Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹6.6 LAccepted-AOC ASHOKA PARK PALLAVA PARK BVT INS VISHWAKARMA INDIAN NAVY OF GE ND VISAKHAPATNAM | BAPATLA | ANDHRA PRADESH | 504214 | 1 | Accepted-AOC ACCEPTED BEING LOWEST | |
| 2 | 2₹7.1 L+₹46,297.60 (6.98%)Rejected-Finance | 2 | Rejected-Finance REJECTED NOT BEING THE LOWEST TENDERER |
Tender Value
Refer Docs
EMD Value
₹16,000
Closing Date
9 Nov 2020, 6:00 pmClosed
AGE I CG VIZAG
AGE (I) (CG) Vizag Military Engineer Services CGWO Building Co Fleet Mail Office visakhapatnam 530 014
REPAIR MAINTENANCE OF EXTERNAL ELECTRIFICATION AT ICGS MALKAPURAM AND ICGS JETTY AT VISAKHAPATNAM
2020_MES_385651_1
AGE(I)CG/VIZ/TOKEN 21 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
VISAKHAPATNAM
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
AGE I CG VIZAG
₹16,000
Yes
22 Jan 2021
12 Oct 2020
11 Nov 2020
12 Oct 2020
9 Nov 2020
26 Oct 2020
Amount
Material & Labour for repair of Lightening arrestor expulsion type 11 KV with all fittings, transmission class, discharge current class II , rating 9 KV/10 KA including fixing arrangement as required and as directed by Engineer-in-Charge.
Supply and install in repairs of HT 11 KV out door type Isolator air break switch suitable for horizontal mounting fixed type complete with 9 insulators of rating upto 400 Amps complete all as directed.
Material & Labour for repair of 11 KV DO Fuse unit Channel type with all types of fixing arrangement complete including dismantling all as specified and directed by Engineer-in-Charge.
Material & Labour for repair of Disc type, porcelain, vitreous, white, brown or green insulator single disc assembly including galvanized mild steel spindle,Two galvanazed iron washer and one galvanazed nut,100 mm height , 65mm dia 11000 Volts grade complete all as specified and as directed.
Material & Labour for repair of end termination heat shrinkable Indoor type kit complete with jointing material and accessories for HT 11 KV 95 to 120 Sqmm 3 core cable including testing. all as specified and directed by Engineer-in-Charge
Material & Labour for repair for making straight through heat shrinkable joint for HT 11 KV XLPE cable 95 Sqmm 3 Core complete including testing complete all as specified and directed by Engineer-in-Charge
Material & Labour for repair for making straight through heat shrinkable joint for HT 11 KV XLPE cable 120 Sqmm 3 Core complete including testing all as specified and directed by Engineer-in-Charge.
Maintenance and complete over hauling of HT RMU/VCB’s including disassembling of operating mechanism parts, well cleaning with petrol CRC 226, replacing unserviceable parts and accessories like spring, gasket, coils, nuts, bolts and washers etc, oiling and greasing of moving parts, re-assembling, fine setting of mechanism, well cleaning and de-carbonizing of arc control pot, fixed and moving contact, testing of Gas Pressure including checking testing, tripping check of HT RMU VCB’s making perfect operational in manual and electric mode including maintenance and cleaning the complete panel board bus bar, de-carbonizing all joints, bus bar CT’s metal parts, replacing unserviceable parts and components etc. complete all as directed by Engineer-in-Charge. Note:- Spare parts for VCB/RMU will be measured and paid separately.
SUPPLY OF SPARES FOR HT VCB/RMU
Supply only Rotable type screw suitable for operating spring.
Supply only Ratchet Bearing Cat No HFL-2530
Supply only Ratchet Bearing cat No HK-1412
Supply only Control wiring kit for Metering, motor charging, indicator lamps, and relays etc
Supply only Motor charged mechanism assembly with close/trip coil & charging handle of existing size and capacity.
Supply only Brass 'O' rings for contacts
Material and Labour for maintenance and overhauling of ACB up to 1600 Amps capacity including de-assembly all operating mechanism parts, well cleaning with petrol CRC 226, replacing unserviceable parts and accessories, oiling/ greasing of moving parts, cleaning of all pole partition hylem sheet, isolating contacts, re-assembly, fine setting of mechanism and pole assembly and making ACB perfect operational including well cleaning the complete panel bus bars chamber, insulator, partition etc and checking of insulation resistance of ACB and main bus bar complete all as directed by the Engineer-in-Charge. Note:- Spare parts for ACB to be measured and paid separately.
SUPPLY OF SPARES FOR LT ACB
Supply only Male contacts of existing size & Capacity.
Supply only Female contacts of existing size & Capacity
Supply only Locakable Trip Push Button (LTPB)
Supply only Lock in Isolation Position (LIP) assembly
Supply only Lock in any position (LAP) assembly)
Supply only Door interlock assembly
Supply only Shunt Release (SR) of existing capacity
Supply only Under Voltage release (UVR)
Supply only Earth Fault Release (for DN1)
Supply only Vertical terminal adaptor
Supply, installation, testing and commissioning of CT 11 KV epoxy type ratio 60/30/5+5 Amps accuracy Class-I single pole ( Three core type) fixing on existing 11 KV panel including necessary connections, any modification required, addition/alteration required for fixing CT in existing 11 KV panel complete all as directed by Engineer-in-Charge.
Supply and fixing in repairs analog meter with multifunction meters with 3 lines LCD display of voltage, current and frequency and power factor size 96x96 sqm flush mounted case accuracy class I.
Material and Labour for painting of HT switches complete with synthetic enamel paint two coats by spray painting approved colour after cleaning of surface/rusted portion including sign writing i.e. MES/SM No Make/ Capacity etc. complete all as directed by the Engineer-in-Charge.
Repair/Maintenance of LT Panel board by taking shut down, removing of carbon particles, rubbing of heated portion of bus bar and cleaning complete by means of CRC-226/Petrol tightening of all joints in bus bar, checking of earth and neutral voltage and make a record, replacement of u/s nuts/bolts/washers including replacement of corroded glands, lugs/ thimbles and tightening them properly including Painting of external surface after rubbing scrapping waste diposited material, appliying primer , with two coat of enamel paint of approved shade all as directed by Engineer-in-charge. Note : (Spares required will be measured and paid separately)
Supply followings only for incorporation in item no 16
Supply only MCCB 400 Amps 4 Pole 36 KA
Supply only MCCB 250 Amps 4 Pole 36 KA
Supply only MCCB 200Amps 4 Pole 36 KA
Supply only MCCB 160 Amps 4 Pole 25 KA
Supply only MCCB 125 Amps 4 Pole 36 KA
Supply only MCCB 63 Amps 4 Pole 36 KA
Supply only On load changover 400 /320 Amps 4 pole suitable mounting in panel
Supply only Multi Funtion Meter with Suitable TCs and PTs
Equipment & labour for filtration of transformer oil as in topping up by filtartion plant to remove moistrure and carbon contentents to achive dielectric strength of oil up to 50KV in 4mm gap and producing test result on recordes before and after filtartion and including Disconnecting the HT and LT cables and cleaning the bus bar surfaces and reconnecting the cables by providing copper washers, bolts, nuts etc all as dirctected by Engineer in Charge Note - Oil required for topping up while for filtaration will issued under respective item of Sch A .
Supply only transformer oil to be incorporated in item above IS -335 and all as directed by Engineer in Charge.
Material & Labour for taking out unserviceable LV bushings and replacing LV Bushings with copper/brass stud complete with rubber gasket, brass bolts, brass nuts all for 11KV/0.433 KV transformer of rating upto 1000 KVA.
Material & Labour for taking out unserviceable HV 11 KV bushings and replacing HV 11 KV Bushings with copper/brass stud complete with rubber gasket, brass bolts, brass nuts all for 11KV/0.433 KV transformer of rating upto 1000 KVA.
Supply & Fix in repairs Silica Gel Breather with silica gel for 11 KV Transformer of Rating from 160 KVA to 250 KVA
Material & Labour for taking down/opening top cover of 11KV/0.433 KV transformer of rating up to 1000 KVA replacing top cover gasket and refixing the top cover & testing complete.
Material & Labour for cutting into the existing road/hard standing surfaces to a depth of 60cm and 50cm wide and getting out for laying under ground cable including returning filling in, watering, well ramming in layers not exceeding 25cm in any type of soil and filling the top surface 15cm thick with PCC 1:2:4 type B1 using 20mm graded stone aggregate and finished even and fair without using extra cement including disposal of surplus soil all as directed by Engineer in charge.
Material & Labour for applying two coat of aluminium paint on steel tubular pole 9/11 m long, including preparation old surfaces, filling cavities and lettering the Pole no in figures, complete all as directed by Engineer-in-charge.
Material & Labour for provn of Earthing complete with M.S. galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal GL) with top edge of the plate not less than 1.5M below normal GL, connected to Galvanized earth strip 32x6mm upto 7.5 mtr with protection pipe by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40 mm thick reinforced with 6 mm dia bar, 3 Nos. both way, 40mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, salt etc. all as shown in electrical plate No. 5 of SSR Pt-I 2009 specification.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5m in depth for taking out/laying cable and getting out, in Soft/Loose Soil complete all as specified and as directed.
Returning, filling including spreading leveling, watering and well ramming in layers not exceeding 25 cm in any type of soil complete all as specified and as directed.
Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed.
Supply and spreading in trenches fine dry crushed stone sand for cable protection and punning down gently by hand complete all as specified and as directed.
Supply and lay cable cover for LT Cable Class LV,type 1 , flat size 250mmx150mm x 40 mm complete all as specified and as directed.
Supply, fixing in repairs and testing XLPE insulated armoured heavy duty electric cable screened pvc bedded with aluminium conductor 1100 v grade laid in unserviceable cable complete all as specified and directed for for following sizes :-
10 sqmm x 2 core
10 Sqmm x 4 core
35 Sqmm x 3.5 core
150 sqmm x 3.5 core
Material and labour for providing of Drainage for AC Water in such a manner to accommodate water at specified place / drain system including necessary fixing arrangement like saddles,skylever,clamps, holdfast with PVC fittings, bend ,elbow ,sockets, PVC insulation tape for prevent leakage of draining water. The cost of all pipe will be paid and measure separately under the relevent items of Schedule.
Supply only PVC conduit pipe 32 mm dia
Supply only PVC conduit pipe 25 mm dia
Supply only PVC conduit pipe 20 mm dia
SRI SAI KRISHNA ENGINEERING WORKS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .