Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.1 LAccepted-AOC H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L1 | Accepted-AOC LOWEST REASONABLE BID | |
| 2 | L2₹29.5 L+₹56,707 (1.96%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | Rejected-Technical 0 NEAR SHIV MANDIR KALYANIPURA KRIPAL NAGAR AJMER RAJASTHAN 305001 UDYAM RJ 01 0091182 | AJMER | RAJASTHAN | 305001 | - | Rejected-Technical Not Eligible bidder as No in WLR |
Tender Value
₹29.9 L
EMD Value
₹59,800
Closing Date
12 Mar 2022, 6:00 pmClosed
CWE ARMY JODHPUR
CWE ARMY MULTAN LINE ARMY AREA JODHPUR
Repair / Maintenance to HT Over head line and Poles of 33 KV and 11 KV, Power and distribution transformers, HT Panels , earthing and other connected wks at Ralawas under GE Banar
2021_MES_497028_2
CWE (A) JODH/BNR-53 OF 2021-22
Open Tender
Civil Works
Item Rate
150 days
Banar
Please refer Tender documents.
4 documents required · 4 mandatory
₹500
GE Banar
₹59,800
4 May 2022
19 Feb 2022
19 Mar 2022
19 Feb 2022
12 Mar 2022
26 Feb 2022
Amount
Supply and fix in repair straight through joint heat shrinkable type suitable for 11 KV 3 core PVC /XLPE cable of cross sectional area 120 Sqmm to 185 Smm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 11 KV grade , out door termination heat shrink type, complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 Sqmm to 185 Sqmm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 11 KV grade , out door termination heat shrink type, complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 50 Sqmm to 95 Sqmm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 11 KV grade , Indoor termination heat shrink type, complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 50 Sqmm to 95 Sqmm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 Sqmm to185 Sqmm complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair cable jointing kit for 33 KV grade cable for Indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 240 Sqmm to 300 Sqmm complete all as specified and directed by Engr-in-charge.
Supply and fix in repair cable jointing kit for 33 KV grade out door termination heat shrink type, complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 240 Sqmm to 300 Sqmm complete all as specified and directed by Engr-in-Charge.
M&L for checking , tightening & Replacement of jumpers , clamps connectors of 33 KV bus bar for the Power transformer in the yard / sub station complete all as specified and directed by Engr-in-Charge.
M&L for Removal of Birds Nest and foreign material from the over head line complete all as specified and directed by EIC.
M&L for resagging of overhead conductor section of 33 KV including binding/re-binding of conductor with suitable size of wire and providing of jumpers at the ends as per site requirements complete all as specified and directed by Engr-in-Charge.
M&L for replacement of rusted/broken GI earth wire of 4 mm dia for guard on Overhead line by providing reels and clamps and any other items required for fixing as per site requirement complete all as specified and directed by Engr-in-Charge.
Dismantling and taking down HT pole of old ACSR conductor complete all as specified and directed by Engr-in-Charge.
M&L for Replacement of old ACSR conductor with new ACSR conductor including binding of wire and providing jumpers at the end as per site requirement complete all as specified and directed by Engr-in-Charge.
Fixing and restringing of old serviceable (ACSR) conductor obtained from items No 13 here in before including binding complete all as specified and directed.
Taking out old unserviceable 33 KV pin insulator incl taking out 33 KV OH ACSR conductor and supply and fix 33 KV pin type, porcelain, vitreous, insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut for fixing of insulator on HT pole incl refixing the OH ACSR conductor at the same place incl binding the conductor to insulator with new binding wire complete all as directed.
M&L for replacement of defective/damaged Disc insulators suitable for 33 KV overhead conductors including removing/providing jumpers with line conductors as per required at site complete all as specified and directed by EIC.
M&L for straightenig of cross arms with clamps including tightening of nut bolts , washers complete all as specified and directed by Engr-in-Charge
M&L for Servicing, testing the functioning of all the existing 33 KV panels,Indoor/Outdoor VCBs & all other connected accessories and carrying out necessary maintenance such as applying grease, gel etc., including calibration of VCBs, carrying out necessary repairs along with making arrangements for testing of equipment, and necessary instruments required for testing of relays installed over the panels all as specified and as directed by Engr-in-charge.Note: Spare parts shall be measured and paid separately under relevent schedule items.
M&L for Servicing, testing the functioning of all the existing 11 KV panels, VCBs & all other connected accessories and carrying out necessary maintenance such as applying grease, gel etc., including calibration of VCBs, carrying out necessary repairs along with making arrangements for testing of equipment, and necessary instruments required for testing of relays installed over the panels all as specified and as directed by Engr-in-charge Note: Spare parts shall be measured and paid separately under relevent schedule items
Supply and fix Over Current and Earth fault protection relay suiable for 33/11 KV VCB Panel complete all as specified and directed by Engr-in-Charge.
Supply and fix Master Trip relay operating viltage 110V AC and 24V DC suiable as per existing make for 33/11 KV VCB Panel complete all as specified and directed by Engr-in-Charge.
Supply and fix announciator panel 12 window type as per existing make and capacity complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair Buch, WTI , OTI Trip relay suitable existing size for 33/11 KV VCB Panel complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair Digital Volt meter suitable for HT VCB Panel complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair Digital Ammeter suitable for HT VCB Panel complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair Auxialiary relay for Buch, WTI,OTI Alarm suitable for HT VCB Panel all as specified and directed by Engr-in--Charge.
Supply and fix in repair battery charging unit of output 110 V DC to existing HT VCB Panel of 33/11 KV complete all as specified and directed by Engr-in-Charge.
Taking out old unsv stay assembly and Supply and fix stay assembly complete comprising of MS galvanized stay plate 30cm x30cmx6mm , MS galvanized stay rod 20 mm dia with nut 180 cm long , MS galvanized stay bow 40cm long with 2 Nos galvanized thimbles with and including all fittings iNote:- Excavation, PCC for foundation (PCC 1:3:6) , loop type insulator, shackle & clamp shall be measured and paid separately under relevent schedule items
Taking out old stay strand wire and Supply and Fix GI stay strand wire of size 7/4mm complete all as specified and directed by EIC.
Supply and topping of transformer oil with adequate dielectric strength as mentioned in relevent IS as and when required to top up as replacement /evaporation ,leakage all as specified and directed by Engineer-in-Charge.
Dehydration of Transformer oil (mounted on plateform/ poles etc) with the help of filtering and drying plant by mechanical machine of suitable capacity to achive dielectric strength of 50 KV complete all as specified and directed by EIC. Note : a) The filteration of the transformer oil is to be carried out at different sub station in AGE E/M Nagtalao and also at Main receiving sub Station. (b) The report along with sample of oil before filteration & after filteration to be submited by contractor for approval by GE (c) The filteration is to be carried out on load i.e. without switching off supply. (d) Transformer oil for topping up will be paid separately under relevant item of Sch 'A'.
Taking out Old unserviceable indicator lamp from 11 KV VCB Panel and Supply and fix new phase indicating lamp neon type complete as per existing make and size with contct block & holder assembly of RYB Colour as directed
M&L cross arms, bracings, supports, clamp and back plates fabricated from structural steel section including nut/bolts washers, welding, bending, cold or hot drilling holes for bolts of any shape and size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including taking out old unserviceable complete all as directed.
Supply fixing and connecting and testing single pole zinc oxide (gaplesssurge type) heavy duty station class, self supporting outdoor type lighting arrester having rated voltage 30 KV (rms) discharge current 65 KA insulationlevel 35/75 KV/KVP (Peak) suitable for rated system voltage of 33 KV supplysystem with maximum continuous operating v oltage (MCOV) not less than17.05 KV (rms) with highly non linear ceramic resister made of zinc oxide inhermetically sealed container complete with metal base, base inculator andsuitable terminals for ground connections and pressure relieving arragementcomplete all as specified Note : The rate quoted against above itemshall include necessary fixing arrangement of lightening arresster on twopole/four pole structure as per recommendations of manufactures.
Dismantling old unserviceable LA and supply and fix lightening arrestor 11000 volts non linear resistor type conforming to IS-3070 Part I complete, line discharge class-2 nominal discharge current 10 KA & high discharge 65 KA assembly suitable for 11 KV incl. all clamps, nuts, bolts & washers & connecting to earth with GI earth wire complete all as specified and directed by Engr-in-Charge
Dismantling of existing defective HT 11 KV Gang operated air break switch and Supply and installation, commissioning and testing of HT 11 KV outdoor type triple pole gang operated air-break switch suitable for horizontal mounting rotating type with 9 insulator 200 amps current rating complete mechanically operated mechanism from ground level consisting of operating rod of 25 mm bore medium grade GI pipe of suitable length with locking arrangement, flat iron clamp 50x6mm including MS channel of suitable size and length for fixing GOD including bolts, nuts and washers complete all as directed by Engr-in-Charge
Dismantling of existing defective HT 33 KV Gang operated air break switch and Supply and installation, commissioning and testing of HT 33 KV outdoor type triple pole gang operated air-break switch double stack type suitable for horizontal mounting rotating type with 9 insulator 200 amps current rating complete mechanically operated mechanism from ground level consisting of operating rod of 25 mm bore medium grade GI pipe of suitable length with locking arrangement, flat iron clamp 50x6mm including MS channel of suitable size and length for fixing GOD including bolts, nuts and washers complete all as directed
Taking out old silica gel breather and Supply & fix new Silica Gel breather having threaded bore as per site required.
Taking out old Moisturised silica gel from breather and Supply & filling new silica Gel in the breathers in crystals complete.
Taking out old unserviceable PG Clamp and supply and fix new PG clamp in repair all as directed and specified.
Taking out old unserviceable HT cable and Supplying,laying, jointing, testing and commissioning of aluminium 95 sqmm XLPE insulated screened PVC bedded galvanised steel strip or wire armourred electric power cable (Heavy duty ) with aluminium conductor 11000 volts grade, cross sectional area 95 sqmm 3 core suitable for 11KV earthed systems all as specified and directed.
Taking out old unserviceable HT cable and Supplying ,laying, jointing, testing and commissioning of aluminium 120 sqmm XLPE insulated screened PVC bedded galvanised steel strip or wire120 sqmm 3 core suitable for 11KV earthed systems all as specified and directed.
Excavating in trenches n.exc 1.5 m width and n.exc 1.5m in depth for taking out cable and cable cover and getting out in any type of soil
Returning, filling in, including spreading levelling, watering and well ramming in layers n.exc 25 Cm
Removing excavated materials n.exc 50 mtr depositing where directed at a level n.exc 1.5 m above the starting point
M&L for sand cushioning to PVC/ XLPE cables with low grade sand and punning to provide required cover to UG cables. Note :- For the purpose of payment only punned thickness will be measured
Supplying and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mmx l80mm x 40mm complete all as directed at site by Engineer-in-Charge.
M & L for laying / topping up of 40 mm stone aggregate in switch yard/electric installations/ two pole/ four pole structure and all as directed at site by Engineer-in-Charge.
M&L for Surface excavation n.exc 30 cm deep and averaging 15 cm and geeting out in any type of soil incl cutting, cleaning and removing of bushes/branches/vegitation complete from the site all as directed by Engineer-in- Charge.
Dismantling of existing PCC/Steel Pole and S&F Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-64 (12 metres long) complete all as directed by Engineer-in- Charge.
Dismantling of existing Air termination and Supply and fix Air termination , single pointed aluminium rod of 12 mm dia and 300 mm long complete all as specified and directed by Engr-in-charge
Dismantling of existing GI pipe and Supply and fix GI pipe of 40 mm dia light grade not less than 1.0 mtr to provide height to the air termination rod alongwith suitable size of stand to fix on the top of pole complete all as specified and directed by Engr-in-charge.
Dismantling of existing aluminium strip and Supply and fix aluminium strip 25X3.15 mm with saddles / porcelin insulator is to be tightend with pole by using suitable size of GI wire for pole and down conductors on the top of pole up to test point complete all as specified and directed by Engr-in-Charge.
Dismantling of existing test point and Supply and fix test point terminal block made of Gun metal or phosphorus bronze size 75X75X25 mm drilled and screwed including 3 nos 8 mm dia 25 mm long hex head screw complete all as specified and directed by Engr-in-charge.
Dismantling of existing earthing and M&L for plate earthing complete with Copper plate electrode 60 cm x 60 cm x 3.15 mm thick buried directly in ground vertically (in earth pit not less than 2.25 metre deep below ground level) with the top edge of earth plate at a depth not less than 1.5 metre below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm in alternate layers on all sides and including Copper earth strip 20x3mm bolted (with brass nuts, bolts & check nuts) and rivetted to earth (Plate) electrode at one end and connected to elect pole/main switch board / Neutral of transformer/ body of transformer at the other, earth strip protected by and incl GI pipe 40 mm dia (medium grade) from top of electrode to connecting point with equipment and also incl watering pipe GI pipe (medium grade) 20 mm bore from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B0 using 12 mm graded crushed stone aggregate, RCC cover with handle, funnel, wire mesh including necessary excavation & earth work, etc as shown on electrical plate No 5 of SSR Part I.
Dismantling of existing earthingand M&L for GI plate Electrode of size 60 Cm X 60 Cm X 6 mm thick burried directly in ground vertically at a depth not less than 2.25 mtr. below normal ground level, with top edge of earth plate at a depth not less than 1.5 mtr. below normal ground level , connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts and washers of galvanised iron , earth lead wire protected by means of 15 mm bore dia light grade GI pipe up to switch board / panel board , all as specified and shown in MES schedule Electrical Plate No:-5 of SSR Part I, including excavation and earth work in any type of siol , PCC 1 : 2 : 4 type C1 in chamber , RCC 1:2:4 type C1 40 mmthick cover slab with 6 mm dia MS bars at 100 mm centre to centre both ways,with 6 mm dia MS hook, Charcoal dust, salt , funnel for watering complete as shown on electrical plate No 2 of SSR Part I. all as specified and as directed.
Dismantling of existing copper strip and Supply & laid copper strip in repairs of size 25 mm X 3.15 mm as a ring conductor network buried in ground 1 mtr below from surface complete all as directed at site by Engineer-in -charge
Material and labour for cutting the branches/trees near the HT OH line upto clearance area 5mtr around OH line by cutting the branches and removing the wastage from site to disposal area and all as specified and direced, Note :-(i) The necessary man power tool and plant , cutting tools and JCB if required for cutting/ prunning of branches is deemed to incl in the rate quoted for the job (ii) Proper shut down will be taken from JE E/M only.
Dismantling of existing GI earthing and M&L for plate earthing complete with galvanized mild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than 2.25 metre deep below ground level) with the top edge of earth plate at a depth not less than 1.5 metre below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm in alternate layers on all sides and including GI earth strip of 32x 6 mm as earth electrode bolted with GI nuts, bolts & check nuts and rivetted to earth (Plate) electrode at one end and connected to Panel at the other, earth strip protected by and incl GI pipe 40 mm dia (medium grade) from top of electrode to Panel and also incl watering pipe GI pipe (medium grade) 20 mm bore from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B0 using 12 mm graded crushed stone aggregate, RCC cover with handle, funnel, wire mesh including necessary excavation & earth work, etc as shown on electrical plate No 3 of SSR Part I.
Dismantling of existing earth continuity and M&L for earth continuity conductor or main earthing lead fixed to wall on insulators or recess or chases or buried in ground or drawn in conduit/pipe for loop earthing etc. as required 32x6mm galvanized strip complete all as specified and as directed by EIC.
Preventive maintance /servicng and testing of power transformer 2.0 MVA of 33/11KV at MRSS Ralawas, following test shall be carried out at site by calibrated instrument (calibration certificate shall be submitted) complete all as specified and directed by Engineer-in-Charge. (a). Magnetic balance test (b). IR Test (c).WTO/OTI tripping (d).Oil level and leakage (e). Transformer oil test (i). earthing valve check body and netural (ii).Megar/dielectric streanth Complete all as specified and directed by EIC.
Preventive maintance /servicng and testing for power transformer 1.0 MVA of 33/11KV at MRSS Ralawas, following test shall be carried out at site by calibrated instrument (calibration certificate shall be submitted) complete all as specified and directed by Engineer-in-Charge. (a). Magnetic balance test (b). IR Test (c).WTO/OTI tripping (d).Oil level and leakage (e). Transformer oil test (i). earthing valve check body and netural (ii).Megar/dielectric streanth Complete all as specified and directed by EIC.
Preventive maintance /servicng and testing of distrubution transformer of various capacity upto 500 KVA at Ralawas, following test shall be carried out at site by calibrated instrument (calibration certificate shall be submitted) complete all as specified and directed by Engineer-in-Charge. (a). Magnetic balance test (b). IR Test (c).WTO/OTI tripping (d).Oil level and leakage (e). Transformer oil test (i). earthing valve check body and netural (ii).Megar/dielectric streanth Complete all as specified and directed by EIC.
Racking out and Servicing for HT switch gear VCB of capacity 400-630,33 KV by tripping off the breaker and draw out the trolleyand servicing and overhauling the mechanical parts with applying the grease and checking the wiring and tripping mechanism,replacement of damaged minor parts such as control wiring ferrules,HRC fuse,caliberation of IDMT/Microprocessor numerica/digital relay existing on panels with secondery injection kit and setting the relay of earth fault,short circuit to over current time delay setting as per existing load of feeder and all as specified and dirtected by Engr-in-charge at 33 MRS Note: Spare parts shall be measured and paid separately under relevent schedule items
Racking out and Servicing for HT switch gear VCB of capacity 400-630,11 KV by tripping off the breaker and draw out the trolleyand servicing and overhauling the mechanical parts with applying the grease and checking the wiring and tripping mechanism,replacement of damaged minor parts such as control wiring ferrules,HRC fuse,caliberation of IDMT/Microprocessor numerica/digital relay existing on panels with secondery injection kit and setting the relay of earth fault,short circuit to over current time delay setting as per existing load of feeder and all as specified and dirtected by Engr-in-charge at 33 MRS Note: Spare parts shall be measured and paid separately under relevent schedule items
Supply and fix in repair Spring charging Motor 230V AC/Dcuniversal type for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Gear assembly Big size for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Gear assembly small size for existing 11 KV VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Trip holding Shaft for existing 11KV VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repairTrip coil for existing VCB complete all as specified and dirtected by Engr-in-Charge
supply and fix in repair Close holding shaft for existing VCB complete all as specified and dirtected by Engr-in-Charge
supply and fix in repair Close coil for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Charging Spring for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Drum Switch for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Anti Pumping device 24V DC for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Limit switch complete all as specified and dirtected by Engr-in-Charge
Supply,and fix in repair power bank unit of 110V DC output to existing HT VCb panel of 33/11 KV complete all as specified and dirtected by Engr-in-Charge
Supply and fix TNC switch for 11 KV VCB breaker as per existing make and specification and directed by EIC
Supply and fix Local remote switch for VCB breaker as per existing make and specification and directed by EIC
Supply and fix in repair 11 KV VCB trolly gear having 9 teeth complete all as specified and directed by Engr-in-Charge
Supply and fix in repair Service position switch for existing 11 KV VCB complete all as specified and directed by Engr-in-Charge
Supply and fix in repair Vaccuminterruptor for existing VCB complete all as specified and dirtected by Engr-in-Charge
Supply and fix in repair Local remote switch for existing11 KV VCB complete all as specified and directed by Engr-in-Charge
Supply and fix in repair Dual Core CT Indoor type suitable for 11000 volts for existing VCB complete all as specified and directed by Engr-in-Charge
Supply and fix in repair 11 KV PT resin cast ration 11KV /110V 25VA class 0.2 for existing VCB complete all as specified and dirtected by Engr-in-Charge
M&L for 33 KV MRS Yard ( 14Nos ) Tower pole 12 mtr height horizental arms and other structures etc complete painting with two coat alunium colours including all clamps,bars,iron item inside the yard
M&L for laying 40 to 50 mm thick quarry faced stone slab 25 to 30 cm wide and not exceeding 60 cm long laid dry abutting each other with gap between adjacent patties n.exc 10 mm for 33KV yard/sub stn protection for aggreagte complete all as specified and dirtected
Supply and Fix PVC insulated multicore FR PVC sheathed multistranded cables with bright annealed electrolytic bare copper conductor 1100 V 2.5 sqmm 12 core conforming to IS-694:2010
Supply and Fix PVC insulated multicore FR PVC sheathed multistranded cables with bright annealed electrolytic bare copper conductor 1100 V 2.5 sqmm 4 core conforming to IS-694:2010
Cleaning of Power transformer,distribution transformer,VCB outdoor body through cleaning agent and removing the dust by blower,remove corrosion take proper shut down complete as specified and dirtected by EIC
Dismantling and taking out old fencing with barbared wire,iron bar and PCC piller etc removing from the site leveling the distrubing area spread the soil and suitable leveling at ralawas area max length of fencing not exc 30 mtr complete as specified and directed by EIC
Supply only Multi use lubricant (DC 2-26) of capacity of 500 ml bottle for cleaning of electrical connect surfaces and removing rust of mechnical parts of VCBs,breakers use displace and seal out moisture released rusted mechanisms compelte
Supply and fix in repair 33 KV outdoor VCB operating mechanisms complete set for as existing VCB as specified and directed
Supply and fix in repair 33 KV SRBP tube only for dropout fuses as specified and directed by EIC
Supply and fix in repair 33 KV Fibre glass tube only for dropout fuses as specified and directed by EIC
Supply and fix in repair 33 KV fibre tube with metal fitting on both ends only for dropout fuses as specified and directed by EIC
Only labour for control wiring for 33/11 KV VCB panel including all connection,testing compete as per directed by EIC
Supply and fix in repair 11 KV SRBP tube only for dropout fuses as specified and directed by EIC
Supply and fix in repair 11 KV Fibre glass tube only for dropout fuses as specified and directed by EIC
Supply and fix in repair 11 KV fibre tube with metal fitting on both ends only for dropout fuses as specified and directed by EIC
Supply and fix in repair 33 KV Male contact/moving contact blade as specified and directed by EIC
Supply and fix in repair 33 KV Female contact/fix contact jaw as specified and directed by EIC
Supply and fix in repair 33 KV Tinned copper flexible jumper 200A/400A as specified and directed by EIC
Supply and fix I n repair33 KV MS Jumper carrier as specified and directed by EIC
Supply and fix in repair 11 KV Male contact/moving contact blade as specified and dirtected by EIC
Supply and fix in repair 11 KV Female contact/fix contact jaw as specified and dirtected by EIC
Supply and fix 11 KV Tinned copper flexible jumper 200A/400A as specified and dirtected by EIC
Supply and fix in repair 11 KV MS Jumper carrier as specified and dirtected by EIC
Supply and fix in repair 12KV/250 Amp H.V brass set stem complete set IS-3347/1967 as specified and dirtected by EIC
Supply and fix 1.1 KV/250 Amp L.V brass bushing set stem complete set IS-3347/1967 as specified and dirtected by EIC
Supply and fix in repair 1.1 KV/400 Amp L.V brass bushing set stem complete set IS-3347/1967 as specified and dirtected by EIC
Supply and fix in repair 1.1 KV/630 Amp L.V brass bushing set stem complete set IS-3347/1967 as specified and dirtected by EIC
Dismantling of chain link fencing wire mesh any type any size complete
S&F MS angle iron as in fencing posts and struts in fencing includling cutting tops to shape as dirtected drilling holes cut to length bent to shape ,notching for wire etc conforming to Fe-310 .
S&F MS work confirming to Fe 310-O as in FI fillets for securing chain link fecing angle iron horns,posts etc cut to length bent to shape with necessary cuts drilling holes etc all as specified and directed by EIC
S&F Chain link fencing of MS GI wire mesh 3mm dia of GI wire mesh upto to into mattresses or cages lapped wired incl staple all fixing arragement complete all as dirtected by EIC
S&F MS round bar 10mm dia confriming to Fe 290 gde E-165 as line wire for chain link fencing type including cutting to length,bend to shape required as per site , welding ,binding with MS wire all complete as dirtected by EIC
S&F MS scew bolts(Machine made) with heagonal or square heads at one end and screwed the other or screwed both ends each screwed end to be fitted with washer and one hexagonal or square nut ex 5cm but not exceeding 10cm long and dia of shank 11 to 15mm all complete as per dirtected
S&F Fe-410-W(gde E250) quality A rolled steel sections/hollow sections as in main and cross beam,purlins,where connected to common rafters and runing rail fixed with angle cleats or other connecting plates all as specified and dirtected by EIC
S&F Pre painted galvatume aluminium zinc coating GI bassed corrugated steel sheet 0.5mm thick of camoflague colour having tensile strenght of 550 Mpa as in roof covering /cladding to wal,fixed with hot dip galvanised self drilling fasters with EPDM washers(One faster on each crest)complete all as specified and dirtected by Engr-in-charge
S&F flat iron FE-290 GdeE-165 as in wind ties including all necessary drilling,bolting or riveting etc as specified and dirtected by Engr-n-Charge
M&L for concrete 1:4:8 type D-2(using 40mm grade stone aggregate) as in sub base foundation/flooring etc.as specified & dirtected by Engr-in-Charge
M&L for stone masionary squared rubble walling jodhpur type brought uptocoursewell bonded bedded and soliding hearted built will cement mortor 1:4 as per pecpcified as directed by Engr-in-Charge
M&L for rendered 10mm thick plaster wall/surface for two coat as per specified as dirtected
M&L for white washing on fresh plaster wall/surface for two coat as per specified as dirtected
M & L for PCC type B2 ratio 1:2:4 (using 20 mm graded stone aggregate ) as in platform, sub base for foundation etc. complete with quick setting cement complete all as specified and directed by Eng-in-Charge.
S&F in replacement of 3 Pole 12 Amp contractor confirming to IEC-60947-4-1 complete all as specified as dirtected .
S&F in replacement of 3 Pole 12 Amp overload protection relay confirming to IEC-60947-4-1 complete all as specified as dirtected
S&F in replacement of Electronic timer 03-30 sec 415V 50Hz with mounting kit suitable for as per site requirement all complete as specified as dirtected by EIC
S&F in replacement of AC to DC Converter DIN Rail Mountable metal single phase 230V 50Hz SMPS type of G31-60-24 protection against short circuit,overload& overvolatge all complete suitable for as per site requirement all complete as specified as dirtected by EIC.
S&F in repair expulsion fuse (drop out fuse) mounted on 2 Nos of HT insulators, single pole upto 50 Amps 11 KV with spring mechanism complete in all respects and connection as directed.
Supply and fixing in repair loop insulator vitreous procelain white,brown,green large size overall dimenssion 90mmx140mm clerance of hole 25.5mm complete as per directed by EIC
M/S SHREE AAINATH ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .