Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹7.4 LAccepted-AOC | L-1 | Accepted-AOC AOC | |
| 2 | L-2₹8.0 L+₹51,632 (6.94%)Rejected-Finance 1128 SECTOR 22 B NEAR AROMA PETROL PUMP CHANDIGARH UT 160022 | CHANDIGARH | CHANDIGARH | 160022 | L-2 | Rejected-Finance Highest | |
| 3 | L-3₹9.4 L+₹1.9 L (25.7%)Rejected-Finance TAILOR MARKET MAIN BAZAAR MANDI ADAMPUR 125052 | HISAR | HARYANA | 125052 | L-3 | Rejected-Finance Highest | |
| 4 | L-4₹9.9 L+₹2.4 L (32.5%)Rejected-Finance 315 INDUSTRIAL AREA II PANCHKULA 134113 | PANCHKULA | HARYANA | 134113 | L-4 | Rejected-Finance Highest |
Tender Value
₹9.6 L
EMD Value
₹19,100
Closing Date
25 Jun 2019, 5:00 pmClosed
Ritesh Nandal
Executive Engineer, Elect. Division PWD B and R Br., Ambala Cantt
Const. of Head Office Building for the Directorate of Employment Haryana (Rojgar Bhawan) Plot no. 1.P. 6b Sector 6 Panchkula (Pdg. Fire Alarm system and PA system).
2019_HRY_80634_1
PWD/Elect-KNL/Elect-AMB/10545
Open Tender
Construction Works
Works
60 days
Ambala
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
Executive Engineer, Elect. Division PWD BandR Br.
₹19,100
8 Nov 2021
13 Jun 2019
27 Jun 2019
13 Jun 2019
25 Jun 2019
13 Jun 2019
Amount
Supply and erection of PVC unsheathed copper conductor cable single core 1100 volts grade in pipe of suitable size excluding cost and erection of pipe. Size 1.5 sqmm (3 / 0.81mm). 31.40 (i)
Supply and erection of PVC conduit pipe ISI marked (Medium) recessed in wall /ceiling etc. including cost of PVC bends, inspection box and all other material required to complete the job in all respect to the entire satisfaction of Engineer-in-Charge of work. 25 mm dia 31.44(b)
SITC of Micro processor based 2 wire fault tolerant, networkable type fire alarm / detection control panel ( having nos. of 2 loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 character L C D unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80LED Indicators. The Panel shall have 3 Serial Ports. The panel shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum of 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work Makes : Bosch FPA 1000 Series ,Cerberus by Siemens, Edwards EST3,Honeywell Morley Zxe Series)
SITC of 6 watt speaker wall mount / ceiling (Make Honeywell/BOSCH/Henrich)
SITC of addressable multisensor detector with a combination of Optical and Thermal including mounting base, auto addressing feauture as required. Detetctor should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module after 20 devices) (Makes: Bosch FAP-440-T+FAA-440, Siemens Cerberus OH921+DB-11, Honeywell Morley MI-PTSE+B501, Edwards SIGA PHD + SIGA )
SITC ofaddressable Heat detector with fixed and rate of raise feature including mounting base with LED… etc. complete as required. Each Detector should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) (Makes: Bosch FAH-440 + FAA-440 , Siemens Cerberus HI921+DB-11, Honeywell Morley MI-RHSE+B501 , Edwards SIGA DHI + SIGA )
SITC of Addressable Loop powered hooter with strobe complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make: Bosch / Morley / Siemens / Edwards
SITC of Exit Signage With Battery Backup Glow Type Size 285mm x 175mm , also as per requirement Material Acrylic, Aluminum, Aluminum Acrylic , Power Consumption 5 V / 220 mA (approx.) Feature With battery backup. rigid sheet signage containing Zink sulphate as bare chemical class 1 material PSPA fixed on 3mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour & material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. (Make: PE / Glolite / Pearl)
SITC of Intelligent Analog Addressable Type Monitor Modules having option of RAIL or Surface Mounting with Tri Color LED status indicator with Built in Short Circuit Isolators having Visible Rotary Decade Address Switch from 01-99 dully approved to GEA GEW1-082 conforming to BS5839 Standards and Duly approved by EN54/LPCB/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. (Make: Bosch / Morley / Siemens / Edwards
SITC of minimum 1000 Mtr. Range Kheraj / National make SIRON generator provided at the roof of the building with separate Power Supply, relay etc. complete the in all respect up to the entire satisfaction of Engineer-in-Charge of work.
Supply & Erection of Fire extinguisher all as Per IS 15683 duly hanged on the wall with necessary hooks to complete the job in all respect upto entire satisfaction of engineer incharge of work Make: Safex / Minimax / cease fire) ABC dry Powder extinguisher 6 Kg Cap
Water/C2 type extinguisher 9 Ltr Cap
CO2 4.5kg capacity
SITC of fault isolator/base to check short circuit every 20 Deductors
SITC of 1KVA online UPS with external SMF 12 Volt of suitable AH battery for minimum 2 hour backup ( Luminous / Microtek / APC libert / Emerson)
SITC of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliat to EN 54 having Rotary Decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Makes : (Makes: Bosch FMM-325A-D,Siemens Cerberus HMS-S, Morley MI-MCP, Edwards SIGA 278, )
SITC of Analog Addressable type Active Repeater fire alarm panel with Backlit LCD Display, having controls for reset, mute, Accept, Silence alarms and self test conforming to BS5839 standards and Duly approved by EN54/UN54/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Makes :(Makes: BOSCH FMR-1000-RCMD, Cerberus by Siemens ,Morley ZXRA , Edwards 3-LCD ANN)
Tele Net Marketing Pvt Ltd
Prime Computers
Insat Techno Services
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .