Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.3 CrAccepted-AOC | ₹7.3 Cr Quoted ₹7.6 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹8.0 Cr+₹40.7 L (5.38%)Rejected-AOC 81 ARYA NAGAR ASSANDH ROAD PANIPAT HARYANA 132103 | PANIPAT | HARYANA | 132103 | ₹8.0 Cr+₹40.7 L (5.38%) | L2 | Rejected-AOC L2 |
| Sl No | Description | Qty | Unit | Anil Kumar Contractor L2 | Anil Dahiya Contractor L1 |
|---|---|---|---|---|---|
| 1.00 | Supply,Installation,Testing and commissioning of CCTV Camera including Video Management software License per lane as per specification compatible with the existing ICCC System | 4 | NO. | 45,000 ₹1,80,000 | 14,000 ₹56,000 Lowest |
| 2.00 | Providing and fixing of DI Resilient seated Sluice valve 400mm WRAS approved complete in all respect as per specifications. Make: VAG, DVD, KIRLOSKAR, Talis. | 4 | Each | 2,55,000 ₹10,20,000 | 2,33,000 ₹9,32,000 Lowest |
| 3.00 | Providing and fixing of non-clog submersible sewerage pumping set with suitable motor capable of 2000m3/hr. discharge and 15m. Head Make:- Kirloskar/ Aqua/KSB/Grundfos Material of Construction (and Design):-
1.) Pump Casing - CI FG 260: IS 210
2.) Motor Casing and other Parts - CI FG 260: IS 210
3.) Mechanical seal - Motor side / Secondary Seal- Carbon v/s Cast Cr Mo Steel
4.) Mechanical seal - Pump side / Primary Seal - SiC v/s SiC
5.) Impeller - CF8 MSS 316
6.) Rotor Mono Solid Single Shaft - AISI 410
7.) Autocoupling with Integral Bend (With Autocoupling PIN) plus Foundation bolt - CI FG 260: IS 210
8.) Foundation Bolt for Auto Coupling - SS 304
9.) Lifting Chain - Alloy Steel - W/O_GI - Lifting chain with `Oval` Ring @ 2 m and with D/Bow Shackle @ 1 End
10.) Guide Rail - GI (with SS 410 Guide Coupler)
11.) Fasteners (Expose to Liquid) - SS 304 (A2) | 4 | Each | 30,00,000 ₹1,20,00,000 | 18,63,000 ₹74,52,000 Lowest |
| 4.00 | Supply Installation Testing and Commissioning of rising spindle flush bottom CI Sluice Gate size(1500mmx1500mm) generally conform to IS:133-19 material detail
1 Frame, door, guide, extension, wedge, wall thimble, floor standard. CI. to IS 210 Gr. Fg 260
2 Spindle SS: 304
3 Seating faces SS :304/SSCF8
4 Wedge Block DI with SS AISI: 304/CF8 Lining
5 Lift Nut High ternide brass(HT2)
6 Fastener (Thimble/Adjustable wedge) Stainless steel 7. Other fasteners Carbon steel 8 Extension spindle SS: 304 9 Guide bracket CI to IS.210 Gr. Fg.260
10. Coupling SS AISI: 304
for sewer disposal/ Intermediate Pumping Station Approved make JASH, IVC and Oriental Casting i/c Inspection of Material at Manufacturing place as per satisfaction of Engineer- in-Charge complete in all respect | 1 | Each | 13,50,000 ₹13,50,000 | 12,30,000 ₹12,30,000 Lowest |
| 5.00 | Supply Installation Testing and Commissioning of rising spindle flush bottom CI Sluice Gate size(1000mmx1000mm) generally conform to IS:133-19 material detail
1 Frame, door, guide, extension, wedge, wall thimble, floor standard. CI. to IS 210 Gr. Fg 260
2 Spindle SS: 304
3 Seating faces SS :304/SSCF8
4 Wedge Block DI with SS AISI: 304/CF8 Lining
5 Lift Nut High ternide brass(HT2)
6 Fastener (Thimble/Adjustable wedge) Stainless steel 7. Other fasteners Carbon steel 8 Extension spindle SS: 304 9 Guide bracket CI to IS.210 Gr. Fg.260
10. Coupling SS AISI: 304
for sewer disposal/ Intermediate Pumping Station Approved make IVC, JASH and Oriental casting as per satisfaction of Engineer- in-Charge complete in all respect | 2 | Each | 9,10,000 ₹18,20,000 | 8,60,000 ₹17,20,000 Lowest |
| 6.00 | Supply installation testing and commissioning of Multi rack mechanical course bar screen
CW:1400 mm
CD: 9500 mm
WD:1400 mm
Bar Spacing :20 mm
Bar Size: 10X50 mm
Inclination 75 Degree
MOC SS-304
Along with panel andsensor and conveyer belt for sewer disposal /intermediate pumping station approved make JASH/Voltas /Johnsons/Oriental casting as per satisfaction of Engineer – in – Charge complete in all respect | 2 | Each | 33,00,000 ₹66,00,000 | 25,00,000 ₹50,00,000 Lowest |
| 7.00 | Supply and installation and testing of Main LT panel made up of 14/16 SWG MS CR sheet duly powder coated with Siemens Gray Shade, dust free and vermin proof with heat shrink sleeved aluminum bus bar with suitable size main incomer 1250A Specifications of LT Panel:- Make LandT/ ABB/ Schnider MAIN INCONER 1250A 4P 50KA ACB EDO MICROPROCESSOR BASED SR 18GDRAW OUT TYPE RELEASE (O/C, S/C )
220VAC - SUNT RELEASE 220VAC - UNDERVOLTAGE RELEASE 220VAC - CLOSING RELEASE 230V AC LED - PHASE INDICATOR RED, YELLOW, BLUE 500V - DIGTAL VIF METER3PH 1600/5A - METERING CTS , 5VA CLASS - 16A SP- MCB 10 KA C-CURVE 4-6 MM - CT and NAUTRAL TERMINAL 1.5/2.5 Sq mm - WIRING WITH COPPER WIRE
INCOMER 1 ( DG SET )
1000A 4P 50KA - ACB EDO MICROPROCESSOR BASED SR 18GDRAW OUT TYPE RELEASE (O/C, S/C )
220VAC - SUNT RELEASE 220VAC - UNDERVOLTAGE RELEASE 220VAC - CLOSING RELEASE
230V AC LED - PHASE INDICATOR RED, YELLOW, BLUE 500V - DIGTAL V METER 3PH 1000/5A - METERING CTS , 5VA CLASS - 1
6A SP - MCB 10 KA C-CURVE 4-6 MM CT and NAUTRAL TERMINAL
1.5/2.5 Sq mm - WIRING WITH COPPER WIRE
6A SP MCB 10 KA C-CURVE
230V AC LED - PHASE INDICATING RED, YELLOW, BLUE
1.5/2.5 Sq mm - WIRING WITH COPPER WIRE
24VDC - BATTERY CHARGER
OUT GOING
400ATP plus N 36KA DN3B-400D - MCCB WITH THERMAL-MAGNETIC 400ATP plus N 36KA DN3B-400D - MCCB SPREADER TERMINAL
400ATP plus N 36KA DN3B-400D- -MCCB HANDLE (ROM) with 4nos. soft starter panel/VFD BUS BAR MAIN BUS BAR CHAMBER OF 1250A FP ALUMINIUM WITH COLOR COATED HEADED SHRRINKABLE SLEEVES AND OUT GOING ACCORDING TO AMP. ACCESSORIES -THIMBLES, H/W, WIRE TIE, WIRE SLEEVE, ,PANEL DOOR LOCK, GASKET A ACB DGSET incommer supply 800A ACB with 4 nos. outgoing panel for running 200HP each motor including multifunction meters with each feeder. All the ACB/MCCB shall have potential free auxiliry contacts for on/off, trip function.
Outgoings: i) 400A FP, 25 kA, MCCB (microprocessor based release with overload, short circuit, earth fault protection, 1 no. NO/NC auxiliary contact and shunt trip, RS-485 communication module similar to Legrand DPX3 250 or equivalent): 2 Nos.
All the MCCBs shall have potential free auxiliary contacts for ON, OFF, TRIP All the MCCB shall have suitable rotory handle with facility for Pad locking Ul) All Breakers shall be provided with Shunt trip coil and auxillary contacts.
iv) Insulated shrouding shall be provided for live parts
v) FRLSH PVC insulated copper wires (not less than 2.5 Sq mm) shall be used for control wiring.
vi) CT`s shall be provided with shorting terminals.
vii) Earthing of LT panel should be done with in all respect.
Approved Make:- Surya, LandT, Siemens, Schneider and ABB | 1 | NO. | 38,00,000 ₹38,00,000 | 30,00,000 ₹30,00,000 Lowest |
| 8.00 | Submersible Cable for pumping set up to 200HP motor pump set size of 95 sqmm. cable as per requirement from pump set to Junction box near sump.
Approved Make:- Polycab, Finolex, Havells. | 70 | Metre | 4,200 ₹2,94,000 | 3,800 ₹2,66,000 Lowest |
| 9.00 | Construction of Staff quarter and JE office complete in all respect i/c all require fitting as per PWD specification and as per satisfaction of Engineer-In- Charge | 230 | Sqm | 23,000 ₹52,90,000 | 18,610 ₹42,80,300 Lowest |
| 10.00 | Dismantling and Demolition Demolishing R.C.C. work by mechanical means and stockpiling at designated locations and disposal of dismantled materials up to a lead of 1 kilometre, stacking serviceable and unserviceable material separately including cutting reinforcement bars and Dismantling and Demolition Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. | 1 | Per job | 33,00,000 ₹33,00,000 | 3,65,000 ₹3,65,000 Lowest |
Tender Value
₹7.0 Cr
EMD Value
₹13.9 L
Closing Date
26 Jan 2026, 5:00 pmClosed
SAMUNDER SINGH
Division FMDA
Designing, re-construction and commissioning of 40 MLD (Average) MPS in place of existing intermediate pumping station and complete scope of work with all contingent works as per scope at Mujesar sector-24 Faridabad
2026_HRY_495193_1
2026312B8778 93F6 4BC5 8F12 A06C5E87A4501851002
Open Tender
Civil Works
Works
180 days
Faridabad (MC)
2 documents required · 2 mandatory
₹1,180
₹13.9 L
Yes
4 Jun 2026
6 Jan 2026
27 Jan 2026
6 Jan 2026
26 Jan 2026
6 Jan 2026
6 Jan 2026 - 8 Jan 2026
Supply,Installation,Testing and commissioning of CCTV Camera including Video Management software License per lane as per specification compatible with the existing ICCC System
Providing and fixing of DI Resilient seated Sluice valve 400mm WRAS approved complete in all respect as per specifications. Make: VAG, DVD, KIRLOSKAR, Talis.
Providing and fixing of non-clog submersible sewerage pumping set with suitable motor capable of 2000m3/hr. discharge and 15m. Head Make:- Kirloskar/ Aqua/KSB/Grundfos Material of Construction (and Design):- 1.) Pump Casing - CI FG 260: IS 210 2.) Motor Casing and other Parts - CI FG 260: IS 210 3.) Mechanical seal - Motor side / Secondary Seal- Carbon v/s Cast Cr Mo Steel 4.) Mechanical seal - Pump side / Primary Seal - SiC v/s SiC 5.) Impeller - CF8 MSS 316 6.) Rotor Mono Solid Single Shaft - AISI 410 7.) Autocoupling with Integral Bend (With Autocoupling PIN) plus Foundation bolt - CI FG 260: IS 210 8.) Foundation Bolt for Auto Coupling - SS 304 9.) Lifting Chain - Alloy Steel - W/O_GI - Lifting chain with `Oval` Ring @ 2 m and with D/Bow Shackle @ 1 End 10.) Guide Rail - GI (with SS 410 Guide Coupler) 11.) Fasteners (Expose to Liquid) - SS 304 (A2)
Supply Installation Testing and Commissioning of rising spindle flush bottom CI Sluice Gate size(1500mmx1500mm) generally conform to IS:133-19 material detail 1 Frame, door, guide, extension, wedge, wall thimble, floor standard. CI. to IS 210 Gr. Fg 260 2 Spindle SS: 304 3 Seating faces SS :304/SSCF8 4 Wedge Block DI with SS AISI: 304/CF8 Lining 5 Lift Nut High ternide brass(HT2) 6 Fastener (Thimble/Adjustable wedge) Stainless steel 7. Other fasteners Carbon steel 8 Extension spindle SS: 304 9 Guide bracket CI to IS.210 Gr. Fg.260 10. Coupling SS AISI: 304 for sewer disposal/ Intermediate Pumping Station Approved make JASH, IVC and Oriental Casting i/c Inspection of Material at Manufacturing place as per satisfaction of Engineer- in-Charge complete in all respect
Supply Installation Testing and Commissioning of rising spindle flush bottom CI Sluice Gate size(1000mmx1000mm) generally conform to IS:133-19 material detail 1 Frame, door, guide, extension, wedge, wall thimble, floor standard. CI. to IS 210 Gr. Fg 260 2 Spindle SS: 304 3 Seating faces SS :304/SSCF8 4 Wedge Block DI with SS AISI: 304/CF8 Lining 5 Lift Nut High ternide brass(HT2) 6 Fastener (Thimble/Adjustable wedge) Stainless steel 7. Other fasteners Carbon steel 8 Extension spindle SS: 304 9 Guide bracket CI to IS.210 Gr. Fg.260 10. Coupling SS AISI: 304 for sewer disposal/ Intermediate Pumping Station Approved make IVC, JASH and Oriental casting as per satisfaction of Engineer- in-Charge complete in all respect
Supply installation testing and commissioning of Multi rack mechanical course bar screen CW:1400 mm CD: 9500 mm WD:1400 mm Bar Spacing :20 mm Bar Size: 10X50 mm Inclination 75 Degree MOC SS-304 Along with panel andsensor and conveyer belt for sewer disposal /intermediate pumping station approved make JASH/Voltas /Johnsons/Oriental casting as per satisfaction of Engineer – in – Charge complete in all respect
Supply and installation and testing of Main LT panel made up of 14/16 SWG MS CR sheet duly powder coated with Siemens Gray Shade, dust free and vermin proof with heat shrink sleeved aluminum bus bar with suitable size main incomer 1250A Specifications of LT Panel:- Make LandT/ ABB/ Schnider MAIN INCONER 1250A 4P 50KA ACB EDO MICROPROCESSOR BASED SR 18GDRAW OUT TYPE RELEASE (O/C, S/C ) 220VAC - SUNT RELEASE 220VAC - UNDERVOLTAGE RELEASE 220VAC - CLOSING RELEASE 230V AC LED - PHASE INDICATOR RED, YELLOW, BLUE 500V - DIGTAL VIF METER3PH 1600/5A - METERING CTS , 5VA CLASS - 16A SP- MCB 10 KA C-CURVE 4-6 MM - CT and NAUTRAL TERMINAL 1.5/2.5 Sq mm - WIRING WITH COPPER WIRE INCOMER 1 ( DG SET ) 1000A 4P 50KA - ACB EDO MICROPROCESSOR BASED SR 18GDRAW OUT TYPE RELEASE (O/C, S/C ) 220VAC - SUNT RELEASE 220VAC - UNDERVOLTAGE RELEASE 220VAC - CLOSING RELEASE 230V AC LED - PHASE INDICATOR RED, YELLOW, BLUE 500V - DIGTAL V METER 3PH 1000/5A - METERING CTS , 5VA CLASS - 1 6A SP - MCB 10 KA C-CURVE 4-6 MM CT and NAUTRAL TERMINAL 1.5/2.5 Sq mm - WIRING WITH COPPER WIRE 6A SP MCB 10 KA C-CURVE 230V AC LED - PHASE INDICATING RED, YELLOW, BLUE 1.5/2.5 Sq mm - WIRING WITH COPPER WIRE 24VDC - BATTERY CHARGER OUT GOING 400ATP plus N 36KA DN3B-400D - MCCB WITH THERMAL-MAGNETIC 400ATP plus N 36KA DN3B-400D - MCCB SPREADER TERMINAL 400ATP plus N 36KA DN3B-400D- -MCCB HANDLE (ROM) with 4nos. soft starter panel/VFD BUS BAR MAIN BUS BAR CHAMBER OF 1250A FP ALUMINIUM WITH COLOR COATED HEADED SHRRINKABLE SLEEVES AND OUT GOING ACCORDING TO AMP. ACCESSORIES -THIMBLES, H/W, WIRE TIE, WIRE SLEEVE, ,PANEL DOOR LOCK, GASKET A ACB DGSET incommer supply 800A ACB with 4 nos. outgoing panel for running 200HP each motor including multifunction meters with each feeder. All the ACB/MCCB shall have potential free auxiliry contacts for on/off, trip function. Outgoings: i) 400A FP, 25 kA, MCCB (microprocessor based release with overload, short circuit, earth fault protection, 1 no. NO/NC auxiliary contact and shunt trip, RS-485 communication module similar to Legrand DPX3 250 or equivalent): 2 Nos. All the MCCBs shall have potential free auxiliary contacts for ON, OFF, TRIP All the MCCB shall have suitable rotory handle with facility for Pad locking Ul) All Breakers shall be provided with Shunt trip coil and auxillary contacts. iv) Insulated shrouding shall be provided for live parts v) FRLSH PVC insulated copper wires (not less than 2.5 Sq mm) shall be used for control wiring. vi) CT`s shall be provided with shorting terminals. vii) Earthing of LT panel should be done with in all respect. Approved Make:- Surya, LandT, Siemens, Schneider and ABB
Submersible Cable for pumping set up to 200HP motor pump set size of 95 sqmm. cable as per requirement from pump set to Junction box near sump. Approved Make:- Polycab, Finolex, Havells.
Construction of Staff quarter and JE office complete in all respect i/c all require fitting as per PWD specification and as per satisfaction of Engineer-In- Charge
Dismantling and Demolition Demolishing R.C.C. work by mechanical means and stockpiling at designated locations and disposal of dismantled materials up to a lead of 1 kilometre, stacking serviceable and unserviceable material separately including cutting reinforcement bars and Dismantling and Demolition Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge.
Providing, fixing, testing of Manual coarse screen of size 1500mm x3000mm of SS 304 with following material :- SS04 Channel 100X50X5,and Angle-640Kg SS Patti(32X5)-207Kg Fastner -20No. Chain pully ,Manually-01 L-Section 250X125 with MS Angle size 50X5 = 1025 KG MS Plate 400X400X12-46 Kg Tower Sal with chain -01 No I/c Fabrication hydra etc. and i/c diversion of sewage during installation. Make:- Jindal
Supply and erection of DN 1000 PN 10 Electromagnetic flowmeter (1000mm) for sewage water Technical Specifications for Electromagnetic Flowmeter Process Data Fluid : Sewage Water Operating Pressure : Please Specify Operating Temperature : 50 Deg. C. Electromagnetic Flow Sensor Model : Optiflux 2000 Type : Pulsed DC Meter size : Refer table below Flow tube : SS 304 Coil housing : Fully welded Sheet Steel, PU coated Liner : Hard Rubber Electrodes : SS 316 Grounding type : Rings Grounding ring material : SS 316 Process connection : Flanged to DIN PN10 (fully welded) Flanges : CS, SORF Area classification : Non-Hazardous Cable entry : M20 x 1.5 Protection class : IP 67 Electromagnetic Signal Converter Model : IFC 100 Cable length : 20 Meters. Mounting : Remote wall mounted Output : 4-20mA, HART plus Pulse/Frequency plus Status Accuracy : ± 0.5% of measured value Display : Large back lit LCD Display, fully programmable Parameters : Actual flow rate, totalized flow (10 digit), flow direction, flow velocity, conductivity, mass flow rate (at constant density) Diagnostics : Empty pipe detection, Electrode error, Noise, Coil temperature, Coil resistance, Conductivity etc Power supply : 85-250VAC, 48-63Hz Housing : Die cast Aluminium with PU finish Cable entry : M20 x 1.5 Area classification : Non-Hazardous Protection class : IP 67 Accessories : NA
Providing and fixing of DI Resilient seated Sluice valve 1000mm dia. PN-16, WRAS approved complete in all respect as per specifications. Make:- VAG,DVD,IVC’Nasik,Kirloskar
Operation and maintenance during defect liability period after three month trial run Trial run will be at the cost of agency.
Operation and maintenance in 1st Year
Operation and maintenance in 2nd Year
Operation and maintenance in 3rd Year
Percentage BoQ
BoQ_Ver3.0
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
HSR Items- Master sewerage scheme Faridabad: - Designing, re-construction and commissioning of 40 MLD MPS in place of existing intermediate pumping station complete in all respect including replacement of all electromechanical parts such as pumping machinery, panel board, DG set, transformer, cabling etc. and all delivery header, suction pipes and complete scope of work with all contingent works as per scope at Mujesar sector-24 Faridabad
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.16 MB
BOQ_573658.xls
BOQ • 0.29 MB
FI9YLKZ137505.pdf
Additional Documents • 1.90 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .