Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹6.6 LAccepted-AOC | 1 | Accepted-AOC lowest | |
| 2 | 2₹6.7 L+₹7,580 (1.15%)Rejected-AOC | 2 | Rejected-AOC second lowest |
Tender Value
₹7.3 L
EMD Value
₹18,300
Closing Date
18 Aug 2023, 5:15 pmClosed
Managing Director, KTDC Ltd
KTDC-Corporate office, Mascot square, PMG, Trivandrum-33
SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF DUCTABLE SPLIT AC UNITS IN RESTAURANT AT KTDC-RAIN DROPS, CHENNAI
2023_KTDC_591943_1
KTDC/EW-TVM/651/RD-Chennai-AC
Open Tender
Miscellaneous Works
Item Rate
20 days
Chennai
As mentioned in NIT and special conditions
8 documents required · 8 mandatory
₹1,723
₹18,300
14 Dec 2023
10 Aug 2023
21 Aug 2023
10 Aug 2023
18 Aug 2023
10 Aug 2023
Amount
Ductable split AC unit
Supply of 8.5 TR Air cooled type ductable split AC units working on 3 Phase 415V, 50 Hz +/-1% AC supply with energy efficient twin compressor including all necessary accessories required etc complete. The compressors shall have independent refrigerant circuits, expansion devices, HP/LP cut off, etc complete. The initial gas charging (R-410A) also considered in this quote (Approved Makes- Bluestar, Carrier, Daikin, O general, Mitsubishi)
Installation, Testing and commissioning of AC units (Both indoor and outdoor units) including, positioning , full charge of refrigerant gas, leak testing, pressure testing, giving all control/power/refrigerant connections etc all required works as per standards etc complete as required at site
Supply and laying of required gauge hard copper refrigerant piping between outdoor units and indoor units with required thickness nitrile rubber insulation for suction and discharge copper pipe line
Supply and l;aying suitable control cable between indoor and outdoor units
Supply, Installation, balancing and commissioning of fabricated at site 0.63mm thick GSS sheet metal rectangular /round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, etc as per approved drawings and specifications of following sheet thickness complete as required.Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006.mps &re-circulation pumps etc.complete
Supply and installation of aluminium foil faced 9mm thick closed cell elastomeric nitrile rubber thermal insulation of exhibiting class"O" properties with density 45-55kg/m3. on supply air ducts with adhesive as per the recommendation of the manufacturer, longitudinal & transverse joints sealed with adhesive in neat & clean manner
Supply and Installation of good quality canvas connection
Supply and fixing suitable supporting stand for fixing the outdoor units using suitable support bars/anchor bolts etc whichever is required at site including all accessories etc complete required at site
Charges for dismantling existing concealed split AC units of capacities 8.5 TR (Both indoor and outdoor) and its refrigerant and control<br>connections and all related accessories etc complete from the position and<br>stacking at a suitable position as per direction of officer in charge and handover to the unit. The rate shall include required gypsum false ceiling cutting, scaffolding and other works required at site
Charges for providing necessary UV ray coating for the exposed portion of copper pipes)
Sri Bhavani Enterprises
Bidder Name
Sri Bhavani Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .