| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹64.7 LAccepted-AOC | ₹64.7 L | L1 | Accepted-AOC Financially lowest |
| 2 | L2₹70.1 LRejected-Finance | ₹70.1 L | L2 | Rejected-Finance Financially not lowest. |
| Sl No | Description | Qty | Unit | GREEN AIR L1 | BS Engineering India Pvt Ltd L2 |
|---|---|---|---|---|---|
| 1.00 | Dismantling of the exisiting ODUs of VRF Circuit 4 & 5, Supply, Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units (latest technology, top discharge machines) suitable for cooling and heating ,having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14HP modules, microprocessor based Controller,top discharge type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping.The unit shall be suitable to work on 400V+/-10%, 3Phase, 50Hz AC power supply.The unit shall be filled with first charge of the refrigerant and ready for use as required.The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The outdoor units shall be compatible with the exisiting AHUs connected(Details of exisiting AHUs will be provided in the tender document). Replacement of necessary refnet joints, header copper pipelines with thermal insulation, branch pipes with thermal insulation etc. to be considered whenever required. The work also includes the ODU connection kits, necessary control wiring, vacuumization, pressure testing, additional refrigerant gas charging, testing, commissioning, suitable thermal insulation for exisiting copper pipes in the terrace area to protect from UV, bird droppings, moisture, weathering etc. ,pedestral arrangements, necessary civil works if required etc. The dismantling of the exisiting units from terrace floor including disconnection, loading, unloading, shifting etc. The rate shall be inclusive of 36 months comprehensive warranty from the date of commisssioning of the new system (includes atleast 3 routine preventive maintenance services of the units per year, rectification of refrigerant gas leakages, gas recharging, replacement of spares etc. on free of cost if required). The work shall be carried out in all respects as required by the Engineer-Incharge & OEM.
(Samsung/LG/Daikin makes preferrable for new ODU units)
Note
1. The Bidder shall visit and assessed the site before quoting the tender
2. The Executing agency will be sole responsible for compatibility of the new outdoor units with the exisiting AHUs and associated systems | 128 | HP | 40,464 ₹51.8 L | 44,156 ₹56.5 L |
| 2.00Supply and Installation of AHU Kits for the below capacities | |||||
| 2.10 | upto 5 TR | 17 | No | 44,545 ₹7.6 L | 46,189 ₹7.9 L |
| 2.20 | 7.5TR (above 5 TR capacity) | 10 | No | 47,938 ₹4.8 L | 48,328 ₹4.8 L |
| 3.00 | Supply and Installation of AHU wired remote | 27 | No | 6,033 ₹1.6 L | 7,459 ₹2.0 L |
| 4.00 | Buyback amount for the existing VRF Outdoor Units (128 HP) | 1 | LS | 1,10,000 ₹1.1 L | 1,15,200 ₹1.2 L |
Updated dates
Tender Value
₹65.3 L
EMD Value
₹1.3 L
Closing Date
28 Oct 2025, 4:00 pmClosed
PROJECT ENGINEER CUM ESTATE OFFICER (I/C)
IISER TVM MARUTHAMALA PO VITHURA TRIVANDRUM
Revamping of 128 HP Samsung VRF A/C Circuit 4 and 5 installed at BSB, IISER Campus, Thiruvananthapuram
2025_IISRT_881362_1
IISERTVM/EO/EM/267/25/2025-26
Open Tender
Miscellaneous Works
60 days
IISER THIRUVANANTHAPURAM
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹1.3 L
12 Dec 2025
14 Oct 2025
29 Oct 2025
15 Oct 2025
28 Oct 2025
15 Oct 2025
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.79 MB
BOQ_926450.xls
BOQ • 0.33 MB
GCC2023.pdf
Tender Documents • 23.40 MB
DetailsofAHUs.pdf
Additional Documents • 0.06 MB
SchematicDrawingsofSamsungVRFCircuit.pdf
Additional Documents • 0.55 MB
Download all tender documents and submit your bid