Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.4 LAccepted-AOC KRISHNAKRIPA KOTTARAKARA | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹7.7 L+₹14,678 (1.93%)Rejected-AOC | L2 | Rejected-AOC REJECTED |
| Sl No | Description | Qty | Unit | K K Associates L1 | DSK ELECTRIC POWER L2 |
|---|---|---|---|---|---|
| 1.00Installation of DG | |||||
| 1.00 | OD57998/2025-2026:Supply(Loading, Conveyance, Unloading), installation testing and commissioning of 20kVA DG Set with Acoustic enclosure as per CPCB IV+ norms and as detailed below 1. Engine a. Make of engine-Cummins/Greevs/Leyland b. Type of Engine - Diesel Engine c. No of Cylinders - As per manufactures standars d. Method of cooling - Water cooled with radiator e. Aspiration - Naturally Aspirated f. Design - Suitable for generating set operation g. Output - Suitable for generating set operation 2. Standard accessories with Diesel Engine a. Fly wheel b. Close Coupled c. Air cleaner d. Raditor with fan provided with fan guard e. Fuel Pump f. Mechanical governor g. Fuel filter h. Lubricating oil filter i. Residential type exhaust silencer j. Battery Charger / Generator 3. Engine Instument Panel with the following items a. Starting switch with key or button b. Lubricating oil pressure gauge c. Water temperature gauge d. RPM Indicator with hour meter e. Battery charging ammeter 4. Saftey Controls for Engine a. Battery control (trip) for low ludricating oil pressure b. Battery control (trip) for high water temperature. 5. Brushless alternator a. Make-Stamford/Crompton/LS b. Type - Self exited and self regulated c. Capacity - 20kVA/16kW @ 0.8PF d. System of Voltage - 3Phase, 415V, 4Wire system f. Speed - 1500 rpm. g. Frequecncy - 50Hz h. Insulation - Class F/H The alternator should confirm to IS 4722/IS13365. Operation and service manual shall be provided. 6. Fuel Tank-Suitable size fitted (built in type) inside the acoustic enclosure 7. Battery -Suitable size fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures required including battery charger 8. Standard control panel a. 40A 4Pole MCB b. 1 No multifunction meter suitable for display of current in 3Phases, voltage in 3Phases, frequency, power factor, KVA, KVAh, KW etc. c. 1 No separate KWH meter d. Instrument fuse/MCB f. Metallic DNB - 1No g. Solid state phase indication lamp for supply ON/OF with Fuse / MCB protection. 9. Warranty period 3 Year . | 1 | each | 5,16,000 ₹5,16,000 Lowest | 5,25,000 ₹5,25,000 |
| 1.00 | OD112066/2025-2026:Supply and filling high speed Diesel for generator | 60 | Litre | 107 ₹6,420 Lowest | 110 ₹6,600 |
| 1.00 | OD60352/2025-2026:Supply and installation of the following capacity Automatic Transfer Switch inside the existing
panel board including drilling holes in cubicle panel, making connections, etc. as required.
40A, 415 V, 50 Hz, AC 23 A duty, 4P Motorised inbuilt LCD Controller. | 1 | ach | 26,100 ₹26,100 Lowest | 27,000 ₹27,000 |
| 1.00 | OD66751/2025-2026:Supply and providing Blue colour LED indicator lamp, AC/DC, 22.5 cm cut out dia- | 2 | each | 123 ₹246 Lowest | 125 ₹250 |
| 1.00 | OD66752/2025-2026:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia- | 4 | each | 95 ₹380 Lowest | 100 ₹400 |
| 1.01 | OD112314/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 1.50 sq mm single run with required sockets. | 8 | metre | 42 ₹336 Lowest | 45 ₹360 |
| 1.01 | OD112315/2025-2026:Supplying and fixing 2A rating, 240/415 volts, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole | 3 | each | 370 ₹1,110 Lowest | 400 ₹1,200 |
| 1.01 | 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.
Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) | 1 | sqm | 3,500 ₹3,500 Lowest | 3,500 ₹3,500 Lowest |
| 1.01 | 90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet | 1.4 | metre | 8 ₹11.2 Lowest | 8 ₹11.2 Lowest |
Tender Value
₹7.5 L
EMD Value
₹18,748
Closing Date
29 Jul 2025, 4:00 pmClosed
Assistant Executive Engineer
Assistant Executive Engineer P.W.D Electrical Sub Division Kollam
MLA-SDF-2025-26, Kundara LAC-P.C Vishnunath M.L.A-Supply and installation of Diesel Generator at Primary Health Centre, Kottamkara, Kollam-General Electrical Work
2025_PWD_778646_1
PWD/BLDG/EST/10743/2025
Open Tender
Electrical Works
Item Rate
90 days
Kottamkara Kundara LAC
Please refer tender document
9 documents required · 9 mandatory
₹1,655
₹18,748
22 Aug 2025
23 Jul 2025
31 Jul 2025
23 Jul 2025
29 Jul 2025
23 Jul 2025
Amount
Installation of DG
OD57998/2025-2026:Supply(Loading, Conveyance, Unloading), installation testing and commissioning of 20kVA DG Set with Acoustic enclosure as per CPCB IV+ norms and as detailed below 1. Engine a. Make of engine-Cummins/Greevs/Leyland b. Type of Engine - Diesel Engine c. No of Cylinders - As per manufactures standars d. Method of cooling - Water cooled with radiator e. Aspiration - Naturally Aspirated f. Design - Suitable for generating set operation g. Output - Suitable for generating set operation 2. Standard accessories with Diesel Engine a. Fly wheel b. Close Coupled c. Air cleaner d. Raditor with fan provided with fan guard e. Fuel Pump f. Mechanical governor g. Fuel filter h. Lubricating oil filter i. Residential type exhaust silencer j. Battery Charger / Generator 3. Engine Instument Panel with the following items a. Starting switch with key or button b. Lubricating oil pressure gauge c. Water temperature gauge d. RPM Indicator with hour meter e. Battery charging ammeter 4. Saftey Controls for Engine a. Battery control (trip) for low ludricating oil pressure b. Battery control (trip) for high water temperature. 5. Brushless alternator a. Make-Stamford/Crompton/LS b. Type - Self exited and self regulated c. Capacity - 20kVA/16kW @ 0.8PF d. System of Voltage - 3Phase, 415V, 4Wire system f. Speed - 1500 rpm. g. Frequecncy - 50Hz h. Insulation - Class F/H The alternator should confirm to IS 4722/IS13365. Operation and service manual shall be provided. 6. Fuel Tank-Suitable size fitted (built in type) inside the acoustic enclosure 7. Battery -Suitable size fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures required including battery charger 8. Standard control panel a. 40A 4Pole MCB b. 1 No multifunction meter suitable for display of current in 3Phases, voltage in 3Phases, frequency, power factor, KVA, KVAh, KW etc. c. 1 No separate KWH meter d. Instrument fuse/MCB f. Metallic DNB - 1No g. Solid state phase indication lamp for supply ON/OF with Fuse / MCB protection. 9. Warranty period 3 Year .
OD112066/2025-2026:Supply and filling high speed Diesel for generator
OD60352/2025-2026:Supply and installation of the following capacity Automatic Transfer Switch inside the existing panel board including drilling holes in cubicle panel, making connections, etc. as required. 40A, 415 V, 50 Hz, AC 23 A duty, 4P Motorised inbuilt LCD Controller.
OD66751/2025-2026:Supply and providing Blue colour LED indicator lamp, AC/DC, 22.5 cm cut out dia-
OD66752/2025-2026:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia-
OD112314/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 1.50 sq mm single run with required sockets.
OD112315/2025-2026:Supplying and fixing 2A rating, 240/415 volts, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
OD60971/2025-2026:Supply and providing Extension of Exhaust pipe up to the roof top with 50mm MS pipe with bends, flanges etc. including paintng etc with standard accessories as per the direction of department staff at site (fire approved rate)
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.33:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 6 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
OD66750/2025-2026:Supply, laying and clamping of 1 no. 1.5 sqmm 6 core PVC/ XLPE insulated armoured control cables with copper conductors for working voltages up to and including 1100 V conforming to IS 1554 part I 1988 for PVC and IS 7098 Part I for XLPE with the cables, spacing of clamps with factory made clamp not exceeding 60cms, making good the damages , colour washing etc. as required.
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.1.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).4 core 10 sq mm
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
OD66758/2025-2026:Fire extinguisher:- Supply and installation of ABC type fire extinguisher 5kg capacity consisting of M.S cylindrical body, squeeze lever discharge valve fitted with pressure indicating gauge internal discharge tube, 30cm long high pressure discharge hose, nozzle etc.
OD60978/2025-2026:Supply and providing 3mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 11 KV dielectric strength.
OD60950/2025-2026:Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required.
OD60951/2025-2026:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD60954/2025-2026:Painting letters or figures of the follwing sizes with enamel paint as identfication mark to SB, DB, panel board etc as required. 2.5 cm, 4 cm, 5 cm height.
OD60952/2025-2026:Charges towards the preparation of necessary plan, scheme and other related papers for submission.
OD60953/2025-2026:Charges towards the preparation of necessary plan, scheme and other related papers for additional sheet.
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.8:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
OD63368/2025-2026:DSR ITEM :5.22 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete up to plinth level. SUB HEAD :5.22.3 Cold twisted bars Kg 74.50/kg
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD112208/2025-2026:Providing and supplying inaguration stone of tele black, size with inscription 0.4x0.3 cm and black 20mm thick granite stone.
OD112321/2025-2026:Amount to be deposited with K.S.E.L.B for scheme approval and energisation sanction.(Actual amount will be reimbursed on production of original documents) Non competitive item. Amount:16000.00
DSK ELECTRIC POWER (BID ID -2265019)
Bidder Name
K K Associates
DSK ELECTRIC POWER
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .