Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.4 LAccepted-AOC CHANGANACHERRY GENERAL ELECTRICAL WORK | L1 | Accepted-AOC lowest |
Tender Value
Refer Docs
EMD Value
₹23,628
Closing Date
10 Sept 2024, 3:00 pmClosed
Assistent Executive engineer
PWD Electrical sub division Kottayam
DEPOSIT-SITC of Diesel Generator and airconditioning at newly proposed Training Centre Kurichi-Govt. Homeo Medical College Hospital, Kurichi-General Electrical Work
2024_PWD_683665_2
ESDK_ET_54_2024_2025
Open Tender
Electrical Works
Item Rate
120 days
Kurichi
Please refer Tender documents.
10 documents required · 10 mandatory
₹2,085
₹23,628
Yes
31 Oct 2024
2 Sept 2024
12 Sept 2024
2 Sept 2024
10 Sept 2024
2 Sept 2024
Amount
DG set
OD245379/2023-2024:Supply & Installation of 40 KVA Diesel Generator set including required control devices, protection such as suitable MCCB and earth fault relay using CT in neutral earthing conductor, and accoustic enclosure and DG set is to be Compliance with CPCB-4 plus norms and as per technical details given below on suitable size CC foundation. 1. Engine.a) Make of Engine - Krilosker/ Cummins/ Layland/ b).Type of Engine - Diesel Engine. c). No. of Cylinders - As per manufactures standards.d). Method of cooling - Water cooled with radiator e). Aspiration - Turbo charged after cooled f). Design - Suitable for generating set operation. g). Out put - Required HP as per manufacturers standards at 1500 rpm under NTP condition. 2). Standard accessories with Diesel Engine a). Fly wheel to suit flexible coupling b.) Close Coupling. c.) Air cleaner. d.) Radiator with fan provided with fan guard e). Fuel Pump. f). Mechanical governor. g). Fuel filter. h.) Lubricating oil filter. i.) Exhaust silencer. j). Exhaust Muffler k). Battery Charging Generator 3.) Engine Instrument Panel with the following items. a). Starting switch with key or button b). Lubricating oil pressure gauge. c). Water temperature gauge. d). RPM Indicator with hour meter. e). Battery charging ammeter. f). Fuel indicator 4). Safety Controls for Engine a). Trip for low lubricating oil pressure. b). Trip for high water temperature. c). Alarm for low fuel level 6). Brushless Alternator a). Make - Stamford/ LS/ Cummins/ KEL b). Type - Self exited and self regulated. c.) Capacity - 40 KVA/ 32.0 kW @ 0.8 PF d.) System of Voltage - 3 Phase, 415 V, 4 wire system e). Speed - 1500 rpm. f). Voltage regulation band - +/- 5% of rated voltage g). Frequency : 50 Hz h). Insulation - Class F / H The alternator should confirm to IS 4722 and warranted for 3 years. Operation and service manual , spares and tools shall be provided. 8. Fuel Tank Suitable size built in type integrated with the acoustic enclosure with full tank Diesel Fuel connection shall be done as per standards 9. Battery. Suitable capacity fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 10. Supplying and providing the standard Electric control panel integrated with acoustic enclosure comprising of the following. a) 80A,4Pole MCCB b) Digital Multi function meter with accuracy class 1 to read parameters such as KW, PF, voltage, Current Frequency etc: c) Digital type single function KWH meter with accuracy class 1, Exhaust Piping shall be vent to the top of the nearest tallest building if required . If the pipe cannot be clamped/fixed to the building or any other structure of permanent nature necessary fabricated structures using channel section or angle iron sections of adequate mechanical strength, duly painted with 2 coats of Heat retardant aluminium paint shall be provided for the support of the exhaust pipe. (Additional piping will be measured excluding the standard length of pipe supplied by the manufacturer.) including arranging load test at site or company assembly unit with presents of department staff .
OD245380/2023-2024:Supply and filling high speed Diesel for generator
OD245381/2023-2024:Supply and providing 12V,15A Automatic Battery charger suitable for 180Ah Battery, having . Full protection against battery overcharging & reverse polarity. Over voltage, overload & short circuit protection, reverse battery protection. Digital meters for voltage & current display , Battery connecting terminals with lead wire, Float and Boost Charging Mode , LED Indication for charger status indication, etc: and giving necessary connections as required
OD245382/2023-2024:Charges for conducting load test of 40KVA DG set at standardized Factory bed as per standard norms and condition. ie in various steps load up to full load for 3 hours & 10% over load for 20 minutes and the rate includes hire and rent of test bed equipment's, labour charges ,loading and unloading and fuel etc.The test certificate should be given the client in standard format
OD245383/2023-2024:Providing, laying, testing and commissioning of 'C' class heavy duty MS pipe conforming to IS:1239 I/c fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc fixing the pipe on the wall/ ceiling with suitable clamps and painting with two or more coats of synthetic enamel paint of required shade complete as required. 80MM
90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
90.12.5.28:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 35 sq mm
90.12.2.12:Supply and laying of one number additional PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground in the same trench in one tier horizontal formation including widening the trench by 20 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil)3 core 4 sq mm
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
90.12.10.4:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation77/63 mm or nearest size
OD245397/2023-2024:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia
OD245398/2023-2024:Supply and providing Blue colour LED indicator lamp, AC/DC, 22.5 cm cut out dia-
OD245403/2023-2024:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 1.50 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.
OD255537/2023-2024:Supply and installation of switch gear units in existing enclosure complete with handle assembly, door interlock and pad locking arrangement of 63A 4 pole on-load COS AC 23A duty
OD245404/2023-2024:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required- 2.50 cm, 4 cm or 5 cm height
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.3.3:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardSupply and providing 'U' section PVC beeding in the panel board
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.6:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG)
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
90.16.5.6:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.6. mm ( 4 SWG)
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.9:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
OD245405/2023-2024:Reinforcement for R.C.C works, bend tied and placed in position (plain grill requiring bend cold) using tor steel as required.
OD245406/2023-2024:Charges for preparation of Electrical/fire Drawing per A3 sheet first copy.
OD245407/2023-2024:Copying charges of Electrical/fire Drawing per A3 sheet additional copies
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
OD245411/2023-2024:Supply and providing 2mm thick Elastomeric fire retardant insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength.
90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface
1.1.2:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
90.3.19.3:Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
OD255558/2023-2024:Supply and installation of Type 1+2, Surge Protection Device having Configuration 3P+N , 4 module, Maximum Discharge Current - Imax up to 50KA, Iimp: 12.5KA, in the existing enclosure and giving connections as required , (L&T Mate or equivalent )
OD255559/2023-2024:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator -- 4 way, Glazed Door (For providing SPD)
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
OD255515/2023-2024:Fire extinguisher:- Supply and installation of ABC type fire extinguisher 5kg capacity consisting of M.S cylindrical body, squeeze lever discharge valve fitted with pressure indicating gauge internal discharge tube, 30cm long high pressure discharge hose, nozzle etc.
Bidder Name
M Y ASSOCIATES
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .