| 1 | Admitted-Finance RZ M 21 NAND BLOCK MAHAVIR ENCLAVE PALAM NEW DELHI 110045 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110045 | Admitted-Finance |
| 2 | Rejected-Technical | Rejected-Technical Not complied technical specification as per NIT. |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Others-Necessary physically documents not submitted as per NIT. |
| 4 | Rejected-Technical | Rejected-Technical Not complied technical specification as per NIT. |
Tender Value
₹40.3 L
EMD Value
₹80,568
Closing Date
15 Apr 2025, 3:00 pmClosed
Executive Engineer (Elect)
Room No.25, T.E. Building Kidwai Bhawa, MTNL, New Delhi
Repairing of 11 KV HT VCB and Transformer at various Sub Station in various RSU,RLU and TE Building under EE (E ) KBN New Delhi.
2025_MTNL_855766_1
EE(E)KBN/2025-26/05-04-25/04
Open Tender
Miscellaneous Services
Item Rate
365 days
Kidwai Bhawan
Please refer Tender documents.
9 documents required · 9 mandatory
₹590
Yes
MTNL Delhi
₹80,568
Yes
25 Apr 2025
5 Apr 2025
16 Apr 2025
5 Apr 2025
15 Apr 2025
5 Apr 2025
Amount
Supply and fixing of Transformer temperature relay with dismantling of brunt out temperature relay and wiring connection testing etc complete as required.
Supply & fixing of power pack unit having input 220 Volt AC and output 24/48/110 Volt DC i/c. making inter connection suitable for existing HT system etc. complete as required.
Supply and fixing of current transformer in existing LT panel (Set of 03 nos for three phase), having suitable CT ratio up-to 2000/5 Amp for protection and metering, including testing, wiring, and installation in the existing LT Panel including connections, testing and commissioning etc. complete as required as per site requirement.
Servicing of 400Amp to 800Amp HT OCB / VCB complete with cleaning, alignment, adjustment of gaps between phase to phase, lubricating all moving parts, adjustment for smooth mechanical operation etc complete as required.
De-hydration of transformer oil with Filter machine at site to maintain the break down value, die electric strength of oil up to 50 KV including providing oil testing facility at site as reqd.
Supplying & filling the transformer oil, sealed pack drum including transportation charges etc. ( Make : M/S Power oil / Savita with ISI marked having 50KV R/C)
Testing and meggaring of 11 KV HT VCB, CT with p.c testing, insulation testing and rectification of moisture in bus bar, insulator, and H.T Cable box, Heating of complete C.T testing etc. complete as required.
Calibration of IDMT relay with secondary injection test set including cleaning servicing of contacts tightening of loose contacts testing repair etc. complete as required.
Servicing of 800 to 3200 Amp ACB Complete with cleaning, alignment, adjustment of gaps between phase to phase, lubricating all moving parts adjustment for smooth mechanical operation etc complete as required.
Checking & arresting at site for Oil Leakages from transformer of various ratings including (a) Dismantling of LT cable’s / Bus- Bar’s connections & dismantling of L.T. Bushing Rods. (b) Dismantling of Main Top cover / inspection window of Transformer. After draining of oil of Transformer into clean empty drums (as per requirement) c) Replacement of Cork rings set along with new Teflon rings of all phases for arresting oil leakages. d) Fixing of all terminals & Bus-bar’s connections & making adjustments. e) Replacement of cork gaskets, oil rings of inspection window side & Buckle relay side & pipe line also for arresting leakages, if any. f) Re-filling of oil into transformer & examining of leakages for improving breakdown value of oil complete as reqd.
SITC of following rating four pole MCCB with operating handle and spreader terminal in the existing panel i/c inter- connection etc complete as reqd (L&T, Type DN2-250 D or SS type from make list) a) 400 Amps(L&T, Type DN3B-400 D or SS type from make list)
b) 630 Amps(L&T, Type DN3-630 D or SS type from make list)
Servicing and cleaning of 11KV / 415 Volt Dry type transformer up to 1250 KVA i/c flexible joint connection and checking temperature relay for its operation, tightening of HT/LT connection and adjustment of tripping, meggaring, high port testing, checking protection etc. complete as required.
Testing of 750 KVA Transformer including meggaring, high voltage test, IR value, balancing test, insulation testing and rectification of moisture in bus bar, insulator, in-coming, out-going and H.T Cable box, Heating of complete P.T, C.T testing etc. complete as required.
Supply and fixing of Digital type, Ammeter up to 2500 Amp. Size 96 x 96 sq.mm, (Make: Trinity / L&T) etc. complete with wiring, connection, testing etc. complete as required.
Supplying and fixing of Digital type, Voltmeter up to 500 Volt, size 96 x 96 sq.mm, (Make: Trinity / L&T) complete with wiring, connection, testing etc. complete as required.
Supply and fixing of LED type indication lamp with holder assembly 230 V AC / 24 DC / 48 V DC / 110 V DC, complete as required.
Supplying and fixing of Digital type, KV Meter size 96 x 96 sq. mm, (Make: Trinity / L&T) complete with wiring, connection, testing etc. complete as required.
Blowing-off dust/dirt from HT Panel, LT Panel, Capacitor panel, Emergency Panel and complete cleaning from inside and outside of these panels by opening of front,middle and rear sections, tightening of all nut-bolts etc. as required.
Supply and fixing of APFC Micro processer relay with calibration, testing etc. complete as required. (8Stage-12 stage).
Providing and making of wiring for existing faulty capacitor panel with required size copper wire and copper lugs testing etc complete as required.
Supply and fixing of current transformer in existing 11KV HT panel having suitable CT ratio for protection and metering including testing wiring and installation in the existing H.T. panel including connections, testing and commissioning etc. complete as required as per site requirement.
SITC of Super heavy duty capacitor in the existing capacitor panel suitable for working of 440 Volts AC Supply i/c removing of faulty capacitor etc complete as required. (Make : EPCOS) a) 1 KVR
c) 5 KVAR
d) 10 KVAR
e) 15 KVAR
f) 20 KVAR
g) 25 KVAR
Supply and fixing of following HRC Fuse assembly with wiring connection testing complete as required. a) 63 Amps
b) 100 Amps
c) 125 Amps
Supply and fixing of 4 Pole power contactor with 1 NO, 1NC for capacitor panel with wiring connection testing complete as required. a) Moc - 12.5 ( for 5/6/10 KVAR capacitor )
b) Moc - 15 ( for 2.5/15 KVAR Capacitor)
c) Moc - 20 ( for 20 KVAR Capacitor)
d) Moc - 30 ( for 20/25 KVAR Capacitor)
S.I.T.C. of Vacuum interrupter bottle suitable for existing 11KV VCB of 400A/630A (Make: Alstom/ Kirloskar/ ABB/ Areva/ Crompton/BE Make) including dismantling & removing existing faulty Vacuum interrupter per bottle, making connections & high voltage testing etc. complete as required.
Supplying and making following type of cable end jointing for following size of 3 core, XLPE aluminium conductor (armored) cable of 11KV grade i/c cutting, removing the existing faulty cable end termination wherever required etc. complete as required. (Note: Make of jointing kit- Denson/ Raychem or equivalent) a) Indoor Type Joint for cable-sizes 150sq.mm. to 185 sq.mm.
b) Straight Type Joint for cable-sizes 120 sq.mm. to 150 sq.mm.
Supply installation and testing of 11 KV HT VCB mechanism and testing, meggaring etc complete as required.
Replacement with Installation of 11KV / 110 Volt PT Class 0.5 accuracy and 100 VA burden with high voltage testing for VCB Type HT Panel etc complete as required including dismantling of old defective burnout PT.
Supply and fixing of LT/HT spares bottom cluster contact / LT/HT M-610 / M-16 top fix contact and testing etc. complete as required.
Supply and fixing of electronic IDMT Relay with testing, complete as required. Make- L&T/ Crompton.
Supply and fixing of 1000 Watt Halogen Light for arresting of moister in HT Panel with 3 core 4 sq mm cable 10 mtr aprox, wiring connection testing complete as required.
Supplying, Laying and fixing, testing, commissioning of following size HT cable of 11 KV grade, Aluminum conductor armored power cable etc. complete as required. a) 3 core 240 sq.mm
b) 3 core 300 sq.mm
Supply and fixing of Rack in & Rack out assembly for 630 amp to 800 amp different type 11 KV HT VCB .
Supplying, installing, testing and commissioning 630A to 1000 Amp of 4 pole, 50kA, 415V, Manual draw-out type air circuit breaker of following full-load current rating, in the existing LT/MV panel i/c carrying-out required modifications in the panel, in the associated incoming/outgoing bus bars of the panel for proper mounting & connections of the ACB, also providing suitable interlocking connections, control wiring, end terminations etc. complete as reqd as per the site requirement. (Make: L&T/ABB /Siemens/Schneider)
Dismantling the 1000 KVA oil type transformer from the foundation i/e dismantling of all incoming & outgoing connection ,bus trunking at LT side and HT site etc complete as reqd and keep it to out side the room. etc. complete as reqd.
Loading the 1000 KVA transformer in tempo with the help to chain pulley / Crain & heavy labour at Tel. Exchange & unloading at workshop from tempo i/c cartage from Tel. Exchange to workshop etc complete as reqd.
Loading the transformer in tempo with the help of chain pulley / Crain & heavy labour at workshop & unloading at Tel. Exchange Frame tempo i/c cartage from workshop to Tel. Exchange etc complete as reqd.
Opening of top and disconnecting all the connection from L. T. and H.T. side and opening of the tap charger , lifting the complete core brunt HT 11 KV copper coils of 3 phase, opening the LT strip winding of 3 phase for cleaning the old insulation etc complete as reqd.
Complete rewinding of 1000 KVA primary Delta and star secondary 11 KV / 415 volts oil filled transformer HT and LT side all 3 HT cores and 3 LT cores with suitable size copper strip / wire with H class insulation ,including dismantling the burnt winding of HT and LT sides cleaning the core, varnishing the new winding, heating, drying, testing commissioning complete in all respect etc complete as required with following test a) Megger Test, b) Ratio Test, c) Resistance Test d) Vector group test e) Magnetic balance Test f) Short Circuit Test g) No load Test.
Re assembling and installation the 1000 KVA oil type transformer after rewinding on the foundation i/e all incoming & outgoing connection , bus trunking at LT side and HT site etc complete as reqd and keep it to in side the room and on loading testing etc. complete as reqd.
Less credit on account of dismantled material.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .