pole 5 to 32 Amps 240 volts 10 KA
Dismantling of unsv MCBs and S&F of MCB SPN 32 Amp, 240 volts, 10 KA
Dismantling of existing old unsv light and Supply & Fixing decorative gate light fitting oriental design landscaspe lighting sutabile for 40 watt LED Lamp with opel diffuser of Make : Crompton Cat Part No-LPTO-40-CDL
M&L GI Pipe 40 mm dia light grade for protection of cable on pole.
Dismantling of existing old unsv light and Supply and Fix LED Street light 45W, pressure die cast Aluminium housing with heat resistant toughned glass & IP 66 Protection and impect resistence IK07 . Make - Cromption Model No - LSTS-45-CDL-1 or equivalent in Philips/Havells/Wipro
Dismantling of existing old unsv light and Supply and Fix LED Street light 72W, pressure die cast Aluminium housing with heat resistant toughned glass & IP 66 Protection and impect resistence IK07 . Make - Cromption Model No - LSTS-45-CDL-1 or equivalent in Philips/Crompton/Wipro
Dismantling of existing old unsv light Supply and fixing of magnum Flood light LED 60 W with high pressure die cast housing and IP65 Protection,complete all as specified and directed by the Engr-in-Charge.Make Cromption Model No - LSTS-45-CDL-1 or equivalvent in Havells/Philips.
Dismantling of existing old unsv item and Supply and fixing single piece moulded SMC Box of size 240x130x110mm outer and 195x135x90mm inner dimension(sintex product code GSJB 2817) or equivalent in (National make) consisting of one SP 6A, 240 V and one 2/4 way connector including all necessary fixing arrangement for fixing to LT pole i.e necessary clamps, nut,bolts and washers of suitable size
Dismantling of existing old unsv item and Supply and fixing street light bracket made out of GI pipe 25/40mm dia light grade 1.2 mtr duly bent in position as per site requirement and including 2 Nos and 2 set MS flat iron clamps of suitable size complete with Nut , bolts and washers for mounting street lights, complete all as specified
Dismantling of existing old unsv item and S&F of Globe integra pole mounted decorative 25W LED post top with spherical shaped polycarbonate connecting up electrically all as specied and directed. Make: Havells, Model No-CORALPT25WLED757PSYMTOPC or equivalent in Philips/CG
M & L for cement concrete for PCC foundation / coping of pole (1:3:6) type C1 with 20 MM graded aggregqate including necessary form work.
M&L for painting of steel tubular electric pole type 410 SP-22 (09 mtr long) with two coats of aluminium paint over priming coat of red oxide primer including preparation of surface and writing pole number in yellow background with black letters (with thick paint) complete all as specified and directed by Engr in Charge. Note :- Painting shall be done on exposed surface of the pole i.e excluding the portion embeded in foundation & coping.
Supplying, transporting, erecting and fixing steel tubular swaged poles type 410 SP-31 (9.0 metres long) complete with cast iron base plate, finial, taper plug, bolts, nuts and screws as specified, including necessary excavation and earth work, PCC 1:4:8 type D-2 in foundations below pole, PCC 1:3:6 type C-2 around poles and PCC 1:3:6 type C-1 as in plinth block, disposal of surplus soil to a distance not exceeding 50 m and depositing where directed, painting steel tubular poles exposed surfaces with aluminium paint two coats over one coat of red oxide primer and providing 300 mm wide bands (3 bands/straps with synthetic enamel paint and 2 bands with black bituminous paint) from plinth block and numbering of poles, painting embedded portion of poles with one coat of bituminous paint complete all as specified and directed.
M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased in and including 40 mm dia GI 'light grade' pipe from upper end of earth plate upto equipments,20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS round bars 6mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as described in electric plate of SSR Part I complete all as specified and directed and testing on completion. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
M&L Mild steel cross arms, bracings, supports, clamps, and back plates fabricated from structural steel sections including nuts, bolts, washers , welding, bending, cold or hot , drilling holes for bolts , in any shape or size as indicated or directed and inclusive of one primer coat with red oxide Zn Chrome and two coats of synthetic enamel paint all as specified.
Dismantling of old ACSR conductor or service feeder distribution span and S&F in repair ACSR conductor of (weasel) 6/2.59, straching properly on insulators and binding with aluminium binding wires,jumpers including fixing on insulators on each poles in span and tightening with permissible sag in between span etc complete all as specified and as directed by Engineer-in-charge.
S&F ( in repairs) Galvanised steel wire 4 mm dia. Continuous bearer wire ( earth wire) on poles for HT/LT feeer over head lines, all as specified.
S&F insulator Shackle type, Porcelain vitreous , white, brown, white or green insulator including galvanised mild steel straps washers, insulator bolts, washers and nuts ; 1100 Volts working pressure, 75 mm height, 90 mm Maximum dia., with 31x3 mm galvanised steel straps and 12 mm dia. of bolts complete all as specified.
S&F Insulator Pin type, pocrcelain , vitreous, white , brown or green, insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut , 100 mm height, 65 mm dia. For 1100 volts grade complete all as specified.
Supply and fixing GI tubes light grade, galvanised with all fittings and fixed complete to wall 50mm dia
Lt spacer 4 ways made out of PVC material and suitable to work on 1100 volts, complete all as specified and directed by Engr-in-Charge.
Sub main wiring with 2 run single core of 1.5 Sq mm insulated FR copper conductor 1100 V grade multi-stranded cable in stove enamalled black rigid steel conduit with 1.5 Sqmm copper conductor as earth wire and connected to earth duly including black rigid steel conduit pipe including tees, bends, elbows, couplers, junctions etc including making good the disturb sufrace to mach the existing specifications
Note : Deduction for amount of Rs 11,685.00 as listed in Schedule A Part - II ( Schedule of Credit) shall be made while awarding of contract.
M/S B K ENTERPRISES
LUXMI ELECTRONIC WORKS
K S BUILDERS
M/S M P Construction Co
M/S HAJI HASSAN ENGINEERING WORKS
VARDHMAN INTERNATIONAL
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .