GE AF TEZPUR
GE AF TEZPUR TEZPUR PO SALONIBARI DISTRICT SONITPUR ASSAM 784104
CERTAIN REPAIRS TO OH LINE UG CABLES AND LT SYSTEM IN DOMESTIC AREA AT AF STN TEZPUR UNDER GE AF TEZPUR
2023_MES_603332_1
8873
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
TEZPUR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF TEZPUR
₹96,000
24 Jun 2023
15 Jun 2023
24 Jun 2023
15 Jun 2023
22 Jun 2023
17 Jun 2023
Amount
Dismantling of ACSR or AAC conductors, service feeder or distributor span complete all as directed.
Dismantling insulator any type, any size complete all as directed.
Dismantling cross arms of M S channels or angle sections etc complete all as directed.
Dismantling stay assembly complete all as directed.
Dismantling steel poles/struts, any size complete all as directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits,manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil , complete all as specified and directed.
Excavating in trenches, n exc 1.5 m wide and exc 1.5 m but n exc 3.0 m in depth; for foundation, etc. or for shafts, wells, cesspits,manholes, pier holes, etc. n exc 10 sq m on plan and exc 1.5 but n exc 3.0 m in depth and getting out in soft/loose soil , complete all as specified and directed.
Returning filling in soft/loose soil, including, spreading levelling watering and well ramming in layers not exc. 25 cm complete all as specified and directed.
Removing excavated soils to a distance not exceeding 50 Metres and depositing where directed at a level n. exc. 1.5 M above the starting point complete all as specified and directed.
Materials and Labour for plain cement concrete (1:3:6) Type C-2 using 40 mm graded aggregate in foundations, filling and mass concrete complete all as specified and directed.
Materials and Labour for plain cement concrete (1:2:4) type B1 using 20 mm graded aggregate in lintels up to 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings up to 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles and throating, as directed including necessary from work complete all as specified and directed.
Supply,laying, jointing and testing of LT, XLPE insulated, PVC sheathed,armoured, heavy duty electric cables with aluminium conductor for working voltage up to and including 1100 volts, of Cross sectional area 16 Sq. mm, 4 core, complete all as specified and directed.
Supply,laying, jointing and testing of LT, XLPE insulated, PVC sheathed,armoured, heavy duty electric cables with aluminium conductor for working voltage up to and including 1100 volts, of Cross sectional area 95 Sq. mm, 3 ½ core, complete all as specified and directed.
Supply,laying, jointing and testing of LT, XLPE insulated, PVC sheathed,armoured, heavy duty electric cables with aluminium conductor for working voltage up to and including 1100 volts, of Cross sectional area 185 Sq. mm, 3 ½ core, complete all as specified and directed.
Supply,laying, jointing and testing of LT, XLPE insulated, PVC sheathed,armoured, heavy duty electric cables with aluminium conductor for working voltage up to and including 1100 volts, of Cross sectional area 300 Sq. mm, 3 ½ core, complete all as specified and directed.
Supply and filling in dry sand in cable trenches before and after the cables are laid, as in sand cushioning to cables complete all as specified and directed.
Supply and laying sub class ‘B’, bricks, in cable trenches, as cable protection complete all as specified and directed.
Horizontal boring of holes, under road/ pavement / hard standing etc.,not exceeding 10 Metres in length, in any type of soil, suitable for passing through upto 80 mm bore, galvanised steel tubing,complete all as specified and directed.
Cutting chase for pass through cable protection pipe ,etc.in existing plain cement concrete pavement/ hardstanding/aprons etc. and making good, cutting in plain cement concrete (1:3:6) Type C1(using 20 mm graded aggregate),exceeding 20 cm but not exc 50 cm girth, complete all as specified and directed.
Supply and Laying galvanized steel tubing,32 mm bore, light grade, in trenches or fixed to poles/Walls etc, for cable protection, complete all as specified and directed.
Supply and Laying galvanized steel tubing,40 mm bore, light grade, in trenches or fixed to poles/Walls etc, for cable protection, complete all as specified and directed.
Supply and Laying galvanized steel tubing,50 mm bore, light grade, in trenches or fixed to poles/Walls etc, for cable protection, complete all as specified and directed.
Supply and Laying galvanized steel tubing,80 mm bore, light grade, in trenches or fixed to poles/Walls etc, for cable protection, complete all as specified and directed.
Supply and Erect, steel tubular swaged poles complete with cast iron base plate,finial taper plug, bolts, nuts & screws as specified, type 410 SP-31 (9.00 Metres Long), complete all as specified and directed.
Supply and laying or fixing or passing through pipe,PVC insulated, sheathed, unarmored multi stranded copper conductor cable, 3 core, 1.5 Sq mm size,1100 Volts grade, in connection to street light/flood light fittings from control box,including taking down existing unserviceable cable,complete all as specified and directed.
Supply and Fix in repair, Cable Junction Box, IP66 ‘halogen free and weather proof’, size 155 mm (W) x 210 mm (H) x 92 mm (D), with knock outs for cable entry for cable size 10-16 sq mm with 03 (Three) Nos.Grommets, IP 65, cable entry M 32, all as per Cat No. DK 1616 G & Cat No.EDK 32 (For Grommets) of Make “Hensel” or equivalent Model of Make ‘Sintex Industries Ltd’/'C&S Electric Ltd',fixed to wall/ pole with suitable aluminium strip clamp 25 X 3 mm, nuts, bolts and washers, including provision of 15 Amps,4 pole,open bakelite terminal block connector,complete all as specified and directed.
(ii) Indoor tape insulated,ring type,BPL (Bar Primary Low Tension) Current Transformers,Ratio 200/5A,Accuracy Class 1.0,Rated Burden 10 VA,Make AE/BCH/ L&T - 03 (Three) Nos. (iii) LED Indicator 16 mm with power consumption < 0.6W, LVGP & surge protection, 64/110 Volts AC/DC / 240 Volts AC (RYB) all as per Model No SIL of Make “L&T” or equivalent Model of Make BCH/ AE - 01 Set (Set of Three) (iv) Miniature circuit breaker (MCBs) single pole, 240 Volts, 10KA,C-curve,6 Amps [Cat No. BB10060C of Make L&T or equivalent Model of Make Legrand/ Hager/Seimens /GE/Schneider/ABB] - 03 (Three) Nos. INCOMING:- (i) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 200 Amps and 36 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable short-circuit settings: 6 - 10 x In [Cat No. CM92109OON1OG of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] - 01 (One) No. OUTGOING:- (i) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 63 Amps and 18 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In [Cat No. CM90518OOHO of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] - 01 (One) No. (ii) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 100 Amps and 18 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In [Cat No. CM90518OOKO of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] - 01 (One) No.
(iii) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 160 Amps and 25 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In.[Cat No. CM90642OOMO of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] – 02 (Two) Nos.
(ii) Indoor tape insulated,ring type,BPL (Bar Primary Low Tension) Current Transformers,Ratio 200/5A,Accuracy Class 1.0,Rated Burden 10 VA,Make AE/BCH/ L&T - 03 (Three) Nos. (iii) LED Indicator 16 mm with power consumption < 0.6W, LVGP & surge protection, 64/110 Volts AC/DC / 240 Volts AC (RYB) all as per Model No SIL of Make “L&T” or equivalent Model of Make BCH/ AE - 01 Set (Set of Three) (iv) Miniature circuit breaker (MCBs) single pole, 240 Volts, 10KA,C-curve,6 Amps [Cat No. BB10060C of Make L&T or equivalent Model of Make Legrand/ Hager/Seimens /GE/Schneider/ABB] - 03 (Three) Nos. INCOMING:- (i) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 200 Amps and 36 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable short-circuit settings: 6 - 10 x In [Cat No. CM92109OON1OG of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] - 01 (One) No. OUTGOING:- (i) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 63 Amps and 18 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In [Cat No. CM90518OOHO of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] - 05 (Five) Nos. (ii) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 100 Amps and 25 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting: 6-10 x In.[Cat No. CM91712OOKOOG of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] – 02 (Two) Nos.
(ii) Indoor tape insulated,ring type,BPL (Bar Primary Low Tension) Current Transformers,Ratio 200/5A,Accuracy Class 1.0,Rated Burden 10 VA,Make AE/BCH/ L&T - 03 (Three) Nos. (iii) LED Indicator 16 mm with power consumption < 0.6W, LVGP & surge protection, 64/110 Volts AC/DC / 240 Volts AC (RYB) all as per Model No SIL of Make “L&T” or equivalent Model of Make BCH/ AE - 01 Set (Set of Three) (iv) Miniature circuit breaker (MCBs) single pole, 240 Volts, 10KA,C-curve,6 Amps [Cat No. BB10060C of Make L&T or equivalent Model of Make Legrand/ Hager/Seimens /GE/Schneider/ABB] - 03 (Three) Nos. INCOMING:- (i) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 160 Amps and 36 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable short-circuit settings: 6 - 10 x In [Cat No. CM92108OOM1OG of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] - 01 (One) No. OUTGOING:- (i) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 63 Amps and 18 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In [Cat No. CM90518OOHO of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] - 01 (One) No. (ii) Moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 100 Amps and 18 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In [Cat No. CM90518OOKO of Make “L&T” or equivalent Model of Make Siemens/ Legrand / ABB.] - 02 (Two) Nos.
Materials and Labour for earthing complete with galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanised steel earth lead strip 32 mm x 6 mm by means of bolts, nuts check nuts and washers of galvanised steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 54 cm x 54 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia. MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil complete all as specified and indicated on electrical plate No 3 of SSR Part –I (2009) including testing on completion.
M/S A K MITRA
KAILSON
Shri A. K. Goswami
M/S N G CHOWDHURY
M/S Mandeep Singh
SHRI D. C. BISWAS
M/S SHIVAYA ENGINEERING
Singhs Construction
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .