Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.2 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹7.4 L+₹27,826 (3.88%)Rejected-AOC ALAPPUZHA | ALAPPUZHA | KERALA | 686534 | L2 | Rejected-AOC second lowest |
| Sl No | Description | Qty | Unit | Best Power Controls L1 | Angel electricals L2 |
|---|---|---|---|---|---|
| 1.00SITC of ups and additional electrifications | |||||
| 1.00 | 1.10.2:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS
PVC insulated copper conductor single core cable etc as required.Group B | 4 | point | 1,200 ₹4,800 Lowest | 1,256.19 ₹5,024.76 |
| 1.00 | OD96051/2025-2026:Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. ceiling/wall with and factory made clamp and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1x17 w LED fitting with electronic driver, 50000 Burning Hrs, flicker free , efficiency 120 lumen/watt suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, (Philips Endura Next, model No. BN 308 C LED 20 S L 120 or its equivalent make) | 4 | each | 1,650 ₹6,600 Lowest | 1,864.89 ₹7,459.56 |
| 1.00 | 90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) | 1 | each | 6,550 ₹6,550 | 6,096.5 ₹6,096.5 Lowest |
| 1.00 | 2.3.4:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door | 1 | each | 3,540 ₹3,540 | 3,338.45 ₹3,338.45 Lowest |
| 1.00 | OD268502/2024-2025:Supplying and fixing FP sheet steel enclosure on surface/ recess | 2 | no | 400 ₹800 Lowest | 403.09 ₹806.18 |
| 1.01 | OD302831/2024-2025:
Supplying and clamping 20 mm sizes of corrugated PVC flexible conduit with necessary compression gland with locking ring and check nut at termination pointed using suitable size GI / painted MS saddles spacing not exceeding 60 cms on surface including making good the damages, colour washing etc. as required. | 4 | metre | 50 ₹200 | 48.39 ₹193.56 Lowest |
| 1.01 | OD302984/2024-2025:Supply Installation Testing and commissioning of 15KVA=15KW Unity output power factor model 3 phase Input and three phase tower type online double conversion pure sine wave ups system with isolation transformer with salient features like, maximum power availability Leading AC-AC efficiency up to 95% . Low harmonic pollution(iTHD<3%) & high input power factor (>0.99) . DSP based technology , IGBT Rectifier and inverter, Generator compatable, Noise level <58dB. Display Panel (In-build LC Display & LED ) Input: Voltage / Frequency Bypass: Voltage / Frequency, Temperature: STS/Inverter/PFC, Battery: Voltage / Capacity Output: Voltage / frequency / Current, Event Logging & Statistical Data (On LCD): UPS should capture and display up to 500 events, User Programmable Parameters & Settings (On LCD), Indications (LED), Audible Alarms for Mains Failure / Battery Low Alarm / UPS Overload / Fault / Shut down etc. The UPS shall be housed in a free standing enclosure, and free from defects, sharp edges, nicks, scratches, burs etc. and provisions for suitable ventilation, easy maintenance, Trolley wheel etc. (Delta /sochomec/Emerson )The supplier should be submitting Tested documents, Operation manual, service manual etc. External Exide make C10 RATED TUBULAR BATTERY 12V, 75AH MINIMUM 32Numbers (Exide /Amaron). including Suitable UPS& Battery Rack, Battery Breaker Switch with Cables and its accessories. Warranty for 3 years for UPS and 5 years for battery from the date of invoice. and three year free service (without water). | 1 | each | 6,18,324 ₹6,18,324 Lowest | 6,50,155.43 ₹6,50,155.43 |
| 1.01 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | 1 | each | 490 ₹490 | 462.02 ₹462.02 Lowest |
| 1.01 | 2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual
current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | 1 | each | 2,950 ₹2,950 | 2,808.23 ₹2,808.23 Lowest |
Tender Value
Refer Docs
EMD Value
₹18,813
Closing Date
18 Jul 2025, 5:00 pmClosed
ASSISTANT EXECUTIVE ENGINEER,
O/o ASSISTANT EXECUTIVE ENGINEER, PWD ELECTRICAL SUB DIVISION, IDUKKI, PAINAVU P.O, PAINAVU-685603
DEPOSIT-THQH- Nedumkandam -SITC of UPS and allied electrical works in Laboratory block .-THQH- Nedumkandam -SITC of UPS and allied electrical works in Laboratory block .-General Electrical Work
2025_PWD_775997_1
PWD/BLDG/TR/1904/2025_6_1_1/1
Open Tender
Electrical Works
Item Rate
90 days
Nedumkandam
Please refer Tender documents.
10 documents required · 10 mandatory
₹1,660
₹18,813
13 Oct 2025
10 Jul 2025
21 Jul 2025
10 Jul 2025
18 Jul 2025
10 Jul 2025
Amount
SITC of ups and additional electrifications
1.10.2:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B
OD96051/2025-2026:Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. ceiling/wall with and factory made clamp and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1x17 w LED fitting with electronic driver, 50000 Burning Hrs, flicker free , efficiency 120 lumen/watt suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, (Philips Endura Next, model No. BN 308 C LED 20 S L 120 or its equivalent make)
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.3.4:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
OD268502/2024-2025:Supplying and fixing FP sheet steel enclosure on surface/ recess
OD302831/2024-2025: Supplying and clamping 20 mm sizes of corrugated PVC flexible conduit with necessary compression gland with locking ring and check nut at termination pointed using suitable size GI / painted MS saddles spacing not exceeding 60 cms on surface including making good the damages, colour washing etc. as required.
OD302984/2024-2025:Supply Installation Testing and commissioning of 15KVA=15KW Unity output power factor model 3 phase Input and three phase tower type online double conversion pure sine wave ups system with isolation transformer with salient features like, maximum power availability Leading AC-AC efficiency up to 95% . Low harmonic pollution(iTHD<3%) & high input power factor (>0.99) . DSP based technology , IGBT Rectifier and inverter, Generator compatable, Noise level <58dB. Display Panel (In-build LC Display & LED ) Input: Voltage / Frequency Bypass: Voltage / Frequency, Temperature: STS/Inverter/PFC, Battery: Voltage / Capacity Output: Voltage / frequency / Current, Event Logging & Statistical Data (On LCD): UPS should capture and display up to 500 events, User Programmable Parameters & Settings (On LCD), Indications (LED), Audible Alarms for Mains Failure / Battery Low Alarm / UPS Overload / Fault / Shut down etc. The UPS shall be housed in a free standing enclosure, and free from defects, sharp edges, nicks, scratches, burs etc. and provisions for suitable ventilation, easy maintenance, Trolley wheel etc. (Delta /sochomec/Emerson )The supplier should be submitting Tested documents, Operation manual, service manual etc. External Exide make C10 RATED TUBULAR BATTERY 12V, 75AH MINIMUM 32Numbers (Exide /Amaron). including Suitable UPS& Battery Rack, Battery Breaker Switch with Cables and its accessories. Warranty for 3 years for UPS and 5 years for battery from the date of invoice. and three year free service (without water).
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
OD302989/2024-2025:Supply of Distilled/Deionized Lead acid battery water (5 Liter Bottle)
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
5.9:Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
OD302598/2024-2025:Painting letters or figures of the 2.50 cm, 4 cm or 5 cm height sizes with enamel paint as identification mark to SB, DB, panel board etc as required<br
Angel electricals (BID ID -2254899)
Bidder Name
Best Power Controls
Angel electricals
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1268459.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .