| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAccepted-AOC 4 KRISHNA COLONY AGRA ROAD JAIPUR | ₹1.1 Cr | L1 | Accepted-AOC The Tender of Water Supply Scheme Burj Hari Singh has been awarded to M/S H. R. and Company Dist. Patiala due to lowest rate than 2nd bidder. |
| 2 | L2₹1.1 Cr+₹5.3 L (5.02%)Rejected-AOC | ₹1.1 Cr+₹5.3 L (5.02%) | L2 | Rejected-AOC Bidder reject due to highest rate than 1st bidder. |
Tender Value
₹1.1 Cr
EMD Value
₹2.1 L
Closing Date
1 Feb 2022, 12:00 pmClosed
Executive Engineer
Water Supply and Sanitation Division No.1 Ludhiana
Providing and Installing New Tube well Size 250mm x 200 mm id 180mtr. depth OHSR Pumping Main Chlorination New Submersible Machinery C.I Fitting Pumping Main Distribution System House Hold Service Connections Development of water works O and M etc.
2022_WSS_81450_1
No.37 Date 04.01.2022
Open Tender
Civil Works
Item Rate
180 days
Ludhiana
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
₹2.1 L
Ludhiana
12 Apr 2022
8 Jan 2022
1 Feb 2022
8 Jan 2022
1 Feb 2022
8 Jan 2022
17 Jan 2022
Amount
TUBEWELL
Drilling of 550mm dia bore with Reverse Rotatry Rig in all kinds of soil including the cost of consumable stores, fuel oil and transportation of rig to the site. complete in all respect.
Drilling of 550mm dia bore with Reverse Rotatry Rig Upto 150 m depth BGL.
Drilling of 550mm dia bore with Reverse Rotatry Rig Beyond 150 m depth BGL up to 300mtr.
1. Erection and dismantling of boaring plant including all arrangement for the transportation of the boaring equipment to site of work from work from the store of contractor at site and back are to be made by contractor at his own cost. All rates should be quoted for supplying the material at site of work. Pits for collection of water and water for drilling tubewell be arranged by the firm / contractor at site at his own cost and levelled after the completion of work.
2. In payment of bore shall be made upto the bail plug plus margin (7% of main bore drilling or as actual as per field requirement whihever is less) reqiured for sustaining the main bore.
Supplying, lowering of MS Pipe as per IS: 4270-2001 including MS sockets having dimensions as per IS code duly welded with MS electrode to have extra strength to lower the pipe into tubewell bore.
250mm nominal diameter (weight 52.3 kg per metre) 8.0 mm thickness
200mm nominal diameter (weight 33.6 kg per meter) 6.4mm thickness
Providing and fixing M.S. taper / reducer made out of 6 mm thick M.S. sheet complete in all respect.
Reducer 250mm x 200 mm
Supplying, fixing, lowering of Stainless Steel Cage type wire wound screen as per IS:8110-2000 or latest ISI marked duly welded with suitable grade S.S welding electrode. to lower the strainer into tubewell bore.
200mm Steel Strainer (slot size 0.75mm) 6.40mm thickness.
Supplying, Fixing & lowering of Stainless Steel socket as per IS 8110-2000 or latest ISI marked Duly welded with suitable grade S.S welding electrode to lower the strainer into tubewell bore complete in all respect.
Supplying, lowering & fixing of M.S Special socket to connect S.S strainer to M.S pipe duly welded with suitable grade welding electrode complete in all respect.
Making electric logging of borehole with electronic well logger including cost of equipment at site etc. complete in all respects.
Supplying and fixing mild steel centering guides made out of 32mm X 6mm thick M.S bar complete in all respect
Supplying at site Wooden box of suitable size with Lid & locking arrangment for preserving strata sample collected from the bore.
Supplying at site of gravel of 1/16" to 1/8" sizes including pouring and packing in the annual space between the pipes assembly & bore. The gravel should be free from dust, dirt, or the vegetable manner as per IS 4097-1967 with latest amendments (to be paid as per actual length of pipe)
Collection of water sample from different strata and testing of sample from approved laboratory (Physical & chemical Analysis)
Supplying and fixing well cap having thread to fix on housing pipe complete in all respect.
250mm internal diameter
Supplying & fixing of bail plug of M.S. pipe complete with inverted U-hook attached to the bottom plug complete in all respect.
200mm internal diameter (weight 23.6 kg per meter) 6.40 mm thickness
Supplying & fixing of M.S. Clamp of size 150mm x 12mm made out of MS Flat 1.52 m long, suitable to fit Housing pipe including the cost of Nut & Bolts of suitable size complete in all respects.
Development and stabillizing of the tubewell with air compressor of required capacity as directed by the engineer-in-charge including cost of tools, appliances & consumable to the satisfaction of Engineer-in-charge.
Capacity of Air compressor 300 cfm at 250 PSI
Development and stabillizing of the tubewell with submersible pump of required capacity as directed by the engineer-in-charge including cost of tools, appliances & consumable to the satisfaction of Engineer-in-charge.
Testing of water sample for Heavy metal from approved laboratory (Toxic material such as Arsenic, lead, mercury, pesticide and uranium etc.)
Supplying of tibba sand/ local sand over packing & clay seal upto G.L. below pipe assembly & bore including carriage complete in all respect.
Supplying and fixing sanitary seal having rubber tight on housing pipe complete in all respect. As per BIS: 2800-2019.
Supplying of clay to provide impervious layer in below pipe assembly & bore above gravel packing all including carriage. As per BIS: 2800-2019.
Sterilization of Well As per BIS: 2800-2019.
Constructing OHSR of 150 KL Capacity with sill level not less than 23.50m height upto FSL 27.50 m from formation level complete with external RCC stair case with landing slabs at each staging RCC roof, ventilator single main hole cover lightening conductor etc. complete as described in schedule No. 3. Providing and fixing D.I. K-9 D/F expansion joints latest bell mouth and D/F puddle collars as per DWSS design on basis of enclosed drawing, Duck foot bends, Conforming to ISI -13382 and C.I/D.I. D/F Sluice Valve duly ISI marked (IS-14846-2000 or latest) one each with inlet, outlet and scour pipe and including providing and installing inlet, outlet scour pipe and overflow DI double flanged pressure pipes DI K-9 horizontally as per IS 8329-2000 and latest duly ISI marked from bottom dome to duck foot bend and further up to 2.75 mtr as per detail specification TMT steel & painting of all complete shall be included in cost & P/F aluminium ladder inside the OHSR complete in all respect as per specifications (The specifications & drawing are based on safe bearing capacity of soil of is less than 8.75 tone per Sqm in case the safe bearing capacity of sail is less than 8.75 tone per sqm. The contractor shall submit his own design for foundation portion based on actual safe bearing capacity as per DWSS specifications. The difference in quantities from the standard drawing based on 8.75 tone per sqm. safe bearing capacity will be paid as per CSR+ Prevailing Ceiling Preminum including providing and fixing automatic Electronic Water Level control Device and Construction of Plinth protection around OHSR with masonry toe wall with 40 mm thick CC 1:2:4 on top over 100 mm thick CC 1:8:16 & inside earth filling, including overflow scower haudi complete in all respects. Including carraige complete .Provision of BC be got tested for construction of OHSR at new water works site before preparing DNIT as per vetted design.
Pumping Machinery
Providing & Installing Testing & Commissioning of One No. Electrically driven Submersible Pumping set of reputed Make capable of delivering 764 LPM against a head of 78mtr. (25.00 BHP) complete in all respects.
i) Providing & Fixing of Electric Control panel board Consisting of elctric appliances such as automatic Star Delta Push Button, (As per PSPCL norms) Main Switch, VM, Ampere, Meter, ELCB, Shunt Capacitor, Single Phase preventer, Indicating Lamps, Kit-Kat etc.complete in all respects.
ii) Providing & Fixing of submersible cable 6mm² =107 mtr complete in all respects.
iii) Providing & Fixing of G.I Column Pipe with flange & welding of 100mm i/d 46 mtr. complete in all respects.
C.I FITTING INSIDE PUMP CHAMBER
Providing and installing 150 mm dia delivery main (From Tube well to Duck Foot bend including cost of C.I/D.F Pipes, D/F Sluice valves, D/F NRV & Specials as C.I Bends, Tail Piece Tees etc.. inside the pump chamber as per standard drawing design complete in all respects.
CONSTRUCTION OF PUMP CHAMBER
Construction of Pump Chamber size 3.05 m x 3.70 m including cost gravel pit and electric wiring complete in all respects as per standard drawing complete in all respects.Construction of Sanitary Latrine in pump Chamber for Foundation and plinth of WC rooms including flooring, PVC pipes, Junction Box, 1 Nos. Leach Pits, Super structure WC Room etc.
PUMPING MAIN
Providing, Laying , fixing & jointing of P.V.C. Pipes as per ISI-4985 (ISI marked with the prior approval of Engineer-in-Charge) along the Trenches and laying the same in Trenches to correct alignment and gradients, cutting, jointing and testing complete as per specifications & specials including cost of earth work in excavation & back complete in all respect.
160mm o/d pipe of 10 Kg. / sqcm²
Providing & fixing C.I/D.I Flanged end, stem of SS (AIS 1410) and Bronze (gunmetal) working parts Sluice Valves ISI marked 14846-2000, including jointing, testing & cost of Nut, Bolt & insertion sheet, all carriage complete (with the approval of Engineer - in – charge)
150mm i/d Sluice Valves flanged
Construction of masonry sluice valve chamber excluding Sluice valve cover as per standard design & drawings of public health department Size 0.9m x 0.9m
Distribution network
Providing, Stringing out uPVC 6kg/sqcm² pipes and specials ISI Marked as per ISI-4985 casting along the Trenches and laying the same in Trenches To correct alignment and gradients, cutting. Jointing and testing complete including cost of earthwork in excavation and back filling complete as per specifications for less than 3 mtr street width. (Manualy)
PVC pipe 63 mm o/d
PVC pipe 90 mm o/d
Providing, Stringing out uPVC 6kg/sqcm² pipes and specials ISI Marked as per ISI-4985 casting along the Trenches and laying the same in Trenches To correct alignment and gradients, cutting. Jointing and testing complete including cost of earthwork in excavation and back filling complete as per specifications for more than 3 mtr street width. (Mechanicaly)
PVC pipe 63 mm o/d
PVC pipe 90 mm o/d
PVC pipe 110 mm o/d
PVC Pipe 160 mm o/d
PVC Pipe 200 mm o/d
Providing and laying, jointing, fixing, testing ISI Marked G.I. Pipe (as per IS 1239) B Class, including cost of Specials such as tees, bends, sockets elbow etc., cutting, threading and testing in trenches in the ground complete.
Dismantling brick or flagged stone flooring without concrete base and relaying of dry brick on edge paving with a dismantled bricks including sand grouting.
PVC pipe 63 mm o/d
PVC pipe 90 mm o/d
Dismantling of metallic road with bituminous course 50 to 75mm thick C.C. 1:8:16.
PVC pipe 63 mm o/d
PVC pipe 90 mm o/d
PVC pipe 110 mm o/d
PVC pipe 160 mm o/d
PVC pipe 200 mm o/d
Dismantling of cement concrete road and restoration in the same to its original condition complete in all respects
PVC pipe 63 mm o/d
PVC pipe 90 mm o/d
Providing & fixing C.I/D.I Flanged end, stem of SS (AIS 1410) and Bronze (gunmetal) working parts Sluice Valves ISI marked 14846-2000, including jointing, testing & cost of Nut, Bolt & insertion sheet, all carriage complete (with the approval of Engineer - in - charge)
Construction of masonry sluice valve chamber excluding Sluice valve cover as per standard design & drawings of public health department With each of Size 0.6m x 0.6m
Construction of masonry sluice valve chamber excluding Sluice valve cover as per standard design & drawings of public health department With each of Size 0.9m x 0.9m
House Service connections
Providing Household connection laying, jointing, fixing, testing MDPE Pipes (As approved by Engineer-in-Charge), including cost of excavation, refilling with meter, C.I bib cock as IS:210 with stainless steel spindle 20mm o/d MDPE / GI pipe 4.50 mtr. (2.50 mtr. MDPE & 2.00 mtr. G.I, Vertical Pipe) 3" i/d uPVC clamps, GM ferrule ISI marked connection of 15mm i/d ferrule medium, special such as tees, bends, sockets, elbows, nipples (100mm & 150mm) union couplings, G.I Hooks etc. and Gun metal peet valve (heavy pattern) with hand wheels on MDPE pipe line laid in the ground or inside building, cutting, treading. making hole in the wall complete in all respect.
CHLORINATOR
Providing, installing, testing & commissioning one no. Electrically actuated, diaphragm operated, Metering system, chemical dosing Chlorinator, suitable for delivering 0.5 to 0.6 litres of bleaching powder solution/ sodium hypo solution per hour under maximum delivering pressure upto 7 kgcm² and suction lift not less than 1.5m as per DWSS standard Specification.
DEVELOPMENT OF HEAD WORKS
Providing & fixing G.I. Barbed wire 3 ply fencing around the head works site in three rows complete in all respects including cost of winding wire & aluminum painting complete in all respects as per standard Drawing.
Providing & fixing angle iron pickets with angle 40mm x40mm x 6mm including cost of concrete block & painting complete in all respects as per standard Drawing.
Providing & fixing D.Hook complete with MS Bolts size 300mm x 18mm as per standard Drawing.
Construction of brick masonry corner pillar including cost of cement pointing including cost of material complete in all respects as per standard Drawing.
Construction of masonry gate pillar including cost of MS Steel Gate size 1.22mtr x 1.37 mtr as per standard Drawing complete in all respects
Construction of Cement Concrete, Foot Path with masonry toe wall & earth filling inside water works as per standard Drawing.
Providing & fixing MS Sign Board as per standard size of DWSS.
Making lawns including plughing & dragging with 'Sohaga' breaking of cluds, removal of earth rubbish dressing & Supplying doob grass roots and planting at 15cm. Apart supplying and spreading of farm yard maanure @0.18cum per 100sqm & loosening.
Supplying and planting permanent tress including digging of pits size 75cm x 75cm x 75cm deep, refilling the excavated earth. With manure supplied @ 0.113 4cum each like Neem, Ashoka, Dake Arjun Etc.
Planting ground cover plants including digging and refilling of beds with excavated soil and FYM, Fertiliser and insecticides, Planting of saplings at 30cm distance from plant to plant and row to row, providing and fixing brick tiles edging.
Planting flower beds including digging and refilling of beds with excavated soil and FYM, fertiliser and insectifieds, planting of sapling at 30cm distance from plant to plant and row to row, Around pump chamber OHSR and both side of path.
Provision for one way stand post with Khurra complete in all respects.
OPERATION AND MAINTENANCE (3 MONTHS)
Pump Operator Salary Cum Chowkidar
Provision for bleaching powder or sodium chlorite for disinfection of water complete in all respects.
CARRIAGE OF MATERIAL (Sand & Bajri)
JASBIR SINGH RUPANA CONTRACTOR
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .