TENDER TO MAINTAIN FIREFIGHTING SYSTEM, UTILITY MAINTENANCE, VALVE SALVAGING AND MANAGEMENT OF ENGINEERING STORE AT JHANSI LPG PLANT Following documents has been uploaded for bidder 1. Annexure 1- Scope of work 2. Annexure 2- Special Terms & conditions 3. Annexure 3- General Conditions of Contract 4. Annexure 4- GCC amendments 5. General instructions to vendors for e-tendering Bidder should read, acknowledge all the forms and provide acceptance in Bid common form.
10097
1000399628
Limited Tender
Works
Jhansi LPG Plant
9 Feb 2023
24 Jan 2023
7 Feb 2023
24 Jan 2023
7 Feb 2023
24 Jan 2023
No. Job Description SAC Code Quantity UOM Unit Rate GST@ 18% Total Amount
Monitoring and managment of Fire Fighting system of location for checking/ maintenance of 1 Deluge
Valve, 1 hydrant, 1 monitor, fire engine operation , first aid box checking, 1 gate valve, fire trolley checking,
fire fighting air compressor , jockey , fire water tank ( every day one FF equipment to be taken so that all
equipments are coveren in a month and system is ready round the clock) covering PMS schedule and
record maintainence of the same so that there is NIL leakage in the fire fightinh system viz.gate
1 valve,Hydrants & Monitor,Fire Pumps etc. including any breakdown maintanance to be attended on top
998441 24 Month
priority as advised by the officer concerned,overall managing of FWPH and Engineering Store ( as per
scope of job,as directed by officer incarge and maintenace of records of store including records for
hazardous waste and inventory updation in computer ) as per SOP as directed by Officer Incharge (HSSE )
and Maintenance Incharge.also at times urgent Refilling of Used DCP fire extinguisher( During drills and
safety trainings)
Fire Hoses testing :Testing of fire hose: 64 nos.
All hoses has to be brought to site, hydrotested, test date & next due date to be painted and
proper records to be maintained and submitted in the format provided by BPCL. rate to be
quoted for each hose as per SOP
LPG Hose testing :130 nos. quaterly testing and record keeping All hoses has to be brought
to site, hydrotested, test date & next due date to be painted and proper records to be
maintained and submitted in the format provided by BPCL. rate to be quoted for testing each
hose as per SOP
Pressure / temperature gauge testing : 100 Presure gauge and 30 Temperature gauge : Half
yearly All gauges has to be brought to site,test as
4 per porcedure,SOP and test date & next due date to be painted and proper records to be 998441 260 Each
maintained and submitted in the format provided by BPCL. rate to be quoted for each
temperature or pressure gauge as per SOP
Sprinklar Cleaning :Sprinkler cleaning on quarterly basis including reparing jobs and testing of
spary density as per OISD Guidelines and as directed by officer incharge as per SOP,basically
all sprinklers to be removed,lines to be flushed for foreign particles responsible for chocking
5 of sprinklers and again spray density to be checked after tightening the nozzles so that NIL 998441 60 Each
sprinklers are chocked and no bad comments during surprise checking of system.
Providing semi skilled manpower for Miscllaneous extra fire fighting works in view of Audits,
VIP visits, night shift etc.
Quarterly cleaning of stariner of DV sucction line and bypass line + 2 stariner of jockey pumps
+ 5 No. of LPG strainer as per SOP and as directed by Officer Incharge, test date & next due
7 date to be painted and proper records to be maintained and submitted in the format 998441 132 Each
provided by BPCL
Quarterly cleaning of stariner of Fire Engines, test date & next due date to be painted and
8 proper records to be maintained and submitted in the format provided by BPCL as per SOP 998441 12 Each
and as directed by officer incharge
Valve Salvaging as per SOP displayed as directed by officer incharge. Collection of rejected SC
9 vaslve in a empty soap drum with proper counting and record and also to secure the drum 998441 50000 Each
when it get fully filled..
Management of Engineering Store ( as per scope of job,as directed by officer incarge and
maintenace of records of store including records for hazardous waste and inventory
10 updation in computer ) as per SOP as directed by Officer Incharge (HSSE ) and Maintenance 998441 12 Month
Incharge.also at times urgent Refilling of Used DCP fire extinguisher( During drills and safety
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
10097.zip
zip • 2.83 MB
BUDGETDOC_10097.pdf
pdf • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .