Director
Regional Cancer Centre Medical College campus Trivandrum
Replacement of 02 nos of existing 250 TR cooling towers of the centralised HVAC system
2025_RCC_768176_2
RCC/ENG-M/2025-26/E-112
Open Tender
Miscellaneous Works
Item Rate
75 days
RCC-TVM
Please refer Tender documents.
19 documents required · 19 mandatory
₹2,950
Yes
₹50,000
Yes
12 Sept 2025
2 Jul 2025
17 Jul 2025
2 Jul 2025
15 Jul 2025
3 Jul 2025
3 Jul 2025 - 15 Jul 2025
Cooling Tower
Supply, Installation, testing & commissioning the cooling towers as per specification including all accessories as specified and as required 250 TR Cooling towers of actual capacity complete in all respects as per technical specifications and equipment schedule complete with FRP casing, FRP fan cylinder, PVC louvers, PVC drift eliminator polypropylene nozzles, drive assembly, HDG fan guard/bird screen, non-clogging nozzle type water distribution system. PVC fill, aluminium ladder with railings, make up, quick fill, drain over flow connections, provision for equilizer line etc. as per specifications.<br> R.C.C foundation BY RCC<br>EWT = 97.5 degree F<br>LWT = 90 degree F<br>WET bulb = 82 degree F<br>250 TR - CTI Approved<br>Induced draft, cross flow cooling tower with vertical air discharge<br>Motor suggested 10 HP ( single motor unit)<br>Flow rate = 1000 usgpm<br>
Valves
AUTO AIR VENTS including Ball Valves<br>Supply & install of airvents / purge valves at the highest points in chilled water piping complete each floor with pipes nipple welded to pipe, hex nipple, socket, Upipe connection at outlet of air vent etc. as required.
BUTTERFLY VALVES:<br>Supply, installation, testing & commissioning of the following butter fly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating. Valve above 300 mm dia shall be gear driven.<br>150 mm dia.
Supply, installation, testing & commissioning of the following butter fly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating. Valve above 300 mm dia shall be gear driven.<br>200mm dia
PVC Drain Pipe
Supply, installation, testing & commissioning of the following PVC Pipes with necessary fitting as per the specifications and as required.<br>50 mm dia. PVC Pipe for Drain
Supply, installation, testing & commissioning of the following PVC Pipes with necessary fitting as per the specifications and as required.<br>80 mm dia. PVC Pipe for Drain
Electrical Work
EARTHING<br>Supply and laying earthing for various equipments and motors. <br>10 SWG copper wire<br>
CABLES<br>Supply of 1.1 Kv PVC insulated PVC sheathed steel armoured cables of approved make and laying and fixing of PVC insulated PVC sheathed cable of 1.1Kv grade on surface/cable tray as required and making end termination with brass compression gland for PVC sheathed cable of 1.1Kv grade and fabricating and installing MS cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from ceiling with MS suspenders including painting etc. ( IN R.M.)<br> 3 core x 1.5 sq mm copper cable
CABLES<br>Supply of 1.1 Kv PVC insulated PVC sheathed steel armoured cables of approved make and laying and fixing of PVC insulated PVC sheathed cable of 1.1Kv grade on surface/cable tray as required and making end termination with brass compression gland for PVC sheathed cable of 1.1Kv grade and fabricating and installing MS cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from ceiling with MS suspenders including painting etc. ( IN R.M.)<br> 3 core 6 sq.mm Al. cables
Lockable off push button near CT
ISOLATORS.<br>3 Phase<br>
Condenser Water line
Condenser water pipesSupplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS ?C? class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. <br> Note:-The Pipes size 150mm & below shall be M.S. ?C? class as per IS : 1239 and pipe size above 150mm shall be welded black steel pipe heavy class as per IS:3589, from minimum 6.35mm thick M.S. Sheet for pipes up to 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.Condenser water piping of nominal size - 200 mm dia
Condenser water pipesSupplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS ?C? class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. <br> Note:-The Pipes size 150mm & below shall be M.S. ?C? class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS:3589, from minimum 6.35mm thick M.S. Sheet for pipes up to 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.Condenser water piping of nominal size - 150 mm dia
Buy Back of 250 TR Cooling Tower
BUY BACK OF EXISTING TWO 250 TR COOLING TOWER<br>Removing, clearing and transportation of existing 250 TR cooling tower, Condenser water line, condenser water line, Valves etc. as per the instructions of RCC & Consultant, to be done with upmost precautions, and making good of surfaces.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .