Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹39.4 LAccepted-AOC NADUVILPAT HOUSE KALLARAMANGALAM PO VIJAY ENGINEERING KADAMPUZHA MALAPPURAM PIN 676553 | MALAPPURAM | KERALA | 676553 | 1 | Accepted-AOC AEE/LIDEW-DIV/MPM/121/25-26 | |
| 2 | Rejected-Technical | - | Rejected-Technical L4 | |
| 3 | Rejected-Technical | - | Rejected-Technical L2 | |
| 4 | Rejected-Technical 152 JAKIR HUSAIN COLONY HAPUR ROAD MEERUT UTTAR PRADESH 250002 | MEERUT | UTTAR PRADESH | 250002 | - | Rejected-Technical L3 |
| Sl No | Description | Qty | Unit | MOHAMMED MUSTHAFA K. L3 | RJ ENTERPRISES L4 | ELECTROWIND ENGINEERING CO L1 | RAJESH R L2 |
|---|---|---|---|---|---|---|---|
| 1.00Generator | |||||||
| 1.00 | OD280846/2025-2026:Supply, Installation, Testing and Commissioning of 160 KVA / 1 28 KW Diesel Generator set including required contactors/control devices and acoustic enclosure as per CPCB norms IV+ and as per technical details given below on suitable size CC foundationAshok Leyland Mark CPCB IV Diesel Generator Set, H6G4DE 160 Model with following specifications: Alternator : Stamford or equivalent , Power Rating : 160 KVA / 1 28 KW Rated Current : 223 Amps Voltage : 415 V/ 50Hz ( THREE Phase) Engine Rating : 128 KW / 197 HP, Ashok Leyland or equivalen, No. of Cylinder : 6 Inline Engine RPM : 1500 Fuel injection Type : Electronic AcousticEnclosure : Mark? sEnclosure with Diesel Tank and Residential Silencer Dimension (LxBxH) : 3 5 00 x 1 4 00 x 1 850 (in Total DG Weight : 2210 kgs (Approx) Fuel Tank Capacity : 250 Liters Battery Capacity : 24 V / 110 Ah Exhaust: Residential Silencer with tail pipe and flange for extension Control Panel :Mark?s 160 KVA control panel Noise Level : 75 dB at 1 meter d istance Certified by CPCB and NAL, 160KVA Diesel Generator Set CPCB IV, Compliance, with full automati transmission etc as required at site.Panel board, Acoustic enclosure carries warranty of 60 months, Battery carries warranty of 24 months, engine carries a warranty of 5000 hrs / 60 months of operation from the date of invoice for Ashok Leyland engine failure against any manufacturing defect and to be followed Ashok Leyland engine service and maintenance procedure.The DG set should have single point service for supply. Testing include Engine ,Alternator and control Panel. The DG should have Warranty period of 3 years and during Warranty period comprehensive maintenance.(Excluding Oil changes) and services as per manufacture recommendation and repairs shall arranged from date of commissioning. Exhaust piping shall be vent to the top of nearest to the building. If the pipe cannot be clamped /fixed to the building or any other structure of permanent nature necessaries fabricated structures using Chanel section or angle iron sections of adequate mechanical strength ,duly painted with two coats of synthetic enamel paint over a coat of zinchromate primer shall be provided for the supports of the exhaust (additional piping will be measured excluding the standard length of pipe supplied by the manufacturer ). Installation it shall be installed in the per-constructed concrete bed complying to relevant IS standard, IE rules and as per direction of the departmental officials , Testing and commissioning the DG set shall be tested as per relevant IS standards as required at site. | 2 | each | 17,39,000 ₹34,78,000 | 19,67,828 ₹39,35,656 | 16,89,954 ₹33,79,908 Lowest | 17,19,000 ₹34,38,000 |
| 1.00 | OD280824/2025-2026:Supply conveyance and providing 150 mm MS/GI pipe or nearest size dia. with required accessories for exhaust pipe to generator. | 30 | metre | 1,850 ₹55,500 | 2,255 ₹67,650 | 1,658 ₹49,740 | 1,650 ₹49,500 Lowest |
| 1.00 | OD280811/2025-2026:Supply of High speed Speed Diesel for test run | 150 | Litre | 110 ₹16,500 | 1,350 ₹2,02,500 | 105 ₹15,750 | 102 ₹15,300 Lowest |
| 1.00 | OD280819/2025-2026:Charges for conducting load test | 200 | L.S | 55 ₹11,000 | 60 ₹12,000 | 49 ₹9,800 | 48 ₹9,600 Lowest |
| 1.00 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. | 4.5 | cum | 400 ₹1,800 Lowest | 490 ₹2,205 | 407 ₹1,831.5 | 400 ₹1,800 Lowest |
| 1.01 | 14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required. | 6 | cum | 15,000 ₹90,000 | 1,210 ₹7,260 Lowest | 9,271 ₹55,626 | 9,000 ₹54,000 |
| 1.01 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels | 10 | sqm | 370 ₹3,700 | 445 ₹4,450 | 368 ₹3,680 Lowest | 370 ₹3,700 |
| 1.01 | 14.13.1:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia | 10 | metre | 800 ₹8,000 Lowest | 1,060 ₹10,600 | 880 ₹8,800 | 800 ₹8,000 Lowest |
| 1.01 | 90.12.5.34:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 185 sq mm | 50 | metre | 1,100 ₹55,000 Lowest | 1,650 ₹82,500 | 1,100 ₹55,000 Lowest | 1,100 ₹55,000 Lowest |
Tender Value
₹39.5 L
EMD Value
₹50,000
Closing Date
20 Sept 2025, 6:55 pmClosed
ASSISTANT EXECUTIVE ENGINEER
Office of the Executive Engineer, LID and EW Division, Malappuram, civil station, Malappuram District Panchayath Building, Malappuram, 676505
Annual Plan - Malappuram District Panchayath Purchasing Generator to District Hospital Perinthalmanna-S1277-26 -General Electrical Work
2025_LSGD_795931_12
DB1/TN/ELE/AEE/29/25-26
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
MALAPPURAM
Please refer Tender documents.
11 documents required · 11 mandatory
₹2,950
₹50,000
Yes
29 Nov 2025
12 Sept 2025
22 Sept 2025
12 Sept 2025
20 Sept 2025
12 Sept 2025
Amount
Generator
OD280846/2025-2026:Supply, Installation, Testing and Commissioning of 160 KVA / 1 28 KW Diesel Generator set including required contactors/control devices and acoustic enclosure as per CPCB norms IV+ and as per technical details given below on suitable size CC foundationAshok Leyland Mark CPCB IV Diesel Generator Set, H6G4DE 160 Model with following specifications: Alternator : Stamford or equivalent , Power Rating : 160 KVA / 1 28 KW Rated Current : 223 Amps Voltage : 415 V/ 50Hz ( THREE Phase) Engine Rating : 128 KW / 197 HP, Ashok Leyland or equivalen, No. of Cylinder : 6 Inline Engine RPM : 1500 Fuel injection Type : Electronic AcousticEnclosure : Mark? sEnclosure with Diesel Tank and Residential Silencer Dimension (LxBxH) : 3 5 00 x 1 4 00 x 1 850 (in Total DG Weight : 2210 kgs (Approx) Fuel Tank Capacity : 250 Liters Battery Capacity : 24 V / 110 Ah Exhaust: Residential Silencer with tail pipe and flange for extension Control Panel :Mark?s 160 KVA control panel Noise Level : 75 dB at 1 meter d istance Certified by CPCB and NAL, 160KVA Diesel Generator Set CPCB IV, Compliance, with full automati transmission etc as required at site.Panel board, Acoustic enclosure carries warranty of 60 months, Battery carries warranty of 24 months, engine carries a warranty of 5000 hrs / 60 months of operation from the date of invoice for Ashok Leyland engine failure against any manufacturing defect and to be followed Ashok Leyland engine service and maintenance procedure.The DG set should have single point service for supply. Testing include Engine ,Alternator and control Panel. The DG should have Warranty period of 3 years and during Warranty period comprehensive maintenance.(Excluding Oil changes) and services as per manufacture recommendation and repairs shall arranged from date of commissioning. Exhaust piping shall be vent to the top of nearest to the building. If the pipe cannot be clamped /fixed to the building or any other structure of permanent nature necessaries fabricated structures using Chanel section or angle iron sections of adequate mechanical strength ,duly painted with two coats of synthetic enamel paint over a coat of zinchromate primer shall be provided for the supports of the exhaust (additional piping will be measured excluding the standard length of pipe supplied by the manufacturer ). Installation it shall be installed in the per-constructed concrete bed complying to relevant IS standard, IE rules and as per direction of the departmental officials , Testing and commissioning the DG set shall be tested as per relevant IS standards as required at site.
OD280824/2025-2026:Supply conveyance and providing 150 mm MS/GI pipe or nearest size dia. with required accessories for exhaust pipe to generator.
OD280811/2025-2026:Supply of High speed Speed Diesel for test run
OD280819/2025-2026:Charges for conducting load test
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
14.13.1:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia
90.12.5.34:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 185 sq mm
90.12.7.34:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm
90.12.10.7:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation120/102.5 mm or nearest size
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD280827/2025-2026:Supply and providing test joint for the earthing system using 2 x 25 x 3 mm GI strip including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required
OD280820/2025-2026:Supply and providing earth lead from the test joint to the earth electrode using 25 x 3 mm GI strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.2:Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
2.2.15:Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 200 Amp, 36 KA
2.2.14:Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 125 Amp, 36 KA
90.14.11.14:MCCB AccessoriesSupply and fixing rotary handle, Direct type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
OD280895/2025-2026:Supplying and Fixing 200/5 A, 15VA,accuracy class0.5,Resin cast Metering CT.
OD280812/2025-2026:Supply conveyance installation testing and commissioning of Three phase multi-function meters to read V, A and F, accuracy class 1
OD280815/2025-2026:Supply and Providing LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour
90.14.11.2:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 125A to 200A with CBCT.
OD281388/2025-2026:Supply, installation, testing and commissioning of 2A SP MCB in the existing panel as required.
OD280809/2025-2026:Supply and installation of ABC type fire extinguisher of 6 kg. Capacity complete with initial charges and installation brackets, with ISI mark IS:15222.
OD280822/2025-2026:Supply and providing 2 mm thick & 1 m wide electrical grade chequered type insulation mat to withstand 3.3 KV dielectric strength conforming to IS 15652/06
OD280894/2025-2026:Charges for preparation of electrical A3 sheet first copy A3 additional copy, inspection of electrical inspectorate and scheme approval including all laison works for obtaining approval from Electrical Inspectorate
OD281394/2025-2026:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required 2.50 cm,4 cm or 5 cm height.
Generator Shed
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
4.1.5:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources)
12.50:Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
12.51.1:Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screwscomplete :Ridges plain (500-600 mm)
13.61.1:Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work
50.10.2:Steel work for purlin/single section with G I pipes including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
RAJESH R (BID ID -2345947)
MOHAMMED MUSTHAFA K. (BID ID -2347349)
RJ ENTERPRISES (BID ID -2347816)
Bidder Name
ELECTROWIND ENGINEERING CO
MOHAMMED MUSTHAFA K.
RJ ENTERPRISES
RAJESH R
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1319147.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .