Loading…
Loading…
Tender Value
₹16.6 L
EMD Value
₹33,259
Closing Date
7 Jul 2026, 12:00 pm
Similar tender results from the same govt authority in the past 3 years.
Executive Engineer, PWD, Jal Electrical Division.
Office of the Executive Engineer, PWD, Jalpaiguri Electrical Division, Purta Bhavan, Hakimpara, Post and Dist. - Jalpaiguri, Pin - 735101.
Upgradation of Banarhat RH under Banarhat Block in the district of Jalpaiguri-SITC of Fire Detection and Alarm system.
2026_WBPWD_5015803_1
WBPWD/EE/JED/NIT 04e/T of 2026-27.
Open Tender
ELECTRICAL WORKS ORG
60 days
Banarhat Rural Hospital Jalpaiguri.
Please refer Tender documents.
3 documents required · 3 mandatory
₹33,259
23 Jun 2026
23 Jun 2026
9 Jul 2026
23 Jun 2026
7 Jul 2026
23 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector ( VDS / UL / LPCB /FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector is to be provided without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. Degree of protection as per OEM Standard. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) | 300 | Nos. | 1,685 | ₹5,05,500 | BI01010001010000000000000515BI0100001112 |
| 2 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL / LPCB / FM approved ) with in built short circuit fault isolator as per NFPA (Note : MCP without built-in fault isolator is also acceptable with one independent short circuit fault isolator is to be provided without extra cost). Degree of protection as per OEM Standard. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) | 48 | Nos. | 2,195 | ₹1,05,360 | BI01010001010000000000000515BI0100001113 |
| 3 | Supply, Installation, Testing & Commissioning of Addressable Loop Powered /panel powered Hooter (sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator as per NFPA (Note :Hooter without built-in fault isolator is also acceptable with one independent short circuit fault isolator is to be provided without extra cost). ( VDS / UL / LPCB / FM approved). Degree of protection as per OEM Standard. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) | 48 | Nos. | 1,579 | ₹75,792 | BI01010001010000000000000515BI0100001114 |
| 4 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector ( VDS / UL / LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have minimum triggering temperature programmable from 58 deg. C to 68 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector in the loop is to be provided without extra cost) the detectors should have built in response indicator with LED indicator.Degree of protection as per OEM Standard. (Approved Make: Cerberus Pro / Honeywell/ Johnson Controls / Edward/Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) | 20 | Nos. | 1,512 | ₹30,240 | BI01010001010000000000000515BI0100001115 |
| 5 | Supply, Installation, Testing & Commissioning of Addressable OPC complied Monitor Modules (VDS/UL/ERTL/LPCB/FM approved) for monitoring Flow switches / Fire exit doors / AHU/ Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of Input or output, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make: Cerberus Pro / Honeywell/ Johnson Controls / Edward/Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) | 20 | Nos. | 1,856 | ₹37,120 | BI01010001010000000000000515BI0100001116 |
| 6 | Supplying, installation, testing & commissioning of Response Indicator on surface/recessed MS Box with metallic cover having two LED and Degree of protection as per OEM Standard etc. complete with all connections etc as required. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire/System Sensor/Agni Suraksha ) | 42 | Nos. | 146 | ₹6,132 | BI01010001010000000000000515BI0100001117 |
| 7 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make : Finolex/ Gloster/ RR Kable/ Polycab/ KEI ) through 19 mm dia PVC 'FR' type Rigid Conduit pipe MMS with necessary arrangement as per G.S. (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall. | 4,000 | Mtr. | 92 | ₹3,68,000 | BI01010001010000000000000515BI0100001118 |
| 8Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable Fire Alarm Control Panel (VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) | ||||||
| 8.1 | Four Loop Panel. | 1 | Each | 2,67,184 | ₹2,67,184 | BI01010001010000000000000515BI0100001120 |
| 10TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done. | ||||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.57 MB
Tendernotice_2.pdf
PDF • 1.04 MB
BOQ_5084782.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid