AP STATE POLICE HOUSING CORPORATION LTD
AP
Providing HVAC System ( Heating Ventilation Air Conditioning system) to FORENSIC SCIENCE LAB Block -II at Tulluru of GUNTUR District-STN
917623
A55/2025-26
OPEN - NCB
Electrical Works
GUNTUR
15 documents required · 15 mandatory
₹6,630
₹1.9 L
15 Apr 2026
24 Mar 2026
24 Mar 2026
Supply of Air cooled VRV / VRF 20HP Air Conditioning system of having high COP complete with indoor and outdoor units duly charged with refrigerant R-410A and oil (first charge) suitable for cooling with individual controller, (suitable for 415 +/- 10% for outdoor and 230 +/- 5% for indoor units) and complete with all accessories, fittings etc. The units shall be BMS Compatible. Outdoor Units shall be fully inverter system complete with 100% scroll/rotary compressor and drive arrangement, initial charge of refrigerant (R-410A),refrigerant piping, drier, sight glass, dual pressure cutout all housed and supported properly in cabinet, air cooled condenser & its controller for following capacities. The VRV system shall be cooling only system. Type of Compressor : Hermitic sealed Inverter Scroll/TwinRotary ODU should delvier the required capacity at the ambient conditions of the place as per ISHRAE Standards. The System should be highly energy efficient and COP shall not be less than 3.7. The outdoor units shall be suitable for operation between 5 and 53 deg C in cooling mode. Makes: Mitsubishi ELectric /Toshiba / O General
Supply of Air cooled VRV / VRF 18HP Air Conditioning system of having high COP complete with indoor and outdoor units duly charged with refrigerant R-410A and oil (first charge) suitable for cooling with individual controller, (suitable for 415 +/- 10% for outdoor and 230 +/- 5% for indoor units) and complete with all accessories, fittings etc. The units shall be BMS Compatible. Outdoor Units shall be fully inverter system complete with 100% scroll/rotary compressor and drive arrangement, initial charge of refrigerant (R-410A),refrigerant piping, drier, sight glass, dual pressure cutout all housed and supported properly in cabinet, air cooled condenser & its controller for following capacities. The VRV system shall be cooling only system. Type of Compressor : Hermitic sealed Inverter Scroll/TwinRotary ODU should delvier the required capacity at the ambient conditions of the place as per ISHRAE Standards. The System should be highly energy efficient and COP shall not be less than 3.7. The outdoor units shall be suitable for operation between 5 and 53 deg C in cooling mode. Makes: Mitsubishi ELectric /Toshiba / O General
Supply of Air cooled VRV / VRF 16HP Air Conditioning system of having high COP complete with indoor and outdoor units duly charged with refrigerant R-410A and oil (first charge) suitable for cooling with individual controller, (suitable for 415 +/- 10% for outdoor and 230 +/- 5% for indoor units) and complete with all accessories, fittings etc. The units shall be BMS Compatible. Outdoor Units shall be fully inverter system complete with 100% scroll/rotary compressor and drive arrangement, initial charge of refrigerant (R-410A),refrigerant piping, drier, sight glass, dual pressure cutout all housed and supported properly in cabinet, air cooled condenser & its controller for following capacities. The VRV system shall be cooling only system. Type of Compressor : Hermitic sealed Inverter Scroll/TwinRotary ODU should delvier the required capacity at the ambient conditions of the place as per ISHRAE Standards. The System should be highly energy efficient and COP shall not be less than 3.7. The outdoor units shall be suitable for operation between 5 and 53 deg C in cooling mode. Makes: Mitsubishi ELectric /Toshiba / O General
Supply of Air cooled VRV / VRF 14HP Air Conditioning system of having high COP complete with indoor and outdoor units duly charged with refrigerant R-410A and oil (first charge) suitable for cooling with individual controller, (suitable for 415 +/- 10% for outdoor and 230 +/- 5% for indoor units) and complete with all accessories, fittings etc. The units shall be BMS Compatible. Outdoor Units shall be fully inverter system complete with 100% scroll/rotary compressor and drive arrangement, initial charge of refrigerant (R-410A),refrigerant piping, drier, sight glass, dual pressure cutout all housed and supported properly in cabinet, air cooled condenser & its controller for following capacities. The VRV system shall be cooling only system. Type of Compressor : Hermitic sealed Inverter Scroll/TwinRotary ODU should delvier the required capacity at the ambient conditions of the place as per ISHRAE Standards. The System should be highly energy efficient and COP shall not be less than 3.7. The outdoor units shall be suitable for operation between 5 and 53 deg C in cooling mode. Makes: Mitsubishi Electric /Toshiba / O General
Supply of Air cooled VRV / VRF 12HP Air Conditioning system of having high COP complete with indoor and outdoor units duly charged with refrigerant R-410A and oil (first charge) suitable for cooling with individual controller, (suitable for 415 +/- 10% for outdoor and 230 +/- 5% for indoor units) and complete with all accessories, fittings etc. The units shall be BMS Compatible. Outdoor Units shall be fully inverter system complete with 100% scroll/rotary compressor and drive arrangement, initial charge of refrigerant (R-410A),refrigerant piping, drier, sight glass, dual pressure cutout all housed and supported properly in cabinet, air cooled condenser & its controller for following capacities. The VRV system shall be cooling only system. Type of Compressor : Hermitic sealed Inverter Scroll/TwinRotary ODU should delvier the required capacity at the ambient conditions of the place as per ISHRAE Standards. The System should be highly energy efficient and COP shall not be less than 3.7. The outdoor units shall be suitable for operation between 5 and 53 deg C in cooling mode. Makes: Mitsubishi Electric /Toshiba / O General
Supply of 1.0 TR 4Way Cassette units Indoor Units consisting of 2/3/4 row deep DX coil, filter, blower section and drive arrangement, initial charge of refrigerant & oil, integral refrigerant piping, electronic expansion valve, electrical panel with controls and duly wired, thermostatic control. including decorative panel and IR receiver and wireless remote. As per the room requirement. Makes: Mitsubishi Electric /Toshiba / O General
Supply of 1.6 TR 4Way Cassette units Indoor Units consisting of 2/3/4 row deep DX coil, filter, blower section and drive arrangement, initial charge of refrigerant & oil, integral refrigerant piping, electronic expansion valve, electrical panel with controls and duly wired, thermostatic control. including decorative panel and IR receiver and wireless remote. As per the room requirement. Makes: Mitsubishi Electric /Toshiba / O General
Supply of 2.0 TR 4Way Cassette units Indoor Units consisting of 2/3/4 row deep DX coil, filter, blower section and drive arrangement, initial charge of refrigerant & oil, integral refrigerant piping, electronic expansion valve, electrical panel with controls and duly wired, thermostatic control. including decorative panel and IR receiver and wireless remote. As per the room requirement. Makes: Mitsubishi Electric /Toshiba / O General
Supply of 2.6 TR 4Way Cassette units Indoor Units consisting of 2/3/4 row deep DX coil, filter, blower section and drive arrangement, initial charge of refrigerant & oil, integral refrigerant piping, electronic expansion valve, electrical panel with controls and duly wired, thermostatic control. including decorative panel and IR receiver and wireless remote. As per the room requirement. Makes: Mitsubishi Electric /Toshiba / O General
Supply of 3/3.5 TR 4Way Cassette units Indoor Units consisting of 2/3/4 row deep DX coil, filter, blower section and drive arrangement, initial charge of refrigerant & oil, integral refrigerant piping, electronic expansion valve, electrical panel with controls and duly wired, thermostatic control. including decorative panel and IR receiver and wireless remote. As per the room requirement. Makes: Mitsubishi Electric /Toshiba / O General
Supply of 4.0 TR 4Way Cassette units Indoor Units consisting of 2/3/4 row deep DX coil, filter, blower section and drive arrangement, initial charge of refrigerant & oil, integral refrigerant piping, electronic expansion valve, electrical panel with controls and duly wired, thermostatic control. including decorative panel and IR receiver and wireless remote. As per the room requirement. Makes: Mitsubishi Electric /Toshiba / O General
Supply and Installation of Ref Nets for Triple ODU connections Makes: OEM of Mitsubishi Electric /Toshiba / O General
Supply and Installation of Multi Connection Joint / Ref Nets for IDUs Makes: OEM of Mitsubishi Electric /Toshiba / O General
Lifting, shifting, positioning, Installation and testing of the 10 to 12 HP ODUs including all accessories with Vibration Isolators for ODUs etc., complete
Lifting, shifting, positioning, Installation and testing of the 14 to 20 HP ODUs including all accessories with Vibration Isolators for ODUs etc., complete
Lifting Shifting, Positioning ,Installation Testing and commissioning 1.0 TR to 2.0 TR Type Of Units :4Way Cassette units the following indoor units with including all required accessoires etc complete.
Lifting Shifting, Positioning ,Installation Testing and commissioning 2.6 TR to 4.5 TR Type Of Units :4Way Cassette units the following indoor units with including all required accessoires etc complete.
Supply and installation of additional Gas of R410a for VRF to all Systems required etc complete.
Supply, installation and testing of 41.30 mm Dia Refrigerant Piping consisting of Copper tubes as per requirement at site of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings,Liqid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required.The piping to be mounted & supported properly with suitable size of clamp,M.S. hanger, tray etc., as required at site. The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations Makes:Totaline/Mandav/Mexico
Supply, installation and testing of 34.90mm DiaRefrigerant Piping consisting of Copper tubes as per requirement sizes at site of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings,Liqid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required.The piping to be mounted & supported properly with suitable size of clamp,M.S. hanger, tray etc., as required at site. The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations Makes:Totaline/Mandav/Mexico
Supply, installation and testing of 28.60mm Dia Refrigerant Piping consisting of Copper tubes as per requirement sizes at site of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings,Liqid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required.The piping to be mounted & supported properly with suitable size of clamp,M.S. hanger, tray etc., as required at site. The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations Makes:Totaline/Mandav/Mexico
Supply, installation and testing of 22.20mm Dia Refrigerant Piping consisting of Copper tubes as per requirement sizes at site of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings,Liqid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required.The piping to be mounted & supported properly with suitable size of clamp,M.S. hanger, tray etc., as required at site. The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations Makes:Totaline/Mandav/Mexico
Supply, installation and testing of 19.10mm Dia Refrigerant Piping consisting of Copper tubes as per requirement sizes at site of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings,Liqid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required.The piping to be mounted & supported properly with suitable size of clamp,M.S. hanger, tray etc., as required at site. The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations Makes:Totaline/Mandav/Mexico
Supply, installation and testing of 15.90mm Dia Refrigerant Piping consisting of Copper tubes as per requirement sizes at site of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings,Liqid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required.The piping to be mounted & supported properly with suitable size of clamp,M.S. hanger, tray etc., as required at site. The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations Makes:Totaline/Mandav/Mexico
Supply, installation and testing of 12.70mm Dia Refrigerant Piping consisting of Copper tubes as per requirement sizes at site of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings,Liqid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required.The piping to be mounted & supported properly with suitable size of clamp,M.S. hanger, tray etc., as required at site. The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations Makes:Totaline/Mandav/Mexico
Supply, installation and testing of 9.52mm Dia Refrigerant Piping consisting of Copper tubes as per requirement sizes at site of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings,Liqid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required.The piping to be mounted & supported properly with suitable size of clamp,M.S. hanger, tray etc., as required at site. The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations Makes:Totaline/Mandav/Mexico
Supply, installation and testing of 6.35mm Dia Refrigerant Piping consisting of Copper tubes as per requirement sizes at site of wall thickness 20G/22G inclusive of Suction Gas Piping & Fittings,Liqid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required.The piping to be mounted & supported properly with suitable size of clamp,M.S. hanger, tray etc., as required at site. The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations Makes:Totaline/Mandav/Mexico
Supply, installation and testing of 25mm dia UPVC hard Drain Piping with 6mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap.
Supply, installation and testing of 32mm Dia UPVC hard Drain Piping with 6mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap.
Supply, installation and testing of 40mm Dia UPVC hard Drain Piping with 6mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap.
Supply and run of 2 core, 0.75Sqmm / 1.0 Sq mm/1.50Sqmm ISI marked, PVC insulated and sheathed FRLS/FRLS-H round copper cable for voltage up to 1100V as per IS 694/1990. Communication cable connecting the IDUs and ODUs.
Providing Pressure testing of entire system with Nitrogen and vaccuming nitrogen for all indoor and outdoor units. The pressure testing shall be done as per OEM recommendation.
(Rupees Seventy Five Lakhs Thirty Nine Thousand Six Hundard Sixteen and Ninty Paisa only)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
BOQ HVAC Block.xlsx
TENDER_DOCUMENT • 0.02 MB
TC FSL HVAC Block-II Tulluru.doc
TENDER_DOCUMENT • 0.68 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].