Loading…
Loading…
Tender Value
₹54.8 L
EMD Value
₹55,000
Closing Date
29 Jul 2026, 6:00 pmClosed
Executive Engineer, Irri. Mech. Dn. No.1, Vadodara
Providing and Erecting of Street Light, Cable, Cable tray, Earthing Works, Stabilizer and Power Panel at Karjan Dam.
323517
NIT-06 of 2026-27
Open
Electrical - All
Works
Vadodara
14 documents required · 14 mandatory
₹2,400
Executive Engineer, Irrigation Mechanical Division No.1, Vadodara
₹55,000
14 Jul 2026
14 Jul 2026
14 Jul 2026
29 Jul 2026
14 Jul 2026
BILL OF QUANTITIES
BILL OF QUANTITIES
1. The bill of Quantities shall be read in conjunction with the Instructions to Bidder,
Conditions of Contract, Technical Specifications and Drawings.
2. The quantities given in the Bill of Quantities are estimated and provisional, and are
given to provide a common basis for bidding. The basis of payment will be the actual
quantities of work ordered and carried out, as measured by the Contractor and verified by
the Engineer and valued at the rates and prices tendered in the priced Bill of Quantities,
where applicable, and otherwise at such rates and prices as the Engineer may fix within
the terms of the Contract.
3. The rates and prices tendered in the priced Bill of Quantities shall, except in so far as
it is otherwise provided under the Contract, include all constructional plant, layout,
supervision, materials, erection, maintenance, insurance, profit, taxes and duties,
together with all general risks, liabilities and obligations set out or implied in the Contract.
4. The rates and prices shall be quoted entirely in Indian Currency.
5. A rate or prices shall be entered against each item in the Bill Quantities, whether
quantities are stated or not. The cost of Items against which Contractor has failed to enter
a rate or price shall be deemed to be covered by other rates and prices entered in the Bill
of Quantities (in case of Item rate contract).
6. The whole cost of complying with the provisions of the Contract shall be included in
the items provided in the priced Bill of Quantities, and where no Items are provided
the cost shall be deemed to be distributed among the rates and prices entered for the
related items of Work.
7. General direction and descriptions of work and materials are not necessarily
repeated or summarized in the Bill of Quantities. References to the relevant sections
of the contract documentation shall be made before entering rates or prices against
each item in the Bill of Quantities.
8. The method of completed work of payment shall be in accordance with the
specification for Road and Bridge works. For building works specifications for
building are to be followed.
9. Errors will be corrected by the Employer for any arithmetic errors pursuant to
Clause 29 of the Instructions to Bidder.
10. Rock is defined as all materials which, in the opinion of the Engineer, required
blasting, or the use of metal wedges and sledgehammers, or the use of
compressed air drilling for its removal, and which cannot be extracted by ripping with a
tractor of at least 150 kw with a single rear mounted heavy dutyripper.
BILL OF QUANTITIES
Name of Work: Providing and Erecting of Street Light, Cable, Cable tray, Earthing Works
Stabilizer and Power Panel at Karjan Dam.
Items Quantities Item of Work Estimated Unit Total amount
Items Quantities Item of Work Estimated Unit Total amount
No. estimated Rates(In according to
figures) estimated
1 1 Supplying 3 Phase Isolation Transformer 253858.28 No.
followed by 3-Phase automatic digital micro
processer. based servo control voltage
stabilizer, air cooled, with indoor enclosure
with bottom cable entry with MCB at input &
contactor at output for tripping at various fault
condition. Stabilizer suitable for unbalanced
input voltage & unbalanced load. Protection
for over voltage, under voltage, over load,
short circuit & single phasing preventer. With
LCD display, with back light for displaying
input/output voltages & load current along
with fault/trip messages/Class-C surge
protection device included copper wound
winding.Input: 320‐500/400V, 3‐Phase,
Hz, 3‐Wire + Earth, Output: 400VAC+/-1%,
3‐phase, 4‐Wire + N + Earth FOLLOWING
(a) Rating 40 KVA[ Approved Make-
Voltamp, Kiloaskar, L&T, Siemens]
2 80 Supplying and erecting LED street light / 3345.12 No.
Flood light fittings with High power White
LEDs wattage of 3 Watt and above
assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High
pressure die cast aluminum housing with
smooth finish powder coated and heat sink
extruded aluminium with diffuser and
Polycarbonate optics/ lenses, with toughened
glass with company mark/name engraved or
embossed 160 to 270 V,Power Factor more
than 0.95, THD < 10 %, CCT 3000 K to
5700K,Uniformity ratio >0.45, Luminaire
efficacy> 100 lumens/watt . LED driver
efficiency > 85 %.( fittings required LM-79 &
LM-80 certificates)(NOTE: Below description
have shown ranges of Wattage capacity of
LED fittings.The Engineer incharge may
select any wattage capacity between the
ranges shown.)(A) Street Light (IP-65), Surge
protection -4KV integral and ,Light must have
440VAC line supply with over-voltage
protection. (a) 48 watts [Approved Make -
Philips, Wipro, Crompton, Havells, Surya,
2a 24 (b) 250 watts [Approved Make - Philips, 10818.11 No.
Wipro, Crompton, Havells, Surya, Bajaj,
3 1200 Supplying and erecting Flexible PVC 46.46 Mtr.
insulated multi strand multi core 1.1 kv grade
ISI marked copper wires of following size to
be erected as directed.
(a) 1.50 Sq.mm 3 core round PVC sheathed
[Approved make - Polycab, Havells,
RRKabel, Finolex, Anchor]
4 400 Supplying and erecting Flexible PVC 284.82 Mtr.
insulated multi strand multi core 1.1 kv grade
ISI marked copper wires of following size to
be erected as directed.(a) 3 1/2 core 50 Sq.
mm ( 25 Sq. mm 1/2 core) [Approved make
- Polycab, Havells, RRKabel, Finolex,
5 180 Providing and, fixing heavy duty flange type 38.38 No.
brass cable gland with rubber ring for PVC
insulated armoured cable complete with out
going tails, insulating tape etc for following
size of cables.
(a) 4 core 6 Sq. mm
5a 60 (b) 4 core 10 Sq. mm 38.38 No.
5b 20 (c) 4 core 16 Sq. mm 47.47 No.
5c 30 (d) 4 core 25 Sq. mm 51.51 No.
6 30 Providing and, fixing heavy duty flange type 75.75 No.
brass double compression type cable gland
with rubber ring for PVC insulated armoured
cable complete with out going tails, insulating
tape etc for following size of cables.
(a) 3 & 1/2 core 35/50 Sq. mm
7 500 Solder less crimping type Aluminium lugs 6.06 No.
conforming to IS suitable for cable of
following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut bolts
in an approved manner. (a) 1.5/ 2.5/4/6
8 100 Providing & Erecting perforated G.I. Cable 698.16 Mtr.
Tray size as below with all necessary
accesS.O.R.ies for fitting like coupler S.S.
Nut bolt.Cable tray with cover fabricated from
G.I.M.S.sheet having thicknes 2 mm.
(a) Cable tray size 100 x 50 x 2 mm
8a 200 (b) Cable tray size 200 x 100 x 2 mm 1133.83 Mtr.
8b 600 (b) Cable tray size 300 x 100 x 2 mm 1606.99 Mtr.
9 480 Providing , erecting , fabricating the M.S. 77.77 Kg
structure as per requirement on site
incorporating proper size of M.S.
angles,square,round, flats, bars, channels,
sections complete with cutting, welding,
grinding & finishing duly painted with one
coat of red oxide with erection on site as per
direction of engineer in charge with
necessary grouting, cementing, plastering &
finishing complete.
10 400 Providing & laying approved make ISI 249.47 Mtr.
marked HDPE 6Kg / cm2 (Class-3) as per
IS:4984:1995 PE-80 to be erected at road
crossing on or floor as directed for laying of
cable. The pipes as following size of dia &
weight per 6 mtr.(A) 63 mm inner Dia.
[Approved Make - Dutron, Universal,
Duraline, Gamson, Dolphin, Rudra]
11 100 Supplying and erecting B class Galvanized 326.23 Mtr.
iron pipe having smooth finished bore of the
pipe on both ends erected nuts and bolts
along the pole / wall shaping the pipe as per
site requirement. Pipe dia as following.
12 100 Painting of street light pole with bracket 215.13 No.
complete with two coats of Aluminium paint
for following size of pole.
(A) up to 4 mtr
12a 80 (B) up to 6 mtr 265.63 No.
13 120 Supplying & erecting approved make SMC 515.10 No.
press moulded composite FRP. loop-in, loop-
out approx. 2mm thick box complete with
Bakelite connector strip 5way(3P+N+E),DIN
rail for mounting mob & hinged doors as per
requirement having locking arrangements
with mounting clamp with nuts, bolts &
washers suitable for erection on pole with
cable clamps& earth bolt of following size of
(A) 250mm x 200mm x 100mm [deep]
[Approved Make - Sintex, National, EPP,
Hensel, Green composites]
14 2000 Providing and erecting XLPE (IS:7098)(I)-88 140.39 Mtr.
ISI armoured cable multistrand / Solid
Aluminium conductor for 1.1 KV. to be laid
on wall with necessary clamps or in existing
trench / pipe of following size of cables.(A)
core 10 Sq. mm [Approved Make - Avocab,
Havells, Finolex, RRKabel, L&T, Polycab]
15 2 Supplying and erecting triple pole & neutral 10559.55 Rn.Mtr.
440V / 500V panel mounting Copper Busbars
with four equal Nos. of electrolyte bus having
current density not more than 1.6 Amp. /
sq.mm (Rated current / cross section area)
duly wrapped with colour insulating tape for
phase sequence of following current carrying
capacity, erected with necessary bus bar
supports /insulators, main cable socket to
each bar, erected in existing cubical panel
with necessary connections.
(A) Suitable for 630 Amp. capacity
16 3 Supplying and erecting approved make 43.43 No.
suitable panel indicator LED type lamp, lens
cover, complete erected with necessary
17 1 Supplying and erecting approved make panel 1275.63 No.
mounting type Digital Voltmeter having
digits LED display, 0 to 750 AC Volts range
erected on existing panel board with all
connection, wiring etc .with manufacturers
calibration certificate.[Approved Make-Gelco,
Meco, Schneider, Siemens, Techno]
18 1 Supplying and erecting approved make panel 1558.43 No.
mounting type Digital Ammeter having
digits LED display, external CT operated,
calibrated for 0 to 1000 Amps suitable to
operate on 500 Volt AC , erected on existing
panel board with all connection, wiring etc
.with manufacturers calibration certificate.
[Approved Make-Gelco, Meco, Schneider,
Siemens, Techno]
19 3 Providing & erecting L.T. Current 274.72 No.
Transformer with bar primary 50/5 to 1000/5
ratio 15 VA burden erected in existing CRCA
box duly secured with insulating materials
connected to the meter
20 2 Supplying and erecting Ammeter / Voltmeter 317.14 No.
selector switch for 3 phase AC Supply 500 V
on existing panel board with necessary
21 3 providing and erecting Miniature circuit 112.11 No.
breaker single pole 6A to 25A suitable to
operate on 240 V A.C. system and having
breaking capacity 10 KA to be erected in
existing box. confirming to IS 8828/1996 with
ISI Mark [Approved Make - Schneider, L&T,
ABB, Siemens, Havells, MDS, C&S]
22 1 Supplying & erecting approved make Four 22255.35 No.
Pole 415V change over switch interior for
panel mounting with operating mechanism
A.C.23 duty confirming to IS for
(A)400A [Approved Make - Schneider, L&T,
ABB, Siemens, Havells, MDS, C&S]
23 1 Providing and erecting Approved make Four 28173.95 No.
pole moulded case circuit breaker having
breaking capacity ICU of 50 K.A. and above
at 415 V having normal current rating up to
630A. with variable thermal & magnetic
release suitable to work on A.C.supply 50 c/s.
with all internal connections, spreader tinned
copper & complete erected in existing
G.M.S. housing ICS=100% of ICU only
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
24 1 Providing and erecting Approved make Four 25228.79 No.
pole moulded case circuit breaker having
breaking capacity ICU of 50 KA and above at
415 V having Normal current rating 400A.
with variable Thermal & magnetic release
suitable to work on A.C.supply 50 c/s. With all
internal connections, spreader tinned copper
& complete erected in existing 16 G.M.S.
housing. ICS=100% of ICU only
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
25 3 Providing and erecting Approved make Four 20946.39 No.
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. and above at
415 V . having normal current rating 250A.
with variable thermal & magnetic release
suitable to work on A.C.supply 50 c/s. with all
internal connections, spreader tinned copper
& complete erected in existing 16 G.M.S.
housing. ICS=100% of ICU only
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
26 3 Providing and erecting Approved make Four 16221.61 No.
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having Normal current rating 200A.with
variable Thermal & magnetic release suitable
to work on A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing
G.M.S.housing ICS=100% of ICU only
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
27 3 Providing and erecting Approved make Four 8055.76 No.
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having normal current rating 125A. with
Fixed thermal & magnetic release suitable to
work on A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
housing.ICS=100% of ICU only
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
28 3.75 Providing & erecting weather proof, dust & 14902.55 Sq mtr
vermin proof, floor mounted front operated
indoor type cubical panel board necessary
IP-42 and above protection as per approval
from engineer incharge made from 14 SWG
thick CRC M.S. sheet for outer body & doors,
16 SWG thick CRC M.S.sheet for internal
partitions with necessary accesories
supporting angles/ flats channel including
cutting, bending, drilling, welding, riveting with
internal partitions & cable alley as per
requirements & instruction of engineer-in-
charge with erection of supplied switch gears,
BUSBARS, suitable size of inter connecting
PVC copper wire / copper-aluminium strips,
rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments, earth
bus & earth bolts, foundation flange - bolts-
base Plates, sufficient nos. of hinged doors,
handles with locking arrangement and rubber
gasket,heavy duty end terminal
connection,danger notice board,necessary
ventilation,earthing strip complete. The Panel
shall be painted with epoxy powder coating.
(The rates excludes the cost of switchgears,
bus bars, inter connecting mains & Copper
Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base
beams) The panel shall be supplied with
following approved manufacturers with
following size.The panel size: 2.5 mtr(W) X
1.5 mtr (H)(A) The standard companies
switch gear shall be used and only
manufacturers at CPRI approved factory (i)
with 350mm depth [Approved make- Make
will be approved by Engineer-in-charge]
29 100 Providing and erecting XLPE (IS:7098)(I)-88 79.79 Mtr.
ISI armoured cable multistrand / Solid
Aluminium conductor for 1.1 KV. to be laid
on wall with necessary clamps or in existing
trench / pipe of following size of cables.(A)
core 4 Sq. mm [Approved Make - Avocab,
Havells, Finolex, RRKabel, L&T, Polycab]
30 2000 Providing and erecting XLPE (IS:7098)(I)-88 140.39 Mtr.
ISI armoured cable multistrand / Solid
Aluminium conductor for 1.1 KV. to be laid
on wall with necessary clamps or in existing
trench / pipe of following size of cables
(A) 4 core 10 Sq. mm [Approved Make -
Avocab, Havells, Finolex, RRKabel, L&T,
31 1500 Providing and erecting XLPE (IS:7098)(I)-88 153.52 Mtr.
ISI armoured cable multistrand Aluminium
conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe
of following size of cables
(A) 4 core 16 Sq. mm [Approved Make -
Avocab, Havells, Finolex, RRKabel, L&T,
31a 1330 (B) 4 core 25 Sq. mm [Approved Make - 190.89 Mtr.
Avocab, Havells, Finolex, RRKabel, L&T,
32 400 Providing and erecting XLPE(IS:7098)(I)-88 220.18 Mtr.
ISI armoured cable multistrand Aluminium
conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe
of following size of cables
(A) 3 1/2 core 35 Sq. mm ( 16 Sq. mm 1/2
core) [Approved Make - Avocab, Havells,
Finolex, RRKabel, L&T, Polycab]
33 12 Providing approved make junction box 20200.00 No.
outdoor type made from 1.6 mm thick
Stainless steel AISI 304. Confirm to IS
part-V Sheet .The box size 400 mm x300mm
x250mm deep . The junction box provided
with 1 nos 63A 4 pole MCB
(C&S,L&T,siemens, havells make only),cable
termination kit suitable for 70sqmm to
120sqmm cable, 63Amp industrial-socket,
complete with internal wiring
sq.mm copper wire & suitable lugs,
necessary Accessories The box shall be
provided with front hinged door And locking
arrangement, rubber packing,bakelite sheet
for erection of above items in junction box
and Danger notice board on door. (Welding
Junction box at Spillway) [Approved Make -
Sintex, National, EPP, Hensel, Green
34 3 Supplying approved make Junction Box 21478.41 No.
outdoor type in two compartments made from
1.6 mm thick Stainless steel AISI 304 confirm
to IS 1570 part-V Sheet .The power
compartments size 400 mm and Control
compartment size 200 mm Junction box sizes
600 x 600x 300 mm with 300 mm leg made
from 35x35x3 mm angle complete fabricated.
The junction box provided with 3 Nos 32 A
MCB FP (C&S, L&T, Siemens) & 1 nos 63A
pole MCB (C&S, L&T, Siemens) complete
with internal wiring 4 sq.mm copper wire &
suitable lugs. All necessary AccesS.O.R.ies
including the item. The box shall be provided
with front door hinged at one end. And
locking at other end, rubber packing should
be provided on closing door. And having
cover inside for M.C.B.& Danger notice board
on door.[Approved Make - Sintex, National,
EPP, Hensel, Green composites]
35 10 Supplying and erecting approved make 5556.01 No.
Octagonal pole made from HR sheet steel.
The pole should be made as per IS. and shall
be coated with hot dip galvanizing as per IS
2629/2633/4759, suitable suspend local wind
speed with integral Junction box consist of
terminal plate of min 6mm Hylam sheet,
standard profile 35mmX7.5mm Din-Rail for
MCB Mounting, stud type terminal and
arrangement for cable termination to be
erected With Suitable foundation (Included)
as per details given by manufacturer
considering site requirement.(A) 4 Mtr. Long
70 mm Top X 130 mm bottom dia, 3 mm
thickness with 200mmX200mmX12mm base
plate, 4-M16 Bolts and 450mm long with
necessary G.I. J Bolts .Approx weight 37 kg
[Approved Make- Utkarsh, Bajaj, RR ISPAT,
FAB, Crompton, Tranrail]
35a 40 (B) 5 Mtr. Long 70 mm Top X 130 mm 6874.06 No.
bottom dia, 3 mm thickness with
200mmX200mmX12mm base plate, 4-M16
Bolts and 600mm long with necessary G.I. J
Bolts .Approx Pole weight 46 kg [Approved
Make- Utkarsh, Bajaj, RR ISPAT, FAB,
Crompton, Tranrail]
36 50 Supplying and erecting Street light pole 491.87 No.
bracket comprising main B Class GI pipe of
4.2 cm/require outside dia. complete with
suitable B Class G.I. sleeve tubing of approx.
45cms.length and suitable for
76.5mm/80mm/require size of pole top having
nuts and bolts for fixing the brackets and
having spread of 0.5 mtr. Length with
deg.with vertical plane and suitable welded
stiffener reducer and nipple with check nut
complete painted with one coat.of Red oxide /
PU base primer and two coats of Aluminium /
PU paint. paint with following nos of arms.
[A] Single Arm bracket 0.5 Mtr [Approved
Make - Sintex, National, EPP, Hensel, Green
36a 12 [B] Double Arm Bracket 0.5 Mtr [Approved 622.16 No.
Make - Sintex, National, EPP, Hensel, Green
37 1200 Providing & laying approved make ISI 108.07 No.
marked HDPE 6Kg / cm2 (Class-3) as per
IS:4984:1995 PE-80 to be erected at road
crossing on or floor as directed for laying of
cable. The pipes as following size of dia &
weight per 6 mtr.
(A) 40 mm inner Dia. [Approved Make -
Dutron, Universal, Duraline, Gamson,
Dolphin, Rudra]
38 10 Supplying and erecting B class galvanised 343.40 No.
iron pipe 32 mm outside dia 45 cm long duly
welded on 20 cm x 20 cm x 3 mm thick M.S.
base plate, erected on wall or corner for
mounting street light luminaire with necessary
hardware materials duly painted.
39 2 Supplying Feeder pillar outdoor stand 35713.43 No.
mounted made from 1.6 mm thick Stainless
steel AISI 304 Confirm to IS 1570 part-V
Sheet, Size 500 mm x 500 mm x 300 mm
deep with leg made from 35x35x3 mm angle
complete fabricated. The Feeder pillar with
A TPN MCB incomer (C&S, L&T, Siemens),
single dial time switch, 45A TP contactor
(C&S, L&T, Siemens) for the automatic
switching of luminaries, power tool control
with 2 no 9 A contactors and raise lower push
button, Incoming 35 sq.mm and outgoing
& 2.5 sq.mm terminal complete with internal
wiring 4 sq.mm copper wire & suitable lugs.
All necessary AccesS.O.R.ies including the
item. The box shall be provided with front
door hinged at one end. And locking at other
end, rubber packing should be provided on
closing door. And having cover inside for
M.C.B.& Danger notice board on door.
40 7 Supplying & erecting earth pit of minimum 4591.46 No.
bore dia.150mm size approved make
Earthing Electrode consisting Pipe-in-Pipe
Technology as per IS 3043-1987 made of
corrosion free hot dipped G.I.Pipes having
Outer pipe dia of 50mm having 80-200
Micron galvanising, Inner pipe dia of 25 mm
having 200-250 Micron galvanising,
connection terminal dia of 12mm with
constant ohmic value surrounded by highly
conductive compound with high charge
dissipation suitable for following type of
applications with chamber and heavy duty
cover. (A)(approved make OEM has to
submit test certificate including value of earth
resistance of installation duly stamped and
signed by agency and officer Incharge has to
ensure the value of earthing resistane
mentioned in test Certificate) & having back
filling compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 ohm / meter
testing as per IEC 62561-2017, Voltage
drop:- < 1 volt at no load & dry form, Sulphar
content:- <2%(C) Back fill Compound :-
Earthing compound should be capable to
retain moisture for long time Necessary test
report must be submitted by Agency.
(a) For Electrical Installation up to 440V in
Length of pipe - 1 Mtr
Back filling compound - 1 Nos Bag of 15 Kg.
[Approved Make- Make will be approved by
Engineer-in-charge]
41 40 Providing and erecting required size HOT 77.77 Kg
deep Galvanised iron strip for earthing of H.T.
, OCB/ ACB/ Transformer LT panel board,
Motors etc. using proper clamp.
42 1500 Providing & laying approved make Double 62.62 Mtr.
walled corrugated pipes (DWC) of
polyethylene(conforming to IS 14930 II )with
necessary connecting accessories of same
material at required depth in existing trench
for laying of cable. below ground / road
surface for enclosing cable (A)50 mm outer
dia [Approved Make - Veronica, Dutron, Rex,
Gemini, Duraline]
43 10 Labour charges for Magnetic brake servicing 795.28 No.
including cleaning, oiling, setting, testing &
connection wire cable from D.H.U. etc.& put
magnetic brake in operation in all respect.
44 4 Rewinding of Coil for Magnetic brake drum 2022.45 Set
dia. 7" and 5 1/2" by using Super enamel
Copper wire of suitable size. (Or as per
sample of dam site)
45 10 Labour charges for forward & reverse motor 593.26 No.
starter panel servicing & repairing including
supply of wire, ferrul, lugs & other misc.l item,
complete repairing & put into operation.
46 20 Providing & erecting Push button with 186.98 No.
elements. (BCH, L&T, Siemens, Tecknik or
equivalent make approved by Engineer in
47 20 Supplying and erecting approved make 43.43 No.
suitable panel indicator LED type lamp, lens
cover, complete erected with necessary
48 5 Supplying and erecting approved make panel 1558.43 No.
mounting type Digital Ammeter having
digits LED display, external CT operated,
calibrated for 0 to 1000 Amps suitable to
operate on 500 Volt AC , erected on existing
panel board with all connection, wiring etc
.with manufacturers calibration
certificate.[Approved Make-Gelco, Meco,
Schneider, Siemens, Techno]
49 5 Supplying and erecting approved make panel 1275.63 No.
mounting type Digital Voltmeter having
digits LED display, 0 to 750 AC Volts range
erected on existing panel board with all
connection, wiring etc .with manufacturers
calibration certificate. [Approved Make-Gelco,
Meco, Schneider, Siemens, Techno]
50 12 Supplying and erecting LED street light / 4819.72 No.
Flood light fittings with High power White
LEDs wattage of 3 Watt and above
assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High
pressure die cast aluminum housing with
smooth finish powder coated and heat sink
extruded aluminium with diffuser and
Polycarbonate optics/ lenses, with toughened
glass with company mark/name engraved or
embossed 160 to 270 V,Power Factor more
than 0.95, THD < 10 %, CCT 3000 K to
5700K,Uniformity ratio >0.45, Luminaire
efficacy> 100 lumens/watt . LED driver
efficiency > 85 %.( fittings required LM-79 &
LM-80 certificates)(NOTE: Below description
have shown ranges of Wattage capacity of
LED fittings.The Engineer incharge may
select any wattage capacity between the
ranges shown.)(A) Post Top Lantern LED
fitting comprises of finish cast aluminum
spigot and spun aluminum canopy fixed with
opal polycarbonate, pipe arrangement for
vertical mounting driver and accessories
wired upto terminal block.IP 65(i)40W
[Approved Make - Philips, Wipro, Crompton,
Havells, Surya, Bajaj, Orient]
51 2500 Making trench in soft soil of suitable width of 55.55 Mtr.
90 cm deep for laying cable or locating the
fault all over the run and back filling the
same and making the surface as normal
52 2500 BY back old GI pipe, panel board, cable,PVC 30.30 Kg. -75750.00
pole box, old pole, Bracket, MCB, MS box all
Electrical scarp Item.
53 1 Supplying and erecting triple pole & neutral 3202.71 Rn.Mtr
440V / 500V panel mounting Copper Busbars
with four equal Nos. of electrolyte bus having
current density not more than 1.6 Amp. /
sq.mm (Rated current / cross section area)
duly wrapped with colour insulating tape for
phase sequence of following current carrying
capacity, erected with necessary bus bar
supports /insulators, main cable socket to
each bar, erected in existing cubical panel
with necessary connections.(A) Suitable for
200 Amp. capacity
54 3 Supplying and erecting approved make 43.43 No.
suitable panel indicator LED type lamp, lens
cover, complete erected with necessary
55 1 Supplying and erecting approved make panel 1275.63 No.
mounting type Digital Voltmeter having
digits LED display, 0 to 750 AC Volts range
erected on existing panel board with all
connection, wiring etc .with manufacturers
calibration certificate.[Approved Make-Gelco,
Meco, Schneider, Siemens, Techno]
56 1 Supplying and erecting approved make panel 1558.43 No.
mounting type Digital Ammeter having
digits LED display, external CT operated,
calibrated for 0 to 1000 Amps suitable to
operate on 500 Volt AC , erected on existing
panel board with all connection, wiring etc
.with manufacturers calibration
certificate.[Approved Make-Gelco, Meco,
Schneider, Siemens, Techno]
57 3 Providing & erecting L.T. Current 274.72 No.
Transformer with bar primary 50/5 to 1000/5
ratio 15 VA burden erected in existing CRCA
box duly secured with insulating materials
connected to the meter
58 2 Supplying and erecting Ammeter / Voltmeter 317.14 No.
selector switch for 3 phase AC Supply 500 V
on existing panel board with necessary
59 3 Providing and erecting Miniature circuit 112.11 No.
breaker single pole 6A suitable to operate on
240 V A.C. system and having breaking
capacity 10 KA to be erected in existing box.
confirming to IS 8828/1996 with ISI Mark
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
60 1 Supplying & erecting approved make Four 12241.20 No.
Pole 415V change over switch interior for
panel mounting with operating mechanism
A.C.23 duty confirming to IS for
(A)200A Approved Make - Siemens,
Schneider, L&T, ABB, Havells, C&S]
61 1 Providing and erecting Approved make Four 16221.61 No.
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having Normal current rating 200A.with
variable Thermal & magnetic release suitable
to work on A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing
ICS=100% of ICU only [Approved Make -
Schneider, L&T, ABB, Siemens, Havells,
62 3 Providing and erecting Approved make Four 6173.12 No.
pole moulded case circuit breaker having
breaking capacity ICU of 25 KA. at
V,having normal current rating up to 25 A to
100A. with Fixed thermal & magnetic release
suitable to work on A.C. supply 50 c/s. with all
internal connections, spreader tinned copper
& complete erected in existing 16 G.M.S.
housing. ICS=100% of ICU only
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
63 21 Providing & erecting 240 V MCB double pole 278.76 No.
switch for lighting Load (B Curve) having
KA breaking capacity & confirms to IS :
in existing box having following capacity
(A) 32 Amp. [Approved Make - Schneider,
L&T, ABB, Siemens, Havells, MDS, C&S]
64 2 Providing & erecting 415 V MCB Four Pole 595.90 No.
for Motor & Inductive Load (C Curve) having
10KA breaking capacity & confirms to IS
:8828 in existing box having following
(A) 32 Amp. [Approved Make - Schneider,
L&T, ABB, Siemens, Havells, MDS, C&S]
64a 6 (B) 63 Amp. [Approved Make - Schneider, 737.30 No.
L&T, ABB, Siemens, Havells, MDS, C&S]
65 3.6 Providing & erecting weather proof, dust & 14902.55 Sq mtr
vermin proof, floor mounted front operated
indoor type cubical panel board necessary
IP-42 and above protection as per approval
from engineer incharge made from 14 SWG
thick CRC M.S. sheet for outer body & doors,
16 SWG thick CRC M.S.sheet for internal
partitions with necessary accesories
supporting angles/ flats channel including
cutting, bending, drilling, welding, riveting with
internal partitions & cable alley as per
requirements & instruction of engineer-in-
charge with erection of supplied switch gears,
BUSBARS, suitable size of inter connecting
PVC copper wire / copper-aluminium strips,
rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments, earth
bus & earth bolts, foundation flange - bolts-
base Plates, sufficient nos. of hinged doors,
handles with locking arrangement and rubber
gasket,heavy duty end terminal
connection,danger notice board,necessary
ventilation,earthing strip complete. The Panel
shall be painted with epoxy powder coating.
(The rates excludes the cost of switchgears,
bus bars, inter connecting mains & Copper
Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base
beams) The panel shall be supplied with
following approved manufacturers with
following size.The panel size: 2.0 mtr(W) X
1.8 mtr (H)(A) The standard companies
switch gear shall be used and only
manufacturers at CPRI approved factory (i)
with 350mm depth [Approved Make- Make
will be approved by Engineer-in-charge]
66 1 Supplying and erecting Direct-on-line, Starter 2046.26 No.
with 15A.rating contractor and with 4-14A.
range, directly operated thermal overload
relay in sheet steel enclosure for 3phase
415V.50 c/s. A.C. motor up to
H.P.complete erected on P.W. Block with
necessary connection.
67 40 providing and erecting Mains with ISI marked, 17.17 Mtr.
1.5KV grade electrolyte multi stranded,
annealed copper conductor with heat
resistant PVC insulated conforms to IS
IEC - 227 erected in existing pipe of following
size (Specifically for control panel, relays,
power switchgears, motor starters & control
wiring) with required size of copper lugs, nuts
and bolts if required.
(A) One wire 1.50 sq. mm
67a 45 (B) One wire 6.00 sq. mm 56.56 Mtr.
67b 40 (C) One wire 10.00 sq. mm 91.91 Mtr.
67c 40 (D) One wire 16.00 sq. mm 142.41 Mtr.
68 70 Providing , erecting , fabricating the M.S. 77.77 Kg
structure as per requirement on site
incorporating proper size of M.S.
angles,square,round, flats, bars, channels,
sections complete with cutting, welding,
grinding & finishing duly painted with one
coat of red oxide with erection on site as per
direction of engineer in charge with
necessary grouting, cementing, plastering &
finishing complete.
69 1 Supplying and erecting triple pole & neutral 7319.47 Rn.Mtr
440V / 500V panel mounting Copper Busbars
with four equal Nos. of electrolyte bus having
current density not more than 1.6 Amp. /
sq.mm (Rated current / cross section area)
duly wrapped with colour insulating tape for
phase sequence of following current carrying
capacity, erected with necessary bus bar
supports /insulators, main cable socket to
each bar, erected in existing cubical panel
with necessary connections.(A) Suitable for
400 Amp. capacity
70 3 Supplying and erecting approved make 43.43 No.
suitable panel indicator LED type lamp, lens
cover, complete erected with necessary
71 1 Supplying and erecting approved make panel 1275.63 No.
mounting type Digital Voltmeter having
digits LED display, 0 to 750 AC Volts range
erected on existing panel board with all
connection, wiring etc .with manufacturers
calibration certificate.[Approved Make-Gelco,
Meco, Schneider, Siemens, Techno]
72 1 Supplying and erecting approved make panel 1558.43 No.
mounting type Digital Ammeter having
digits LED display, external CT operated,
calibrated for 0 to 1000 Amps suitable to
operate on 500 Volt AC , erected on existing
panel board with all connection, wiring etc
.with manufacturers calibration
certificate.[Approved Make-Gelco, Meco,
Schneider, Siemens, Techno]
73 3 Providing & erecting L.T. Current 274.72 No.
Transformer with bar primary 50/5 to 1000/5
ratio 15 VA burden erected in existing CRCA
box duly secured with insulating materials
connected to the meter
74 2 Supplying and erecting Ammeter / Voltmeter 317.14 No.
selector switch for 3 phase AC Supply 500 V
on existing panel board with necessary
75 3 providing and erecting Miniature circuit 112.11 No.
breaker single pole 6A suitable to operate on
240 V A.C. system and having breaking
capacity 10 KA to be erected in existing box.
confirming to IS 8828/1996 with ISI Mark
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
76 1 Supplying & erecting approved make Four 22255.35 No.
Pole 415V change over switch interior for
panel mounting with operating mechanism
A.C.23 duty confirming to IS for
(A)400A [Approved Make - Schneider, L&T,
ABB, Siemens, Havells, MDS, C&S]
77 2 Providing and erecting Approved make Four 25228.79 No.
pole moulded case circuit breaker having
breaking capacity ICU of 50 KA and above at
415 V having Normal current rating 400A.
with variable Thermal & magnetic release
suitable to work on A.C.supply 50 c/s. With all
internal connections, spreader tinned copper
& complete erected in existing 16 G.M.S.
housing.ICS=100% of ICU only [Approved
Make - Schneider, L&T, ABB, Siemens,
Havells, MDS, C&S]
78 2 Providing and erecting Approved make Four 16221.61 No.
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. at 415 V.
having Normal current rating 200A.with
variable Thermal & magnetic release suitable
to work on A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing
G.M.S.housing ICS=100% of ICU only
[Approved Make - Schneider, L&T, ABB,
Siemens, Havells, MDS, C&S]
79 1 Providing and erecting Approved make Four 20946.39 No.
pole moulded case circuit breaker having
breaking capacity ICU of 35 KA. and above at
415 V . having normal current rating 250A.
with variable thermal & magnetic release
suitable to work on A.C.supply 50 c/s. with all
internal connections, spreader tinned copper
& complete erected in existing 16 G.M.S.
housing.ICS=100% of ICU only [Approved
Make - Schneider, L&T, ABB, Siemens,
Havells, MDS, C&S]
80 3.60 Providing & erecting weather proof, dust & 14902.55 Sq mtr
vermin proof, floor mounted front operated
indoor type cubical panel board necessary
IP-42 and above protection as per approval
from engineer incharge made from 14 SWG
thick CRC M.S. sheet for outer body & doors,
16 SWG thick CRC M.S.sheet for internal
partitions with necessary accesories
supporting angles/ flats channel including
cutting, bending, drilling, welding, riveting with
internal partitions & cable alley as per
requirements & instruction of engineer-in-
charge with erection of supplied switch gears,
BUSBARS, suitable size of inter connecting
PVC copper wire / copper-aluminium strips,
rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments, earth
bus & earth bolts, foundation flange - bolts-
base Plates, sufficient nos. of hinged doors,
handles with locking arrangement and rubber
gasket,heavy duty end terminal
connection,danger notice board,necessary
ventilation,earthing strip complete. The Panel
shall be painted with epoxy powder coating.
(The rates excludes the cost of switchgears,
bus bars, inter connecting mains & Copper
Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base
beams) The panel shall be supplied with
following approved manufacturers with
following size.The panel size: 2.0 mtr(W) X
1.8 mtr (H)(A) The standard companies
switch gear shall be used and only
manufacturers at CPRI approved factory (i)
with 350mm depth [Approved Make- Make
will be approved by Engineer-in-charge]
81 40 providing and erecting Mains with ISI marked, 17.17 Mtr.
1.5KV grade electrolyte multi stranded,
annealed copper conductor with heat
resistant PVC insulated conforms to IS
IEC - 227 erected in existing pipe of following
size (Specifically for control panel, relays,
power switchgears, motor starters & control
wiring) with required size of copper lugs, nuts
and bolts if required.(A) One wire 1.50 sq.
81a 10 (B) One wire 25.00 sq. mm 236.34 Mtr.
81b 30 (C) One wire 35.00 sq. mm 300.98 Mtr.
82 80 Providing , erecting , fabricating the M.S. 77.77 Kg
structure as per requirement on site
incorporating proper size of M.S.
angles,square,round, flats, bars, channels,
sections complete with cutting, welding,
grinding & finishing duly painted with one
coat of red oxide with erection on site as per
direction of engineer in charge with
necessary grouting, cementing, plastering &
finishing complete.
* All rates are exclusive of GST
I/We am/are willing to carry out the work at…………………….% above/below
percent(Should be written in figures and words) of the estimated rate mentioned above.
Amount of my /our Quotation works out as under.
Estimated amount put to Quotation Estimated amount put to Quotation
Deduct……………% below Add……………….…% Above
1. The Contractor shall exhibit a board with detailed specification and details of work as directed by the
Engineer-In-Charge and as per GR No. MIS/102010/17(2)/k-1 of dtd. 29/01/2011 for which no extra
payment shall be made.
2. The labor cess will be deducted as per prevailing rules i.e. 1% of the work done.
3. GST and Income tax TDS will be deducted at a source while making payments of bills.
4. Rates quoted include clearance of site (prior commencement of work and at its close) in all respects and
hold good for work under all conditions, site, moisture, weather etc.
5. The quoted rates should be inclusive of cost of minor rectification work which may have to be done for
correcting the distortion caused during transportation of the gate components.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Bank Gurantee.pdf
BOQ Nprocure.pdf
Mendatory Documents(1).pdf
Mendatory Documents(2).pdf
Bank Gurantee.pdf
NIT-06 of 2026-27 (Electrical Work at Karjan Dam).pdf
SBD - Electrical Work at Karjan Dam.pdf
Corrigendum-1 Online Electrical Work - Karjan Dam.pdf
CORRIGENDUM
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .