| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.5 LAccepted-AOC 3RD CROSS 44 AND 97A ELECTRONIC CITY BENGALURU KARNATAKA INDIA 560100 | BENGALURU URBAN | KARNATAKA | 560100 | L1 | Accepted-AOC Overall accepted as L1 | |
| 2 | L2₹27.3 L+₹79,920 (3.01%)Rejected-AOC | L2 | Rejected-AOC Overall rejected | |
| 3 | Rejected-Technical MAALGODAM ROAD FURNITURE MARKET HALDWANI 263139 DISTT NAINITAL UTTARAKHAND | HALDWANI | NAINITAL | UTTARAKHAND | 263139 | - | Rejected-Technical The Bidder did not qualifies the TQR |
| Sl No | Description | Qty | Unit | Infosys Technologies L1 | Manvi Traders L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing & commissioing of Linear Heat Detection Cable (LHDC) System for strengthening of fire protection system in cable trenches for various power and control cables at 132 KV substation Kathgodam as per the following design and technical specifications;
(a) Creation of multiple heat detection zones (17 nos. in total) in cable trenches of 132 KV and 33 KV switchyards having total length of 598 metres alongwith installation of temperature alarm at pre-set values for each zone of 35 metres.
(b) Digital LHDC shall be weather proof.
(c) Digital LHDC shall comprise of twin core cable twisted under tension having special heat reactive polymer insulation.
(d) Digital LHDC shall have an overall protective sheath which is resistant to hydrocarbons, chemicals as well as UV resistant.
(e) Digital LHDC shall have a maximum conductor resistance of 100Ω/km (at 20°C).
(f) Digital LHDC shall not in contact with any heat sink material which may delay the sensing process after final installation.
(g) Digital LHDC shall be terminated with manufacturers’ Industrial grade junction boxes. .
(h) The Digital LHDC shall have a fixed alarm temperature of 70/90 deg or above and be capable of installation where intrinsically safe configurations in hazardous areas are required.
(i) Digital LHDC shall be UL approval and certified.
(j) Number of cores shall be 2.
(k) Max Ambient Temperature: 700-070=45°C, 700-090=70°C & 700-180=150°C
(l) Minimum Operating Temperature: -40°C
(m) Minimum Installation Temperature: -10°C
(n) Cable Outer Sheath: Nylon (70°C & 90°C–Black), Hytrel (180°C – Violet) & Nylon with Stainless Steel Armour.
(o) Voltage Rating: 150 Vdc (Dielectric Test 500Vdc).
(p) Cable Outer Diameter: Nylon 4.0mm±0.3mm & Nylon & Stainless Steel Armour 4.5±0.3mm
(q) Resistance: 100/km (29/kft) per leg
(r) Velocity of Propagation: 55%
(s) Capacitance: 88–150 pF/m (26–45 pF/ft)
(t) Inductance: 540–1050 nH/m (165–320 nH/m | 1,196 | Mtr. | 11,12,280 ₹13,12,490 Lowest | 11,66,100 ₹13,75,998 |
| 2.00 | Supply, installation, testing and commissioning of LHDC Controller Logic Module Panel DXc1 or 4007ES, Fire Detection & Alarm Control Panel LPCB approved support up to 1-5 loop intelligent single loop addressable panel 6#40 characters, blue liquid crystal display panel inbuilt sound 105 db operational environment 2 degree centigrate to 80 degree configuration by keyoad and PC the panel is compatible with add on feature as per site requirment/instructions of site engineer complete in all respect.
Expandable Logic module 230 VAC input, Data logging, AC 230 V, Relay max. 10 A, Maximum configuration 24DI/20DO/8AI/8AO, Power supply AC/DC 115/230V, including clock, Noise emission limit class B group 1, Ambient temperature 0 to 55°C, Output Relays: Fire relay: Single Pole changeover 24V DC 1A Extended: Single pole changeover 24V DC 1A Aux relay: Programmable single pole changeover 24V DC 1A Onboard Data Ports:1 x RS485 (Repeater connection) 1 x PC Programming Port 4 Optional Ports: RS232 third party protocol interface Sounder Circuits: 2 output circuits, 1A p | 2 | Nos. | 3,20,000 ₹3,77,600 | 3,17,000 ₹3,74,060 Lowest |
| 3.00 | Supply, installation, testing and commissioning of Manual Call Point to report the fire in case of Digital LHDC fire incident is visually reported. Technical Specifications: Material-PC/ABS, Weight-130g Flush/180g Surface, Colour-Red/Ral3001, IP Rating-IP24D, Operating Temperature-10*C to 55*C, Relative Humidity-10%-90% Non condensing, Current Consumption-Quiescent Current: 80μA (24V, no comms) Alarm Current.-130A (24V, no comms) | 6 | Nos. | 93,900 ₹1,10,802 Lowest | 1,09,800 ₹1,29,564 |
| 4.00 | Supply, installation, testing and commissioning of Flameproof Outdoor Hooters cum Strobe for triggering the alarm in case of Digital LHDC fire incident. Technical Specifications:Material: ABS, Color: Red, Alarm Current (mA): 100, Weight: 200, Voltage: 24, Voltage: 20 - 30 V.D.C., Size:185×130× 70 (mm) 24V DC | 5 | Nos. | 65,000 ₹76,700 Lowest | 68,500 ₹80,830 |
| 5.00 | Supply, installation, testing and commissioning of Monitor Module with termination 4090-9001 for zone control and required to operate the LHS including cost of all material, consumables, labour and T&P..The technical specifications are: Operating Voltage 24 VDC Nominal, Alarm Current 2.7 mA Max.(Latched), Standby Current 0.7 mA, End of Line Resistor 47K Ohms, Loop Impedance 40 Ohms, IDC Wiring Resistance 100 Ohms Max, IDC Voltage 8 V Max, Operating Temperature 0*C to 49*C / 32*- 120*F Storage Temperature 0*C to 60*C Humidity 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ±3° F | 17 | Nos. | 5,78,000 ₹6,82,040 Lowest | 5,95,000 ₹7,02,100 |
| 6.00 | Supply, installation, testing and commissioning of Back Box with accessories with EOL Register, glander, termination block, wheather proof junction box, PVC pipe, support wire as per site requirment including cost of all material, consumables, labour and T&P. | 2 | Job | 1,08,500 ₹1,28,030 | 88,200 ₹1,04,076 Lowest |
| 7.00 | Supply, installation, testing and commissioning of FDA System including all required programming, commissioning and gateway programming and handing over for Linear Heat Cable Sensing system including cost of all material, consumables, labour and T&P. | 2 | Job | 2,24,000 ₹2,64,320 | 2,21,000 ₹2,60,780 Lowest |
| 8.00 | Supply, installation, testing and commissioning of 2 core, 1.5 Sqmm, FRLS, Armored signal cable for LHS interfacing with FDA loop as per site requirment including cost of all material, consumables, labour and T&P. | 2 | Job | 73,000 ₹86,140 Lowest | 78,000 ₹92,040 |
| 9.00 | Supply, installation, testing and commissioning of miscellaneous electric and civil works as per site requirment for strengthing of LHDC system including cost of all material, consumables, labour and T&P. | 2 | Job | 80,000 ₹94,400 Lowest | 91,000 ₹1,07,380 |
Tender Value
Refer Docs
EMD Value
₹95,000
Closing Date
9 Apr 2025, 5:00 pmClosed
Chief Engineer
Office of CE, OandM, Kumaon Zone, PTCUL, Haldwani
Installation of Linear Heat Detection Cable (LHDC) system for strengthening of fire protection in cable trenches alongwith associated works at 132KV S/s, Kathgodam under 220KV OandM Division, PTCUL, Haldwani
2025_PTC21_81309_1
CE/OandM/PTCUL/HLD/128/2024-25
Open Tender
Electrical Works
Item Rate
180 days
132KV S/s, Kathgodam
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,360
EE, 220KV OandM Division, PTCUL, Haldwani
₹95,000
Office of CE, OandM, Kumaon Zone, PTCUL, Haldwani
12 Sept 2025
10 Mar 2025
11 Apr 2025
10 Mar 2025
9 Apr 2025
10 Mar 2025
25 Mar 2025
Supply, installation, testing & commissioing of Linear Heat Detection Cable (LHDC) System for strengthening of fire protection system in cable trenches for various power and control cables at 132 KV substation Kathgodam as per the following design and technical specifications; (a) Creation of multiple heat detection zones (17 nos. in total) in cable trenches of 132 KV and 33 KV switchyards having total length of 598 metres alongwith installation of temperature alarm at pre-set values for each zone of 35 metres. (b) Digital LHDC shall be weather proof. (c) Digital LHDC shall comprise of twin core cable twisted under tension having special heat reactive polymer insulation. (d) Digital LHDC shall have an overall protective sheath which is resistant to hydrocarbons, chemicals as well as UV resistant. (e) Digital LHDC shall have a maximum conductor resistance of 100Ω/km (at 20°C). (f) Digital LHDC shall not in contact with any heat sink material which may delay the sensing process after final installation. (g) Digital LHDC shall be terminated with manufacturers’ Industrial grade junction boxes. . (h) The Digital LHDC shall have a fixed alarm temperature of 70/90 deg or above and be capable of installation where intrinsically safe configurations in hazardous areas are required. (i) Digital LHDC shall be UL approval and certified. (j) Number of cores shall be 2. (k) Max Ambient Temperature: 700-070=45°C, 700-090=70°C & 700-180=150°C (l) Minimum Operating Temperature: -40°C (m) Minimum Installation Temperature: -10°C (n) Cable Outer Sheath: Nylon (70°C & 90°C–Black), Hytrel (180°C – Violet) & Nylon with Stainless Steel Armour. (o) Voltage Rating: 150 Vdc (Dielectric Test 500Vdc). (p) Cable Outer Diameter: Nylon 4.0mm±0.3mm & Nylon & Stainless Steel Armour 4.5±0.3mm (q) Resistance: 100/km (29/kft) per leg (r) Velocity of Propagation: 55% (s) Capacitance: 88–150 pF/m (26–45 pF/ft) (t) Inductance: 540–1050 nH/m (165–320 nH/m
Supply, installation, testing and commissioning of LHDC Controller Logic Module Panel DXc1 or 4007ES, Fire Detection & Alarm Control Panel LPCB approved support up to 1-5 loop intelligent single loop addressable panel 6#40 characters, blue liquid crystal display panel inbuilt sound 105 db operational environment 2 degree centigrate to 80 degree configuration by keyoad and PC the panel is compatible with add on feature as per site requirment/instructions of site engineer complete in all respect. Expandable Logic module 230 VAC input, Data logging, AC 230 V, Relay max. 10 A, Maximum configuration 24DI/20DO/8AI/8AO, Power supply AC/DC 115/230V, including clock, Noise emission limit class B group 1, Ambient temperature 0 to 55°C, Output Relays: Fire relay: Single Pole changeover 24V DC 1A Extended: Single pole changeover 24V DC 1A Aux relay: Programmable single pole changeover 24V DC 1A Onboard Data Ports:1 x RS485 (Repeater connection) 1 x PC Programming Port 4 Optional Ports: RS232 third party protocol interface Sounder Circuits: 2 output circuits, 1A p
Supply, installation, testing and commissioning of Manual Call Point to report the fire in case of Digital LHDC fire incident is visually reported. Technical Specifications: Material-PC/ABS, Weight-130g Flush/180g Surface, Colour-Red/Ral3001, IP Rating-IP24D, Operating Temperature-10*C to 55*C, Relative Humidity-10%-90% Non condensing, Current Consumption-Quiescent Current: 80μA (24V, no comms) Alarm Current.-130A (24V, no comms)
Supply, installation, testing and commissioning of Flameproof Outdoor Hooters cum Strobe for triggering the alarm in case of Digital LHDC fire incident. Technical Specifications:Material: ABS, Color: Red, Alarm Current (mA): 100, Weight: 200, Voltage: 24, Voltage: 20 - 30 V.D.C., Size:185×130× 70 (mm) 24V DC
Supply, installation, testing and commissioning of Monitor Module with termination 4090-9001 for zone control and required to operate the LHS including cost of all material, consumables, labour and T&P..The technical specifications are: Operating Voltage 24 VDC Nominal, Alarm Current 2.7 mA Max.(Latched), Standby Current 0.7 mA, End of Line Resistor 47K Ohms, Loop Impedance 40 Ohms, IDC Wiring Resistance 100 Ohms Max, IDC Voltage 8 V Max, Operating Temperature 0*C to 49*C / 32*- 120*F Storage Temperature 0*C to 60*C Humidity 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ±3° F
Supply, installation, testing and commissioning of Back Box with accessories with EOL Register, glander, termination block, wheather proof junction box, PVC pipe, support wire as per site requirment including cost of all material, consumables, labour and T&P.
Supply, installation, testing and commissioning of FDA System including all required programming, commissioning and gateway programming and handing over for Linear Heat Cable Sensing system including cost of all material, consumables, labour and T&P.
Supply, installation, testing and commissioning of 2 core, 1.5 Sqmm, FRLS, Armored signal cable for LHS interfacing with FDA loop as per site requirment including cost of all material, consumables, labour and T&P.
Supply, installation, testing and commissioning of miscellaneous electric and civil works as per site requirment for strengthing of LHDC system including cost of all material, consumables, labour and T&P.
Manvi Traders (BID ID -370431)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .