Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.7 LAccepted-AOC H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L1 | Accepted-AOC Accepted being lowest | |
| 2 | L2₹32.8 L+₹2.8 L (9.34%)Rejected-Finance | L2 | Rejected-Finance Higher Rate |
Tender Value
₹32 L
EMD Value
₹64,000
Closing Date
16 Sept 2022, 6:00 pmClosed
GARRISON ENGINEER ARMY UTILITY JODHPUR
GARRISON ENGINEER ARMY UTILITY JODHPUR
REPAIR AND MAINTENANCE OF PUMP PANELS AND ALLIED WORKS AT ARMY AREA JODHPUR
2022_MES_534306_2
8807/E8
Open Tender
Civil Works
Item Rate
180 days
GARRISON ENGINEER ARMY UTILITY JODHPUR
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GARRISON ENGINEER ARMY UTILITY JODHPUR
₹64,000
Yes
18 Oct 2022
26 Aug 2022
23 Sept 2022
26 Aug 2022
16 Sept 2022
2 Sept 2022
Amount
M&L for routine check up and servicing of soft starter of model EMX4i of capacity 24 to 200 Amp ,duly recommending the maintanance/replacement of UNSV parts required which are not working properly. Maintanance/servicing shall be carried out by OEM maint engineer only & proper setting of O/L, running, starting / stopping, ramping time with proper measurememnt of each & every set of starter. Mainly HMI module, PCB, CT, Fan, Thyristor and by pass. complete all as specified & directed by Engr-in-Charge at site. Note: All required parts shall be measured and paid seperately in respective items.
Supply and fix in replacement of Kit User Iinterface CI M/R 0020-0129 make L&T model EMX4i Of capacity 24Amp to 135Amp , Cat No 995-18604-00
All as item No 1.01 but for capacity 184 Amp to 200 Amp , Cat No 995-18605-00
S&F as in replacement of Kit Motor Ctrl V5 M/R 0020-0129 make L&T model EMX4i of capacity 24Amp to 135Amp, Cat No 995-18607-00
S&F as in replacement of Kit Motor Ctrl V5 M/R 0143-0580 make L&T model EMX4i of capacity 184Amp to 200 Amp ,Cat No 995-18608-00
S&F as in replacement of Kit SCR M/R 0020 make L&T model EMX4i of capacity 24Amp , Cat No 995-18612-00
S&F as in replacement of Kit SCR M/R 0034-0041 make L&T model EMX4i of capacity 42Amp to 52 Amp, Cat No 995-18613-00
S&F as in replacement of Kit SCR M/R 0085-0107 make L&T model EMX4i of capacity 105Amp to 115 Amp, Cat No 995-18615-00
S&F as in replacement of Kit SCR M/R 0129 make L&T model EMX4i of capacity 135 Amp ,Cat No 995-18616-00
S&F as in replacement of Kit SCR M/R 0143-0193 make L&T model EMX4i of capacity 184 Amp to 200 Amp, Cat No 995-18617-00
S&F as in replacement of Kit Fan M/R 0041-0129 make L&T model EMX4i of capacity 24Amp to 135Amp, Cat No 995-18622-00
S&F as in replacement of Kit Fan M/R 0043-0580 make L&T model EMX4i of capacity of capacity 184Amp to 200Amp, Cat No 995-18623-00
S&F as in replacement of Kit CT M/R 0020-0129 make L&T model EMX4i of capacity 24Amp to 135Amp, Cat No 995-18624-00
S&F as in replacement of Kit CT M/R 0143-0243 make L&T model EMX4i of capacity 184Amp to 200Amp, Cat No 995-18625-00
S&F as in replacement of Bypass Contactor Kit, M/R 0020-0069 make L&T model EMX4i of capacity 24Amp to 69Amp, Cat No 995-18628-00
S&F as in replacement of Bypass Contactor Kit, M/R 0085-0129 make L&T model EMX4i of capacity 105Amp to 135Amp, Cat No 995-18629-00
S&F as in replacement of Bypass Contactor Kit, M/R 0143-0243 make L&T model EMX4i of capacity 184Amp to 200Amp, Cat No 995-18630-00
S&F as in replacement of Kit snubber M/R 0020-0069 make L&T model EMX4i of capacity 24Amp to 69Amp, Cat No 995-18633-00
S&F as in replacement of Kit snubber M/R 0085-0129 make L&T model EMX4i of capacity 105Amp to 135Amp, Cat No 995-18634-00
S&F as in replacement of Kit snubber M/R 0143-0243 make L&T model EMX4i of capacity 184Amp to 200Amp, Cat No 995-18635-00
M&L for routine check up and servicing of soft starter of model CSXi of capacity 7.5KW to 110KW,duly recommending the maintanance/replacement of the UNSV parts required which are not working properly. Maintanance/servicing shall be carried out by OEM maint engineer only & proper setting of O/L, running, starting / stopping, ramping time with proper measurememnt of each & every set of starter. Mainly PCB, CT, Fan, Thyristor and by pass complete all as specified & directed by Engr-in-Charge at site. Note: All required parts shall be measured and paid seperately in respective items.
S&F as in replacement of CSXi, Kit,Mn Ctrl PCB,1,V4,C1,007-110 make L&T model CSXi of capacity 7.5 to 110 KW , Cat No 995-02537-00
S&F as in replacement of CSXi, Kit,,Interface PCB,022 make L&T model CSXi of capacity 22 KW , Cat No 995-02549-00
S&F as in replacement of CSXi, Kit,,Interface PCB,037 make L&T model CSXi of capacity 37 KW , Cat No 995-04517-00
S&F as in replacement of CSXi, Kit,,Interface PCB,055 make L&T model CSXi of capacity 55 KW , Cat No 995-04519-00
S&F as in replacement of CSXi, Kit,,Interface PCB,110 make L&T model CSXi of capacity 110 KW , Cat No 995-03877-00
Supply and fix in replacement CSXi, Kit,,By pass Relay, 007-030 make L & T model CSXi of capacity 7.5 KW to 30KW , Cat No 995-02568-00
S&F as in replacement of CSXi, Kit,,By pass Relay, 037-055 make L&T model CSXi of capacity 37 KW to 55KW , Cat No 995-04515-00
S&F as in replacement of CSXi, Kit,,By pass Relay, 075-110 make L&T model CSXi of capacity 75 KW to 110KW , Cat No 995-03873-00
S&F as in replacement of CSXi, Kit,Current transformer 037-055 make L&T model CSXi of capacity 37 KW to 55KW , Cat No 995-02572-00
S&F as in replacement of CSXi, Kit,SCR 037 make L&T model CSXi of capacity 37 KW , Cat No 995-02562-00
S&F as in replacement of CSXi, Kit,SCR 055 make L&T model CSXi of capacity 55 KW , Cat No 995-02564-00
S&F as in replacement of power contactor 3 pole of capacity 300 Amp rating 415 Volt / AC-3. Note: The new power contractor shall be of existing type, make & model to suit existing mounting space.
All as item No. 3.00 but of capacity 250 to 265 Amp
All as item No. 3.00 but of capacity 185 to 200 Amp
All as item No. 3.00 but of capacity 140 to 150 Amp
All as item No. 3.00 but of capacity 225 Amp
All as item No. 3.00 but of capacity 95 to 110 Amp
All as item No. 3.00 but of capacity 63 to 70Amp
All as item No. 3.00 but of capacity 40 to 50 Amp
S&F as in repair start / stop push botton. Note: The new parts shall be of existing type, make & model to suit existing mounting space.
S&F as in replacement of Pneumatic Timers Time Delay Relay-Electro Pneumatic type along with suitable Nos of NO+NC as per control panel of starter as existing for time delay 0 to 60 second setting on steps suitabile for 100 to 150 HP motor starting panel. cat no KRTPCN11M- 1
S&F as in replacement of overload relay of Range 10 to 30 Amp rating to suit safe operation of induction/ submersible motor of capacity up to 15HP motor.
All as item No. 6.00 but for CT operated relay range 188 to 300A for 150/100HP motor starter of auto transformer type for ATS panel make BCH HSN Code 8536 cat code CT6MC305ANA3C
M&L for rewinding of auto transformer unit of A/T starter complete with winding wire of super enamelled Impregnated copper wire of existing size and type complete with empire tape, glass tape, impregnated paper, bamboo Chips etc & transporting from panel place to wksp and back, reconnection after completion and testing of load, for 150 HP PUMP complete all as specified & directed by Engr-in-Charge.
M&L for electrical disconnetion of submersible pump for taking out existing column pipe of size 32 to 80 mm along with pump set 1to 10 HP from borewell with essential tools like tripod, chain, pully, etc and manpower & replacement of unserviceable parts of column pipe, motor, pump etc as per requirement, lowering of submersible pumping set with column pipe complete and testing after completion of work complete all as specified and directed by Engr-in-Charge. Note: (i) Repair of pump and motor will be paid and measured seperately under respective items. (ii) Minor items such as rubber packing, gaskets, grease etc deemed to be included. (iii) All required spare parts and column pipe shall be measured and paid seperately.
M&L for repair /servicing of submersible pump set, strip opening multi stage submersible pumpset of capacity 1 to 1.5HP. Replacement of unserviceable parts & reassembling the same, testing after completion of of job & spare parts shall be measured & paid seperately under respective items as supply only complete all as specified & directed by Engr-in-Charge. Note: The cost of labour charges of spare parts shall be included in the quoted rate of this item.
Supply only Impeller as required for Item No 9.00.
Supply only Sleeve coupling as required for Item No 9.00.
Supply only allen key screw as required for Item No 9.00.
Supply only thrust bearing set as required for Item No 9.00.
Supply only Bush as required for Item No 9.00.
M&L for rewinding of submersible electric motors transporting from site to repair shop and repair shop to site, dismantling, stripping out and removing old burnt winding wire, cleaning of slots etc. Rewinding complete with super enamelled copper winding wire of appropriate gauge including all necessary insulation material class-I, varnishing and heating as per requirment. Re-installing in position, assembling at site, realigning with pump set, coupling with pump, making electric connection all as direcred and testing for smooth functioning for following capacity (a) 1/1.5 HP Single phase.
M&L for repair of submersible pump set, strip opening multi stage submersible pumpset of capacity 5 to 10HP. Replacement of unsv parts & reassembling the same, testing after completion of of job &spare parts shall be measured & paid seperately under respective items as supply only complete all as specified & directed by Engr-in-Charge. Note: The cost of labour charges of spare parts shall be included in the quoted rate of this item.
Supply only Thrust bearing as required for Item No 11.00.
Supply only Bowl set as required for Item No 11.00.
Supply only impellor driving rod (shaft) complete as required for Item No 11.00.
Supply only Impellor as required for Item No 11.00.
Supply only Bush as required for Item No 11.00.
Supply only MS Coupling as required for Item No 11.00.
M&L for rewinding of submersible electric motors of capacity 5 HP three phase. Rewinding shall be complete with PVC submersible copper winding wire of appropriate gauge including all necessary insulation material as per requirment. Re-installing in position, assembling at site, realigning with pump set, coupling with pump, making electric connection all and testing for smooth functioning complete all as specified & directed. Note: The cost of transportation from site to repair shop and repair shop to site, dismantling, stripping out and removing old burnt winding wire, cleaning of slots etc shall be included in the quoted rate of this item.
M&L for rewinding of submersible electric motors of capacity 7.5 HP three phase. Rewinding shall be complete with PVC submersible copper winding wire of appropriate gauge including all necessary insulation material as per requirment. Re-installing in position, assembling at site, realigning with pump set, coupling with pump, making electric connection and testing for smooth functioning complete all as specified & directed. Note: The cost of transportation from site to repair shop and repair shop to site, dismantling, stripping out and removing old burnt winding wire, cleaning of slots etc shall be included in the quoted rate of this item.
M&L for rewinding of submersible electric motors of capacity 10 HP three phase. Rewinding shall be complete with PVC submersible copper winding wire of appropriate gauge including all necessary insulation material as per requirment. Re-installing in position, assembling at site, realigning with pump set, coupling with pump, making electric connection and testing for smooth functioning complete all as specified & directed. Note: The cost of transportation from site to repair shop and repair shop to site, dismantling, stripping out and removing old burnt winding wire, cleaning of slots etc shall be included in the quoted rate of this item.
S&F as in repair Single phase preventor type D2, VMR1
S&F as in repair high pressure cooling pipe with end connections suitable for 50/60/75/100/150HP kirloskar pump.
S&F as in repair rubber coupling Star type suitable for 150 HP Pump complete all as specified and directed.
All as Item No 17.00 but for 75/100HP
All as Item No 17.00 but for 50 /60HP
All as Item No 17.00 but for10/12.5/15HP
S&F as in repair rubber coupling tyre type suitable for 150 HP centrifugal Pumping set complete all as specified and directed.
All as Item No 18.00 but for 75/100 HP
All as Item No 18.00 but for 20/25 HP
M&L for routine / Preventive maint of pump / motor set complete of size 100 to 150 HP. SKF high performance, high temperature superior quality pump & motor bearing grease of model - SKF LG HP 2/18 or equivalant quality of make castrol / Valvoline etc, nut / bolts, complete with including repair / replacment of unserviceable acessories like cooling pipe/ drain pipe, washer, packing etc complete. Note: (i) The cost of all items like hose set nipple, washer, ball valve Gland having high purity with lubricant, alignment of pump and motor etc shall be included in the quoted rate of this item. (ii) Record of routine / Preventive maintenance shall be maintained in register duly singed by Engr-in-Charge.
M&L for routine / Preventive maint of pump / motor set complete of size 50 to 75 HP. SKF high performance, high temperature superior quality pump & motor bearing grease of model - SKF LG HP 2/18 or equivalant quality of make castrol / Valvoline etc, nut / bolts, complete with including repair / replacment of unserviceable acessories like cooling pipe/ drain pipe, washer, packing etc complete. Note: (i) The cost of all items like hose set nipple, washer, ball valve Gland having high purity with lubricant, alignment of pump and motor etc shall be included in the quoted rate of this item. (ii) Record of routine / Preventive maintenance shall be maintained in register duly singed by Engr-in-Charge.
M&L for routine / Preventive maint of pump / motor set complete of size 12.50 to 20 HP. SKF high performance, high temperature superior quality pump & motor bearing grease of model - SKF LG HP 2/18 or equivalant quality of make castrol / Valvoline etc, nut / bolts, complete with including repair / replacment of unserviceable acessories like cooling pipe/ drain pipe, washer, packing etc complete. Note: (i) The cost of all items like hose set nipple, washer, ball valve Gland having high purity with lubricant, alignment of pump and motor etc shall be included in the quoted rate of this item. (ii) Record of routine / Preventive maintenance shall be maintained in register duly singed by Engr-in-Charge.
M&L for routine / Preventive maint of pump / motor set complete of size 03 to 10 HP. SKF high performance, high temperature superior quality pump & motor bearing grease of model - SKF LG HP 2/18 or equivalant quality of make castrol / Valvoline etc, nut / bolts, complete with including repair / replacment of unserviceable acessories like cooling pipe/ drain pipe, washer, packing etc complete. Note: (i) The cost of all items like hose set nipple, washer, ball valve Gland having high purity with lubricant, alignment of pump and motor etc shall be included in the quoted rate of this item. (ii) Record of routine / Preventive maintenance shall be maintained in register duly singed by Engr-in-Charge.
M&L for Gland filing having high purity with lubricant of suitable size & suitable for high speed, high temprature and high pressure application complete all as specified & directed.
M&L for strip opening of submersible mono block pump motor of capacity 03 to 05 HP, rewinding with PVC copper wire winding wire of existing size with insulated paper / bamboo clips empire tape / glass tape etc, tesing after completion of job complete all as specified & directed.
M&L for strip opening of submersible mono block pump motor of capacity 10 to 12 HP, rewinding with PVC copper wire winding wire of existing size with insulated paper / bamboo clips empire tape / glass tape etc, tesing after completion of job complete all as specified & directed.
S&F as in replacemnt of Bush of mono block submersible pump 03 to 05 HP complete all as specified & directed.
All as Item No 26.00 but for 10 to 12 HP.
M&L for repair of centrifugal pump of Capacity 100 to 150 HP strip opening of casing of pumping set. for checking of defective parts and including repair / replacement of unserviceable parts & reassembling the same & testing after completion of work complete all as specified & as directed by Engr-in-Charge.. Note: (i) The cost of gasket and minor parts like nut bolt and washer etc shall be included in quoted rate of this item. (ii) All required spare parts shall be measured & paid seperately under respective items as supply only.
Supply only impellor C.I. with all acessories for pumping set capacity of 100 to 150 HP pumping set.
Supply only impeller Wearing Ring C .I. as per existing of capacity of 100 to 150 HP pumping set.
Supply only impeller Casing Ring C .I. as per existing of capacity of 100 to 150 HP pumping set.
Supply only of shaft Sleeve/bush C.I. as per existing of capacity of 100 to 150 HP pumping set.
Supply only NDE/DE pump bearing as per existing size, type, of capicity 100 to 150 HP.
Supply only Gland plate CI capacity of 100 to 150 HP pumping set.
M&L for straightening of Pump shaft including filling/welding cutting of existing size and leath work for pump as per existing size, type, make & model.capacity of 100 to 150 HP pumping set.
M&L for repair of centrifugal pump of Capicity 50 to 75 HP strip opening of casing of pumping set. for checking of defective parts and including repair / replacement of unserviceable parts & reassembling the same & testing after completion of work complete all as specified & as directed by Engr-in-Charge. Note: (i) The cost of gasket and minor parts like nut bolt and washer etc shall be included in quoted rate of this item. (ii) All required Spare parts shall be measured & paid seperately under respective items as supply only.
Supply only impellor C.I. with all acessories for centrifugal pumping set capacity of 50 to 75 HP pumping set.
Supply only impeller Wearing Ring C .I. as per existing of capacity of 50 to 75 HP centrifugal pumping set.
Supply only impeller Casing Ring C .I. as per existing of capacity of 50 to 75 HP centrifugal pumping set.
Supply only shaft Sleeve/Bush C.I. as per existing of capacity of 50 to 75 HP centrifugal pumping set.
Supply only NDE/DE pump bearing as per existing size, type, of capicity 50 to 75 HP,centrifugal pump set.
Supply only Gland plate CI capacity of 50 to 75 HP centrifugal pumping set.
M&L for straightening of Pump shaft including filling,welding,cutting of existing size and leath work for pump as per existing size, type, make & model.capacity of 50 to 75 HP pumping set.
M&L for repair of centrifugal pump of Capicity 10 to 15 HP strip opening of casing of pumping set. for checking of defective parts and including repair / replacement of unserviceable parts & reassembling the same & testing after completion of work complete all as specified & as directed by Engr-in-Charge. Note: (i) The cost of gasket and minor parts like nut bolt and washer etc shall be included in quoted rate of this item. (ii) All required Spare parts shall be measured & paid seperately under respective items as supply only.
Supply only impellor C.I. with all acessories for centrifugal pumping set capacity of 10 to 15 HP pumping set.
Supply only impeller wearing Ring C .I. as per existing of capacity of 10 to 15 HP pumping set.
Supply only shaft Sleeve/Bush C.I. as per existing of capacity of 10 to 15 HP pumping set.
Supply only NDE/DE pump bearing as per existing size, type, of capicity 10 to 15 HP.
Supply only Gland plate CI capacity of 10 to 15 HP pumping set.
Supply only mechnical seal for capacity 10 to 15 HP pumping set
M&L for straightening of Pump shaft including filling,welding,cutting of existing size and leath work for pump as per existing size, type, make & model.capacity of 10 to 15 HP pumping set.
M&L for repair of centrifugal pump of Capicity 5 to 7.5 HP strip opening of casing of pumping set. for checking of defective parts and including repair / replacement of unserviceable parts & reassembling the same & testing after completion of work complete all as specified & as directed by Engr-in-Charge. Note: (i) The cost of gasket and minor parts like nut bolt and washer etc shall be included in quoted rate of this item. (ii) All required Spare parts shall be measured & paid seperately under respective items as supply only.
Supply only CI impellor with all acessories for pumping set upto the capacity of 5 to 7.5 HP pumping set.
Supply only NDE/DEbearing as per existing size, type, make & model.of capicity 5 to 7.5 HP HP
Supply only Gland plate CI capacity of 5 to 7.5 HP pumping set.
Supply only mechnical seal for capacity 5 to 7.5 HP
M&L for straightening of Pump shaft including filling,welding,cutting of existing size and leath work for pump as per existing size, type, make & model.capacity of 5 to 7.5 HP pumping set.
M&L for repair of centrifugal pump of Capicity 1.0 to 3.0 HP strip opening of casing of pumping set. for checking of defective parts and including repair / replacement of unserviceable parts & reassembling the same & testing after completion of work complete all as specified & as directed by Engr-in-Charge. Note: (i) The cost of gasket and minor parts like nut bolt and washer etc shall be included in quoted rate of this item. (ii) All required Spare parts shall be measured & paid seperately under respective items as supply only.
Supply only impellor with all acessories for pumping set upto the capacity of 1.0 to 3.0 HP pumping set.
Supply only NDE/DEbearing as per existing size, type, make & model.of capicity 1.0 to 3.0
Supply only mechnical seal for capacity 1.0 to 3.0 HP pumping set
M&L for straightening of Pump shaft including filling,welding,cutting of existing size and leath work for pump as per existing size, type, make & model.capacity of 1.0 to 3.0 HP pumping set.
M&L for strip opening of electric motor after electrically disconnecting 100 to 150 HP pump for rewinding / replacement of unserviceable parts & reassembling the same & testing on load at existing place complete all as specified & directed by Engr-in-Charge. Note: (i) The cost of transportation from site to repair shop and repair shop to site shall be included in the quoted rate of this item. (ii) All required spare parts shall be measured and paid seperately under respective items. (iii) The cost of rewinding of electric motor shall be measured and paid seperately under respective items.
Rewinding of motor of capacity 150 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & testing after completion of job complete all as specified & directed by Engr-in-Charge.
Rewinding of motor of capacity 100 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & testing after completion of job complete all as specified & directed by Engr-in-Charge.
S&F as in repair NDE/DE bearing of Motor as per existing size, type, make & model. of Capicity 100HP to 150 HP
S&F as in repair cooling fan of motor as per existing size, type, make & model. of Capicity 100HP to 150 HP
M&L for strip opening of electric motor after electrically disconnecting 50 to 75 HP pump for rewinding / replacement of unserviceable parts & reassembling the same & testing on load at existing place complete all as specified & directed by Engr-in-Charge. Note: (i) The cost of transportation from site to repair shop and repair shop to site shall be included in the quoted rate of this item. (ii) All required spare parts shall be measured and paid seperately under respective items. (iii) The cost of rewinding of electric motor shall be measured and paid seperately under respective items.
Rewinding of motor of capacity 75 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
Rewinding of motor of capacity 50 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
S&F as in repair NDE/DE bearing of motor as per existing size, type, make & model of Capicity 50 HP to 75 HP
S&F as in repair motor cooling fan as per existing size, type, make & model of Capicity 50 HP to 75 HP
M&L for strip opening of electric motor after electrically disconnecting10 to 20 HP pump for rewinding / replacement of unserviceable parts & reassembling the same & testing on load at existing place complete all as specified & directed by Engr-in-Charge. Note: (i) The cost of transportation from site to repair shop and repair shop to site shall be included in the quoted rate of this item. (ii) All required spare parts shall be measured and paid seperately under respective items. (iii) The cost of rewinding of electric motor shall be measured and paid seperately under respective items.
Rewinding of motor of capacity 20HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
Rewinding of motor of capacity 15 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
Rewinding of motor of capacity 12.5HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge. .
Rewinding of motor of capacity 10HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
S&F as in repair NDE/DE bearing of motor as per existing size, type, make & model. of Capacity 10HP to 15 HP
S&F as in repair NDE/DE bearing of motor as per existing size, type, make & model. of Capacity 20 HP
S&F as in repair cooling fan as per existing size, type, make & model. of Capacity 10HP to 15 HP
S&F as in repair cooling fan as per existing size, type, make & model. of Capacity 20 HP
M&L for strip opening of electric motor after electrically disconnecting 05 to 7.5HP pump for rewinding / replacement of unserviceable parts & reassembling the same & testing on load at existing place complete all as specified & directed by Engr-in-Charge. Note: (i) The cost of transportation from site to repair shop and repair shop to site shall be included in the quoted rate of this item. (ii) All required spare parts shall be measured and paid seperately under respective items. (iii) The cost of rewinding of electric motor shall be measured and paid seperately under respective items.
Rewinding of motor of capacity 7.5 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
Rewinding of motor of capacity 05 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
S&F as in replacement of NDE/DE bearing of motor as per existing size, type, make & model. of Capacity 05 HP to 7.5 HP
S&F as in replacement of cooling fanof motor as per existing size, type, make & model. of Capacity 05 HP to 7.5 HP
M&L for strip opening of electric motor after electrically disconnecting 03 to 01 HP pump for rewinding / replacement of unserviceable parts & reassembling the same & testing on load at existing place complete all as specified & directed by Engr-in-Charge. Note: (i) The cost of transportation from site to repair shop and repair shop to site shall be included in the quoted rate of this item. (ii) All required spare parts shall be measured and paid seperately under respective items. (iii) The cost of rewinding of electric motor shall be measured and paid seperately under respective items.
Rewinding of motor of capacity 03 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
Rewinding of motor of capacity 02 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
Rewinding of motor of capacity 1.5 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
Rewinding of motor of capacity 01 HP with superenamelled pre-insulationed copper winding wire of existing size of copper wire with insulated paper / bamboo chips, empire tape / glass tape etc & tesing after completion of job complete all as specified & directed by Engr-in-Charge.
Replacement of NDE/DE bearing as per existing size, type, make & model. Of Capicity 3HP to 1.0HP
Replacement of cooling fan as per existing size, type, make & model. Of Capicity 1 HP to 3 HP
Hiring of JCB/ Cranes with operator & fuel for mechanical work at site / as spl task work as and when demanded, record shall be maintained for hours run on register and duly signed by Engr-in-Charge.
S&F as in replacement of LED Decorative post top light 20W with IP65 protection elegantly designed spun aluminium and high grade aluminium heat sink for efficient thermal management, sturdiness and excellent corrosion resistance. MS base provided to support the housing. Powder coated black after phosphocromate treatment.
M&L for rewinding of 300 mm/450mm sweep exhaust fan of any make with super enamelled copper wire of suitable for incl all insulating materials varnishing complete incl satisfactory test run on load complete all as specified and directed.
S&F as in repair D shine MCCB for motor backup protection 3 Pole rated 400 Amps,breaking capacity 50 KA. Ics = 100% ICU Including Spreader Link between phase Cat part No CM94516OOROOG Model/Type DN3-400M. The new MCCB shall be of existing type and make to suit existing mounting space.
S&F as in repair D shine MCCB for motor backup protection 3 Pole rated 250 Amps,breaking capacity 50 KA. Ics = 100% ICU Including Spreader Link between phase Cat part No CM92171OOPOOG, Model/Type DN2-250M. The new MCCB shall be of existing type and make to suit existing mounting space.
S&F as in repair D shine MCCB for motor backup protection 3 Pole rated 160 Amps,breaking capacity 50 KA Ics = 100% ICU Including Spreader Link between phase . Cat part No DZ1T0160NXM1A , Model/Type DZ1-160M. The new MCCB shall be of existing type and make to suit existing mounting space.
S&F as in repair D shine MCCB for motor backup protection 4 Pole rated 125 Amps,breaking capacity 50 KA Ics = 100% ICU . Including seperator between phase Cat part No DZ1T0125NXM1A , Model/Type DZ1-160M. The new MCCB shall be of existing type and make to suit existing mounting space.
M&L for preparation of old painted surface of pipe lines, railing etc with spray gun with one coat of existing colour complete all as specified and directed. Note: The existing meters,switches,moving parts shall be protected from paint and the cost of this arrangement shall be included in the quoted rate of this item.
Disconnecting of all electrical connection, M&L for prepraction of old painted surface with the help of paint remover,scrapper & fine ambery paper and painting with two coat of heat resistance paint with the help of spray gun over one coat of red oxide and writing SM No/ Machine No. and connect back all electrical connections complete all as specified and directed for 100 to 150 HP Capicity Pump set (Motor+Pump+ Foundation Frame) .
All as Item No 104.00 but for 50 to 75 HP
All as Item No 104.00 but for10 to 20 HP
Supply and laying as in replacement of 95 sq mm XLPE insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core of following sizes from LT panel to starter and starter to motor, complete laid in floor/wall or cable duct complete all as specified & directed.
All as Item No 105.00 but for 70 sq mm
All as Item No 105.00 but for 25 sq mm
All as Item No 105.00 but for16 sq mm
S&F as in replacement of chlorine test kit complete with box all as specified & directed.
M&L for replacement in earthing complete with galvanized steel earth plate electrode, 60Cm X60 Cm X 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 Mtr deep below ground level) with top edge of the earth plate not less than 1.5 Mtr below normal ground level, connected to galvanized earth strip 32x6 mm by means of galvanised iron or steel with 40mm dia GI pipe light grade for protection of earth strip and all as shown in electrical plate No. 3 connected to elelctrical equipments all as specified or indicated including Exc & earth work, constn of PCC pit with RCC cover, watering pipe 20mm dia light grade with funnel & wire mesh & testing on completion all as directed. Note: (i) The cost of earth strip of size 32x6mm up to 7.5 mtr shall be included in the quoted rate of this Item. (ii) The cost of dismantling of exising earthing shall be included in the quoted rate of this Item.
S&F as in repair GI earth strip of size 32x6mm complete all as specified & directed.
M&L for replacement of existing filter media consisting of gravel and sand in water purification plant having working pressure 25 PSI H. Pn 50 PSI as per details given below complete all as specified & directed by Engr-in-Charge. (a) Removing the existing filter media consisting of gravels and sand, spreading and leveling out side for refilling, cleaning the surface, walls, bed sand Nozzles with wire brushes and cleaning the walls with bleaching powder solution, washing with fresh water and finally washing the complete filter bed twice with Anti bacterial spray treatment in all respect, and cleaning with high pressure water nozzle spray etc complete. (b) Refilling the filter media in the filter bed, gravels (pebbles) removed from the existing filter media after the washing pebbles with 5% ( Dil)Diluted aquous solution of Hydrochloric Acid (HCL) and treatment with 10% ( Dil)Diluted aquous solution of NAOH (sodium Hydro Oxide) and laying and stacking in different layers into filter beds. (c) Painting of complete filter assembly including incoming and outgoing pipe with two coat of synthetic enamel paint after scraping the old surface.
M&L for replacement of existing filter media consisting of gravel and sand in filter bed tank having filtration capacity 32 lakh ltr /12 hrs at swimming pool as per details given below complete all as specified & directed by Engr-in-Charge. (a) Removing the existing filter media consisting of gravels and sand, spreading and leveling out side for refilling, cleaning the surface, walls, bed sand Nozzles with wire brushes and cleaning the walls with bleaching powder solution, washing with fresh water and finally washing the complete filter bed twice with Anti bacterial spray complete in all respect, Anti bacterial spray with high pressure water nozzle spray cleaning etc complete. (b) Refilling the filter media in the filter bed, gravels (pebbles) removed from the existing filter media after the washing pebbles with 5% (Dil) Diluted aqous solution of Hydrochloric Acid (HCL) and treatment with 10% (Dil) Diluted aqous solution of NAOH (sodium Hydro Oxide) and laying and stacking in different layers into filter beds. (c) Painting of complete filter assembly including incoming and outgoing pipe with two coat of synthetic enamel paint after scraping the old surface.
Supply and filling filter media conisting of screened graded sand on supporting gravel bed of size 0.5 to 1.5 mm to suit existing size and type complete all as specified & directed.
Supply and laying pebbles 8 mm to 25 mm in different sizes to suit existing size and type complete all as specified & directed.
Supply and laying pebbles upto 6 mm in different sizes to suit existing size and type complete all as specified & directed.
M&L as in repair for mild steel or iron work in heavy size for Fabricate of foundation Base frame for Pumps and motor including drilling holes riveting or welding where necessary and their fixing required for proper completion of work complete all as specified & directed.
S&F as in replacement of factory made 1-Phase DOL with 2P CPG Contactor & 2P Overload Relay DOL motor starter suitable for 2 HP motor complete with start stop push buttons powder coated enclosure with PU gaskets consisting of 1Ø, 220V, 50Hz, Overload Relay Range13.2 - 20.0 (A) Contactor Type 2P CPG,Contactor Rating 25A,Make BCH model HSN: 8536 cat code NALBW-SP or equivalent
S&F as in replacement of DOL submersible pump motor starter 3-PH complete powder coated enclosure with PU gaskets with protection consisting of,phase failure , phase imblance, phase reversal, short circuit protection, ammeter, voltmeter,ON/ OFF and trip indication, dry run preventor, start stop push buttons,Overload Relay Range 13 - 20.0 (A),Contactor Rating 20A, with coil voltage 380-415V Make BCH HSN code: 8536, model type SHAKTI P10 cat code CPEYSBL or equivalent
Supply and laying in replecement XLPE insulated, armoured heavy duty electric cable multi strand aluminium conductor, 1100 Volts Grade cross section area 2 Core 6 Sqmm
Excavation in trenches not exc 1.5m width and not exc 1.5 m in depth and getting out for laying of pipes etc in soft/loose soil .
Returning filling in including spreading levelling watering and ramming in layers not exceeding 25 cm in any type of soil.
Removing of excavated surplus soil to a distance not exceeding 50M where directed and at a level not exceeding 1.5m above the starting point.
M&L for sand cushioning to underground cable screened un-washed river sand and punning for cushioning as per technical data to the cable all as specified and as directed.
Supplying and laying of precast concrete cable cover class LV, type 1, flat size 250mmx150mmx40mm and abutting each other with gap between adjacent precast concrete cable cover not exceeding 10mm over underground cable for protection.
Supply, laying, testing and commissioning of 25mm X 3mm Aluminium strip from existing earth pit to the panel/ motor, including earth work as required complete in all respect as directed by Engineer-in- Charge.
S&F as in repair CI foot valve flanged/threaded type of dia 50 mm as per existing including accessories like nut-bolt, gasket etc as required complete in all as specified and directed.
All as item No. 124.00 but for dia of foot valve 80 mm
All as item No. 124.00 but for dia of foot valve 100 mm
Supply and fixing in replacement of complete rotating assembly CI+40C8 including pump casing, CI impeller of pump capacity 100 HP centrifugal pump set suitable for pump model No. UP 150/45 code 01 total head - 70M, discharge - 225 Cum/Hr, size 150x200mm, speed - 1450rpm including testing and commissioning as required complete all as specified and directed.
M/s R K Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .