| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.4 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹16.7 L+₹1.2 L (7.81%)Rejected-Finance DOOR NO 14 6 21 5 OPP MARVAL SCHOOL BC ROAD NEW GAJUWAKA VISAKHAPATNAM 530026 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530026 | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹17.9 L+₹2.4 L (15.6%)Rejected-Finance | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹18.4 L+₹3.0 L (19.2%)Rejected-Finance | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹20.1 L+₹4.7 L (30.3%)Rejected-Finance | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹24 L
EMD Value
₹48,000
Closing Date
3 Jan 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (I) (DM) VISAKHAPATNAM
GE (I) (DM) VISAKHAPATNAM Naval Dockyard 530014
PERIODICAL MAINTENANCE, REPAIR OF PACKAGE TYPE AC PLANTS AND ALLIED WORKS AT NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) (DM) VISAKHAPATNAM
2021_MES_492890_1
SSGE/8660/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (I) (DM) VISAKHAPATNAM
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE (I) (DM) VISAKHAPATNAM
₹48,000
Yes
4 Feb 2022
6 Dec 2021
10 Jan 2022
6 Dec 2021
3 Jan 2022
20 Dec 2021
60 days
Amount
Supply only R-22 gas complete all as specified and as directed Make:- Refron 22/Floron 22/Mafron 22
Material and labour for taking out the defective pressure cut-outs of HP/LP pressure cut-out MP-15 model and supply & fix new pressure cut-outs, connecting the pressure lines/control wiring, leak testing and commissioning complete all as specified and as directed Make:-Indofoss/Danfoss/Ranco
All as per item No 2.00 above but for Water pressure cut-out IPS-70
All as per item No 2.00 above but for Low pressure cut-out MP-1
All as per item No 2.00 above but for High pressure cut-out MP-5
All as per item No 2.00 above but for Oil pressure cut-out MP-55
M&L for painting of outer surface of multiple section of complete LT Panel board size up to 5.5 m x 3.2 in one substation comprising ACBs/MCCBs/SDFs ,busbar chamber, swich gear chamber, metering chamber cable termination/tray using one coat of synthetic enamel paint after preparation of surface, providing protection cover to all metering equipment, panel meters, switchgears, cleaning of all meters and switch gears complete all as specified and as directed
Material and labour for complete checking, servicing / rectification of electrical circuits for all units and control wiring showing phase sequence with proper lugging of AC plant control panel including replacement of fused indication lamps with new ones, cleaning of all power contacts, rectification of minor defects in Ammeters and Voltmeters, testing and commissioning complete all as specified and as directed Note :- Material such as indication lamp, ammeter, voltmeter will be measured and paid separately.
Material and labour for de-scaling the condensers of 5 to 7.5 TR package AC units by using HCL acid agent with continuous circulation method using circulation pump, finally neutralizing with fresh water, opening both ends covers of shell and tube condenser, cleaning of copper tubes manually by using nylon brushes, re-fixing the end cover with new ‘Neoprene make’ rubber gaskets, nuts, bolts etc., and commissioning after conducting performance test of the system complete all as specified and as directed
Supply and fix in repairs pilot solenoid valve to the refrigerant system, reconnecting the refrigeration piping including leak testing, brazing to the pipe line, necessary copper tubing etc wherever required complete all as specified and as directed Make :- Sporlon/Donfos
Material and labour for taking out compressor, evaporator coils and blower with motor from corroded / unserviceable MS Sheet enclosure of Package AC unit 5/7.5 TR by disconnecting all electrical connection refrigerant lines condenser water pipe lines and re-install the compressor, condenser, evaporator coil and blower with motor in newly fabricated MS Sheet enclosure of package unit and AC unit cleaning of body, air filters and cooling coils by air blow with electric air blower and with water jet, drying up the AHU and connecting all electrical, refrigerant and condenser, water pipe lines, and pressure testing with nitrogen gas under constant pressure of 250 PSI for 24 hours, vaccumization, performance test and commissioning and charging the gas to unit , refixing and alignment of the blower and shaft, greasing the pedastal bearings, adjustment of 'V' belts tension including replacement of trunking canvas with zip, refixing the belt guards in position complete all as specified and as directed Note : Replacement of MS sheet enclosure will be measured and paid for separately.
Material and labour for taking out unserviceable condensor from ductable type unit 7.5 TR capacity by disconnecting all electrical connection refrigerant lines condenser water pipe lines and supply & fixing new condensor aircooled type and making all connections, electrical, refrigerant and condenser, water pipe lines, and pressure testing with nitrogen gas under constant pressure of 250 PSI for 24 hours, vaccumization, performance test and commissioning and charging the gas to unit making alignment complete all as specified and as directed Make : Voltas/Carrier
Material and labour for taking out unserviceable condensor from package type unit 5.0 TR capacity by disconnecting all electrical connection refrigerant lines condenser water pipe lines and supply & fixing new condensor Shell and tube type having Shell size pressure 21 Kg/sq cm and tube side 7 kg/ sq cm and making all connections, electrical, refrigerant and condenser, water pipe lines, and pressure testing with nitrogen gas under constant pressure of 250 PSI for 24 hours, vaccumization, performance test and commissioning and charging the gas to unit making alignment complete all as specified and as directed Make : Voltas/Carrier
All as per item No. 13.00 above but for 7.5 ton capacity.
Supply only MS sheet enclosure made out of 2mm gauge MS sheet suitable for accommodating 5/7.5 TR capacity of ductable AC outdoor unit including painting with two coats of synthetic enamel paint over a coat of redoxide primer and complete all as specified and as directed Note :- 1. Unit rate quoted shall be deemed to include for providing ISMC & angle iron of size as existing for mounting the enclosure embedded in and including necessary brick work duly plastered and finished all as directed. 2. Electrical connection, refrigerant lines compressor, blower, condenser, water pipe lines and gas charging will be measured and paid for separately.
Taking out unserviceable V-Belts and Supply and fixing of V-Belt of “A” section of size A-27, complete all as specified and as directed Make : Fenner/Dunlop/Gate
All as per item No 16.00 above but for A - 28
All as per item No 16.00 above but for A - 29
All as per item No 16.00 above but for A - 30
Taking out unserviceable V-Belts and supply & fixing of B-62 size complete all as directed and as directed : - Make : Fenner/Dunlop/Gate
All as per item No 20.00 above but for B - 63
All as per item No 20.00 above but for B - 66
All as per item No 20.00 above but for B - 68
All as per item No 20.00 above but for B - 96
All as per item No 20.00 above but for B - 98
All as per item No 20.00 above but for B- 128
All as per item No 20.00 above but for C - 158
Supply and fix new suction valve suitable for 5 T / 7.5 T package units, pressure testing with nitrogen gas under constant pressure of 250 PSI for minimum 24 hours vaccumisation, performance testing and commissioning including taking out old unserviceable suction valves complete all as directed and as directed
Supply and fix discharge valve suitable for 5 T / 7.5 T package units, pressure testing with nitrogen gas under constant pressure of 250 for minimum 24 hours vaccumisation, performance testing and commissioning including taking out old unserviceable discharge valves complete all as directed and as directed
Supply and fix PVC mesh Air filters with MS frame suitable for 5 to 7.5 TR package AC plants including taking out old unserviceable filter complete all as directed and as directed
Material and labour for taking out unserviceable filter drier from package type AC unit 5/7.5 TR and fixing the same complete all as specified and as directed Make:- Sporlon/Danfoss
M&L for repairs/maintenance of 5 to 7.5 TR package units by leak testing with N-2 gas under constant Pressure of 250 PSI (17 kg/cm2) after complete transfer of refrigerant gas from the entire system, rectification of leakage by cutting and brazing the refrigeration system wherever required, replacement Of “O” rings, teflon washers of valves, copper tubing, safety valves, flare nuts etc., neutralising after the Pressure holds, good for atleast 24 hours, vaccumization, charging the system with refrigerant Gas, performance test and commissioning complete all as specified and as directed Note : Referigerant gas will be measured as supply only.
Material and labour for cleaning of evaporator coil with caustic soda neutralising with fresh water blowing with electric blower for package type AC unit and replacement of canvas cloth with Zip arrangement for jointing the duct as required at site, complete all as specified and as directed .
Material and labour for taking out unserviceable thermostatic type expansion valve supply and fix thermostatic type expansion valve suitable for 7.5 ton package unit with necessary modification to refrigerant copper pipe line with silver brazing replacement of shut off valves flushing out the system pressure testing with nitrogen gas under constant pressure of 250 PSI at least 24 Hours vaccumization performance testing and commissioning and charging the gas to unit complete all as specified and as directed . Make : Sporlon
All as per item No. 34.00 above but for 5 ton capacity package type AC unit.
Supply and fix pressure gauge for suction/discharge refrigerant lines and water lines of square/round type 2"/4" dial of 0-150 PSI for refrigerant line for Package/Central type AC plants including taking down old unserviceable pressure gauge complete all as specified and as directed Make -Air Master/Febig/Scientific
All as per item No. 36.00 above but for 0-300 PSI for refrigerant line
All as per item No. 36.00 above but for 0-12 Kg./cm2 for water line
Material and labour for monthly cleaning of entire package AC plant substation buildings inside wall, ceiling, floor and outside wall, plinth protection with suitable brush/broom/wiper, removing wild vegitation around substation building complete all as specified and as directed
Supply and fix rubber insulating mat in front of LT panel board of size 2 mm thick, 1 m width up tp 3.3 KV, make RPG or equivalent as approved by GE complete all as specified and as directed
Supply only indication lamps (LED type) red, yellow and blue in colours of 22.5 mm dia to monitor on LT panel board suitable for 240 V AC supply and taking down unserviceable indication lamps complete all as directed and as directed . Make:-Siemens/C&S/schneider/ABB
Material & labour for taking down unserviceable burnt compressor, supply and fix new sealed scroll compressor suitable for 7.5 TR water cooled package units complete all as directed and as directed .
Material & labour for taking down unserviceable burnt compressor, supply and fix new sealed scroll compressor suitable for 5.5 TR water cooled package units complete all as directed and as directed .
Material & labour for taking down unserviceable burnt compressor, supply and fix new sealed scroll compressor suitable for 8.5 TR ductable unit complete all as directed and as directed .
Supply and fix remote assembly with senser for indoor unit of ductable AC unit, suitable for 8.5 TR ductable AC unit complete with control wiring, checking, correcting complete all as specified and directed including taking down the old assembly.
Supply, fabricate and erect MS supports (such as channel, angle, flats etc.) to package unit enclosure including painting to steel surfaces with two coats of synthetic enamel paint over a coat of zinc chromate primer including dismantling existing corroded MS supports complete all as specified and as directed
Material and labour for cleaning of air duct of any size as per plant ducts length including ducts filter and repairing/replacement / tighting existing sizes nuts, bolts, packing material etc., by brush, cleaning agents complete all as specified and as directed.
Material and labour for cleaning of air diffuser and repairing/ replacement / tighting existing sizes nuts, bolts, packing material etc., by using brush, cleaning agents complete all as specified and directed.
Material and labour for repairs and overhauling of blower motor of ductable AC plant upto 1.5HP capacity by disconnecting and taking out from the bed, replacement of worn out bush/ball bearing, lugs, studs, bolts etc., re-installing in it's original position including painting the motor body with one coat of synthetic enamel paint, connecting up, testing all as specified and directed.
Material and labour for disconnecting, taking out the blower motor of ductable AC plant upto 1.5 HP capacity from the bed, tranportation to workshop and removing the existing winding and rewinding with new super enameled copper wire of same gauge and same number of turns after thorough cleaning of stator body and rotor applying insulating varnish, drying up by heating for improving ohmic valve, reassembling the motor by replacement of both end bearings, including painting with one coat of synthetic enamel paint, reinstalling on its original position connecting up, testing complete all as specified and as directed.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .