Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.5 LAccepted-Finance NARAYANGARH DOLTALA GHOLA CANNING PIN 743376 | CANNING | SOUTH 24 PARGANAS | WEST BENGAL | 743376 | L1 | Accepted-Finance Lowest Bidder | |
| 2 | L2₹4.6 L+₹8,878 (1.97%)Rejected-Finance | L2 | Rejected-Finance Higher Bid | |
| 3 | L3₹4.8 L+₹32,673 (7.23%)Rejected-Finance | L3 | Rejected-Finance Higher Bid |
Tender Value
Refer Docs
EMD Value
₹11,514
Closing Date
7 Feb 2024, 1:00 pmClosed
EE, South 24 Pgs Elect Divn
57/2 Diamond Harbour Road Kolkata -700 023
Proposed Repair and Renovation of Sarisha BPHC, Diamond Harbour-II Block in the District of South 24 Parganas - Internal Electrical Installation Works for BMOH Quarter.
2024_WBPWD_650758_1
WBPWD/EE/S24PED/eNIT63/2023-24
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Sarisha BPHC, Diamond Harbour-II
Please refer Tender documents.
4 documents required · 4 mandatory
₹11,514
South 24 Pargana Electrical Division
20 Jun 2024
19 Jan 2024
9 Feb 2024
19 Jan 2024
7 Feb 2024
31 Jan 2024
31 Jan 2024
Amount
S&F 250V, (6-16)A per way, SPN MCBDB way with SS enclosure double-door(Ivory White with IP-42/43 protection with DP Isolators as incomer and SPMCBs ('C' Curve, 10kA) as outgoing,on the surface of the wall with fastners & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as per GS. i) 2+12 way SPN DB - 1 no. ii) I/C - 240V, 40A DP Isolator - 1 no. iii) O/G - 240V, 6-16A SP MCB - 12 nos. [Make - Legrand/Siemens/Havells/ABB]
Supplying and fixing MCB SS enclosure with IP-20/3 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachmen . with following item. i) 2 way SPN DB - 1 no. ii)32A MCB---2 Nos. iii) Neutral BAR--1no. [Make - Legrand/Siemens/Havells/ABB]
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm)single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed] Average run 8 mtr
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC On Board
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required
a) 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
b) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC [16A Socket, (2x15A)Computer board]
c) 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC [AC & Giser]
2x80/0.4 (10 sqmm) + 1x84/0.3 (6 sqmm) as ECC [ m/s to SPN DB]
Cutting channel of 40 mm x 40 mm size on masonry wall incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire as fish wire incl. mending good damages to building works i) 19 mm dia 3 mm thick polythene pipe without earth continuity wire
Cutting channel of 43 mm x 43 mm size on masonry wall incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire as fish wire incl. mending good damages to building works i) 25 mm dia 3 mm thick polythene pipe without earth continuity wire
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
a. 2×2.5 + 1×1.5 sqmm
b. 2×4 + 1×2.5 sqmm
e. 2×10 + 1×6 sqmm
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wire etc
Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Brand approved by EIC), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 16 Module GI Modular type switch board with 2 row 16 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. (Computer Board)
Supply & Fixing 240 V, 3 nos. 16 A, 3 pin Modular type plug socket with 3 nos. 16A Modular type switch (Brand approved by EIC), 20A Modular switch type SP MCB (C-Curve) and Indicator without plug top on 12 Module GI Modular type switch board with 12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wire etc
Supply & Fixing 240V, 25A, 3 pin Modular type plug socket (Brand approved by EIC), with plug top, on 2 module GI Modular Switch Board complete with top cover plate flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works. (For AC)
Supply & Fixing 240V, 25A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply and delivery of Single LED Fitting (18Watt, 230VAC, 50hZ, 4000K NW, THD<10%, bult in 2.5KV SPD) with all accessories and 1 nos LED Tube, as directed by EIC. [Make: Philips Havells, Bajaj, CG, Wipro or as per EIC] (Luminous efficiency > 105 & <120 Lumen/watt. The LED Luminaries & accessories shall have BEE certification)
Supply and delivery of Twin LED Fitting (18Watt, 230VAC, 50hZ, 4000K NW, THD<10%, bult in 2.5KV SPD) with all accessories and 1 nos LED Tube, as directed by EIC. [Make: Philips Havells, Bajaj, CG, Wipro or as per EIC] (Luminous efficiency > 105 & <120 Lumen/watt. The LED Luminaries & accessories shall have BEE certification)
Fixing only single/twin florescent light fitting complete with all accessories Directly on wall/ceiling with HW block and suitable size MS fastener, Ceiling plate, nipples etc. as required
Supply & Fixing of 220-240 V B22 9 Watt CDL/ 6500K LED Lamp as per EIC (Make-Havells Cat no.LED ADORE PLUS 9W B22 CDL 3 STAR LAMP, Philips/Crmpton)
S&F angular batten holder (Anchor) on 75mm dia PVC round block / round bakelite on wall/ceiling.
Supply & delivery of 1200 mm sweep 230 volt AC Ceiling fan incl. Blades, canopy etc. With 18" down rod(14SWG), Fork(10SWG), Heavy type insulator, 3/8th inch bolt with nut, heavy type split pin etc.with safety wire & PS2 type capacitor, as directed by EIC. [Make-Orient - Summer cool (1200 mm Metalic Bronze Copper) or similar spec of Crompton/Usha - Striker 1 Star (Safety Wire & S3/P2 Capacitor)]
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. As per GS
Supplying & Fixing iron beam fan clamp of two piece type, as per approved specification, fabricated from 40 mm x 9 mm MS sheet flat suitable for beam having flange upto 150 mm wide – (As per Drawing no. 476 of PWD Specification Book – May 1991) As per GS
Supply & delivery of wall Fan 450 mm (Make-Havells/Orient-Tornado - Wall II/CG/Usha)
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20PVC insulated flexible copper wire 0.5 mt. length
Supply and delivery of 230V 230mm (9") Exhaust fan with all necessary accessories, as directed by EIC. [Make: EPC Heavy Duty, Usha, CG, Bajaj or equiv Make]
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter: As per GS b) 23 cm (9")
Fixing only louver shutter/cowl on wall with necy. bolts & nuts (6 mm dia x 62 mm long) As per GS b) For 23 cm (9") Exhaust fan
Earthing with 50mm dia GI pipe (ISI-M) 3.64mm thick x 3.04 Mts. long and 1x4 SWG GI (Hot Dip) wire (4 Mts. long), 13mm dia x 80mm long GI bolts, double nuts, double washers incl. S&F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under-ground level and partly above-ground level driven to an average depth of 3.65 Mts. below the ground, as per GS.
Excavation of soil for installation of Earth Electrode and filling & ramming, for Soft Soil, as per GS.
S&F earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as reqd., as per GS.
Connecting the equipments to earth busbar incl. S&F 2x8 SWG GI (Hot Dip) wire on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as reqd. & mending good damages as per GS.
S & F Lightning conductor Air-terminals made of 15 mm dia 1500 mm long GI pipe (ISI Medium) having five prongs of 4 SWG GI (Hot Dip) wire at top with 85 mm dia 6 mm thick GI base plate at bottom incl. necessary holes etc. duly grouted on the parapet etc. in CC mortar (4:2:1)
Supply & fixing GI (Hot Dip) strips 20 mm x 3 mm thick for horizontal run on the Parapet/Roof/ Wall with GI Saddles 1100 mm apart incl. mending good the damages to building works
Supply & fixing of GI (Hot Dip) strips 20 mm x 3 mm thick for vertical run on wall with GI saddles spaced not exceeding 1000 mm apart incl. mending good damages to building work..
Cutting cornices/ steps etc. including cutting recess in buildings etc. & supply & fixing 15 mm bore (ISI-Medium) GI pipe protection as below and mending good damages to the building works.
(a) Length upto 0.5 Mtr
(b) Length above 0.5 Mtr
Making soldered joints between conductors, conductors and air terminals for 4 SWG GI (Hot Dip) wire incl. supply of jointing materials and painting with 2 (two) coats of bituminous paint.
Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation, per storey of building per vertical run( for G+1)=2 storied for 5 nos earthing =10nos.
Supply & Fixing of Testing Joints by 20 mm x 3 mm thick GI (Hot Dip) strip 125 mm long grouted on wall having clearance of 6 mm from wall for making connection with thimbles at the end of 7/10 SWG GI (Hot Dip) stranded Wire and 4 SWG GI (Hot Dip) wire of vertical conductor and conductor from earth electrode complete with S & F thimbles, GI bolts, nuts, check-nuts, spring washers etc. as required.
Excavation of soil for installation of Earth Electrode and filling & ramming for soft soil.
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the groundlevel ( ISI Medium Pipe)
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe.
Extra for treatment of soil by using salt & charcoal or coke for pipe electrode.
Note: 1) All the above rates should be quoted inclusive of all taxes & duties, District charges and LWC as applicable, with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees.
M/S. TOAD TO TOWER
ASIAN ELECTRICAL & ENGINEERING WORKS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .