Supply Erection Testing Commissioning of 01 no 40 MVA 132 33 KV Transformer associated 132KV and 33KV bays 3 nos 33KV Feeder bays 2X5 MVAR Capacitor Bank and extension of 132 KV and 33 KV Main and transfer Bus at 132 KV Substation ELDECO Sitarganj
2020_PTCU4_26907_1
PTCUL/CandP-II/SS-09/2020-21
Open Tender
Electrical Works
365 days
Dehradun
Please refer Tender documents.
5 documents required · 5 mandatory
₹23,600
MD PTCUL
₹16.3 L
Dehradun
25 Aug 2021
17 Oct 2020
11 Dec 2020
17 Oct 2020
10 Dec 2020
10 Nov 2020
28 Oct 2020
Amount
Part-A (Supply of Material)
for Increasing the capacity
1. 132/33 KV 40MVA Transformer
for 132 KV Bay
1. 132/33 KV 40MVA Transformer Control and Relay Panel with double energy meter. (HV and LV)
2. 145 KV, 2000A spring operated SF6 Circuit Breaker with structure
3. 145 KV 3 Ph, 1250A,31.5 KA Motor operated Horizontal Center Break Isolator without Earth Switch
4. 145 KV 3 Ph, 1250A,31.5 KA Motorize operated staggered Center Break Isolator without Earth Switch
5. 132 KV Post Insulator solid core type.
6. 145 kV CT 400/200/1, 5 Core, (1 ph.) 0.2s Acc. Class
7. 145KV PT single phase
8. 120 KV,10 KA, Gapless type discharge class IIIrd, Lighting Arrestor with counter & leakage current monitor.
9. CT/PT Junction Box having at least 20No disconnecting link type terminal connector 65A; 750Volt
10. Marshalling/Terminal Kiosk as per drawing/sample.
11. Armoured Copper Control Cable 2 core x2.5 Sq mm, 1.1KV
12. Armoured Copper Control Cable 4 core x2.5 Sq mm, 1.1KV
13. Armoured Copper Control Cable 6 core x2.5 Sq mm, 1.1KV
14. Armoured Copper Control Cable 16 core x2.5 Sq mm1.1KV
15. power Armoured cable 3.5X35 Sq mm, 1.1KV.
16. Lattice type galvanized main and auxiliary structure complete with foundation, nuts & bolts as per approved drawing & specification.
17. ACSR moose Conductor.
18. Disc Insulator (120 KN)
19. C Wage clamps and different type of connectors, seprasur, suitable for Twin moose conductor.
20. Bolted type suspension fitting for Twin moose conductor for Disc Insulator (120 KN)
21. Bolted type tension fitting for Twin moose conductor for Disc Insulator (120 KN)
22. Switch Yard LED Light.
23. Earth strip of required size
24. GS shield wire
25. MS Round 36mm dia.
26. Pipe earthing material
for 33 KV Bay
1. Lattice type galvanized main and auxiliary structure complete with foundation, nuts & bolts as per approved drawing & specification.
2. Triple feeder control and relay panel
3. Control and Relay pannel for capacitor bank
4. 36 KV,1600Amp Isolator (without E/S)
5. 36 KV,1200Amp Isolator (without E/S)
6. 36 KV, 1200Amp Isolator (with E/S)
7. 36 KV SF6 Circuit Breaker along with support structure.
8. 33/.4KV, 630KVA, Station Transformer
9. 36 KV single phase CT (800-400/1A)3 core (2 core for protection and one core for metering class and accuracy 0.2S) with junction box
10. 36 KV single phase CT (400-200/1A)3 core (2 core for protection and one core for metering class and accuracy 0.2S) with junction box.
11. 33 KV, 1 Phase NCT
12. 2X6.63 MVAR, 38KV (i.e. 33 KV, 2X5 MVAR) double star connected Capaciotor Bank consist of 24 nos of 552.5 KVAR, 10.97 KV Internally fused Capacitor units The Capacitor bank will be complete with its Hot Dip Galvanized Mounting racks, stranded copper conductor/ Aluminium Bus bars & Support Insulators.
13. 33 KV, 2.21 KVAR, 50.37 Amp, 0.871 Ohm, Al wound Dry type Series Reactor with TC.
14. 36 KV single phase PT accuracy class 0.2 with junction box
15. 33KV lightening arrester with surge monitor and connecting cable
16. AAC tarantula conductor
17. ACSR Panther conductor
18. Disc Insulator (120 KN)
19. Different type of Clamps, connectors, seperator cum droppers cable lug,and C-wedge clamp for 33 KV Bus, Breakers, Isolators, C.Ts., P.T. & L.As.
20. Bolted type tension fitting for tarantula conductor for Disc Insulator (120 KN)
21. Bolted type tension fitting for single tarantula conductor for Disc Insulator (120 KN)
22. Bolted type tension fitting for single panther conductor for Disc Insulator (120 KN)
23. Armoured copper cable 2 Core 2.5 sq. mm, 1.1KV
24. Armoured copper cable4 Core 2.5 sq. mm, 1.1KV
25. Armoured copper cable6 Core 2.5 sq.mm, 1.1KV
26. Armoured copper cable10 Core 2.5 sq. mm, 1.1KV
27. Power armoured cable 3.5X400 Sq mm, 1.1KV.
28. Switch Yard LED Light.
29. Marshalling/Terminal Kiosk as per drawing/sample.
30. 415V ACDB
31. lighting Junction box
32. Horn gap fuse set
33. Earth strip of required size
34. MS Round 36mm dia.
Description of Work / Item(s)
Amount
Part-B (Erection Work)
for Increasing the capacity
1. Dragging & shifting of 40 MVA T/F from store to T/F Plinth (App. 100 Mtr.) with Proper Safety
2. Erection of 40 MVA T/F including Centrifuging, Cable connection, feruling, complete work, Earthing, Testing & commissioning complete
3. Work of Testing & Commission of 132 & 33 kV Bays including all concern testing of New Transformer.
for 132 KV Bay
1. Super structure erection of 132 KV isolator, CT, PT, BPI , gantry structure and all work above ground level including extension with proper tightening of bolt & nut work include labour and equipment.
2. Complete erection of bus bar by laying, stringing, tensioning, clamping, jointing, etc. complete with moose conductor including hoisting of fitting of insulator and all other accessories on 132 KV gantries.
3. Preparation of cable schedule, terminations details & laying and termination of different types of control cables between switchyard equipments and control room, complete in all respect
a. Armoured Copper Control Cable 2 core x2.5 Sq mm, 1.1KV
b. Armoured Copper Control Cable 4 core x2.5 Sq mm, 1.1KV
c. Armoured Copper Control Cable 6 core x2.5 Sq mm, 1.1KV
d. Armoured Copper Control Cable 16 core x2.5 Sq mm1.1KV
e. power Armoured cable 3.5X35 Sq mm, 1.1KV.
4. Safe and proper erection, jumpering, testing and commissioning of following items
a. 132 KV CTS with Junction Box
b. 132 KV PT
c. 132 KV Bus Isolator
d. 133 KV staggered Isolator
e. 132 KV Circuit Breaker
f. 120 KV,10 KA, Lighting Arrestor
g. 132 KV PI
h. Control Panel / Relay Panel
i. Marshalling/Terminal Kiosk
j. Switch Yard LED Light.
5. Earthing of all equipment structure at 2 point with earthmat by 50x6 mm earth strip including cost of earth strip, nuts & bolts and civil work complete in all respect.
6. Laying of earth mat 7X8 mtr grid work include welding and civil work complete in all respect.
7. Erection of pipe earthing material.
for 33 KV Bays
1. Lattice type galvanized main and auxiliary structure complete with foundation, nuts & bolts as per approved drawing & specification.
2. Complete erection of bus bar by laying, stringing, tensioning, clamping, jointing, etc. complete with single Taruntula conductor including hoisting of fitting of insulator and all other accessories on 33 KV gantries.
3. Bus bar erection of 2X5 MVAR Capacitor Bank including Laying,Stringing,tensioning with single panther conductor including hoisting of fitting of insulator and all other accesssories of gantries
4. Installation and Testing of 2x6.63 MVAR, 38KV (i.e. 33 KV, 2x5 MVAR) double star connected Capaciotor Bank consist of 24 nos of 552.5 KVAR, 10.97 KV Internally fused Capacitor units.The Capacitor bank will be complete with its Hot Dip Galvanized Mounting racks, stranded copper conductor/ Aluminium Bus bars & Support Insulators.
5. Erection installation and testingh work of 33 KV, 2.21 KVAR, 50.37 Amp, 0.871 Ohm, Al wound Dry type Series Reactor with TC.
6. Safe and proper erection, testing and commissioning of following items
a. Triple feeder control and relay panel
b. contol and Relay pannel of 2X5 MVAR Capacitor bank
c. 36 KV,1600Amp Isolator (without E/S)
d. 36 KV,1200Amp Isolator (without E/S)
e. 36 KV, 1200Amp Isolator (with E/S)
f. 36 KV SF6 Circuit Breaker along with support structure.
g. 36 KV CT (800-400/1A) & (400/200/1A)
h. 36 KV NCT(200/1A)
i. 36 KV single phase PT
j. 33KV lightening arrester
k. Armoured copper Cable 2 Core 2.5 sq. mm, 1.1KV.
l. Armoured copper Cable 4 Core 2.5 sq. mm,1.1KV.
m. Armoured copper Cable 6 Core 2.5 sq. mm,1.1KV.
n. Armoured copper Cable 10 Core 2.5 sq. mm,1.1KV.
o. Fixing switch yard LED light and Juction box and lying cable and conneting.
p. Marshalling/Terminal Kiosk as per drawing/sample.
q. 33/.4KV, 630KVA Station Transformer
r. 415V ACDB
s. Horn gap fuse set
t. Power armoured cable 3.5X400 Sq mm, 1.1KV.
7. making of all jumpers of 33KV bays
8. Earthing of all equipment structure at 2 point with earth mat by 50x6 mm earth strip including cost of earth strip, nuts & bolts and civil work complete in all respect.
9. Laying of earth mate 7X8 mtr grid work include welding and civil work complete in all respect.
(Civil Works) for 132 KV Bay
1. Earth work in excavation by mechanical means and manual means in foundations, trenches or pits of any size including dressing of sides and ramming of bottoms, including getting out the excavated soil and disposal of surplus excavated soil up to 50mtr as directed including all leads & lifts in all type of soils.
2. Providing and laying in position cement concrete of specified grade including the cost of centering and shuttering, material, forming, concreting curing of water. all work up to plinth level:1:4:8 (1cement:4 coarse sand:8 graded stone aggregate 40 cm nominal size)
3. Providing and laying in position specified grade of reinforce cement concrete including cost of centering, shuttering, finishing, fooming, concreting, curing of water. all work up to plinth level:1:1.5:3 (1cement:1.5 coarse sand:3 graded stone aggregate 20 cm nominal size) include fixing bolts including nuts & washer complete. .
4. Reinforcement for RCC work including cost of all size of bars, straightening, cutting, bending, placing in position and binding all complete up to plinth level cold twisted bars.
5. 12 mm cement plaster of mix 1:4 (1cement : 4 fine sand )
6. Brick work with machine perforated bricks of class designation 125 conforming to IS 2222- 1991 in superstructure above plinth level up to floor five level in cement mortar 1:4 ( 1 cement : 4 coarse sand) with F.P.S. bricks.
7. Construction of 30CM deep trenches with cover size mm 65x40X10 cm complete including excavation, CC work 1:4:8,CC work 1:2:4 , first class brick work, plaster and fixing of 40X40X5 mm angle on top side of trench, also fixing of angle inside the trench, fixing of cable tray and making frame of trench covers of required size by 40X40mm size angle. CC ratio of trench cover 1:2:4. Including cost of all material
8. Construction of 60CM deep trenches with cover size mm 90x40X10 cm complete including excavation, CC work 1:4:8,CC work 1:2:4 , first class brick work, plaster and fixing of 40X40X5 mm angle on top side of trench, also fixing of angle inside the trench, fixing of cable tray and making frame of trench covers of required size by 40X40mm size angle. CC ratio of trench cover 1:2:4. Including cost of all material
9. Construction of 0.3X0.25 Mtr drain in continuation of existing drain Including cost of all material
10. Dismantling of existing mesh fencing
11. Providing and fixing of mash fencing
(Civil Works) for 33 KV Bays
1. Earth work in excavation by mechanical means and manual means in equipment foundations, pits and runnel around the switch yard. including dressing of sides and ramming of bottoms, including getting out the excavated soil and disposal of surplus excavated soil up to 50mtr as directed including all leads & lifts in all type of soils.
2. Preparation of Electrical layout plan/earth - mat/ section elevations drawing.
3. supply and spreading of earth by earth work in excavation by mechanicacl means/mannual means over surface area in switch yard in layer not exceeding 20 cm in depth consolidated each deposited layer by ramming and watering etc.
4. Providing and laying in position cement concrete of specified grade including the cost of centering and shuttering, material, forming, concreting curing of water in surface of dovelope switch yard in 15cm deep. and making of 33 KV Cable Tray all work up to plinth level:1:4:8 (1cement:4 coarse sand:8 graded stone aggregate 40mm nominal size)
5. Providing and laying in position cement concrete of specified grade including the cost of centering and shuttering, material, forming, concreting curing of watering and makingj the base for foundation of all equipment.and base of runnel all work up to plinth level:1:2:4 (1cement:4 coarse sand:8 graded stone aggregate 40mm nominal size)
6. Providing and laying in position specified grade of reinforce cement concrete including cost of centering, shuttering, finishing, forming, concreting, curing of water of equipment foundation and all work up to plinth level:1:1.5:3 (1cement:1.5 coarse sand:3 graded stone aggregate 20 mm nominal size) include fixing bolts including nuts & washer complete.
7. Reinforcement for RCC work including cost of all size of bars, straightening, cutting, bending, placing in position and binding all complete up to plinth level cold twisted bars.
8. 12 mm cement plaster of mix 1:4 (1cement : 4 fine sand )
9. Brick work with machine perforated bricks of class designation 125 conforming to IS 2222- 1991 in superstructure above plinth level up to floor five level in cement mortar 1:4 ( 1 cement : 4 coarse sand) with F.P.S. bricks. For construction of runnel and foundation of 33/.4 Transformer etc.
10. Construction of 50CM deep trenches for main tranch and 33KV cable trench with cover size 100x40X5 cm complete including excavation, CC work 1:4:8,CC work and1:4 ratio first class brick work, plaster and fixing of 50X50X5 mm angle on top side of trunch, also fixing of angle in side the trench, fixing of cable tray and making frame of trench covers of required size by 50X50X5mm size angle. CC ratio of trench cover 1:2:4. Including cost of all material
11. Construction of 30CM deep trenches with cover size mm 90x40X5 cm complete including excavation, CC work 1:4:8,CC work 1:4 ratio, first class brick work, plaster and fixing of 50X50X5 mm angle on top side of trunch, also fixing of angle in side the trench, fixing of cable tray and making frame of trench covers of required size by 50X50X5mm size angle. CC ratio of trench cover 1:2:4. Including cost of all material
12. Construction of 75CM deep 33 KV cable trenches with cover size 200x50X10cm complete including excavation, CC work 1:4:8,CC work 1:4 ratio, first class brick work, plaster and fixing of 50X50X5 mm angle on top side of trunch, also fixing of angle in side the trench, fixing of cable tray and making frame of trench covers of required size by 50X50X5mm size angle. CC ratio of trench cover 1:2:4. Including cost of all material
13. Providing and laying of crushed gravel in switchyard.
14. Dismantling old and rusted wire mesh fencing and electric wire fencing.
15. refixing useable existing wire mesh fencing and electric wire fencing with angle and making foundation base of RCC columns and base wall
16. Providing and fixing of wire mesh fencing, M.S. angle(size 70X70X6) mm.M.S. flat including work of making the RCC column, base wall grouting of angle etc. complition of all required work
(Civil Works ) for Increasing the capacity
1. Earth work in excavation by mechanical means and manual means in foundations, trenches or pits of any size including dressing of sides and ramming of bottoms, including getting out the excavated soil and disposal of surplus excavated soil up to 50mtr as directed including all leads & lifts in all type of soils.
2. Providing and laying in position cement concrete of specified grade including the cost of centering and shuttering, material, forming, concreting curing of water for construction of T/F foundation bed and all work up to plinth level:1:4:8 (1cement:4 coarse sand:8 graded stone aggregate 40 cm nominal size)
3. Providing and laying in position specified grade of reinforce cement concrete including cost of cenetring, shuttering, finishing, fooming, concreting, curing of water, all work up to plinth level:1:1.5:3 (1cement:1.5 coarse sand:3 graded stone aggregate 20 cm nominal size) include fixing bolts including nuts & washer complete.
4. Reinforcement for RCC work including cost of all size of bars, straightening, cutting, bending, placing in position and binding all complete up to plinth level cold twisted bars.
5. Providing of rail suitable for foundation of 40 MVA T/F (132/33KV) as per drawing.
6. Fixing of rail on the foundation of (132/33KV) 40 MVA T/F & including the cost of all labour & T&P, fabrication work & material required for proper completion of work.
7. 12 mm cement plaster of mix 1:4 (1cement : 4 fine sand )
8. Brick work with machine perforated bricks of class designation 125 conforming to IS 2222- 1991 in superstructure above plinth level up to floor five level in cement mortar 1:4 ( 1 cement : 4 coarse sand) with F.P.S. bricks.
(Civil Works) for Approach road
1. Providing and laying in position cement concrete of specified grade including the cost of centering and shuttering, material, forming, concreting curing of water. all work up to plinth level:1:4:8 (1cement:4 coarse sand:8 graded stone aggregate 40 cm nominal size)
2. Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) in pavements, laid to required slope and camber in panels as required including consolidation finishing and tamping complete.
3. Reinforcement for RCC work including cost of all size of bars, straightening, cutting, bending, placing in position and binding all complete upto plinth level cold twisted bars.
4. Brick work with machine perforated bricks of class designation 125 conforming to IS 2222- 1991 in superstructure above plinth level up to floor five level in cement mortar 1:4 ( 1 cement : 4 coarse sand) with F.P.S. bricks.
5. Supplying and stacking at site. 90 mm to 45 mm size stone aggregate.
6. Supplying and stacking at site. 63 mm to 45 mm size stone aggregate.
7. Laying, spreading and compacting stone aggregate of specified sizes to WBM specifications in uniform thickness, hand picking, rolling with 3 wheeled road/ vibratory roller 8-10 tonne capacity in stages to proper grade and camber, applying and brooming requisite type of screening/ binding material to fill up interstices of coarse aggregate, watering and compacting to the required density
8. Providing and laying in position bitumen hot sealing compound for expansion joints etc.:Using grade 'A' sealing compound. Per cm
Description of Work / Item(s)
Amount
Total Part-A (Supply of Material ) from BoQ1 sheet WITHOUT GST
Total Part-B (Erection and Civil Works ) from BoQ2 sheet WITHOUT GST
Add GST* Amount on (Total of Part-A + Total of Part-B above)
Mishrilal Associates Pvt. Ltd.
SNS Technocorp Private Limited
Madan Contractors & Co.
Modern Transformers Pvt. Ltd.
GUPTA POWER INFRASTRUCTURE LIMITED
Mishrilal Associates Pvt. Ltd.
Modern Transformers Pvt. Ltd.
Shriya Associates
GUPTA POWER INFRASTRUCTURE LIMITED
SNS Technocorp Private Limited
Madan Contractors & Co.
Shriya Associates
SNS Technocorp Private Limited
Modern Transformers Pvt. Ltd.
GUPTA POWER INFRASTRUCTURE LIMITED
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid