| Sl No | Description | Qty | Unit | Chicago Constructions International Pvt Ltd L2 | R K INFRA (INDIA) PVT LTD L1 |
|---|---|---|---|---|---|
| 1.00CIVIL WORKS Pile Foundation | |||||
| 1.01 | Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M -35 (Min Cement quantity -400kg/m3 and no payment shall be made for extra cement) of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.600 mm dia piles | 2,576.4 | Metre | 7,000 ₹1.8 Cr | 6,686 ₹1.7 Cr |
| 1.02 | Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M -35 (Min Cement quantity -400kg/m3 and no payment shall be made for extra cement) of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.700 mm dia piles | 6,741.9 | Metre | 8,450 ₹5.7 Cr | 9,099 ₹6.1 Cr |
| 1.03 | Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M -35 (Min Cement quantity -400kg/m3 and no payment shall be made for extra cement) of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete,including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.800 mm dia piles | 5,335.2 | Metre | 10,500 ₹5.6 Cr | 10,959 ₹5.8 Cr |
| 1.04 | Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge. Single pile 137 tonne capacity. Initial test (For 600mm dia) | 1 | Per test | 5,94,000 ₹5.9 L | 5,85,675 ₹5.9 L |
| 1.05 | Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile 137 tonne safe capacity. (Test Load 1.5 times the Safe capacity) Routine test(For 600mm dia Pile) | 1 | Per test | 3,61,680 ₹3.6 L | 3,36,609 ₹3.4 L |
| 1.06 | Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge. Single pile 188 tonne capacity. Initial test(For 700mm dia | 1 | Per test | 8,27,200 ₹8.3 L | 6,03,057 ₹6.0 L |
| 1.07 | Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile 188 tonne safe capacity. (Test Load 1.5 times the Safe capacity) Routine test(For 700mm dia Pile) | 2 | Per test | 4,96,320 ₹9.9 L | 3,69,533 ₹7.4 L |
| 1.08 | Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge. Single pile 251 tonne capacity. Initial test(For 800mm dia) | 1 | Per test | 11,04,400 ₹11.0 L | 8,05,145 ₹8.1 L |
| 1.09 | Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile 251 tonne safe capacity. (Test Load 1.5 times the Safe capacity) Routine test(For 800mm dia Pile) | 2 | Per test | 6,62,640 ₹13.3 L | 5,15,052 ₹10.3 L |
Updated dates
Tender Value
₹85.2 Cr
EMD Value
₹5 L
Closing Date
10 Apr 2026, 3:00 pmClosed
Managing Director, INKEL Limited
1st Floor, Ajiyal Complex, Post Office Road, Kakkanad, Cochin - 682030
Civil and MEP works
2026_INKEL_838217_1
NIT/INKEL/KIIFB/2025-26/171 dated 19/02/2026
Open Tender
Civil Works - Buildings
540 days
Taluk Head Quarters Hospital Pulinkunnu
As per Tender Document
21 documents required · 21 mandatory
₹17,700
₹5 L
Yes
INKEL Limited
30 Apr 2026
19 Feb 2026
13 Apr 2026
20 Feb 2026
10 Apr 2026
5 Mar 2026
26 Feb 2026
CIVIL WORKS Pile Foundation
Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M -35 (Min Cement quantity -400kg/m3 and no payment shall be made for extra cement) of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.600 mm dia piles
Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M -35 (Min Cement quantity -400kg/m3 and no payment shall be made for extra cement) of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.700 mm dia piles
Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M -35 (Min Cement quantity -400kg/m3 and no payment shall be made for extra cement) of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete,including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.800 mm dia piles
Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge. Single pile 137 tonne capacity. Initial test (For 600mm dia)
Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile 137 tonne safe capacity. (Test Load 1.5 times the Safe capacity) Routine test(For 600mm dia Pile)
Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge. Single pile 188 tonne capacity. Initial test(For 700mm dia
Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile 188 tonne safe capacity. (Test Load 1.5 times the Safe capacity) Routine test(For 700mm dia Pile)
Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge. Single pile 251 tonne capacity. Initial test(For 800mm dia)
Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile 251 tonne safe capacity. (Test Load 1.5 times the Safe capacity) Routine test(For 800mm dia Pile)
Coconut Pile
60.64.1 Coconut Pile - Supplying and stacking well matured straight coconut post for driving down throug various strata bellow bed level including cost coveyance labour charges etc complete.
Coconut Pile - Driving down coconut pile to lines and levels through variuos strata including all hire charges and labour for fixing , staging platform and all other appliances necessary for pile driving down after pointing the bottom end
60.64.6 Cutting and removing the excess length of wooden piles to lines and levels and removing the cut end of piles and stacking within 150m
Earth work
2.6.1 Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. All kinds of soil
2.8.1 Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
2.26.1 Extra for every additional lift of 1.5 m or part thereof in excavation /banking excavated or stacked materials. All kinds of soil
Extra rates for quantities of works, executed : In or under water and/or liquid mud, including pumping out metre water as required. For Foundation trenches and drains
Extra rates for quantities of works, executed : In or under water and/or liquid mud, including pumping out metre water as required.For Over area cutting
2.25 Filling available excavated earth ( excluding rock) in trenches, plinth sides of foundations etc in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead upto 50 m and lift upto 1.50 m
50.2.26.1 Filling with contractor own earth (excluding rock) in open areas in layers not exceeding 20 cm in depth,consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge
50.2.25.1 Filling with contractor's own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge"
2.10.1.3 Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the excavated soil. and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m: All kinds of soilPipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm"
Conveying and depositing of surplus earth beyond 50m and upto 1Km including loading and unloading as directed by Engineer- in-Charge.
Extra for conveying & depositing surplus earth every additional 1Km lead and part thereof
2.16.2 Close timbering in trenches including strutting, shoring and packing cavities (wherever required) complete (Measurements to be taken of the face area timbered).Depth exceeding 1.5 m but not exceeding 3 m
60.7.2 DR PACKING Under foundation - Dry stone packing under foundation with good quality blasted rubble including conveyance of material and labour charges etc. complete as per direction of departmental officers at site.
Plain Cement Concrete work
4.1.8 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
4.13 Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per square metre on damp proof course after cleaning the surface with brushes and finally with apiece of cloth lightly soaked in kerosene oil.
Providing and applying Anti-termite treatment by injecting chemical emulsion Imidacloprid 30.5%SC at a concentration 5 litres per sqm or as per manufacturers recommendation for preconstructional treatment and creating a chemical barrier as per IS 6313 (Part II) 2001 for wall trenches, foundation, top surface of plinth filling, foundation of wall and floor, along the external perimeter of the building, etc. complete conforming to manufacturers specification and as directed by the Engineer-in- Charge. (Plinth area only to be measured for the payment )
Reinforced cement concrete
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All work upto plinth level Concrete of M25 grade(Note :- Minimum Cement content is 330 kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All work upto plinth level Concrete of M35 grade (Note:- Min cement content is 370kg/cum and no payment shall be made for extra cement).
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note :- Minimum Cement content is 390 kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design .All work upto plinth level. Concrete of M40 grade with minimum cement content of 390 kg/cum
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. .All work above plinth level upto floor V level. Concrete of M25 grade (Note :- Minimum Cement content is 330 kg/cum and no payment shall be made forextra cement however contractor shall be bound to use required cement quantity as per the approved mix design)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. concrete.(Note :- Minimum Cement content is 350 kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design).All work above plinth level upto floor V levelConcrete of M30 grade with minimum cement content of 350 kg /cum
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. (Note :- Minimum Cement content is 350 kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design).All work up to plinth level Concrete of M30 grade with minimum cement content of 350 kg /cum
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. All work above plinth level upto floor V level Concrete of M35 grade (Note:- Min cement content is 370kg/cum and no payment shall be made for extra cement).
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. (Note :- Minimum Cement content is 390 kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design).All work above plinth level upto floor V level Concrete of M40 grade with minimum cement content of 390 kg /cum
5.38 Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each four floors or part thereof.
Providing and fixing at all levels precast cement concrete in slabs,kerbs, edgings etc. as per approved pattern and setting in position with cement mortar 1:3 (1 cement : 3 coarse sand), including the cost of required centering, shuttering complete.1:1.5:3 ( 1 cement : 1.5 coarse sand (Zone III): 3 graded stone aggregate 20mm nominal size)
5.9.1 Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.2 Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
5.9.3 Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
5.9.5 Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
5.9.6 Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
5.9.7 Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases)
5.9.19 Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges
5.9.13 Centering and shuttering including strutting, etc. and removal of form for:Vertical and horizontal fins individually for forming box louvers band, facias and eaves boards
5.9.16.1 Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and wallsUnder 20 cm wide
5.11.1 Extra additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentering at all levels, over a height of 3.5m, for every additional height of 1 metre or part thereof (Plan area to be measured).Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
Steel Reinforcement Work
5.22.6 Steel reinforcement for RCC Work including straightening, cutting, bending, placing in position and binding all complete up to plinth levels - Thermo - Mechanically Treated bars of grade Fe-500D or more
5.22A.6 Steel reinforcement for RCC Work including straightening, cutting, bending, placing in position and binding all complete above plinth level - Thermo - Mechanically Treated bars of grade Fe-500D or more
Block Work
50.6.1.4 Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand ) etc complete
50.6.1.5 Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete
50.6.1.6 Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor two level upto floor five level thickness 20cm and above in : CM 1:6 ( 1 cement : 6 coarse sand sand) etc complete
50.6.2.1 Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x15 cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 15cm in: CM 1:6 ( 1 cement :6 coarse sand) etc complete
50.6.2.2 Solid masonry using pre cast solid blocks (factory made) of size 30x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level with thickness 15cm in : CM 1:6 ( 1 cement : 6 coarse sand) etc complete
50.6.2.3 Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor two level upto floor five level with thickness 15cm in : CM 1:6 ( 1 cement : 6 coarse sand) etc complete
50.6.3.1 Solid block masonry using pre cast solid blocks ( Factory made) of size 40x20x10cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth for 10 cm thick wall in CM 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding etc complete
6.47 Providing and laying Autoclaved Aerated concrete (AAC) blocks masonry 150mm/230mm/300 mm thick with Grade- I AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately).
6.4.2 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in:Cement mortar 1:6 (1 cement : 6 coarse sand)
6.5 Extra for brick work/ AAC block masonry/Tile brick masonry in super structure above floor V level, for each four floors or part thereof by mechanical means
7.1.1 Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand)
60.7.1 DRY RUBBLE MASONRY _ Dry rubble without concrete levelling course masonry with good quality blasted rubble including packing to compactness to lines and levels cost and conveyance of all materials labour charges etc. complete as per direction of Departmental officers at site
13.33.1 Pointing on stone work with cement mortar 1:3 ( 1 cement : 3 fine sand):Flush/ Ruled pointing
Sub Head - Joinery works
21.1.1.2 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
21.1.2.2 For shutters of doors, windows & ventilators including providing and fixing hinges /pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade II Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With toughned glass of 6mm thickness
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer -in -Charge. ( Cost of aluminium snap beading shall be paid in basic item): With toughned glass panes of 4.0 mm thickness with U value>=5.7,VLT>=89% and SHGC<=0.85.
Providing and fixing Powder coated aluminium (minimum thickness of powder coating 50 micron) locking arrangement for sliding windows including necessary screws and fittings of approved make as directed by Engineer-in-charge.
Providing and fixing roller for shutters of sliding aluminium windows with necessary screws etc.complete. As approved by Engineer-in-charge
Providing and fixing pin headed glass in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): glass of 4.0 mm thickness
Providing and fixing roller for Aluminium sliding door
21.4.1 Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS: 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors including cost of cutting floors, embeding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer -in- Charge.With stainless steel cover plate minimum 1.25 mm thickness
9.84 Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete
9.121 Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of crosssection 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame
9.122.1 Providing and fixing to existing door frames.30 mm thick Glas Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS : 14856, including fixing to frames.
9.97.1 Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:300x10 mm
9.97.2 Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:250x10 mm
9.97.5 Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:100x10 mm
9.100.1 Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm
9.100.2 Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:100 mm
21.15.2 Providing and fixing aluminium casement windows fastener of required length for aluminium windows with necessary necessary screws etc. complete.Powder coated minimum thickness 50 micron aluminium
9.108.2 Providing and fixing PTMT Tower Bolts with 12 mm one piece rod inside and necessary screws etc., complete.202x42x18 mm weighing not less than 78 gms
9.106.2 Providing and fixing PTMT handles with necessary screws etc. complete.150x34x24 mm weighing not less than 26 gms
9.101.1 Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Single rubber stopper
9.101.2 Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper
Supplying and fixing 100mm mortice cylinder lock for aluminium door with following specification. a)Hook bolt has to be made of MS and SS for end plate and strike plate with lock set of size minimum 37mm, back set of min 20mm and hock bolt of min 18mm. b)Cylinder should be made of brass with minimum weight 0.20kg with nickel plated brass key(3 sets) and it should be of 5pin brass tumbler mechanism
50.9.15.2 Supplying and fixing 300 mm Aluminium aldrop
Providing and fixing in position frameless fixed glazing using 12mm toughened glass fitted with patch fittings of approved brand or manufacture as detailed in the drawing of specified size including supplying and fixing necessary hold fasts, screws for fixing cleats, toughened glass with all labour and materials complete as per drawings and as directed.
Frosted film - Supply and installation of 3M make frosted film pattern throughout all the internal glass panels wherever required of approx. 1.5 m height as per the approved pattern
600mmx1500mm Single shutter Fire rated Duct doors with vision glass and handle - Supply, installation, testing and commissioning of 600mmx1500mm shaft door having 2hr fire rating with 46mm thick Shutter and outer frame of size 100x57mm. Shutter should be manufactured from 0.8mm thick GI sheet sandwiching with Honey comb insulation material. The door frames are manufactured from 1.2mm thick GI sheet with Honey comb insulation material. The door frame and single leaf door should be finished with powder coating of 50micron approved shade.Vision Panel Active (VPW X VPH):200 mmX300 mm. Fire doors are inclusive of ball bearing SS hinges, mortice shaft lock and SS flush handle of size 120x40mm etc.as per the direction of Engineer -in charge.
600mmx1500mm Single shutter GI Powder coated Duct doors with vision glass and handle -Supply, installation, testing and commissioning of 600mmx1500mm shaft door with 46mm thick Shutter and outer frame of size 100x57mm. Shutter should be manufactured from 0.8mm thick GI sheet sandwiching with Honey comb insulation material. The door frames are manufactured from 1.2mm thick GI sheet with Honey comb insulation material. The door frame and single leaf door should be finished with powder coating of 50micron approved shade. Vision Panel Active (VPW X VPH):200 mmX300 mm. Fire doors are inclusive of ball bearing SS hinges, mortice shaft lock and SS flush handle of size 120x40mm etc.as per the direction of Engineer -in charge.
2000mmx2400mm double shutter GI Powder coated Doors with handle and vision glass :Providing and fixing of Hollow metal doors made of pressed galvanized steel confirming to IS 277 with the following specification. Doors shall be with vision glass and louver as a part of complete assembly.Door frame shall be single rebate profile of size 125 x 55mm made out of minimum 1.20mm (18gauge) thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with puff. Door leaf shall be 46mm thick fully flush double skin door, with or without vision lite. Door leaf shall be manufactured from minimum 0.8mm (22guage) thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be resin bonded honeycomb core. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable should be provided as per manufacturers recommendation with a clipon arrangement. The glass should be 5mm clear toughned glass of relavant rating of the door.All doors and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate shall include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule. Once frame installed should be filled with PUF as recomended by the manufacturer or engineer. 2000mmX2400mm
1500mmx2400mm double shutter GI Powder coated Doors with handle and vision glass:Providing and fixing of Hollow metal doors made of pressed galvanized steel confirming to IS 277 with the following specification. Doors shall be with vision glass and louver as a part of complete assembly.Door frame shall be single rebate profile of size 125 x 55mm made out of minimum 1.20mm (18gauge) thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with puff. Door leaf shall be 46mm thick fully flush double skin door, with or without vision lite. Door leaf shall be manufactured from minimum 0.8mm (22guage) thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be resin bonded honeycomb core. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable should be provided as per manufacturers recommendation with a clipon arrangement. The glass should be 5mm clear toughned glass of relavant rating of the door.All doors and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate shall include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule. Once frame installed should be filled with PUF as recomended by the manufacturer or engineer. 1500mmX2400mm
1200mmx2400mm Single shutter GI Powder coated Doors with handle and vision glass:Providing and fixing of Hollow metal doors made of pressed galvanized steel confirming to IS 277 with the following specification. Doors shall be with vision glass and louver as a part of complete assembly.Door frame shall be single rebate profile of size 125 x 55mm made out of minimum 1.20mm (18gauge) thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with puff. Door leaf shall be 46mm thick fully flush double skin door, with or without vision lite. Door leaf shall be manufactured from minimum 0.8mm (22guage) thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be resin bonded honeycomb core. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable should be provided as per manufacturers recommendation with a clipon arrangement. The glass should be 5mm clear toughned glass of relavant rating of the door.All doors and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate shall include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule. Once frame installed should be filled with PUF as recomended by the manufacturer or engineer. 1200mmX2400mm
1000mmx2100mm Single shutter Fire rated doors with out Panic bar ,vision glass & handle-Supply, installation, testing and commissioning of 2hr fire rated fire door of size 1000mmx2100mm with 46mm thick shutter manufactured from 1.2mm thick GI sheet sandwiching with Honey comb insulation material. The door frames manufactured from 1.6mm thick GI sheet pressed from single rebate profile of size 125mmx55mm and sandwiching with Honey comb insulation material. The door frame and double leaf door is finished with powder coating of 50 micron approved shade.Fire doors are inclusive of vision panel with 6mm thick 2hr fire rated glass of size 200mmx300mm, panic bar/latch (double point), external lever handle, surface door closer, dash fastener and other accessories required for the full functioning of the Fire rated Doors
1200mmx2100mm Single shutter Fire rated doors with vision glass and handle but with Panic bar-Supply, installation, testing and commissioning of 2hr fire rated fire door of size 1200mmx2100mm with 46mm thick shutter manufactured from 1.2mm thick GI sheet sandwiching with Honey comb insulation material. The door frames manufactured from 1.6mm thick GI sheet pressed from single rebate profile of size 125mmx55mm and sandwiching with Honey comb insulation material. The door frame and double leaf door is finished with powder coating of 50 micron approved shade.Fire doors are inclusive of vision panel with 6mm thick 2hr fire rated glass of size 200mmx300mm, external lever handle, surface door closer, dash fastener and other accessories required for the full functioning of the Fire rated Doors.
1800mmx2400mm Double shutter Fire rated doors without Panic bar ,vision glass & handle-Supply, installation, testing and commissioning of 2hr fire rated fire door of size 1800mmx2400mm with 46mm thick shutter manufactured from 1.2mm thick GI sheet sandwiching with Honey comb insulation material. The door frames manufactured from 1.6mm thick GI sheet pressed from single rebate profile of size 125mmx55mm and sandwiching with Honey comb insulation material. The door frame and double leaf door is finished with powder coating of 50 micron approved shade.Fire doors are inclusive of vision panel with 6mm thick 2hr fire rated glass of size 200mmx300mm, panic bar/latch (double point), external lever handle, surface door closer, dash fastener and other accessories required for the full functioning of the Fire rated Doors
Steel Work
9.48.2 Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc
13.52.1 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.On steel work
Providing and fixing 1 mm thick M.S. sheet door with shutter frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings with outer frame of size 50x50x6 mm complete, including applying a priming coat of approved steel primer.Using M.S. angels 40x40x6 mm for diagonal braces
10.6.2 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.80x1.20 mm M.S. laths with 1.20 mm thick top cover
10.7 Providing and fixing ball bearing for rolling shutters.
10.9 Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by Engineer -in-Charges, (area of grill to be measured).
10.8.1 Extra for providing mechanical device chain and crank operation for operating rolling shuttersExceeding 10.00 sqm and upto 16.80 sqm in the area
10.25.1 Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In stringers, treads,landings etc. of stair cases, including use of chequered plate wherever required, all complete
10.25.2 Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
10.28 Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
10.26.1 Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approves steel primer.M.S. tube
10.16.3 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Electric resistance or induction butt welded tubes
Structural Glazing
25.1 Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. ( The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account).The weight of aluminum extruded section shall be taken for purpose of payment
25.2 Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including: (a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: (b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. (c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment, including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. (d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. (e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub- head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves) on the external face shall be measured in sqm. up to two decimal places. Note:-2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately.The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NABL accredited lab or any other accreditation body which operates in accordance with ISO/ IEC 17011 and accredits labs as per ISO/IEC 17025 1. Performance Laboratory Test for Air Leakage Test (-50pa to - 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr 2. Static Water Penetration Test. (50pa to 1500pa) as per ASTME- 331-09 testing method for a range up to 2000 ml. 3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing method for a range upto 2000 ml 4. Structural Performance Deflection and deformation by static air pressure test (1.5 times design wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm 5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing method for Qualitative test, Tests to be conducted on site. 6. Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml
Providing and supplying 6 mm thick monolithic toughened glass for structural glazing (Single glazing) of approved colour and shade with VLT>=36% and SHGC<=0.43 and U value 5.5 (including structural silicone sealant) etc., all complete for the required performance as specified, as per the architectural drawings, as per the approved shop drawings, as specified, and as directed by the Engineer- in - Charge. For payment, only the actual area of glass shall be measured in sqm
Supply & Installation aluminium louvers of Hindalco section 85191 or equivalent. The Fins should be fixed at 200mm module based on the requirement to the suitable Installation frame of aluminium(Powder coated aluminium minimum thickness of powder coating 50 micron) extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings .The maximum length of the fin shall be determined based on the wind load calculation and deflection.
Flooring & Waterproofing works
4.2.5 Providing and laying cement concrete in retaining walls, return walls, walls ( any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts,buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor, etc.Excluding the cost of centering, shuttering and finishing:1:3:6 ( 1 cement : 3 coarse sand :6 graded stone aggregate 20 mm nominal size).
22.23.1 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerincharge. The product performance shall carry guarantee for 10 years against any leakage.For vertical surface two coats @0.70 kg per sqm
22.23.2 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerincharge. The product performance shall carry guarantee for 10 years against any leakage.For horizontal surface one coat @1.10 kg per sqm.
22.5 Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
Grading roof for water proofing treatment with: 12mm thick plastering in cement mortar 1:4 ( 1 cement : 4 coarse sand ) and mixing with water proofing material in proportion recommended by the manufacturers
12.63 Providing and applying two coats of High Albedo paint having minimum Solar Reflective Index (SRI) 108 (with solar reflectance & thermal emittnce tested as per ASTM) C 1549 and ASTM C 1371 respectively), VOC less than 10 cc/gm. The coating thickness and the methodology of application shall strictly as per manufacture's specifications and as approved by engineer in charge. Surface preparation includes cleaning with metal wire brush to remove all dust, fungus etc., washing with water all complete. The contractor shall give guarantee for the performance of SRI and also the durability of coating, all complete as per direction of Engineer - in- charge.
Waterproof Coating & Protection to the waterproofing system for Terrace Area:: Providing and applying two component, cold applied, high strength, fast-curing, hybrid urethane waterproof coating to the concrete surface must be brought into SSD condition, apply the first coat at a rate of 0.90 kg/m² without dilution, using a lamb?s wool roller while the coating is still wet, roll and embed a 225 gsm Fiberglass Chopped Strand Mat, ensuring full bonding without air bubbles or wrinkles. Overlap the chopped strand mat by at least 5cm at the joints. apply the second coat at 0.90 kg/m², to achieve a total dry film thickness of 1100 microns, with material consumption of 1.80 kg/m². Allow each coat to air cure for a minimum of 3-4 hours after application. All coats should be applied in directions perpendicular to each other, allow the system to air cure for 5-7 days minimum. The material has followed technical properties: Attains a Tensile Strength with Fiber ?15N/mm2 as per ASTM D 2370, Tear Strength ? 100 N/mm as per ASTM D 624, Dynamic Crack bridging as per EN 13251:2016 - No Cracks after 20000 sinusoidal cycles, Dynamic Crack bridging as per ASTM C 1305- 2016 - Pass, No Crack, Elongation at break ? 200% as per ASTM D 2370. Waterproofing coating shall be applied on the entire horizontal surface extending upto 300mm on the vertical surface as per the manufacturer methodology. All waterproofing work suggested above shall be carried out by the in house application wing of the manufactuer or skilled waterproofing contractor under the guidance of a technical expert from the manufacturer. The finished cost to include surface preparation, carry out mechanical grinding to achieve CSP 4-CSP 5 profile, making coving at Junction, treatment of cracks completely as per specification. Supplying and laying 150GSM Geo-textile as seperation/protective layer over the fully cured entire membrane with 50mm overlap and spot bonding with Fevicol SR998.
11.41.2 Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.
Providing and laying anti skid vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600 x 600mm.
11.3.1 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate)finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete.40 mm thick with 20 mm nominal size stone aggregate
Providing and laying C.C pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator, vacuum dewatering process and finally finished by floating brooming with wire brush, including panelling with 4mm glass strip for the entire depth of flooring etc. complete as per specifications and directions of Engineer-in-charge (Note :- Minimum Cement content is 330 kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design)
Providing and applying 2mm epoxy screed on concrete floors after the surface preparation & application of epoxy priming coat including application of epoxy self levelling floor topping over the cured epoxy screed. The surface preparation shall include dry grinding of existing concrete surface of floor with diamond wheel grinder followed by cleaning with wire brushing etc . A coat of low viscous epoxy primer 200 microns shall be applied over prepared surface by using brush/roller sufficiently covering the prepared surface. The screed shall be laid with the help of serrated trowels and spike rollers to ensure uniform level and no air entrapment. Epoxy floor topping shall be solvent free, resin rich ,non toxic, self levelling , pure liquid epoxy poly urethane resin flooring compound which shall be spread over the cured epoxy screed by serrated trowels/spiked rollers .The cost shall include materials & labours including treatment of construction joint filling etc complete as per the direction of engineer in charge.
Providing and laying Vitrified step tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. (ONLY FOR STAIR TILE)
11.55.1 Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge :Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
8.3.2 Providing edge moulding to 18 mm thick marble stone counters, vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer -in-Charge.Granite work
8.2.2.2 Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Area of slab over 0.50 sqm
11.20.2 Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete on 20 mm thick bed of cement mortar 1:4 ( 1 cement : 4 coarse sand).Medium shade pigment using 50% white cement 50 % Grey cement
11.48.2 Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg). including filling /grouting and finishing complete as per direction of Engineer-in-charge.Size of Tile 600x600 mm
8.31 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in- Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in dadoing over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), fixing with cement based high polymer modified quick-set tile adhesive (Water based) conforming to IS: 15477, joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling /grouting and finishing complete as per direction of Engineer-in charge. Size of Tile 600x600 mm
11.46.2 Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm
Providing and fixing machine cut, mirror/ eggshell polished, Granite stone work for wall lining (veneer work) including dado, skirting, risers of steps, etc., in required design and pattern wherever require, stones of different finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1cement : 3 coarse sand) laid and fixing with chemical adhesive, including pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing, polishing etc. all complete as per Architectural drawings, and as directed by the Engineer-in-charge. A. 18mm thick Granite of any colour and shade
Extra for using or fixing glazed/ Ceramic/ Vitrified wall tiles with cement based high polymer modified quick-set tile adhesive ( Water based) conforming to IS : 15477, in average 3 mm thickness
False Ceiling Works
12.52.1 Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all Tsections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending
GI PERFORATED FALSE CEILING WORK:Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge.GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece.
Aluminium Non perforated false ceiling - Providing & Fixing true horizontal level swing down suspended ceiling comprising of approved make Aluminium Clip in Swing Down with double pip self levelling feature and special tabs to allow swing down of tile to enable plenum access with plain visual consisting of 600X600 mm clip in plain tiles of 0.7mm uniform thickness Aluminium with bevel edge in approved colour precoated with primer coat at the rear side with Light Reflectance > 60%.Tiles should have fire performance of Class A2-s1.d0 as per EN13501.The grade of aluminium shall mandatorily be AA 3003. The AluminiumTile shall mandatorily be RoHS Compliant (Resistance of Hazardous Substance).Compliant certificate shall be provided on demand.The tile shall maintain uniform Thickness of 0.7mm across all areas of tiles with no deviation. The tile shall have paint thickness of 25microns to enable better scratch resistance.The tile shall have the ability to combine the main light with extra illumination providing 77% light reflectance & enables to achieve light uniformity. The tile shall have g Ceiling Attenuation Class of 44db. It shall withstands upto 150 Scrub cycle using Scrubablity tester as per ASTM D 2486. The tile shall offer superior wash performance without compromising panel finish integrity using a washablity tester as per ASTM D 4828. Installation: To comprise 3000mm long ‘C’ channels spaced at 1200mm centers securely fixed to the structural soffit by support clamp & approved hangers.The last hanger at the end of each C channel should not be greater than 600mm from the adjacent wall. Use a C-channel connector for splicing two pieces of C-channels. 4000mm spring tee bars shall be spaced at 600mm centers in a direction perpendicular to the C-channels and shall be secured at every intersection with C channel using a tee bar hanger. Use T bar connector to splice two pieces of spring tee bars. Tiles should be clipped in between two spring tee bars from below. This is a downward installation. All full panels can be removed and reinstalled without movement up into the plenum area. Perimeter trims of approved color secured to walls at 450mm maximum centers. Cut tiles to be secured to the wall angles using a spring clamp. The installation shall be undertaken as per the manufacturer’s installation instructions and as directed by the Engineer-in-Charge.
12.45.3 Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board
Finishing Work
5.23 Smooth finishing of the exposed surface of RCC work with 6mm thick cement mortar 1:3 ( cement : 3 fine sand).
13.1.1 12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
13.7.2 12 mm cement plaster finished with a floating coat of neat cement of mix:1:4 ( 1 cement : 4 fine sand)
13.22 Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
13.5.1 15 mm cement plaster on rough side of single or half brick wall of mix:1:4 ( 1 Cement : 4 coarse sand)
13.43.1 Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
Wall painting with acrylic emulsion paint(low VOC paint as per Griha norms V- 2015) of approved brand and manufacture to give an even shade: Two or more coats on new work
Finishing walls with Acrylic Smooth exterior paint (low VOC paint as per Griha norms V- 2015) of required shade:New work (Two or more coat applied @ 1.67 litre/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
Finishing walls with textured exterior paint (low VOC paint as per Griha norms V- 2015) of required shade:New work (Two or more coats applied @ 3.28 ltr/ 10 sqm) over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm
13.80 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturr, over the plastered wall surface to prepare the surface even and smooth complete
Roofing Work
12.50 Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
160mm uPVC for Rain Water Gutter with Leaf Guard - Supply, Installation, Testing and commissioning of 160mm uPVC Rain water gutter with Leaf Guard for Truss roof, including different types of fittings, required clamps and accessories. Gutters and fittings are specially designed to meet the requirements of all types of sloped roofs buildings. The system is provided with specially designed rubber gasket/seals to give totally leak proof joints to install with brackets and clamp complete
12.51.1 Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screwscomplete :Ridges plain (500-600 mm)
Supply, Fixing & installation of approved Polycarbonate Sheet of 3mm Thick SOLID/ COMPACT and UV Protection on bothsides with necessary screws, Flashings and C channels at all height complete as per the direction and approval of site in charge. It should have 1.2g/cm3 density,Heat deflection of 130 C, 0.21W/mK Thermal conductivity , Tensile strength at yield and breaking are 65 Mpa(10mm/Min) and 60Mpa(1mm/min).
External Works
2.31 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared
19.35.1 Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete.450 mm dia RCC pipes
19.35.2 Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete.600 mm dia RCC pipes.
2.33.1 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 30 cm girth up to and including 60 cm girth
2.33.2 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 60 cm girth up to and including 120 cm girth
16.78.2 Construction of granular sub- base by Providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, Carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in- Charge.With material conforming to Grade-II (size range 53 mm to 0.075 mm ) having CBR Value-25
16.91.1 Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.60mm thick cement concrete paver block of M-35 grade with approved colour, design & pattern.
16.91.2 Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.80 mm thick C.C. paver block of M-30 grade with approved color design and pattern.
16.69 Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature jointed with cement mortar 1:3 ( 1 cement : 3 coarse sand) , including making joints with or without grooves ( thickness of joints except at sharp curve shall not to more than 5 mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge ( length of finished kerb edging shall be measured for payment ). ( Precast C.C. kerb stone shall be approved by Engineer-in-Charge)
16.70.2 Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts , bolts and washers as required complete as per the direction of Engineer-in- charge.Made of G.I wire of dia 4 mm. PVC coated to achieve outer dia. not less than 5 mm in required colour and shade
19.17.1 Replacement of M.S. foot rests in manholes including dismantling concrete blocks and fixing with 20x20x10 cm cement concrete blocks 1:3:6 ( 1 cement : 3 coarse sand: 6 graded stone aggregate 20 mm nominal size):With 20x 20 mm square bar
Road Work
11.9 Planting of trees by the road side (Avenue trees) in 0.60 m dia holes, 1 m deep dug in the ground, mixing the soil with decayed farm yard/sludge manure, planting the saplings, backfilling the trench, watering, fixing the tree guard and maintaining the plants for one year
2.5.1.B Dismantling of flexible pavements and disposal of dismantled materials up to a lead of 1000 metres, stacking serviceable and unserviceable materials separately <br> Granular courses - By Manual Means
Clearing and grubbing land including uprooting rank vegetation, grass, bushes, shrubs, saplings and trees girth up to 300 mm, removal of stumps of trees cut earlier and disposal of unserviceable materials and stacking of serviceable material to be used or auctioned, up to a lead of 1000 metres including removal and preservation of top organic soil not exceeding 200 mm in thickness In area of thorny jungle - By Mechanical Means
Dismantling Work
15.3 Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge.
15.60 Disposal of building rubbish/ malba/ similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved
15.7.4 Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar
15.43.2 Dismantling manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer -in-Charge:Bituminous road
Relaying the excavated GSB in Specified Thickness in all lift and leads spreading in uniform layers of specified thickness and compacting with plate vibrator to achieve the desired density, complete as per specifications and directions of Engineer-in- Charge.
ROAD WORK Pavement
4.1.A.1 Construction of granular sub-base by providing graded Material, mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with a motor grader on the prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401 Grading-I - Plant Mix Method
4.1.A.2 Construction of granular sub-base by providing graded Material, mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with a motor grader on the prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401 Grading-II - Plant Mix Method
4.12 Providing, laying, spreading and compacting graded stone aggregate to Wet Mix Macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub- base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density.
12.8.B.1 Plain/Reinforced Cement Concrete in Open Foundation complete as per Drawing and Technical Specifications & PCC Grade M20
Paver
55.22 Supplying and laying interlocking tile 100 mm or nearest size thickness, minimum strength M 40 including providing a layer of 6 mm aggregate for 5 cm thickness, then laying interlock cobbles in lines and levels as per the directions of the departmental officers at site inclusive of all cost & conveyance charges etc.; complete
Pavement
3.6 Excavation for roadwork in soil with hydraulic excavator of 0.9 cum bucket capacity including cutting and loading in tippers, trimming bottom and side slopes, in accordance with requirements of lines, grades and cross sections, and transporting to the embankment location within all lifts and lead upto 1000m
3.16 Construction of embankment with approved material obtained from borrow pits with all lifts and leads, transporting to site, spreading, grading to required slope and compacting to meet requirement of table 300-2.
3.18 Construction of sub-grade and earthen shoulders with approved material obtained from borrow pits with all lifts & leads, transporting to site, spreading, grading to required slope and compacted to meet requirement of table No. 300-2
Earth works -1
2.2.2.A Clearing and Grubbing Road Land & Clearing and grubbing road land including uprooting wild vegetation, grass, bushes, shrubs, saplings and trees of girth upto 300 mm, removal of stumps of such trees cut earlier and disposal of unserviceable materials and stacking of serviceable material to be used or auctioned, upto a lead of 1000 m including removal and disposal of top organic soil not exceeding 150 mm in thickness as per Technical Specification Clause 201. (II) By Mechanical Means (A) In area of non-thorny jungle
Road Furniture
8.4.3 Providing and fixing of retro- reflectorised cautionary, mandatory and informatory sign with 7years warranty manufactured as per IRC :67 made of Type IV micro prismatic grade sheeting vide clause 801.3.3 fixed over aluminium sheeting, 2 mm thick/ aluminium composit material sheeting 4 mm thick with suitable back supporting frame of MS angle 25x25x3 and supported on GI pipe pole 50mm NB confirming to IS 1239 firmly fixed to the ground by means of properly designed foundation with M 15 grade cement concrete min size 45 cm x 45 cm x 60 cm, 60 cm below ground level including painting all exposed surface with 2 coats of epoxy painting over epoxy primer and as per approved drawing and clause 801 including lettering symbols etc.& 60 cm circular
8.4.4 Providing and fixing of retro- reflectorised cautionary, mandatory and informatory sign with 7years warranty manufactured as per IRC :67 made of Type IV micro prismatic grade sheeting vide clause 801.3.3 fixed over aluminium sheeting, 2 mm thick/ aluminium composit material sheeting 4 mm thick with suitable back supporting frame of MS angle 25x25x3 and supported on GI pipe pole 50mm NB confirming to IS 1239 firmly fixed to the ground by means of properly designed foundation with M 15 grade cement concrete min size 45 cm x 45 cm x 60 cm, 60 cm below ground level including painting all exposed surface with 2 coats of epoxy painting over epoxy primer and as per approved drawing and clause 801 including lettering symbols etc. 80 mm x 60 mm rectangular
8.15 Supplying and installation of delineator (Roadway indicators) posts 80- 100cm high above ground level, pained black, and white in 15 cm wide strips, fitted with min. 80 x 100 mm rectangular or 75 mm dia circular retro reflectorized panels at the top with minimum visibility of 300m with provisions to prevent edge lifting and vandalisam, and conforming to clause 806 , IRC-79 and the drawings including fixing to ground (The deleniator shall be of approved type as per specification)
8.35 Providing and fixing reflective road studs (Raised Pavement Marker) of ' category A' made out of ASA/HIPS/ABS moulded body with shanks and conforming to ASTM D 4280, strong enough to support a load of more than 13.635 T when tested in accordance with ASTM D 4280, reflective panel confirming to ASTM D 788, and reflectivity conforming to clause 804.4. including installation, drilling, fixing with adhesive etc. with 2 years warranty for the road stud as well as for in field performance as per clause 804.7.3 Road Markers/Road Stud with Lense Reflector :-
Culvertes
Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-30 (Cement quantity -400kg/m3) of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap).600 mm dia piles.
2.6.1 Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.All kinds of soil
2.25 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
4.1.8 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. (Note :- Minimum Cement content is 350 kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design).All work upto plinth level. Concrete of M30 grade. with minimum cement content of 350 kg /cum.
5.22.6 Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
2.17.1 Close timbering in case of shafts, wells, cesspits, manholes and the like including strutting, shoring and packing cavities (wherever required) etc. complete (Measurements to be taken of the face area timbered).Depth not exceeding 1.5 m
5.9.1 Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.2 Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
5.9.3 Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
Service trench
4.1.8 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. (Note :- Minimum Cement content is 330 kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design).All work up to plinth level. Concrete of M25 grade with minimum cement content of 330 kg /cum
Providing and fixing at or near ground level precast cement concrete in kerbs, slab, edgings etc. as per approved pattern and setting in position with cement mortar 1:3 (1 cement : 3 coarse sand), including the cost of required centering, shuttering complete. 1:1.5:3 ( 1 cement : 1.5 coarse sand (Zone III): 3 graded stone aggregate 20 mm nominal size)
5.22.6 Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
5.9.1 Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.2 Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc
PUBLIC HEALTH ENGINEERING SANITARY FIXTURES, BATH FITTINGS AND ACCESSORIES
Providing and fixing White Vitreous China Floor Mounted EWC, Complete Set with 3/6 LPF (Adjusting up to 2/4 LPF) Dual Cistern, Overall size as per approved model and shape, including Cistern Fittings, Soft Close Seat Cover, bolts, nuts, washers, expansion / rawl sleeves, gasket etc. complete, and fixing to wall, as per manufacturers instruction and to the approval of Engineer-in-charge. The Float Valve for Cistern shall be capable of withstand 3.0 Bar. Working Pressure
Providing and fixing sanitary fixtures for handicapped toilet including one number White Vitreous China Extended Wall Mounted EWC, Complete Set with 3/6 LPF (Adjusting up to 2/4 LPF) Dual Cistern, overall size 660 x 375 x 760mm. or as per approved model and shape,including Cistern Fittings, Soft Close Seat Cover, bolts, nuts, washers, expansion / rawl sleeves, gasket etc.complete, wash basin, one pair mounting brackets, one number elbow operated pillar cock 3.8 LPM @ 3 Bar and all other related fittings like waste coupling one number hinged rail 76 cm and 4 nos. of grab rails 60cm etc., designed for people with special needs comes with as per manufactures specification including cutting and making good the walls and floors wherever required as per drawing and as directed by Engineer in charge
17.1.1 Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm Sand Cast Iron P or S trap, 10 litter low level white P.V.C.flushing cistern, including flush pipe, manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever require:White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests
Providing and fixing White Virtuous China Urinal, of approved shape and size, with Integral P-Trap and with Integrated Electronic Flushing System with Passive and Extra Sensitive Infra-Red Sensor (Battery/AC Operated, as per final requirement), overall size: 610 x 390 x 370mm, with a Total Flushing Rate of 0.75 LPF, having pre and post flushing with water, (250 ml and 500 ml respectively),and with water inlet from back side including fixing at wall with suitable Brackets, all as per manufacturers instruction and direction of Engineer-in-charge
8.10.2 Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in Charge and finished smooth.Granite Stone of approved shade
Providing and fixing White Vitreous China Counter Top / Bottom Wash Basin, 400 x 550 mm or equal, compatible for a washing rate of 6 LPM or less, including 32mm. CP Waste Coupling, C.P.Brass Chain with rubber plug, and fixing to counter with suitable fixtures, all as per manufacturers instruction and the direction of Engineer-incharge.
17.7.4 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap
Providing and fixing wash basin with C.I. brackets, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Angle back wash basin size 400x400 mm
Providing and fixing 15mm. CP Pillar Tap, Self Closing Type with Pre Set time 5 to 6 Sec, with a controlled flow rate of 6 LPM at 3 Bar.(overall dimensions:110 x 120 /150mm. or equal ), complete with all necessary accessories for Domestic Wash Basins, all as per manufacturer’s instructions and to the approval of the Engineer-in-charge.
Providing and fixing CP Surgical Purpose Elbow Action Pillar Tap with extended lever handle, flow rate of 6 LPM at 3 Bar, complete with all necessary accessories for Wash Basins in Doctors /Treatment Rooms, all as per manufacturers instructions and to the approval of the Engineer-in-charge
Providing and fixing of Black colour Poly Propylene Laboratory Sink, Dimensions: external 558 x 355 x 240mm, Net weight: 2.7 kg, Temperature range: 0-80°C, 1/2” BSP Waste connection, Net weight: 0.2 kg Dimensions: Ø73, 1½” BSP with PTMT/PP waste coupling, adjustable screw on nut. including cutting and making good the walls wherever required: Polypropylene Laboratory Sink without drain board
17.10.2.2 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required: Kitchen sink without drain board610x460 mm bowl depth 200 mm
Providing and fixing CP Surgical Purpose Elbow Action, Wall Mounted type, Clinical Sink Mixer with extended lever handle, flow rate of 3.8 LPM @ 3 Bar, complete with Wall Flanges and all necessary accessories, all as per manufacturers instructions and to the approval of the Engineer-in-charge.
Providing and fixing CP Shower Set, for Cold Water only, low flow rate of 6 LPM or less,Commercial Range, complete with Concealed Valve Exposed Control Unit, Head Shower, Shower Arm, etc., including all necessary accessories, all as per manufacturers instructions and to the approval of the Engineer-in-charge
Providing and fixing CP Long Body Tap, both Cold and Hot Water Supply, with a controlled flow rate of 6 LPM @ 3 Bar, 15mm. nominal bore, 185mm. long with wall flanges and all other necessary accessories, all as per manufacturers instructions and to the approval of the Engineer-in-charge
Providing and fixing Health Faucet with a controlled flow rate of 3.8 LPM @ 3Bar, 15mm.CP Braided Hose of length 1.2m, Hook and all other necessary accessories, all as per manufacturers instructions and to the approval of the Engineer-in-charge.
18.53.1 Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 893115 mm nominal bore
18.21.2.1 Providing and fixing uplasticised PVC connection pipe with brass unions:45 cm length15 mm nominal bore
50.17.1.3 Supplying and fixing CP Towel rod 60cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in charge.
17.72 Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms
50.17.1.1 Supplying and fixing Stainless steel soap dish including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
17.34.1 Providing and fixing toilet paper holder:C.P. brass
Providing and Fixing ABS Body P-Trap with threaded union connections, flanges and all other necessary accessories, all as per manufacturers instructions and to the approval of the Engineer-in-charge. For Wash Basin, 32mm, Size
Providing and Fixing ABS Body P-Trap with threaded union connections, flanges and all other necessary accessories, all as per manufacturers instructions and to the approval of the Engineering- charge. For Clinical Sinks and Scrub, 40mm, Size
Providing and fixing of C. P. Robe Hook, 60mm. Dia. x 45mm. High
17.31 Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
17.71 Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms
Providing and fixing cooler (hot, cold and normal water) with inbuild RO filter including cost and conveyance of all materials labour charges etc. complete, including necessary wall cutting /chasing and making good as required etc. complete, testing and commissioning to the satisfaction of Engineer in Charge as per direction of Engineer-In charge at all levels. Flow Rate - 125 Ltrs / Hr, Processing Tank Capacity - 17 Ltrs, Storage tank Capacity / Ltrs (Normal, Hot &Cold) - 40 Ltrs Normal, 4 Ltrs Hot &40 Ltrs Cold.
Providing and fixing of Slop Hopper with Pressing valve 304G Stainless Steel,Conical flushing bowl with continues flushing rim having whirl effect, P / S trap for drainage, Health faucet Dimension : 24 inch L x 24 inch W x 35 inch H
INTERNAL DRAINAGE
Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type B (IS:13592) including fixing the pipe with clamps/clips at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent & clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site (For Soil & Waste pipes -Internal). 110mm OD
Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type B (IS:13592) including fixing the pipe with clamps/clips at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site (For Soil & Waste pipes -Internal).75mm OD
50.18.8.6.2 Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 50 mm pipe 6 kgf/cm2
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes and fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge.63 mm dia 4 Kgf/cm2 Internal work - Exposed on wall
50.18.7.6.2 Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing . This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 6 Kgf/cm2 - Internal work- Exposed on wall
Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type A (IS:13592) including fixing the pipe with clamps/clips at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site(For Vent pipes -Internal).75mm OD
Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type B(IS:13592) including fixing the pipe with clamps/clips at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent and clamping with Position,including cutting and making good the walls and floors as required at site (For Vertical &; Horizontal Shaft piping).Core Cutting in RCC Structure shall measured separately. Clamping details - For Vertical Shafts G.I. "U"bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2" STD Powder Coated Clamping details - For Suspended lines G.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm),nuts, washers etc complete.160mm OD
Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type B(IS:13592) including fixing the pipe with clamps/clips at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical &; Horizontal Shaft piping).Core Cutting in RCC Structure shall measure separately. Clamping details - For Vertical Shafts G.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2" STD Powder Coated Clamping details - For Suspended lines G.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.110mm OD
Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type B(IS:13592) including fixing the pipe with clamps/clips at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent and clamping with Position,including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping). Core Cutting in RCC Structure shall measured separately.Clamping details - For Vertical Shafts G.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated Clamping details - For Suspended lines G.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete. 75mm OD
Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type A(IS:13592) including fixing the pipe with clamps/clips at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical &; Horizontal Shaft piping for rainwater/Vent).Clamping details - For Vertical Shafts G.I."U" bolts (8 mm thick) on G.I. slotted rails (1.6 /2.5 mm thick) , Rail Leg 2 1/2" STD Powder Coated, Clamping details - For Suspended lines G.I. "U" bolts (8mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.75mm OD
Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe of 4kg/cm2 (IS:4985)) including fixing the pipe with clamps/clips at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping for rainwater/Vent).Clamping details - For Vertical Shafts G.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2" STD Powder Coated Clamping details - For Suspended lines G.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners (10mm), Threaded Rod (10mm), nuts, washers etc complete. 63mm OD (4kg/cm2)
50.18.9.20.1 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63 mm dia Elbow
50.18.9.20.2 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -63 dia 45 degree Elbow
50.18.9.20.4 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63 mm dia Bend
Providing and fixing PVC moulded fitting / accessories for Rigid PVC pipes, including jointing with PVC solvent cement-63 mm dia Y
50.18.9.20.7 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63 mm dia vent cowl
50.18.9.20.8 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 63 mm dia End cap
50.18.9.20.9 Providing and fixing PVC moulded fitting / accessories for Rigid PVC pipes, including jointing with PVC solvent cement-63 mm dia Socket /coupling
50.18.9.21 Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Elbow
50.18.9.21.2 Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia 45 degree Elbow
50.18.9.21.3 Providing and fixing PVC moulded fittings / accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia Door Elbow
50.18.9.21.4 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Bend
50.18.9.21.7 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Vent cowl
Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75mm dia Y
50.18.9.21.9 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Socket /coupling
50.18.9.22.1 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia Elbow
50.18.9.22.11 Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes,including jointing with PVC solvent cement - 110 mm dia Socket/ coupling
50.18.9.22.2 Providing and fixing PVC moulded fittings / accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia 45 degree Elbow
50.18.9.22.3 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement-110 mm dia Door Elbow
Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes,including jointing with PVC solvent cement - 110 mm dia Y
50.18.9.22.4 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement- 110 mm dia Bend
50.18.9.22.8 Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes,including jointing with PVC solvent cement -110 mm dia Vent cowl
Deep Seal uPVC fabricated Multi floor trap - Providing, Fixing, testing and commissioning at site in position Deep Seal (7") uPVC Fabricated Multi Floor Trap, with suitable supporting on GI slotted rails (1.6mmthick) full threaded rod, Anchor fasteners etc. complete in all respects - 50/75 mm dia inlet/outlet (In Ceiling)
uPVC fabricated Multi floor trap - Providing, Fixing, testing and commissioning at site in position uPVC Fabricated Multi Floor Trap, with thrust block support including complete cost of cutting chases and making good the walls in all respects - 50/75 mm dia inlet/outlet (In Sunken)
Supplying, installing, testing & commissioning at site in position 110mm dia deep seal PVC P Trap with boss tee and access cap including all necessary fittings and supports complete
Providing and Fixing C.P. brass or stainless steel(SS-304) Square Flat cut single piece Gratings size 125x125 mm. Gratings for 110mm. Floor Traps.
Heavyduty stainless steel cover for Concealed Floor Trap for Urinal - Providing and Fixing 125x125mm dia Heavyduty stainless steel cover for Concealed Floor Trap ISI 304 Cover, for Urinal.
Heavy duty stainless steel cleanout cover - Providing and Fixing Heavy Duty Stainless Steel A ISI 304 Clean out Cover, sealed, threaded covers, including suitable keys for opening, if required. -For 110mm
Heavy duty stainless steel cleanout cover - Providing and Fixing Heavy Duty Stainless Steel A ISI 304 Clean out Cover, sealed, threaded covers, including suitable keys for opening, if required. -For 75mm
17.35.1.3 Providing and fixing soil, waste and vent pipes: 100 mm dia Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
17.38.1.3 Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. 100 mm dia Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
17.42.1.3 Providing and fixing double equal plain junction of required degree. 100x100x100x100 mm Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
17.44.1.3 Providing and fixing single equal plain junction of required degree: 100x100x100 mmHubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
17.49.1.3 Providing and fixing double equal plain invert branch of required degree: 100x100x100x100 mmHubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
17.50.1.3 Providing and fixing single equal plain invert branch of required degree: 100x100x100 mmHubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
17.56.1.3 Providing and fixing terminal guard: 100 mm Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
17.60.1.3 Providing and fixing trap of self cleansing design with screwed down or hinged grating without vent arm complete, including cost of cutting and making good the walls and floors: 100 mm inlet and 100 mm outletHubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
17.57A.1.1 Providing and fixing shielded coupling for Hubless centrifugally cast iron pipeSS 304 grade coupling with EPDM rubber gasket
Supply, fix at site in position, Rain Khurra (Rain Water Outlet) Dome Type with Cast Iron body, Aluminium Ring, Aluminium Dome, S.S. Screws etc. complete with Gratings, suitable for 110mm.of down pipes.100mm dia. for 110mm. PVC Down Pipe
Supply, fix at site in position, Rain Khurra (Rain Water Outlet) Side Wall Parapet Type in Cast Iron body, Aluminium Gratings, S.S. Screws etc. complete with Gratings, all as per Technical Specifications. 100mm dia. for 110mm. PVC Down Pipe
Supply, fix at site in position, Rain Khurra (Rain Water Outlet) Side Wall Parapet Type in Cast Iron body, Aluminium Gratings, S.S. Screws etc. complete with Gratings, all as per Technical Specifications.150mm dia. for 160mm. PVC Down Pipe
WATER SUPPLY
18.8.1 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.15 mm nominal dia pipes
18.8.2 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal dia pipes
18.8.3 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.25 mm nominal dia pipes
18.7.1 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall15 mm nominal dia pipes
18.7.2 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall20 mm nominal dia pipes
18.7.3 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall25 mm nominal dia pipes
18.7.4 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall32 mm nominal dia pipes
18.7.5 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall40 mm nominal dia pipes
18.7.6 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall50 mm nominal dia pipes
Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm),Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall - Ceiling and Shaft-20 mm nominal outer dia. Pipes.
Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing, Anchor fastners (8mm),Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall - Ceiling and Shaft-25 mm nominal outer dia. Pipes.
Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing, Anchor fastners(8mm),Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall - Ceiling and Shaft-32 mm nominal outer dia. Pipes.
Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm),Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall - Ceiling and Shaft-40 mm nominal outer dia. Pipes.
Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing, Anchor fastners(8mm),Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall - Ceiling and Shaft 50 mm nominal outer dia. Pipes.
Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2467) Fittings, fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall - Ceiling and Shaft 65 mm nominal outer dia. Pipes
Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing, Anchor fastners(8mm),Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work- Exposed on wall - Ceiling and Shaft 80 mm nominal outer dia. Pipes
Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in charge. Internal work - Exposed on wall - Ceiling and Shaft 50 mm nominal outer dia. Pipes.
Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in charge. Internal work - Exposed on wall - Ceiling and Shaft 65 mm nominal outer dia. Pipes.
Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings withone step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall - Ceiling and Shaft 80 mm nominal outer dia. Pipes
18.17.1A Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :20 mm nominal bore
18.17.1 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore
18.17.2 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :32 mm nominal bore
18.17.3 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :40 mm nominal bore
18.17.4 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :50 mm nominal bore
Supply, fix at site in position, test and commission, Brass Ball Valves to IS: 554 / BS:21 /ISO: 7, PN;25, with Screwed Female Ends complete with all necessary accessories. 40mm. (11/2”)
Supply, fix at site in position, test and commission, Brass Ball Valves to IS: 554 / BS:21 /ISO: 7, PN;25, with Screwed Female Ends complete with all necessary accessories.50mm. (2”)
Supply, fix at site in position, test and commission Gun Metal Globe Valves, PN:20,Screwed Female ends, complete with all necessary accessories.15mm. (1/2”)
Supply, fix at site in position, test and commission Gun Metal Globe Valves, PN:20, Screwed Female ends, complete with all necessary accessories. 20mm. (3/4”)
Supply, fix at site in position, test and commission Gun Metal Globe Valves, PN:20,Screwed Female ends, complete with all necessary accessories. 25mm. (1”)
Supply, fix at site in position, test and commission Gun Metal Globe Valves, PN;20,Screwed Female ends, complete with all necessary accessories.32mm. (11/4”)
Supply, fix at site in position, test and commission Gun Metal Globe Valves, PN;20,Screwed Female ends, complete with all necessary accessories.40mm. (11/2”)
18.19.4.2 Providing and fixing gun metal non-return valve of approved quality (screwed end): 50 mm nominal boreVertical
18.19.5.2 Providing and fixing gun metal non-return valve of approved quality (screwed end): 65 mm nominal boreVertical
18.19.6.2 Providing and fixing gun metal non-return valve of approved quality (screwed end): 80 mm nominal boreVertical
Brass Automatic Air Release Valves - Providing, Fixing, testing and commissioning at site in positions Brass Automatic Air Release Valves, of approved quality and make on the top of the vertical water supply pipes as per specification and drawing - 3/4 " (20mm) dia
Supplying, Installing & Testing at site in position Brass Float valve (PN10) of approved make with PP float & nipple with brass threaded in-sert, brass back nuts, piston and bolts etc complete in all respect to the satisfaction of Project Manager. 50mm dia (2”)
SS ball valve 50mm dia - Providing, Fixing at site in position full way lever operated SS ball valve (screwed end)of SS body (316) of approved make with necessary MTA fittings in position as per drawings. – 2”(50mm) dia
SS ball valve 40mm dia - Providing, Fixing at site in position full way lever operated SS ball valve (screwed end)of SS body (316) of approved make with necessary MTA fittings in position as per drawings. - 1½”(40mm) dia
SS ball valve 32mm dia - Providing, Fixing at site in position full way lever operated SS ball valve (screwed end)of SS body (316) of approved make with necessary MTA fittings in position as per drawings. - 1¼"(32mm) dia
Supplying, installing,Testing & commissioning at site in position Multi Jet Water Meter with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser,retrofittable for pulse output and conforming to ISO-4064 Class B complete.Water meter 40mm
Supplying, installing, Testing & commissioning at site in position Multi Jet Water Meter with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser, retrofittable for pulse output and conforming to ISO-4064 Class B complete. Water meter 50mm
Supplying, installing,Testing & commissioning at site in position Multi Jet Water Meter with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser,retrofittable for pulse output and conforming to ISO-4064 Class B complete.Water meter 65mm
Supplying, installing, Testing & commissioning at site in position Multi Jet Water Meter with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser, retrofittable for pulse output and conforming to ISO-4064 Class B complete. Water meter 80mm
CI Y Strainer 2 ½" (65mm) dia - Supply, Installation, Testing and Commissioning of CI Y type stainer with drain plug, SS screen 304 complete in all respects
CI Y Strainer 3" (80mm) dia - Supply, Installation, Testing and Commissioning of CI Y type stainer with drain plug, SS screen 304 complete in all respects
Terrace / Roof shall be with 19mm. thick flexible closed cell elastomeric thermal insulation and additional protection with Poly Shield Coating or Self Adhesive Glass Cloth Covering all from Approved Manufactures and to the approval of Engineer - incharge / Consultant. For 50 mm. dia. (2") pipe.
EXTERNAL SEWERAGE AND STORM WATER DRAIN
Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipeline as per specification, testing the pipeline after installation including Supplying, installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742- 1983 (Code of practice for building drainage) complete (excluding excavation) 200mm OD.
Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipeline as per specification, testing the pipeline after installation including Supplying, installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742- 1983 (Code of practice for building drainage) complete (excluding excavation) 160mm OD.
Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipeline as per specification, testing the pipeline after installation including Supplying, installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742- 1983 (Code of practice for building drainage) complete (excluding excavation)110mm OD
Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(4kg/cm2), jointing the pipeline as per specification, testing the pipeline after installation including Supplying, installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742- 1983 (Code of practice for building drainage) complete (excluding excavation).160mm OD
Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work (Including excavation) 50 mm nominal outer dia Pipes
Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, this includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work (Including excavation)65 mm nominal outer dia Pipes.
Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.External work (Including excavation)80 mm nominal outer dia Pipes.
Supply,installation, testing and commissioning of stainless-steel Bar Screen (opening 15mm) suitable for screen mesh of size 500mmx500mm removable type Screen Member 10mm S.S. Grade 316S Rods in Vertical Pattern.
Providing and fixing square-mouth PVC gully trap complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design:100x100 mm size P type With Sewer bricks conforming to IS: 4885
2.10.1.2 Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the excavated soil. and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m: All kinds of soilPipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia
18.41.1A Providing and filling sand of grading zone V or coarser grade, all - round the G.I. pipes in external workSub analysis item for sand filling component
4.1.10 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:5:10 (1 cement : 5 coarse sand (zone-III) derived from natural sources : 10 graded stone aggregate 40 mm nominal size derived from natural sources)
CIVIL WORK FOR RCC MANHOLE AND PUMPING PIT
2.8.1 Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
2.25 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
2.26.1 Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil
4.1.8 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
5.1.2 Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size derived from natural sources)
5.12 Providing, hoisting and fixing up to floor level precast reinforced cement concrete work in string courses, bands, copings, bed plates, anchor blocks, plain window sills and the like, including the cost of required centering, shuttering but excluding cost of reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone - III) : 3 graded stone aggregate 20 mm nominal size)
5.22.6 Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
5.9.1 Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.2 Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
5.9.6 Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
13.16.1 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
10.25.1 Item Shifted to Sub head 14 as item 14.73 Item Shifted to head 14 as item 14.74 Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In stringers, treads,landings etc. of stair cases, including use of chequered plate wherever required, all complete
Supplying, Installation, Testing and Commissioning of the Ductile Iron Circular Manhole cover with Frame (Double seal with EPDM Gasket and SS Bolting arrangement lifting key holes & load tested as per IS:1726 BS EN:124. 600mm Dia. (Heavy duty) (Minimum weight 75Kg).
Supplying, Installation, Testing and Commissioning of the Ductile Iron Circular Manhole cover with Frame (Double seal with EPDM Gasket and SS Bolting arrangement lifting key holes & load tested as per IS:1726 & BS EN:124.600mm Dia. (Medium duty) (Minimum weight 68Kg)
MISCELLANEOUS ITEMS
Supplying, Installing & Testing at site in position Fabricated 100mm (4")uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. - 100mm(4") uPVC Astm Sch 80 Puddle flange
Supplying, Installing & Testing at site in position Fabricated 80mm (3")uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. - 80mm(3") uPVC Astm Sch 80 Puddle flange
Supplying, Installing & Testing at site in position Fabricated 65mm (2½") uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. - 65mm (2½") uPVC Astm Sch 80 Puddle flange
Supplying, Installing & Testing at site in position Fabricated 50mm (2”) uPVC Astm Sch 80 Puddle flange in the water tanks as per the drawings and the requirement of the Project Manager. - 50mm (2”) uPVC Astm Sch 80 Puddle flange.
Supplying, Installing & Testing at site in position Fabricated 40mm (1½") uPVC Astm Sch 80 Puddle flange in the water tanks as per the drawings and the requirement of the Project Manager. -40mm (1½") uPVC Astm Sch 80 Puddle flange
Supplying, Installing & Testing at site in position Fabricated 32mm (1¼") uPVC Astm Sch 80 Puddle flange in the water tanks as per the drawings and the requirement of the Project Manager. - 32mm 1¼"uPVC Astm Sch 80 Puddle flange.
PLUMBING PUMPS AND HEAT PUMPS
Supply, installation, testing & commissioning of Solar assisted Heat pump, insulated pressurised SS storage tank, hot water expansion vessel, insulated piping between the system, valves & accessories required to complete the system in position with the following specification. 2000 LPD,consisting of Solar Hot Water Panels of Aggregate Capacity: 1000 LPD (50% of the total requirement), 58 Deg C required Insulated Hot Water Storage Tank suitable for 6 bar pressure SS 316 - 2000 Litre, COP of Heat pump 4, Including of the Circulation Pumps between heat pump/Panels and storage tank, control panel. Plumbing work Between storage tank and heat pump CPVC Pipe with suitable CPVC Fittings.Suitable Brass Fittings like NRV, Y Strainer, Air Vent, MTA, FTA, Flow Switches, Pipeline Insulation Electrical Work From Pump panel to heat pump 6 Square MM 4 core cable, 1.5 Square MM 3 core cable, 2.5 Square MM cable,Communication cable, 3 x 9Amps 3MP Contactors Coil Operated, PVC conduits for cables with suitable fittings etc. complete
Supplying, Installing, Testing & Commissioning at site hot water recirculation pump with suitable pressure switch, dry run protection & The Enclosure should be of IP 55 standards. The Panel should have BMS compatible thro RS 485 Communication(Modbus). Type : Thermostatic controlled.Horizontal, multistage, end-suction centrifugal pump with axial suction port and radial discharge port. The shaft, impellers and chambers are made of stainless steel. The inlet and discharge parts are made of cast iron. It’s supporting up to 95 degree Celsius temperature, digital control panel with Time and Temperature settings facility.Flow for each pump in LPS : 5 Head in mtr : 7 MOC : SS 304 Impeller Total no of pump: 1 SET ( 1Working + 1Standby )
Providing, Fixing, Testing and Commission Submersible Type Dewatering Pump Set, complete set with 1 working Submersible non- clog pump, Solids handling: 10mm, and with Common Control Panel for auto and cyclic operation. Capacity 3.5lps at 13.5Mtrs. head each, Head range 5 to 17 mtrThree Phase, with float switches/level sensors etc. necessary control valves, fittings and accessories, for discharging rain water from collection pits in basement floor, to lower strata. The price shall inclusive of all connected electrical work as detailed in the technical specification. Impeller - Cast Iron FG 260 Cast Iron - S.S AISI 410
FILTER FEED PUMP SET. Supply, Testing and Commission Filter Feed Pump Set, Submersible Type for Pumping Raw Water to Water Treatment Plant, 2 Pump System with One Working + 1 One Cyclically Stand by Pumps, each Pump of Capacity: 10M3/Hr. @ 16Mtr. Head, Head range 10 to 20 mtr, having CI Casing, SS Shafts, CF8 Impeller with 3Ph, complete with Microprocessor Based Control Panel, for Auto and Cyclic Operation, with all Protection (Digital display, Low & high voltage protection, dry run, phase reversal, pump over load, etc.), Level Sensors / Float Switches in Treated Water &; Raw Water Tanks and Control Cabling / Wiring between Level Sensors / Float Switches and Control Panel, Delivery Manifold, Isolating Valves, Non Return valves, Pressure Gauge, Fittings, Stainless Steel (Grade:304) Lifting Chains, Accessories etc. all as per Technical Specifications. The Control Panel shall be capable operating the pumps (starts and stops) by sensing the level difference in water in the Treated Water Tank. Also; capable of not starting or stopping the running pumps when the water in the underground Raw Water Tank goes below the pre-set minimum level. The Pumps to be installed in the Underground Raw Water Tank and Common Control Panel in the Pump Room, in Basement Floor, approx. 50 Mtr. away from Raw Water Tank. The Underground Power Cabling between Pumps and Control Panel and Control Cabling between Control Panel & Level Sensor / Float Switch, in the Underground Raw Water Tank, shall be measured as a part of Electrical Work. The Quoted Price for the Pump Set shall be inclusive of all above requirement, necessary Level Sensors /Float Switches, Power Cabling, changeover switch for operating pumps intermittently, Control Cabling etc, except what measured as a part of Electrical Work, as detailed above
Supplying, Installing, Testing & Commissioning of SOIL WATER TRANSFER CUM CUTTER PUMPSAND ACCESSORIES Shall be Heavy Duty, Durable & Long Lasting Pumps with High Efficiency Electrical Motors, One Working + Cyclically Stand by with Microprocessor Based Control Panel for Auto and Cyclic Operation, Float Switches, for Auto Start and Stop of Pumps, changeover switch for operating pumps intermittently, Feet / Base, Stainless Steel (Grade:304) Lifting Chains etc, complete. Required upto 35mm size solid handling. Impeller Material: Cast Iron FG260 Shaft Material: S.S AISI 410 Capacity: 4.7LPS @ 18Mtr. Head, Head range 13 to 23 mtr,3Ph,Complete Set.
Supplying, Installing, Testing & Commissioning of MEDICAL WASTE WATER TRANSFER CUM CUTTER PUMPS AND ACCESSORIES Shall be Heavy Duty, Durable & Long-Lasting Pumps with High Efficiency Electrical Motors, One Working + Cyclically Stand by with Microprocessor Based Control Panel, for Auto and Cyclic Operation, Float Switches, for Auto Start and Stop of Pumps, Feet /Base,Stainless Steel (Grade:304) Lifting Chains etc, complete. Required upto 35mm size solid handling.Impeller Material: Cast Iron FG 260 Shaft Material: S.S AISI 410 Capacity: 2.35LPS @ 18Mtr. Head, Head range13 to 23 mtr, 3Ph, Complete Set
Domestic water pump:Supply, Installation, Testing and Commissioning 2 nos, Vertical multi stage centrifugal pumps (surface pump) set, having SS Impeller and Shafts, CI/SS Casing, Mechanical Seal Each pumps should be capable to deliver 7.14lps @ 45 mtr head, Head range 35 to 55 mtrs, “F” class Insulation, IE3 Rated Electric Motors, IP 55 Protection, Hydraulic efficiency more than 65% motor efficiency more than 80% with Wall mounting Microprocessor based common control Panel to operate the pumpset as ( 1Working + 1Standby ) Star Delta, having features of automatic pump change over in every Start/Stop, Dry run, Overload, Phase Reversal Protections etc. level controller for Auto Start/ Stop Function, Digital display, Pressure gauge, Float Switches, Auto/Manuel Operation, changeover switch for operating pumps intermittently. The price is inclusive of all connected electrical work.
Flush Water pump: Supply, Installation, Testing and Commissioning 2 nos, Vertical multi stage centrifugal pumps (surface pump) set, having SS Impeller and Shafts, CI/SS Casing, Mechanical Seal Each pumps should be capable to deliver 2.50lps @ 45 mtr head, Head range 35 to 55 mtrs, “F” class Insulation, IE3 Rated Electric Motors, IP 55 Protection, Hydraulic efficiency more than 65% motor efficiency more than 80% with Wall mounting Microprocessor based common control Panel to operate the pump set as ( 1Working + 1Standby ) Star Delta, having features of automatic pump change over in every Start/Stop, Dry run, Overload, Phase Reversal Protections etc. level controller for Auto Start/ Stop Function, Digital display, Pressure gauge, Float Switches, Auto/Manuel Operation, changeover switch for operating pumps intermittently. The price is inclusive of all connected electrical work.
WATER TREATMENT PLANT
Supply, Installation, testing and commission Water Pre-Treatment Plant Capacity: 10M3 /Hr, for continuous operation of 10 Hr, complete with High Pressure Sand Filter, Activated Carbon Filter,with Multiport valves, Chemical Dosing etc as per final requirement, connected Pipe Work etc, all as per Technical Specifications. Filter Feed Pumps shall be measured separately.
SEWAGE TREATMENT PLANT
Supply, Installation, testing and commission Sewage-Treatment Plant Capacity: 50KLD,MBBR Type for continuous operation complete with Ultra Filter,with Multiport valves, Chemical Dosing etc as per final requirement, connected Pipe Work etc, all as per Technical Specifications.(Excluding Civil Works)
VALVES (E AND M)
16.11.1.5 Supplying, fixing testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. Butterfly Valve (Manual) with C I body SS disc nitrile sheet & O ring & PN 16 pressure rating as specifiedButterfly Valve (Manual) 80 mm dia
16.11.1.6 Supplying, fixing testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. Butterfly Valve (Manual) with C I body SS disc nitrile sheet & O ring & PN 16 pressure rating as specifiedButterfly Valve (Manual) 65 mm dia
ELECTRICAL WORKS Wiring and Accessories
1.10.3 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.55.3 Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
1.14.1 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.3 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.21.1 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
1.26 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
1.28.2 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.31 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
1.32 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
1.56 Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings).
1.33 Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
15.1 Supplying,Installation, testing and commissioning of Passive Infrared (PIR) technology based occupancy sensor having high preformance, non regulating programmable type, suitable for connected load upto 10 Amp, for mounting height up to 2.8 Mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming and site etc. complete as required
15.4.3 Supplying, installation, testing and commissioning of Astronomical time switch capable of following output in feeder pillars/ Lighting DBs for automatic switching On &OFF of street lights at sun set & sun ruse or twilight override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete ad required3 output (1output per phase) and suitable for three phase supply
Light Fitting
SITC of 2x 2 LED Recess mounted 30W light fixture, system efficacy >120 lm/W and system lumen output not less than 3600 lm. Luminaire shall have satin finished translucence (HET) diffuser for Uniform illumination and wider light distribution with CRCA powder coated housing, driver with minimum 4 KV internal surge protection with electronic drive system, power factor >/=0.95, THD<10%, rated life of50,000 hours at L70 with a CRI>80, UGR < 19, SDCM<5 and CCT in between 4000K to5700K.Luminaire shall be flicker free with ripple factor < 5%, ANSI rated LEDs from reputed makesshould be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor,single core cable and earthing etc. all necessary accessories as required for the light fixture.LM79, LM80,type test certificate &; BIS certificate shall be submitted, Luminaire/Drive shall be BIS approved of same make.
SITC of 2x 2 LED Recess mounted 34W light fixture, system efficacy >120 lm/W and system lumen output not less than 4080 lm. Luminaire shall have satin finished translucence (HET) diffuser for Uniform illumination and wider light distribution with CRCA powder coated housing, driver with minimum 4 KV internal surge protection with electronic drive system, power factor >/=0.95, THD<10%, rated life of50,000 hours at L70 with a CRI > 80, UGR <19, SDCM<5 and CCT in between 4000K to5700K.Luminaire shall be flicker free with ripple factor < 5%, ANSI rated LEDs from reputed makes should be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor ,single core cable and earthing etc. all necessary accessories as required for the light fixture.LM79, LM80,type test certificate & BIS certificate shall be submitted, Luminaire/Drive shall be BIS approved of same make
SITC of LED recessed downlight fixture Maximum 14W(+/- 10% Tolerance) light fixture. System efficacy>110 lm/W and system lumen output not less than 1540 lm. Luminaire shall have satin finishedtranslucence (HET) diffuser for uniform illumination and wider light distribution with Die Cast Al powdercoated housing, driver with minimum 2.50 KV internal surge protection with electronic drive system,power factor >/=0.95,THD<10%, rated life of 50,000 hours at L70 with a CRI > 80, UGR<19,SDCM<5and CCT in between 4000K to 5700K. Luminaire shall be flicker free with ripple content is less than 10%,ANSI rated LEDs from reputed makes should be provided and including connection with 1.5 sq.mmFRLS PVC insulated, copper conductor, single core cable and earthing etc. all necessary accessories asrequired for the light fixture.LM79, LM80, type test certificate & BIS certificate shall be submitted,Luminaire /Drive shall be BIS approved of same
SITC of LED recessed downlight fixture Maximum 8W(+/- 10% Tolerance) light fixture. System efficacy>110 lm/W and system lumen output not less than 880 lm. Luminaire shall have satin finished translucence (HET) diffuser for uniform illumination and wider light distribution with Die Cast Al powdercoated housing, driver with minimum 2.50 KV internal surge protection with electronic drive system, power factor >/=0.95,THD<10%, rated life of 50,000 hours at L70 with a CRI > 80, UGR<19,SDCM<5and CCT in between 4000K to 5700K. Luminaire shall be flicker free with ripple content is less than 10%,ANSI rated LEDs from reputed makes should be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. all necessary accessories as required for the light fixture.LM79, LM80, type test certificate & BIS certificate shall be submitted ,Luminaire /Drive shall be BIS approved of same
SITC of LED recessed mounted downlight fixture Maximum 18W(+/- 10% Tolerance) light fixture. System efficacy>110 lm/W and system lumen output not less than 1980 lm. Luminaire shall have satin finished translucence (HET) diffuser for uniform illumination and wider light distribution with Die Cast Al powder coated housing, driver with minimum 2.50 KV internal surge protection with electronic drive system, power factor >/=0.95,THD<10%, rated life of 50,000 hours at L70 with a CRI > 80, UGR<19,SDCM<5and CCT in between 4000K to 5700K. Luminaire shall be flicker free with ripple content is less than 10%,ANSI rated LEDs rom reputed makes should be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. all necessary accessories as required for the light fixture.LM79, LM80, type test certificate & BIS certificate shall be submitted, Luminaire /Drive shall be BIS approved of same
SITC of of LED Tube Lights of 34W(+/- 10% Tolerance) with minimum system lumens 3740 Lumens Extruded Aluminum Profile linear batten and polycarbonate diffuser having driver of minimum 4KV Surge protection inbuilt with electronic drive system, , SDCM<5 and CCT in between 4000K to 5700K,powerfactor >/= 0.95, THD<10%,rated life of 50,000 hours at L70, system efficacy>110 lm/W, with a CRI > 80,or above, Luminaire shall be flicker free with ripple factor < 5%, ANSI rated LEDs from reputedmakes should be provided and including connection with 1.5 sq.mm FRLS PVC insulated, copperconductor, single core cable and earthing etc. all necessary accessories as required for the lightfixture.LM79, LM80, type test certificate & BIS certificate shall be submitted, Luminaire/Drive shall be BISapproved of same
SITC of 10W LED BULKHEAD LIGHT fixture , System efficacy>=100 lm/W and system lumen output not less than 1000 lm. , driver with minimum 2.50 KV internal surge protection with electronic drive system ,power factor >0.95, THD<10%, rated life of 50,000 hours at L70 with a CRI > 80, SDCM<5 and CCT inbetween 4000K to 5700K. ANSI rated LEDs from reputed makes should be provided and includingconnection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. allnecessary accessories as required for the light fixture.LM79, LM80, type test certificate & BIS certificateshall be submitted, Luminaire/Drive shall be BIS approved of same make
90.15.4.3 Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
SITC of 3W LED skirting lamp (foot lamp) to provide dim lighting to make path during night, including necessary accessories required for connection
19.1 Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no:s blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accesories including safety pin, nut and bolts , washers, temperature rise equal to 75 deg celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required
E X T E R N A L F E E D E R P I L L A R : - S u p p l y a n d i n s t a l l a t i o n o f Thermoplastic polycarbonate Junction Box IP67. Junction box should be made of thermoplastic Polycarbonate, having IP 67 degree of protection and 5pole terminals suitable to terminate up to 2.5sqmm. The color of Junction boxes shall be Siemens Grey RAL7035. The gasket should be internally embedded, and made of Polyurethane The boxes shall be tested as per IEC 60670-2 / 60670-22. The boxes shall have self- threaded holes & provision for mounting din rail, The boxes should withstand temperature of -40c to +120c, The glow wire test should be conducted at 960c, and material should be flame retardant & selfextinguishing. UL subject 94, V-0. The boxes should be free of toxic substances like halogen and silicon, The boxes should have suitable pre-molded knock out, suitable size IP68 polyamide glands shall be provided for in and out cables / wires. Incomer:25A,30mA RCBO,Outgoing: 8 nos.6/10/16/20A 10KA SP MCBs
DB and Accessories
90.11.1.18 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.19 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.20 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
Supplying and fixing 16A to 100A TM TPN MCCB 25KA in the existing Vertical DB complete with connections, testing and commissioning etc. as required
90.11.1.10 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
90.11.1.11 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
90.11.1.12 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+24) - three phase double cover (IP 42/43)
2.10.1 Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA,"C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA,”C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Four Pole
Supplying and fixing 40A to 63 A rating, 240/415 volts, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Four Pole
2.10.4 Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.11 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCBO), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.32A 4P 30mA RCBO
Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCBO), having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63A 4P 100mA RCCB
SITC of MCB Isolator in sheet steel powder coated enclosure with lockable door facility confirming to IEC 60947-3 complete with all accessories, connections etc as required and as instructed by engineer in charge also making good any damages made during installation. 16A to 32A TP MCB Isolator
SITC of MCB Isolator in sheet steel powder coated enclosure with lockable door facility confirming to IEC 60947-3 complete with all accessories, connections etc as required and as instructed by engineer in charge also making good any damages made during installation. 40A to 63A TP MCB Isolator
SITC of MCB Isolator in sheet steel powder coated enclosure with lockable door facility confirming to IEC 60947-3 complete with all accessories, connections etc as required and as instructed by engineer in charge also making good any damages made during installation. 100A TP MCB Isolator
2.18 Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
2.24.1 Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 4 way, Double door TPN MCBDB
2.24.2 Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 6 way, Double door TPN MCBDB
2.24.3 Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 8 way, Double door TPN MCBDB
2.25 Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for tripple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required
Cable Tray and Accessories
4.1.1 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness
4.1.2 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness
4.1.3 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 225 mm width X 50 mm depth X 1.6 mm thickness
4.1.4 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness
4.1.5 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 375 mm width X 50 mm depth X 2.0 mm thickness
4.1.6 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X50 mm depth X 2.0 mm thickness
4.1.7 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness
4.2.1 Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
4.2.2 Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
4.2.3 Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
4.2.4 Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
4.2.5 Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.375 mm width X 50 mm depth X 2.0 mm thickness
4.2.6 Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.450 mm width X 50 mm depth X 2.0 mm thickness
4.2.7 Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.600 mm width X 50 mm depth X 2.0 mm thickness
4.3.1 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness
4.3.2 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness
4.3.3 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 225mm width X 50 mm depth X 1.6 mm thickness
4.3.4 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness
4.3.5 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 375 mm width X 50 mm depth X 2.0 mm thickness
4.3.6 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness
4.3.7 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness
4.4.1 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness
4.4.2 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness
4.4.3 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 225 mm width X 50 mm depth X 1.6 mm thickness
4.4.4 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness
4.4.5 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 375 mm width X 50 mm depth X 2.0 mm thickness
4.4.6 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness
4.4.7 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts &nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness
4.5.1 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness
4.5.2 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness
4.5.3 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 225 mm width X 50 mm depth X 1.6 mm thickness
4.5.4 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness
4.5.5 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 375 mm width X 50 mm depth X 2.0 mm thickness
4.5.6 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness
4.5.7 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness
Cables and Termination
90.12.1.32 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 120 sq mm
90.12.1.36 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 300 sq mm
90.12.1.37 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 400 sq mm
90.12.1.38 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).4 core 4 sq mm
90.12.1.39 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).4 core 6 sq mm
90.12.1.41 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).4 core 16 sq mm
90.12.7.13 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 6 sq mm with factory made clamp
90.12.7.14 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 10 sq mm with factory made clamp
90.12.7.15 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 16 sq mm with factory made clamp
90.12.7.28 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
90.12.7.29 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
90.12.7.30 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm
90.12.7.31 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm
90.12.7.32 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 120 sq mm
90.12.7.34 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm
90.12.7.35 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 240 sq mm
90.12.7.37 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 400 sq mm
90.12.7.38 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 4 sq mm with factory made clamp
90.12.7.39 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 6 sq mm with factory made clamp
90.12.7.40 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.7.41 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.7.42 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
90.12.7.20 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 95 sq mm
Supply, laying, clamping of the following size 1.1kV grade XLPE insulated PVC sheathed, Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date using clamps noted along with the cables, spacing of clamps nor exceeding 60cms making good the damages, colour washing etc as required. 1CX185Sq mm cu cable
Supply of following size 1.1 kV grade XLPE insulated, PVC sheathed, armored copper conductor cable conforming to IS 7098 (Part 1) amended up to date.12CX2.5Sqmm (Cu Control cable)
Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.12CX2.5Sqmm
9.1.11 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 50 sq. mm (32mm)
9.1.16 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 185 sq. mm (57mm)
9.1.21 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
9.1.22 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.23 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.24 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
9.1.25 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)
9.1.27 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 185 sq. mm (57mm)
9.1.29 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.31 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)
9.1.32 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.34 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
9.1.8 Supplying and making end termination with brass compression gland and aluminiumlugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 16 sq. mm (25mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 6 sq. mm
Supplying and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required.4 X 6 sq. mm (19mm)
Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required. 4 X 6 sq. mm
9.1.13 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 95 sq. mm (38mm)
Earthing
90.16.1.3 Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.3.10 Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 6 mm copper strip
90.16.3.16 Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)50 x 6 mm copper strip
90.16.3.9 Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip
90.16.4.8 Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 3 mm copper strip
90.16.5.3 Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling, including necessary clamps and bolts etc and all accessories as required for complete installation as instructed by engineer in charge/consultant. 25x3 Cu strips tinned at the joints
Lightning Protection System
Providing and fixing of maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of min 2500mm length (8.20 feet), having a diameter of 20mm with copper bonding thickness of 250 microns as per UL 467. The Rod has to be either continuous arrangement with fault current withstand capability of 20 KA rms value for 1 second and I peak of 50 KA. The rod must be having corrosion test, peel off test for uniform coating, 180 degree bend test with out peeloff of copper bonding.Stainless steel Clamp for Bonding. Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The material should have a resistivity less than 0.2 ?m. It should be free from hazardous substances. The mineral compound is required to have minimum 15 Kg of the total composite. The compound should be chemically inert and needs to submit Govt approved Indian labs test certificate. FRP Earth electrode inspection chamber with weight bearing capacity of 60KN. The dimension shall be 290mmx 290mmx 209mm. Govt approved Indian labs test certificate required.
Providing and laying copper coated steel solid round conductor 10mm diameter from earth electrode directly in ground as required. copper coated steel, high corrosion resistant. Meets the requirement of (IS/IEC 62305) copper coating thickness of 100microns Should be tested and use exclusively for lightning protection earthing system and ring equipotential bonding. After test link needs to be routed inside Heavy duty conduit to avoid touch potential till ground level. Govt approved Indian labs test certificate required.
Providing and fixing of Stainless Steel Test Joint suitable with suitable Outdoor Enclosure: For 8mm dia solid round aluminium conductor & 10mm dia copper coated solid steel round conductor having 100 microns of copper bonding . Conforms to the requirements according to (IS/IEC 62305).The enclosure should be outdoor glassfibre reinforced polycarbonate opaque having minimum inner dimension of 75mm x 75 mm x 50 mm. The test link has to be straight and needs minimum 4 mounting screws for strong joints. Inspection of bimetallic corrosion at site required. Seperation of 8mm Aluminium & 10mm Copper bonded steel is required for future inspection and contractor has to make sure both conductors should not touch eachg other to avoid bimetallic corrosion. Single bolt joints are not permitted. Govt approved Indian labs test certificate required.
Providing and fixing of Cross Connector/T Connector/Folding Clamp/Clamping Shoe/ Expansion Piece with Connector: to route vertical down conductor /mesh formation made of Aluminium Ferrule using screw free joints. Folding Clamp/Clamping Shoe for metal panels (up to 20mm thickness of the metal frame): Folding clamp/clamping shoe for metal frame thickness up to 20mm, made of stainless steel SS 304/316 grade , conforms to the requirements according to (IS/IEC 62305). Expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length at every 20 meters horizontally. Using round conductor 8mm aluminium conductor with straight Connector: using Aluminium Ferrule. Quick installation using crimp joints. Conforms to the requirements according to (IS/IEC 62305). Make sure all joints are strong and will be inspected at site. Galvanised Iron joints are not permitted to avoid risk of corrosion. Single bolt joints are not permitted to avoid risk of faulty loose joints and reduce risk of flash over. Govt approved Indian labs test certificate required.
Providing & fixing of 8mm solid aluminium round conductor with necessary holders @ required interval as specified below: Meets the requirement of (IS/IEC 62305) : semi-hard (E-AlMgSiO5 )with 50 sq.mm cross sectional area. Govt approved Indian labs test certificate required. Conductor with Terrace Conductor Fibre Reinforce Concrete holder @ every 0.75 meters
Providing & fixing of 8mm solid aluminium round conductor with necessary holders @ required interval as specified below: Meets the requirement of (IS/IEC 62305) : semi-hard (E-AlMgSiO5 )with 50 sq.mm cross sectional area. Govt approved Indian labs test certificate required. Conductor with Down Conductor Holder made of whether resistant plastic holder @ every 0.75 meters
Providing & fixing of 8mm solid aluminum round conductor with necessary holders @ required interval as specified below: Meets the requirement of (IS/IEC 62305) : semi-hard (E-AlMgSiO5 )with 50 sq.mm cross sectional area. Govt approved Indian labs test certificate required.Conductor with Parapet Holder made of whether resistant plastic holder @ every 0.5 meters
Providing and fixing Fully Solid Vertical Air terminals for wind stability as per IS/IEC -62305 part-3 For 1,2,3, 4 meter air terminal 16mm rod tapered to 10 mm aluminium rod meter rod: For 6, 8 meter 40mm rod tapered to 16mm and then to 10mm Meets the requirement (IS/IEC 62305) Semi-hard (E-AlMgSiO5) Suitable for high wind load. All air terminal must have Interception Tip at the Top of air terminal. Air terminal Joining Clip Stainless Steel SS 304 clamp required to connect horizontal air termination to vertical air termination; Lightning tested for 100 KA 10/350 micro sec waveform. This is required if using 17 KG stone supports. Stainless Steel Wall Clamp or 17 KG stone of 365 mm diameter, high level of stability is required to mount 1,2,3,4 meters. No of concrete stones/wall clamps depending on wind load needs to be considered. For 6 & 8 meter air terminalfor mounting: tripod stand or 3 nos & 4 nos respectively wall clamp will be required to withstand heavy wind load. Govt approved Indian labs test certificate required. d )4 meter air terminal with Interception Tip mounted on Concrete Stone & Stainless Steel mounting accessories
Providing and fixing Fully Solid Vertical Air terminals for wind stability as per IS/IEC -62305 part-3 For 1,2,3, 4 meter air terminal 16mm rod tapered to 10 mm aluminium rod meter rod: For 6, 8 meter 40mm rod tapered to 16mm and then to 10mm Meets the requirement (IS/IEC 62305) Semi-hard (E-AlMgSiO5) Suitable for high wind load. All air terminal must have Interception Tip at the Top of air terminal. Air terminal Joining Clip Stainless Steel SS 304 clamp required to connect horizontal air termination to vertical air termination; Lightning tested for 100 KA 10/350 micro sec waveform. This is required if using 17 KG stone supports. Stainless Steel Wall Clamp or 17 KG stone of 365 mm diameter, high level of stability is required to mount 1,2,3,4 meters. No of concrete stones/wall clamps depending on wind load needs to be considered. For 6 & 8 meter air terminalfor mounting: tripod stand or 3 nos & 4 nos respectively wall clamp will be required to withstand heavy wind load. Govt approved Indian labs test certificate required. c)3 meter air terminal with Interception Tip mounted on Concrete Stone & Stainless Steel mounting accessories.
Providing and fixing Fully Solid Vertical Air terminals for wind stability as per IS/IEC -62305 part-3 For 1,2,3, 4 meter air terminal 16mm rod tapered to 10 mm aluminium rod meter rod: For 6, 8 meter 40mm rod tapered to 16mm and then to 10mm Meets the requirement (IS/IEC 62305) Semi-hard (E-AlMgSiO5) Suitable for high wind load. All air terminal must have Interception Tip at the Top of air terminal. Air terminal Joining Clip Stainless Steel SS 304 clamp required to connect horizontal air termination to vertical air termination; Lightning tested for 100 KA 10/350 micro sec waveform. This is required if using 17 KG stone supports. Stainless Steel Wall Clamp or 17 KG stone of 365 mm diameter, high level of stability is required to mount 1,2,3,4 meters. No of concrete stones/wall clamps depending on wind load needs to be considered. For 6 & 8 meter air terminal for mounting: tripod stand or 3 nos & 4 nos respectively wall clamp will be required to withstand heavy wind load. Govt approved Indian labs test certificate required.b)3 meter air terminal with Interception Tip mounted on Stainless Steel Wall Clamp mounting accessories
Providing and fixing Fully Solid Vertical Air terminals for wind stability as per IS/IEC -62305 part-3 For 1,2,3, 4 meter air terminal 16mm rod tapered to 10 mm aluminium rod meter rod: For 6, 8 meter 40mm rod tapered to 16mm and then to 10mm Meets the requirement (IS/IEC 62305) Semi-hard (E-AlMgSiO5) Suitable for high wind load. All air terminal must have Interception Tip at the Top of air terminal. Air terminal Joining Clip Stainless Steel SS 304 clamp required to connect horizontal air termination to vertical air termination; Lightning tested for 100 KA 10/350 micro sec waveform. This is required if using 17 KG stone supports. Stainless Steel Wall Clamp or 17 KG stone of 365 mm diameter, high level of stability is required to mount 1,2,3,4 meters. No of concrete stones/wall clamps depending on wind load needs to be considered. For 6 &; 8 meter air terminal for mounting: tripod stand or 3 nos &; 4 nos respectively wall clamp will be required to withstand heavy wind load. Govt approved Indian labs test certificate required. a) 2 meter air terminal with Interception Tip mounted on Stainless Steel Wall Clamp mounting accessories
Installation of Exothermic Weld Joints for 10mm round copper bonded steel conductor having 100 microns as per IS/IEC 62305. Each under ground joints has to be wrapped with petrolatum- coated chemical fibre fabric having 1.1mm thick and width 50mm. Govt approved Indian labs test certificate required.
HT Works
180KVA DG Set:- Supply, Installation, Testing and Commissioning of 180 kVA prime rated DG set with acoustic enclosure, DG control panel including RPR relay including control cable to the solar AC side , protection and digital metering, controls and interlocks, CT's and transducers for all metering and protection with suitable size breaker, suitable for AMF operation and synchronization and the automatic switching and the load sharing controlled by the PLC system, antivibration mountings, exhaust silencer etc. conforming to latest environment protection regulations for emission and noise levels water/coolant cooled, (radiator type) four stroke, electric start conforming to BS: 5514 , brushless, self excited, self regulated and suitable for continuous operation at 1500 RPM, generating 415 V +/- 5% Volts at 0.8 p.f (lag),50 Hz,3Phase, 4 wire system generally conforming to IS 4722. Both Engine and alternator shall be mounted on common channel iron base frame, and with standard accessories such as lead acid batteries and engine driven battery charger along with leads, battery stand, necessary control wiring with control cables, first fill of lubricating oil, and earthing as per standards, Inbuilt Fuel tank suitable for 8hrs continuous operation, fuel piping from fuel tank to Engine, Residential silencer, suitable size of cable termination box etc.as required and as per specifications. The work should be as per Electrical Inspectorate / pollution control board standards and comply to latest CPCB IV plus norms.(Civil works excluded).
250KVA DG Set:- Supply, Installation, Testing and Commissioning of 250 kVA prime rated DG set with acoustic enclosure, DG control panel including RPR relay including control cable to the solar AC side, protection and digital metering, controls and interlocks, CT's and transducers for all metering and protection with suitable size breaker, suitable for AMF operation and synchronization, antivibration mountings, exhaust silencer etc. conforming to latest environment protection regulations for emission and noise levels water/coolant cooled, (radiator type) four stroke, electric start conforming to BS: 5514 , brushless, self excited, self regulated and suitable for continuous operation at 1500 RPM, generating 415 V +/- 5% Volts at 0.8 pf (lag),50 Hz,3Phase, 4 wire system generally conforming to IS 4722. Both Engine and alternator shall be mounted on common channel iron base frame, and with standard accessories such as lead acid batteries and engine driven battery charger along with leads, battery stand, auto charge, necessary control wiring with control cables, first fill of lubricating oil, and earthing as per standards, Inbuilt Fuel tank suitable for 8 hrs continuous operation, fuel piping from fuel tank to Engine, Residential silencer, suitable size of cable termination box etc.as required and as per specifications. External battery charger of adequate capacity shall also be supplied and connected. The work should be as per MOEF standards and comply to latest CPCB IV plus norms.(Civil works excluded)
EXHAUST PIPES: Supplying and fixing exhaust gas piping of suitable dia, welded black M.S, B class pipe confirming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral Wool/ rockwool, 50 mm thick wire mesh & aluminum cladding etc., as required as per specifications. suitable rain cap for top to avoid rain water entry. The distance between exhaust pipe at top and rain cap should be higher than diameter of pipe. Horizontal run of exhaust piping should slope downwards away from engine to the condensate trap. Silencer should be installed with drain plug at bottom. Fixing shall be done with proper clamps, expansion bolts, and all other accessories as instructed by the Engineer and the rate inclusive of all minor civil works required, bolts, clamps etc as required for installation. Support to exhaust piping should be done in such a manner that load of exhaust piping is not exerted to turbo charger and the vertical run of the pipes shall be provided with indirect supporting method so that when the pipes are hot and expanded they will be lifted into the supports. Exhaust pipe height shall be 3m more than the top of any adjacent building within 10m radius of the exhaust- 5 inch dia Exhaust pipe
EXHAUST PIPES; Supplying and fixing exhaust gas piping of suitable dia, welded black M.S, B class pipe confirming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral Wool/ Rockwool,50 mm thick wire mesh & aluminium cladding etc., as required as per specifications. suitable rain cap for top to avoid rain water entry. The distance between exhaust pipe at top and rain cap should be higher than diameter of pipe. Horizontal run of exhaust piping should slope downwards away from engine to the condensate trap. Silencer should be installed with drain plug at bottom. Fixing shall be done with proper clamps, expansion bolts, and all other accessories as instructed by the Engineer and the rate inclusive of all minor civil works required, bolts, clamps etc as required for installation. Support to exhaust piping should be done in such a manner that load of exhaust piping is not exerted to turbo charger and the vertical run of the pipes shall be provided with indirect supporting method so that when the pipes are hot and expanded they will be lifted into the supports. Exhaust pipe height shall be 3m more than the top of any adjacent building within 12m radius of the exhaust. For 250kVA DG Set- 6 inch dia Exhaust pipe
Supply of following 11kV grade XLPE insulated PVC sheathed wire armored aluminum conductor power cable suitable for 11kV earthed system conforming to IS 7098 (Part 2) and other relevant standards. (Refer detailed technical specification) 3 Core 300 Sq.mm 11kV(E)
8.1.2 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sq. mm and upto 400 sq. mm
8.3.2 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 120 sq. mm and upto 400 sq. mm
8.4.2 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required.Above 120 sq. mm and upto 400 sq. mm
10.5.4 Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
10.4.4 Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
7.9 Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required.
LT Panels
Main Panel: -Supply, Installation, Testing and Commissioning of 415 V 50Hz LT Switch board OEM Design Verified Assembly Panel complying to IEC 61439 Part 1&2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type, Ingress Protection rating shall be IP42 and Impact protection shall be IK10 with cable entry facility at top or bottom (as per site condition), cable alley, switchgear compartment, meter chamber, C.T chamber, Aluminum bus bar with bus bar chamber etc. Control wiring shall be with 2.5sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with DIN rail mounted 2A SP MCB. Doors shall be earthed as per prevailing standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Form of construction of panel shall be 3B or above. Note: Relevant Test certificates from third party certification agencies: Panel must be BMS compactable. ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. Incomer 1: - (KSEB Side) a) 1 No 800 A 50 kA 4P ACB EDO P based with 3O/C 1E/Releases S/T O/V relay with CT at neutral earthing conductor b) 1 Set RYB Indication Lamp c) 1 Nos (0-800) A three phase digital ammeter d) 1 Nos (0-500) V three phase digital Voltmeter e) 1 Nos of 51G relay f)1 Nos. of Multifunction Digital meter V, A, F, KW, KVA, PF, THD g) 1 Nos. of Under Voltage/Over Voltage Relay. Incomer 2:- (250KVA DG ) a) 1 No 400A, 50 kA, 4P, MCCB set at 350A with PLC controlled demand based switching and AMF operation is required for auto changing of power supply. b) 1 Set RYB Indication Lamp c) 1 Nos (0- 400)A three phase digital ammeter d) 1 Nos (0-500)V three phase digital voltmeter e) 1 Nos. of Multifunction Digital meter V,A,F,KW,KVA,PF,THD f) Reverse current protection relay. Incomer 3:- (180KVA DG ) a) 1 No 320A, 50 kA, 4P, MCCB st at 252A with PLC controlled demand based switching and AMF operation is required for auto changing of power supply b) 1 Set RYB Indication Lamp c) 1 Nos (0- 500)A three phase digital ammeter d) 1 Nos (0-500)V three phase digital voltmeter e) 1 Nos. of Multifunction Digital meter V,A,F,KW,KVA,PF,THD f) Reverse current protection relay Outgoings:-a) 6 Nos 400 A, 35 kA, TP MCCB b) 3 Nos 320 A 35 kA TP, MCCB c)1 Nos 200 A, 35 kA, TP MCCB c) 1 No 400A TP, Isolator d) ON-OFF-TRIP Lamps with 2A fuse -11 sets e)Surge Protection Devices for Main Panel: Type 1-2 sets f) MFDM, with 2A fuse as per SLD -11 sets, 1000 A 415V, 50kA best conductivity Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. All Breakers in the incoming side shall be with LSIG protection and all the breakers in the outgoing side shall be with LSI protection. ON/OFF/TRIP indicators shall be provided for all the breakers (incoming & outgoing). Necessary spreader terminals, extended ROH, phase barriers, shrouding etc shall be as per the rules. The system shall be connected to AMF cum ATS relays and operated as per the logic given in the SLD. Details as shown in SLD.
HVAC Panel : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a)Incomer- 320A 36KA 4P MCCB - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 320)A three phase digital ammeter d)1 No (0- 500)V three phase digital voltmeter e)1 No. of multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:- a)200A, TPN Isolator-2 Nos b)100A, TPN Isolator- 2 No. ON-OFF-TRIP Lamps with 2A fuse as per SLD 320A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
HVAC outdoor Panel : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a)Incomer- 200A 25KA 4P MCCB - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 200)A three phase digital ammeter d)1 No (0- 500)V three phase digital voltmeter e)1 No. of multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:- a)100A, 16KA TPN MCCB-4 Nos b)63A, 16KA TPN MCCB-3 No. ON-OFF-TRIP Lamps with 2A fuse as per SLD 200A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
HVAC AHU Panel : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a)Incomer- 100A 25KA 4P MCCB - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 200)A three phase digital ammeter d)1 No (0- 500)V three phase digital voltmeter e)1 No. of multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:- a) 63A, 16KA TPN MCCB-2 No. b)40A, 16KA TPN MCCB-2 c)16A, 16KA TPN MCCB-3 ON-OFF-TRIP Lamps with 2A fuse as per SLD 100A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD
Sub Panel-1(Floor Panel) : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a)Incomer- 320A 36KA 4P MCCB - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 320)A three phase digital ammeter d)1 No (0-500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:-a)100A, 25kA, TP+ NL Thermal Magnetic Base MCCB - 1 No. b)63A, 25kA, TP+ NL Thermal Magnetic Based MCCB-5 Nos. c)40A, 25kA, TP+ NL Thermal Magnetic Based MCCB-1 No ON-OFF-TRIP Lamps with 2A fuse as per SLD 320A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
Common Panel-2: Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. . Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 320A 36KA 4P MCCB - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 320)A three phase digital ammeter d)1 No (0-500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:- a)160A,TPN isolator -2 Nos. b) 80A TPN Isolator -2Nos, c)63A TPN Isolator -1Nos, c)40A TPN Isolator -1Nos ON-OFF-TRIP Lamps with 2A fuse as per SLD 320A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
Plumbing Main Panel : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 160A 36KA 4P MCCB-1 No. b)1 Set RYB Indication Lamp c)1 No (0- 160)A three phase digital ammeter d)1 No (0-500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:-a)100A,TPN Isolator- 2Nos. b)63A,TPN Isolator -1No, c)40A,TPN Isolator -1No ON-OFF-TRIP Lamps with 2A fuse as per SLD 160 A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
Pump Sub-Panel 1 : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better.Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 100A 25KA 4P MCCB-1 No. b)1 Set RYB Indication Lamp c)1 No (0- 100)A three phase digital ammeter d)1 No (0- 500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:-a)50A,TPN MCB -3 Nos. b)25A,TP MCB -4Nos . ON-OFF-TRIP Lamps with 2A fuse as per SLD 100A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
Pump Sub-Panel 2 : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP65, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 50A TPN Isolator - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 50)A three phase digital ammeter d)1 No (0-500)V three phase digital voltmeter e)1 No. of multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:-a)25A,TP MCB -2 Nos. b)32A,TP MCB -2 Nos ONOFF- TRIP Lamps with 2A fuse as per SLD 50A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD
Sewage Pump Panel : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will beaccepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 50A TP Isolator - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 50)A three phase digital ammeter d)1 No (0-500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:-a)25A,TP MCB -4 Nos. ON-OFF-TRIP Lamps with 2A fuse as per SLD 50A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD
EV CHARGING : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, freestanding powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shallbe IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall beat top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meterchambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory.<br>Incomer:-a)1 No 100A TPNISOLATOR b)1 Set RYB Indication Lamp c)3 Nos 100/5A CL:1, 15VA CT d)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:-a)1 Nos 63A, 25 kA, TM TPN,MCCB b) 6 Nos 25A, 25 kA, TM TPN, MCCB 100A 415V 25kA best conductivity Al bus barwith SMC supports, heat shrinkable sleeves etc complete as required with necessary interlockingarrangement. Details to be as shown in SLD
Lighting Panel : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminum bus bar with bus bar chamber etc. Control wiring shall be with 2.5sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 40A 25KA 4P Isolator- 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 120)A three phase digital ammeter d)1 No (0- 500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:-a)25A,TPN MCB -2 Nos b)25A DP MCB-1No. ONOFF- TRIP Lamps with 2A fuse as per SLD 40A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
UPS Output Panel: Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2.The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 125A 16KA 4P MCCB-1 No. b)1 Set RYB Indication Lamp c)1 No (0- 200)A three phase digital ammeter d)1 No (0-500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF outgoings:-a) 63A,16KA FP MCCB-4Nos,b) 40A,16KA FP MCCB-4 No c) 32A,16KA FP MCCB-1 No. ONOFF- TRIP Lamps with 2A fuse as per SLD 125A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
Common Panel-1: Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 , form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. . Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 400A 36KA 4P MCCB - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 400)A three phase digital ammeter d)1 No (0-500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:- a)320A,TPN MCCB -2 Nos. b) 160A TPN MCCB -2Nos ON-OFF-TRIP Lamps with 2A fuse as per SLD 400A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
Lift Panel : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 160A TP Isolator - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 160)A three phase digital ammeter d)1 No (0-500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:-a)100A,FP isolator -2 Nos. b) 80A,,FP isolator -1 Nos. ON-OFF-TRIP Lamps with 2A fuse as per SLD 160A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
LIFT PANEL Sub panel-1 :-Supply, Installation, Testing and commissioning of factory fabricated OEM 415 V 50Hz 4 way complying to IEC 61439 Part 1 & 2. The Enclosure shall be IP42 with cable end box, cable alley, pre wired meter 300mm and maximum up to 1800mm from the finished floor level complete as per the directions of Engineer in charge Incomer a)1 No 100A TPN ISOLATOR Outgoings: -a) 2 Nos 63A, 4P 300mA RCCB+MCB b) 1Nos 16A, DP MCB+ 16A 30mA DP RCBO .
LIFT PANEL Sub panel-2 :-Supply, Installation, Testing and commissioning of factory fabricated OEM 415 V 50Hz 4 way complying to IEC 61439 Part 1 & 2. The Enclosure shall be IP42 with cable end box, cable alley, pre wired meter 300mm and maximum up to 1800mm from the finished floor level complete as per the directions of Engineer in charge Incomer ? a)1 No 80A TPN ISOLATOR Outgoings: -a) 1 Nos 63A, 4P 300mA RCCB+MCB b) 1Nos 16A, DP MCB+ 16A 30mA DP RCBO .
Medical Panel : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer-320A 36KA 4P MCCB-1 No. b)1 Set RYB Indication Lamp c)1 No (0- 320)A three phase digital ammeter d)1 No (0-500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:- a)160A,FP MCCB- 2Nos. b)63A,FP MCCB -2No, ON-OFF-TRIP Lamps with 2A fuse as per SLD 320A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD.
CSSD Panel : Supply, Installation, Testing and Commissioning of 415 V 50Hz OEM design verified LT Switch board complying to IEC 61439 Part 1 & 2. The Enclosure shall be self-supported, free standing powder coated compartmentalized cubicle type with CRCA sheet, Ingress Protection rating shall be IP42, Impact protection shall be IK10 & form of construction 3B or better. Cable entry facility shall be at top or bottom (as per site condition) with necessary cable alleys, switchgear compartments, meter chambers, C.T chambers, Aluminium bus bar with bus bar chamber etc. Control wiring shall be with 2.5 sq.mm copper cable of 1100 volts grad for C.T leads and 1.5 sq.mm for voltage leads and protection of control shall be with appropriately rated HRC fuses. Doors shall be earthed as per standards. The main earth bus shall be of suitable size copper and run through the switch board for earthing metallic parts of switch gears. All copper joints shall be tinned. Gland plates shall be 3mm thick and knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of any switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level. Note: Relevant Test certificates from third party certification agencies: ASTA, ASEFA, DEKRA, KEMA, UL will be accepted as proof of compliance. OEM certification is also mandatory. a) Incomer- 160A 36KA 4P MCCB - 1 No. b)1 Set RYB Indication Lamp c)1 No (0- 320)A three phase digital ammeter d)1 No (0- 500)V three phase digital voltmeter e)1 No. of Multifunction Digital meter V,A,F,KW,KVA,PF Outgoings:- a)100A, 25kA, TP Thermal Magnetic Based MCCB -3 Nos. b)32A, 25kA, TP Thermal Magnetic Based MCCB-2 Nos. ON-OFF-TRIP Lamps with 2A fuse as per SLD 160A, 433V best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc complete as required. Necessary interlocking arrangement. Details to be as shown in SLD
MEDICAL GAS PANEL (SMDB -6WAY) :-Supply, Installation, Testing and Commissioning of factory fabricated OEM 415 V 50Hz 6 way complying to IEC61439 Part 1 & 2. The Enclosure shall be IP42 with cable end box, cable alley, pre wired meter chamber with all meters & indicating lamps, Aluminum bus bar, neutral link, DIN bar with all accessories etc. complete with necessary control wiring and protection of control shall be with DIN rail mounted 2A SP MCB. Doors shall be earthed as per prevailing standards. The main earth bus shall be of suitable size copper. All copper joints shall be tinned. Knock - outs of proper diameter shall be provided on gland plates. The height of the operating handle of switch gear shall be minimum 300mm and maximum up to 1800mm from the finished floor level complete as per the directions of Engineer in charge. Incomer – 1 No. 80A 25KA FP MCCB Outgoings: - a)6 Nos 32A, 25KA TP, MCCB
100KVA Modular type N+1 UPS :-Supply of MODULAR UPS 1X125 kw FRAME With maximum 25kw modules in each frame of 3 phase modules three phase in and out with built in PRS configurations. with indoor (IP20) with surge protection system with 15 min backup battery @80 kW load battery sizing calculation to be provided from the OEM, with isolator for each bank of SMF battery of reputed approved make , Input pf 0.99, Input THDi <3 double conversion technology with input 400V, 50Hz three phase, output 400V, 50Hz three phase, SNMP card for network monitoring, BMS compatibility etc. It shall be100% generator compatible, with Efficiency > 96 % and output power factor Unity (kva = kW), Eco mode Efficiency 99% and including all accessories etc as required. The acoustic noise at 1m of the system should be < 80dB.The system shall comply to IEC /EN 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, CE,IEC62040-4 or ISO14025 or equivalent relevant IS standard. The system shall be true online double -conversion DSP based UPS system and also UPS shall be with automatic & manual bypass switch. The system shall have 3 level IGBT rectifier and inverter. including rack and interconnecting cables. Battery backup time required is 15 Min. using External SMF Batteries. The product of the offered battery Ah capacity and the total rated DC Bus voltage shall be a minimum of 78000vAH
Miscellaneous Items
2.21 Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required
2.22 Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Supply and fixing single line diagram, schematic diagrams etc. of A1 size including laminations etc. as required complete on wall
Supplying and Providing 15" long rubber hand gloves 15 kV
Supply and providing First Aid Box
Supply and providing laminated First Aid chart duly framed and placed in a conspicuous location for clear vision.
Supplying of 6mm thick MS chequered plates duly painted. Plates to be cut size as per site requirement
Painting letters or figures of 2.5cm/4.5cm sizes with enamel paint as identification mark to SB, DB, panel board etc as required
Supplying and installing fire buckets of 24 gauge galvanized steel sheet, standard 9 liter capacity and of round bottom shape, painted white inside and red outside black on the bottom, inscribed with letters “FIRE” in black or duly painted over a coat of primer. Cost inclusive of providing 4 Nos of sand filled fire bucket and MS stand frame as directed by the Engineer in charge.
Supply and providing 2.5/3 mm thick and 1 m wide electrical grade chequered type rubber mat to withstand 11 kV dielectric strength conforming to IS 5429/1969
Supply and providing 2/3 mm thick synthetic type and 1 m wide electrical grade chequered type rubber& mat to withstand 3.3 kV dielectric strength conforming to IS 5429/1969
SOLAR SYSTEM - 160 KwP
Supply, Installation, Testing and Commissioning of 160 kWp on grid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of N-Type TOPCON solar PV Module solar PV Modules, net metering facility, necessary protections, earthing, mounted on Aluminium /GI structure of suitable strength with following components complete as required:-a) Solar photovoltaic Module of capacity 560Wp or above, manufactured in India, conforming to IS14286/IEC61215,IS/IEC61730-Part-1,IS/IEC61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 22%. PV modules used in solar power plants/systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10years and 80% at the end of 25years. b) Power Conditioning Unit (PCU) of 400VAC, three phase,4wire,50Hz+/-2.5Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50- degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. c) Data monitoring System complete with accessories. d)Fixing of array junction box & Main junction box with IP65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required.e) Lightning and surge voltage protection. f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying &fixing of necessary channel/ conduit lugs and other accessories etc.as required g) Isolation Mechanism should be provided in the solar panel when the RPR is enabled.
Extra Low Voltage Works VOICE
Supply, Installation, Testing, and Commissioning of an IP-PBX System capable of handling hybrid telephony networks with a scalable and feature-rich architecture. System Capacity with minimum 200 Analog Extensions,20 IP Extensions. Supports connectivity through PRI / SIP / Analog / GSM Trunks Trunk Interfaces :included with minimum 30 SIP Trunks Features & Functionalities: 8-Port IVR, Built-in Call Recording,DISA (Direct Inward System Access),Call Hunt Groups,Video & Audio Calling / Conferencing,Supports Web-based Voice Calling &Web-based Receptionist Console,Call Dashboard (Real-time Monitoring & Reporting) Web Interface for System Administration. Should include modules /accessories for EXTERNAL PAGING To connect with Amplifier with Complete installation, configuration, and integration of the system End-to-end testing and commissioning ,Coordination for connectivity with PRI/SIP/Analog/GSM trunks ,3 year service support from OEM and training for administrative and operational.
FXS Gateway -48 Port FXS Gateway which is fully compatible with PABX(Same OEM of IP-PBX) with Web Based GUI ,Echo Cancellation, Caller ID Display Including Power Supply and Accessories - Should Include Patch cords and complete accessories to connect with the Network Switch and Telephone lines.
FXS Gateway -32 Port FXS Gate way which is fully compatible with PABX(Same OEM of IP-PBX) with Web Based GUI ,Echo Cancellation, Caller ID Display Including Power Supply and Accessories Should Include Patch cords and complete accessories to connect with the Network Switch and Telephone lines.
FXS Gateway -24 Port FXS Gateway which is fully compatible with PABX(Same OEM of IP-PBX) with Web Based GUI ,Echo Cancellation, Caller ID Display Including Power Supply and Accessories - Should Include Patch cords and complete accessories to connect with the Network Switch and Telephone lines.
FXS Gateway -16 Port FXS Gateway which is fully compatible with PABX(Same OEM of IP-PBX) with Web Based GUI ,Echo Cancellation, Caller ID Display Including Power Supply and Accessories - Should Include Patch panel to connect with the Network Switch
Surge Protection Device For Analog trunk: Supply, Installation, Testing and commissioning of SPD Class D (Type 2) SPD for Line Surge Arrester plus technology(This SPD needs to be purchased only if the client takes Analog Trunk line)
Supply and providing basic IP Telephone Including Sufficient Patch cord to connect from the I/O socket to Phone with Display ,Speakerphone as mentioned in the tender Specification
Basic Analog Telephone with Called ID and Loud speaker including Patch cords to connect in RJ45 I/O
CLOSED CIRCUIT TELEVISION
Supply and Installation of Minimum 4MP IP Varifocal Bullet Camera, Minimum 1/2.8 inch image sensor, motorized Lens: 2.8 to 12mm or near , IR Distance: 40 Mtr, Supports Compression: H.265, H.264, MJPEG ,Video Streaming: Triple streaming, Motion Detection: 4 zone, Rectangle ,Supports TCP/IP,HTTPS,SNMP,FTP, Supports ONVIF (S,G,T), Event Trigger for Face Recognition, Perimeter Intrusion Detection and Line Crossing Detection True WDR(120dB),Supports Micro SD Card Slot Minimum up to 128GB, Alarm I/Privacy Mask up to 8 level, Metal ,Weatherproof Standard: IP67 ,product must comply with NDAA compliance, Non Black Listed Declaration, UL/CE,BIS,STQC Complied.Should comply with tender specification
Supply and Installation of 4MP IP Vandal Dome Camera ,Minimum 1/2.8 inch image sensor, 2.8/3.6/3.8 mm fixed lens Video Compression: H.265,H.264,MJPEG ,Triple Video Streaming ,ONVIF (S,G,T); Supports Face Recognition, WDR(120dB),Micro SD Card Slot up to 128GB, Privacy Mask, ICR ,PoE : Metal ,Weatherproof Standard: IP67; NDAA complied, BIS, UL/CE,STQC Complied
Supply and Installation of Minimum 4MP IP Varifocal Vandal Dome Camera, Minimum 1/2.8 inch image sensor, Motorized Lens: 2.8 to 12mm or near, minimum IR Distance of 30 Mtr, Supports Compression: H.265,H.264, MJPEG ,Video Streaming: Triple streaming, Motion Detection: 4 zone, Rectangle ;Supports TCP/IP,HTTPS,FTP, ONVIF (S,G,T);Event Trigger for Face Recognition True WDR(120dB),Supports Micro SD Card Slot Minimum up to 128GB, Alarm I/Privacy Mask up to 8 level, Metal ,Weatherproof Standard: IP67,IK10 product must comply with NDAA compliance, Non Black Listed Declaration, UL/CE,STQC Complied
Supply and installation of Network Video Recorder, support 64 Channel, Should support Resolution:- Minimum upto 8 MP IP Camera, Network Bandwidth incoming 400 Mbps and outgoing 400 Mbps for access, support for H.265,H.264 compression, Recording resolution up to 8 MP, Video output: 2xHDMI Support min. 8 SATA HDDs , Each port supports min. 10TB HDD(Enterprise class), support-RAID5, RAID6 Support dual Gigabit Ethernet ports, Alarm Input/out:16 in /4 out ,Audio:1 in / 1 out ,Supports intelligent analytics such as facial detection, perimeter intrusion, and line crossing statistics , product must comply with NDAA compliance, BIS,CE/UL Complied
Enterprise HDD for CCTV Surveillance-10TB
SITC of Monitoring PC Station Intel I7 Quad Core Xeon Processor 6 Core ,Minimum 3 GHZ ,32 GB (16x2 or Single) DDR5 RAM ,Minimum 4 GB Dedicated Graphics card with HDMI output ,1 TB SSD, Gigabit Network Interface Port, Wireless Scroll Mouse and Keyboard, including 1No of Minimum 21 inch Full HD LED CCTV Monitor, original Latest Windows Professional Software original OS + Microsoft Office 2021 or above, min 2 Serial Ports, 1 Parallel port, 4 USB Ports, 2 Expansion slots. with VMS/CMS software for CCTV integration of multiple NVRs.
LED Display - Supply, installation, testing and commissioning of Minimum 50 inch full HD LED display including bracket ,24 x 7, 500 nits or above with HDMI input Setup including necessary connection, HDMI cable, Wall Mount bracket, rating tray etc. as required for complete installation with all accessories as required and directed by engineer in charge.
PUBLIC ADDRESSING SYSTEM
Power Amplifier - Supply, fixing, testing and commissioning of Power Amplifier of 480 Watts with necessary jacks and cable for connections and interconnection with all accessories required for installation as required.
17.3.2 Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required.
17.3.1 Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
17.3.3 Supplying, installation, testing and commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.
SITC of 12 W Wall Mounted Speaker - Supply, fixing, testing and commissioning of Cabinet Speakers with ABS/Metal body with 100-volt, matching transformer. Cost inclusive of necessary interconnection connection wire etc. required for complete installation.
SITC of Call Stations - Supply, fixing, testing and commissioning of 6 Zone Calling Station with mic, which can be expandable minimum up to 12 Zones(optional) including as per the drawing as required for complete installation.
SITC of Audio player- MP3 player with LCD display and remote control and with USB, SD, MMC card and Bluetooth inputs with connecting cables
ACCESS CONTROL SYSTEM
Supply, Installation, Testing and Commissioning of IP Based 2 Door Controller can connect minimum 4 readers, 8 outputs, 8 inputs, buzzer indicator output, and LED indicators for TCP/IP, serial bus, output status with enclosure, power supply .Supports full online and offline operation and all the necessary accessories. UL Listed
Supply, Installation, Testing & Commissioning of IP Based 2 Door Controller can connect minimum 2 readers, 4 outputs, 4 inputs, buzzer indicator output, and LED indicators for TCP/IP, serial bus, output status with enclosure, power supply .Supports full online and offline operation and all the necessary accessories.UL Listed
Biometric / Card Reader with on board TCP/IP facility with display and built in 13.56 MHz MIFARE RFID card reader.RS-485, TCP/IP, and Wiegand 26- or 34-bit connectivity. IP65 ,with a minimum capacity for 10,000 fingerprint credentials (For attendance / Payroll function), Should beable to connect USB/LAN to take user information. Option should be there to connect with PMS/HMS as per requirement. UL/CE/FCC approved including Power supply,Back boxes and all accessories for completion as recommended by site in charge / Consultant"
Supply, Installation, Testing and commissioning of Smart readers supports 125 kHz, 13.56 MHz, Bluetooth and NFC.IP68 water and dust resistant, IK09 vandal resistant.UL/CE Approved
Supply of Access Cards Mifare Classic-1 K- ISO Card-Printable-Supports with the proposed Reader/Controller
Supply, Installation, Testing and commissioning of 600 lbs Single/double leaf EM Lock with ZL bracket as per Site situation and all necessary accessories. UL/CE Approved
Supply, fixing and commissioning of Stainless steel Push button with suitable PVC /GI Modular Back Box etc. in recess / surface mounted including necessary connections with all accessories required for complete installation as directed by the Engineer in charge.
Supply, fixing and commissioning of break glass with Faceplate, suitable PVC / GI Modular Backbox etc in recess/ surface mounted including necessary connections with all accessories required for complete installation as directed by Engineer in Charge.
Supply, Installation, Testing & Commissioning of Access control system Software for managing access control system and Biometric attendance System(separate or combined software can be accepted)
ACTIVE COMPONENTS AND ACCESSORIES
Supply Testing and configuration of Manageable 24 Port PoE+ Switch with minimum 190 Watts PoE Budget with minimum 100 GBPS Bandwidth capability and 90 MPPS packet forwarding rate with 4 Dedicated 10G uplinks, Port based QoS, Cloud/Remote management, - UL / CE Certified, As per Tender specification
Supply Testing and configuration of Manageable 24 Port PoE+ Switch with minimum 190 Watts PoE Budget with 4 Dedicated 1G uplinks, Port based QoS,Cloud/Remote management, - UL / CE Certified, As per Tender specification
Supply Testing and configuration of 48 Port Smart Managed PoE Gigabit minimum 370W PoE Switch with 4 x 10G SFP+ Port as per Tender Specs including 1 quantity of cable manager- 48 PoE+-capable Gigabit copper ports minimum 140 GBPS Bandwidth capability and 120 MPPS packet forwarding rate with 4 Dedicated 10G uplinks
Supply Testing and configuration of 24 Port Non- PoE Switch with minimum with minimum 100 GBPS Bandwidth capability and 80 MPPS packet forwarding rate with 4 Dedicated 10G uplinks,Port based QoS,Cloud/Remote management, - UL / CE Certified as per Tender specification
Supply Testing and configuration of Min 16 Port CORE SWITCH supports 1G and 10 G -16 Port 10G Fiber Port(supports both 1Gand10G at least 12 ports), Layer 3 with 4 nos of dedicated 10G/25G Uplink ports (Supports 1,10,25G) with Power Supply redundancy slot, Rack Mount as per Tender specification
Supply Testing and configuration of 10G SFP+ Transceiver, 10GBase-SR for Single mode Supports a minimum distance of 500 Mtrs, fully compatible with both Core Switch and Access Switch ( Should be from Same OEM of Network switches)
Supply Testing and configuration of 1G SFP+ Transceiver, 1GBase-SR for Single mode Supports a minimum distance of 500 Mtrs, fully compatible with both Core Switch and Access Switch ( Should be from Same OEM of Network switches)
Supply, Installation, Testing and Commissioning of Dual Band PoE Multi-Gig WiFi 6 Access Point which supports 5.0GHz: 802.11a/n/ac/ax, 2.4GHz: 802.11b/g/n/ax as per technical specification
PASSIVE SYSTEMS
Information Outlet RJ 45 CAT 6A -UTP- Supply, fixing, fluke testing, Labelling and Ferruling and commissioning of CAT6A Information Outlets (Key stone) UL Listed including necessary connections with all accessories required for complete installation as directed by the Engineer in charge.
Information Outlet RJ 45 CAT6 UTP - Supply, fixing, fluke testing, Ferruling, Labelling and commissioning of CAT6 Information Outlets (Key stone) UL Listed , including necessary connections with all accessories required for complete installation as directed by the Engineer in charge.
Supply Installation of Single /Dual faceplate for Telephone and DATA -Need separate color or marking option to Differentiate CAT6 CAT 6A B& Voice
Supply Installation and Fixing of GI modular Box for Network/ Telephone Sockets including Chipping and Other accessories
Supply installation of CAT6A/6 Modular plug -Unshielded Modular plug which is suitable for CAT 6 and 6A, UL Listed for Camera ,Wifi etc on ceiling termination to obtain 25 years performance warranty
U/UTP CAT 6A Cable- Supplying and drawing of Category 6A cable consists of 4 pairs of solid insulated copper 23AWG,LSZH,(complying IEEE802.3 AF and IEEE802.3 AT) Fluke testing with reports, labeling,as built drawings, with 25 years manufacturer warranty through the existing surface/recessed steel/ PVC conduit as required. as instructed by engineer in charge/consultant
1.53.1 Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
Supply, Installation, Testing and installation of Cat - 6 U/UTP, 24 port fully loaded patch panel with necessary cable manager for routing the cable inside rack with all accessories required for complete installation as required as directed by the engineer in charge.
Supply, Installation, Testing and commissioning of CAT - 6A, 24 port fully loaded unshielded patch panel with rear cable management and including crimping /Splicing and patching of cable with fluke report, Ferrule and Labelling. with all accessories required for complete installation as required as directed by the engineer in charge-UL Approved
Patch Cable - User Side - Supply, fixing, testing and commissioning of CAT6A Patch Cable - 2 Meter length etc. of approved make as required for complete installation- UL Listed
Patch Cable - User Side - Supply, fixing, testing and commissioning of CAT6APatch Cable - 1 Meter length etc. of approved make as required for complete installation.
Patch Cable - User Side - Supply, fixing, testing and commissioning of CAT6 Patch Cable - 2 Meter LSZH length etc. of approved make-UL Listed with all accessories required for complete installation.as required as directed by the engineer in charge.
Patch Cable - Hub Side - Supply, fixing, testing and commissioning of CAT6 Patch Cable - 1 Meter LSZH-UL Listed- of approved make as required for complete installation.
OFC Cable - Supplying and drawing of 12 core SM (OS2) Outdoor armored Jel Free Optical Fiber Cable (OFC), LSZH through wall/tray with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
Patch Cable - Hub Side - Supply, fixing, testing and commissioning of Single mode (LC) Fiber patch cable Duplex 2 Mtr of approved make with proper tagging, Labelling and Ferruling as per the instruction by engineer in charge/consultant.
Supply, Installation, Testing and commissioning of 24 port Light Interface Unit (LIU) / Fiber Patch Panel, rack mountable with mounting brackets, loaded with Adaptors, Ferruling, labelling, Couplers OS2 Single Mode (SM) pigtails with splicing including OTDR/OLTS reports with all accessories and 25 years Performance warranty, cable manager with all accessories required for complete installation as required as directed by the engineer in charge.
Supply, Installation, Testing and commissioning of 12 port Light Interface Unit (LIU) / Fiber Patch Panel, rack mountable with mounting brackets, loaded with Adaptors, Couplers Multi Mode (MM) OM4 pigtails with splicing including OTDR/OLTS reports with all accessories and 25 years Performance warranty. complete installation as required as directed by the engineer in charge
Supply and Installation of 48/50 Port Patch panel for Voice which can support CAT 6 cables along with Patch cables to connect with FXS/FXO Gateway
Supply and Installation of 24/25 Port Voice Patch Panel including Patch cords to connect with FXO/FXS Gateway
Supplying and drawing of 4C X 1 Sqmm Overall Shielded Armoured FRLS-ZH Cable for Controller to EM Lock with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
Supplying and drawing of 8C X 1Sqmm Overall Shielded Armoured FRLS-ZH Cable for Controller to Reader with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
Supplying and drawing of 2C X 1Sq mm Overall Shielded Armoured FRLS-ZH Cable with all accessories as required for complete installation and as instructed by engineer in charge/ consultant and making good all damages made for installation.
SITC of Speaker Cable - Supplying and drawing of 2 Core, Twin Twisted, ATC tinned copper, overall sheathed, Armored Speaker cable, 16 AWG for speakers through Wall/Ceiling with saddle a maximum distance of 35cm with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
SITC of CAT 6 LIFT CABLE - Supplying and drawing of CAT 6 Lift cable with stainles steel rod, FRPVC outer Sheath with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
SATELLITE COMPONENTS
Outlet RG6 - Supply, fixing and commissioning of RG6 Outlet with face plate, suitable PVC / GI GI Modular box etc. in recess / surface mounted including necessary connections with all accessories required for complete installation as directed by the Engineer in charge.
RG6 Cable - Supplying drawing and testing of RG6 Co-axial cable including BNC /F Connectors on both sides as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
RG11 Cable - Supplying Testing and drawing of RG11 Co-axial cable through wall/tray with all accessories including BNC/F connectors on both sides as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
RACKS CONDUIT AND TRAYS
Supply and fixing of Pre-Galvanized closed raceway with Cover ,horizontal and vertical bends, Endcaps,reducers, cross over, suitable supports and brackets and other accessories. The Tray shall be galvanized for corrosion protection .The trays should be tested for a max. safe working load of 1.5 times than the actual 1.6 mm thickness with cover in ceiling and shafts, floor etc with complete MS supports and Galvanized accessories fabricated per site requirements. It should also include the cost of bends, tees etc as required. 400 x 60 x 1.6 mm thick. All nuts, couplers and complete accessories should be Galvanized.
Supply and fixing of Pre-Galvanized closed raceway with Cover ,horizontal and vertical bends, reducers, Tees,Endcaps. cross over, suitable supports and brackets and other accessories .The Tray shall be galvanized for corrosion protection .The trays should be tested for a max. safe working load of 1.5 times than the actual,1.6 mm thickness with cover in ceiling and shafts, floor etc with complete MS supports and Galvanized accessories fabricated per site requirements. It should also include the cost of bends, tees etc as required. 150 x 60 x 1.6 mm thick,All the sides should be closed with End cap.
SITC of 15U Wall mounted Rack with Front glass door, Front/Rear 15U mounting angles, top, bottom open, including necessary exhaust / circulation fan(2 Nos), PDU (Minimum 6 Sockets) and 2x Cable Manager with all other accessories required for complete installation as directed by the engineer in charge.
SITC of 6U Wall mounted Rack with Front glass door, Front/Rear 6 U mounting angles, top, bottom open, including necessary exhaust / circulation fan(2 Nos), PDU (Minimum 6 Sockets) and 2x Cable Manager with all other accessories required for complete installation as directed by the engineer in charge.
42U Server Rack Supply, installation, testing, testing and commissioning of 42U Rack with Front glass door,Rear Perforated door with handle Lock and key, castors. Side and rear panels, Front / Rear 42U 800Wx1000D MM mounting angles, top, bottom open, RAL 9005,including necessary 4/6 qty of exhaust / circulation fan with all other accessories required for complete installation as directed by the engineer in charge., Horizontal Cable Manager- 7 Nos , Should contain PDU to connect up to 16 Devices of 16Ampere ,With Wheels and blank plates to cover all the empty areas
1.21.2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
SITC of Lubricated HDPE Pipe (Outdoor) for OF Cable (100mm diameter) with all accessories like Couplers ,Bends etc including Welding ,Civil trenching and as per TECH specification.
PVC Cable Manager/Organizer
LIFT WORKS Passenger & Service Lift
Supply, installation, testing and commissioning of following dumb waiter Capacity : 200 kg Speed : 0.5 Meter per second. Stops and opening : 2 Stop 2 Opening : Travel Height :- 18 meter Drive : Geared machine with variable voltage variable frequency drive on top of lift shaft, 2.0 HP motor, 3 ropes, 1:1 roping Control : Microprocessor based with VFD Power supply : 415 V, 3 phase, 50Hz, AC Shaft dimensions W x D required : 1200mm x 1200mm Cabin shall be STAINLESS STEEL SHEET HAIRLINE FINISH, 304 GRADE, 1.2 MM THICK, WITH FRONT SIDE OPENING Door: Minimum 900 MM X 900 MM (H) STAINLESS STEEL 304 GRADE, 1.2 MM THICK HAIR LINE FINISH VERTICAL BI-PARTING, MANUALLY OPERATED. Complying IS-3938-2005 ,IS 8587, IS807 ,IS/IEC 602-04-32 and other relevant standards Detailed Technical specification attached.
Supply, installation, testing and commissioning of following dumb waiter Capacity : 200 kg Speed : 0.5 Meter per second. Stops and opening : 2 Stop 2 Opening : Travel Height:- 5 Meter Drive : Geared machine with variable voltage variable frequency drive on top of lift shaft, 2.0 HP motor, 3 ropes, 1:1 roping Control : Microprocessor based with VFD Power supply : 415 V, 3 phase, 50Hz, AC Shaft dimensions W x D required : 1200mm x 1200mm Cabin shall be made of STAINLESS STEEL SHEET HAIRLINE FINISH, 304 GRADE, 1.2 MM THICK, WITH FRONT SIDE OPENING Door: Minimum 900 MM X 900 MM (H) STAINLESS STEEL 304 GRADE, 1.2 MM THICK HAIR LINE FINISH VERTICAL BI-PARTING, MANUALLY OPERATED . Complying IS-3938-2005 ,IS 8587, IS807 ,IS/IEC 602-04-32 and other relevant standards Detailed Technical specification attached.
FIRE PROTECTION SYSTEM FIRE PUMP ROOM
18.1.4 a)Supplying,installation,testing and commissioning of Electric driven Main Fire Pump suitable for Automatic operation and consisting of following, complete in all respect , as required : b) Horizontal type, Multi stage ,centrifugal, split casing Pump of Cast Iron body and bronze impeller with stainless steel shaft ,mechanical seal conforming to IS 1520. c) Suitable HP Squirrel Cage Induction Motor, TEFC, Synchronous speed 1500rpm suitable for operation on 415 V 3 phase 50 HZ AC supply with IP55 Protection for enclosure ,horizontal foot mounted type with class F insulation, conforming to IS 325. d) M.S Fabricated common base plate coupling, coupling guard ,foundation bolts etc as required. e) Suitable cement concrete foundation duly plastered with Anti vibration pads 2280 lpm at 88 m head
18.2.4 a)Supplying,installation,testing and commissioning of Diesel Engine driven Main Fire Pump suitable for Automatic operation and consisting of following, complete in all respect , as required :(Diesel Driven Pump) b) Horizontal type, Multi stage ,centrifugal, split Pump of Cast Iron body and bronze impeller with stainless steel shaft ,mechanical seal conforming to IS 1520. C) Suitable HP ,1500rpm,water cooled with radiator,diesel engine conforming to relevant IS standard complete with auto starting mechanism 12/24 V Electric starting equipment,diesel tank, exhaust pipe extended upto 10m outside pump house duly insulated with 50 mm thick glass wool with 1 mm thick Al sheet cladding residential silencer, instruments and protection as per standard specifications, stop solenoid for Auto stop in the event of fault with audio indications, painted with post office red colour etc as required. d) M.S Fabricated common base plate coupling, coupling guard ,foundation bolts etc as required. e) Suitable cement concrete foundation duly plastered with Anti vibration pads2280 lpm at 88m head
18.3.1 a)Supplying, installation, testing and commissioning of Electric driven Pressurisation Pump suitable for Automatic operation and consisting of following, complete in all respect , as required :(Jockey Pump) b) Horizontal type, Multi stage ,centrifugal, split casing Pump of Cast Iron body and bronze impeller with stainless steel shaft ,mechanical seal conforming to IS 1520. C) Suitable HP Squirrel Cage Induction Motor, TEFC type suitable for operation on 415 V 3 phase 50 HZ AC supply with IP55 Protection for enclosure ,horizontal foot mounted type with class F insulation, conforming to IS 325. d)M.S Fabricated common base plate coupling, coupling guard ,foundation bolts etc as required. e) Suitable cement concrete foundation duly plastered with Anti vibration pads180 lpm at 88m head
Supply, erection, commissioning of additional length of Exhaust Pipes with long radius bend from silencer with necessary clamps, fixtures, civil works and thermal insulation with 50 mm thick glass wool and with 1.0 mm thick aluminium sheet cladding of following adequate size including suitable rain cap for top to avoid rainwater entry. The distance between exhaust pipe at top and rain cap should be higher than diameter of pipe. The horizontal run of exhaust piping should slope downwards away from engine to the condensate trap. Silencer should be installed with drain plug at bottom. Fixing shall be done with proper clamps, expansion bolts, and all other accessories as instructed by the Engineer and the rate inclusive of all minor civil works required, bolts, clamps etc as required for installation. Support to exhaust piping should be done in such a manner that load of exhaust piping is not exerted to turbocharger. Exhaust pipe height shall be 3m more than the top of any adjacent building withing 10m radius of the exhaust Size-80mm.
18.7.9 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:200mm dia(Wall thickness 6.3mm)
18.7.8 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:150mm dia
18.7.7 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:100mm dia
18.7.6 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:80mm dia
18.7.4 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:50 mm dia
18.7.1 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:25 mm dia
Supply, installation, testing and commissioning of Heavy Duty Neoprene Expansion Joints / Flexible Connectors, PN:16, with Spilt Retainer Rings and Control Units, drilled to BS 10 Table E including all other necessary fixing accessories. Dia - 200mm
Supply, installation, testing and commissioning of Heavy Duty Neoprene Expansion Joints / Flexible Connectors, PN:16, with Spilt Retainer Rings and Control Units, drilled to BS 10 Table E including all other necessary fixing accessories. Dia - 150mm
Supply, installation, testing and commissioning of Heavy Duty Neoprene Expansion Joints / Flexible Connectors, PN:16, with Spilt Retainer Rings and Control Units, drilled to BS 10 Table E including all other necessary fixing accessories. Dia - 80mm
Supply, installation, testing and commissioning of Heavy Duty Neoprene Expansion Joints / Flexible Connectors, PN:16, with Spilt Retainer Rings and Control Units, drilled to BS 10 Table E including all other necessary fixing accessories. Dia - 65mm
18.14.5 Providing,installation,testing and commissioning of non-return valve of following sizes conforming to IS :5312 complete with rubber gasket, GI bolts , nuts, washers etc as required.100 mm dia
18.14.7 Providing,installation,testing and commissioning of non-return valve of following sizes conforming to IS :5312 complete with rubber gasket, GI bolts , nuts, washers etc as required.150mm Dia
18.11.7 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:200 mm dia
18.11.6 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:150 mm dia
18.11.5 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:100 mm dia
18.11.4 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:80 mm dia
Providing and fixing Ductile Iron Gate Valve, Rising Spindle, OS & Y TypeBody: ASTM A536, 65-45-12, Flanged to BS5163, PN16, UL Listed / FM Approved with Tamper / Supervisory Switches and with required flanges, rubber insertions, bolts, nuts, Washers etc. complete. 200mm
18.15.4 Providing, installation ,testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel , Grade 304,sheet with3 mm dia holes with stainless steel flange.200 mm dia
HYDRANT SYSTEM, SPRINKLER SYSTEM, FIRE PIPING, VALVES AND ACCESSORIES
18.7.8 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:150mm dia
18.7.7 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:100mm dia
18.7.6 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:80mm dia
18.7.5 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:65mm dia
18.7.4 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:50 mm dia
18.7.3 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589/IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:40 mm dia
18.7.2 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589,IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required: 32 mm dia
18.7.1 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 3589/IS 1239 i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required:25 mm dia
18.6.2 Providing, laying, testing and commissioning of C class heavy duty M S Pipe conforming to IS 1239/3589 i/c fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., in ground including welding ,excavation and providing cement concrete blocks as supports, Anti corrosive treatment with coal tar ,Asphalt type as per IS 10221, refiiling the trench etc., of following sizes150 mm dia
Providing, fixing, testing and commissioning of Vertical Check Valve of Bronze Construction, PN:25, single piece design with Integral Seat and with features as detailed in the Technical Specifications. Dia 50mm.
18.11.6 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:150 mm dia
18.11.3 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:65 mm dia
Providing, fixing, testing and commissioning of Ball Valve, PN-25 Forged Brass , Nickel / Chrome Plated, conforming to IS: 9890 with Screwed Female Ends to BS:21, and with non-corrosive handle / lever, all as per Technical specification. including necessary accessories and connections. Dia - 25mm.
16.11.1.4 Supplying, fixing testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. Butterfly Valve ( Manual) with C I body SS disc nitrile sheet & O ring & PN 16 pressure rating as specifiedButterfly Valve (Manual) 100 mm dia
16.11.1.5 Supplying, fixing testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. Butterfly Valve ( Manual) with C I body SS disc nitrile sheet & O ring & PN 16 pressure rating as specified Butterfly Valve (Manual) 80 mm dia
18.22 Providing and fixing of pressure switch in MS pipeline including connection etc as required:
16.8 Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
18.20 supplying and fixing air vessel made of 250 mm dia 8 mm thick MS sheet , 1200 mm in height with Air release valve on top and flanged connection to riser , drain arrangement with 25 mm dia Gun metal wheel valve with required accessories, pressure guage and painting with synthetic enamel paint of approved shade as required.
18.9.1 Supplying and fixing single headed internal hydrant valve with instantaneous Gun metal or stainless steel coupling of 63mm dia with cast iron wheel ISI marked conforming to IS 5290(Type A) with blank Gun metal or Stainless steel cap and chain as required:Single headed Gunmetal
18.10.1 Supplying and fixing single headed external yard hydrant valve with one no: 63 mm dia instantaneous FM Gun metal or stainless steel coupling and cast iron wheel, ISI marked ISI marked conforming to IS 5290 (Type A) with blank Gun metal or Stainless steel cap and chain as required: Single headed Gunmetal
18.17.1 Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. a) 20 mm nominal Internal dia water hose thermoplastic (Textile reinforced) type-2 as per IS:12585 b) 20 mm nominal internal dia gun metal globe valve &nozzle c) Drum and brackets for fixing the equipments on wall. d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m
18.16.2 Supplying and fixing 63 m dia,15m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required: Stainless steel (Grade 304)
Supply, installation, testing and commissioning of Branch Pipe, Stainless Steel-304, short type, with 63mm. male instantaneous inlet, male threaded outlet, fitted with 16mm. bore nozzle, having IS: 903 mark
18.19.2 Supplying and fixing fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia M.S. Pipe connection conforming to IS 904 as required:4 way-150 mm dia M.S. Pipe
Supply, installation, testing and commissioning of Fire Brigade Draw Off Outlet C.I. body, having 4 Gunmetal, 63mm. male instantaneous inlet, conforming to IS: 903, with non return valves, 25mm. drain valve, flanged outlet, 3 nos. of rubber blank caps and G.I. chains
Supply and fix at site in position Weatherproof Fire Hose Cabinet, wall / pole mounting type, 30” x 24” x 10” size, to accommodate two 15m length of delivery hose and branch pipe, acrylic fronted double door, with lock, 2 keys and a break glass recess for keys, painted Fire Red. The price shall be inclusive of fixing accessories and as per requirement
Supply and fix at site in position Fire Hose Cabinet, wall / pole mounting type, 30” x 24” x 10” size, to accommodate two 15m length of delivery hose and branch pipe, acrylic fronted double door, with lock, 2 keys and a break glass recess for keys, painted Fire Red. The price shall be inclusive of fixing accessories and as per requirement.
Providing and fixing sight glass assembly of brass body and brass ball with chrome plated, steel handle, PN16 or above, UL Listed & FM Approved. Test and drain valve shall be with compact 3 position ball valves with drain orifice having K-factor 5.6 and a sight glass. 3 positions consist of OFF, TEST and DRAIN. Test and drain valves shall be provided for test as well as express drain functions in wet sprinkler systems with grooved end connection ends. The Test and Drain Valve shall be in Brass ASTM B584 material of construction. These have integral tamper resistant sight glass.
Supply, installation, testing and commissioning of Air Release Valve Gunmetal, conforming to IS 903:1993, having rubber ball with sealing seat and with 25mm. BSP threaded male inlet, including isolation valve and necessary accessories and connections.
18.13 Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure of the outlet to the level of 3.5kg/cm2 complete as required.
Supply, installation, testing and commissioning of orifice plates; with the following;specification, 25 mm dia Orifice plate made out of 8 mm thick stainless steel plate ( in tee off to fire hose reel) for pipe to reduce pressure upto 3.5 Kg/sqcm;complete in all respects
18.21.1 Providing,fixing, testing and commissioning of 15 mm dia quatzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Pendent Sprinkler
18.21.2 Providing,fixing, testing and commissioning of 15 mm dia quatzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Upright sprinkler
18.21.3 Providing,fixing, testing and commissioning of 15 mm dia quatzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Horizontal side wall sprinkler
Supply, installation, testing and commissioning of Hydraulically Operated Fire Sprinkler Alarm Valve (Installation Control Valve), Flanged / Grooved Ends (as per final requirement without any cost variation). complete with Constant Pressure Trim Assembly, Water Motor Gong, Control Valves, Pressure Switch, Pressure Gauges etc. Including all necessary fixing accessories, all as per Technical Specifications. The control cabling from Pressure Switches to concerned Monitor Module shall be measured with proposed Fire Alarm System. The Alarm Valve and the Total Parts / Components / Accessories shall be UL Listed / FM approved. Dia - 200mm
18.23.2 Providing and fixing of flow switch in MS pipe including connection etc as required:150 mm dia
18.25.2 Supplying, installation, testing & commissioning of sprinkler flexiblepipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 1000 mm
18.25.1 Supplying, installation, testing & commissioning of sprinkler flexiblepipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 700 mm
18.29 Providing, installation, testing and commissioning of adjustable rosette plate for 15 mm dia in white finish UL listed or FM approved complete as required:
INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM
17.2.1.1 Ten Loop Panel
17.2.10 Supplying, installation, testing & commissioning of addressable fire control module complete as required.
17.2.14 Supplying, installation, testing &; commissioning of addressable manual call point complete as required.
17.2.15 Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
17.2.2 Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required.
17.2.3 Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required.
17.2.5 Supplying, installation, testing & commissioning of response indicator on surface/ recessed MS Box having two LED, metallic cover complete with all connections etc as required.
17.2.6 Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required.
17.2.7 Supplying, installation, testing & commissioning of fault isolator complete with base as required.
17.5.2 CABLING & WIRING Supplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring ; FRLS outer sheath complete as required.
Supply Installation Testing and Commissioning of Work station with minimum 13th generation or above Core i7 Processor with 32 GB RAM ,1TB SSD ,4 GB Dedicated Graphics with Giga bit Ethernet (NIC) Card along with Wireless Keyboard and Mouse with 21" or above LED Monitor
Providing, fixing, testing and commission Intelligent Addressable Input / Monitor Module, for interface with Flow Switches, Fire Pumps, Supervisory Switches, Alarm Valve, Water Tank Level etc
Providing, fixing,, test and commission Intelligent Addressable Relay Module, for interface with AHUs, Ventilation System, Smoke Management System, LPG System, Power Distribution etc.
Power Supply Panel - 220V AC Input and 24 V DC 5 Ampere Power supply with built in charger
Cost of perforated G.I.sheet cable tray with neccessory angle iron suspensionr& supports, anchor fasteners etc. complete. Maximum height of suspension shall not exceed 500mm. Size of the tray is 200mm(width) x 50mm and 2mm thick
FIRE EXTINGUISHER
Clean Agent Modular Type Ceiling mounted Fire Extinguisher 5 Kgs Capacity made of Mild Steel Body of 1.6 mm thickness with pressure gauge, refillable device and safety release device CE Certified Brass valve suitable for A, B and C Classes of Fire complete with Charge of Clean agent (Gas) is also known as HFC Blend A, It is a blend of Hydro Fluoro carbon and organic detoxicant essence P26. The sprinkler body will comprise of temperature sensitive quartzoid bulb of temperature rating of 680. The cylinder will be supplied with a proper mounting arrangement to mount it on the ceiling. The Extinguisher shall be externally epoxy powder coated as per IS: 5 Color Shade No. 538 (For Server room) 5 Kgs
Supplying, installing and commissioning Portable Fire extinguishers of following type & capacity - ABC powder type fire extinguisher with initial filling in brand new cylinder with powder coated finish, fitted with Gun metal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket etc. complete, confirming to IS:15683 : 6 Kgs
Supplying, installing and commissioning Portable Fire extinguishers of following type & capacity. Co2 type Fire Extinguisher, made from brand new seamless steel cylinder, as per IS: 7285 and CCE approval, fitted with Discharge hose and horn and Wheel type valve with initial Charge and mounted on Rubber Wheels / wall mounted brackets as per IS: 16018 specification, bearing ISI Mark.9Kgs
Supplying, installing and commissioning Portable Fire extinguishers of following type &; capacity.Co2 type Fire Extinguisher, made from brand new seamless Steel cylinder, as per IS: 7285 and CCE approval, fitted with Discharge hose and horn and Wheel type valve with initial Charge and mounted on Rubber Wheels / wall mounted brackets as per IS: 16018 specification, bearing ISI Mark. 4.5 Kgs
Supplying, installing and commissioning Portable Fire extinguishers of following type & capacity. Mechanical Foam Fire Extinguisher, 9 Litre’s capacity Fire Extinguishers pressurised by Nitrogen Gas fitted with brass valve, plastic syphon tube and discharge hose with Nozzle and Pressure Gauge to indicate pressure inside. Extinguisher is Phosphated and Epoxy powder coated internally and externally as per IS: 5 Shade No. 538 complete with wall brackets. The Extinguisher is manufactured as per IS 15683-2018 bearing ISI Mark.
Fire Bucket in 9 Ltr. Capacity, made of MS sheet in round bottom with side handle painted with Red in colour & mentioned FIRE over it. 4 Nos. per set with one Fabricated M. S. Stand
FIRE SIGNAGES
Signage with printed ;IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE of 1.25cm height letters in red with white back ground. The size of the board shall be 25cm x 30 cm and shall be fixed at the height of 2 mts. from finished floor near Manual call points.Fire signage shall conform to IS 9457, IS 12349, and IS 12407, and this compliance shall be mentioned in the BoQ/Technical Specifications.
Floor identification signage ( ie, GROUND FLOOR, FIRST FLOOR, etc.) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 5 cm with contrasting colour from back ground.Size shall be 15cm x 30cmFire signage shall conform to IS 9457, IS 12349, and IS 12407, and this compliance shall be mentioned in the BoQ/Technical Specifications.
Floor Identification Signage (MAIN STAIRCASE, FIRE STAIRCASE, FIRE ASSEMBLY POINT, PUMP ROOM, FIRE CONTROL ROOM, ELECTRICAL ROOM, FIRE LIFT, PASSENGER LIFT Etc.) on every floor, lettering size shall be 5 Cm. with contrasting colour from back ground. Size shall be 15cm x 30cm.Fire signage shall conform to IS 9457, IS 12349, and IS 12407, and this compliance shall be mentioned in the BoQ/Technical Specifications.
Providing and fixing in position the signage FIRE ORDER on 3mm thick ;Opaque PVC foam board of computerized cut, PVC nonreflective self adhesive vinyl painted foam board of 2' x 3'.
Providing and fixing in position the signages Fire Hydrant Chamber it should contain the following matter on 3mm thick;Opaque; PVC foam board of computerized cut, PVC non-reflective self adhesive vinyl painted foam board of 2' x 3'. Fire signage shall conform to IS 9457, IS 12349, and IS 12407, and this compliance shall be mentioned in the BoQ/Technical Specifications.
Supply, installation, testing and commissioning of Fire Exit Light, Laser type, with High Glow LED, size: 300x 178 x 32 mm. or 390 x190 x 60mm, Ceiling Mounting type with hanging clamps, on/off switch, Red / Green Colour option with minimum of 25 Mtr. viewing distance, power consumption: 5.0 Watt per face (maximum),with 4 Hr. Battery Backup.Single Side Display Fire signage shall conform to IS 9457, IS 12349, and IS 12407, and this compliance shall be mentioned in the BoQ/Technical Specifications.
Supply, installation, testing and commissioning of Fire Exit Light, Laser type, with High Glow LED, size: 300x 178 x 32 mm. or 390 x190 x 60mm, Ceiling Mounting type with hanging clamps, on/off switch, Red / Green Colour option with minimum of 25 Mtr. viewing distance, power consumption: 5.0 Watt per face (maximum),with 4 Hr. Battery Backup.;Double Side Display. Fire signage shall conform to IS 9457, IS 12349, and IS 12407, and this compliance shall be mentioned in the BoQ/Technical Specifications.
SITC of self glowing 'FIRE EXITINGUISHER' sign boards of size (150 X 150 mm) in triangular shape fixed on the wall.
MISCELLANEOUS ITEMS
MGPS Shaft -Supply and installation Fire stop mortar system with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, for horizontal openings in floors or slabs after passing Plastic or Metal Pipes. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration- Time-history method and VERTEQII for seismic zone 4 withFire intumescent sealants to provide minimum 2 hours fire rating when tested in accordance with UL 1479 standards. The products shall be age tested as per Dafstb and DIBT standards. The products shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96. The products shall be UL listed & classified and shall bear the UL approval logo on the packing .The instalation shall be done by maufacturer certifed contractor in accordance with the manufacturer guidelines. The contractor needs to provide complete installation report through Software for inspection purpose. Engineering Judgements (EJs) should be used for situations where a tested system is not available.
HVAC Shaft - Supply and installation of Fire stop mortar system with minimum 2 hours fire rating in services passing through fire rated walls and floors made of concrete, masonry, metal, gypsum partition when tested in accordance with UL1479 standards, for horizontal openings in floors or slabs after passing service lines like Metal Pipes or Ducts. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2-57:1999- 11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-historymethod and VERTEQII for seismic zone 4. Acrylic fire stop sealant with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, shall be used along the peripher of ducts & chiller pipes without insulation. Fire intumescent firestop sealant with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, shall be used along the periphery of ducts & chiller pipes with insulation. The products shall be age tested as per Dafstb and DIBT standards. The products shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96. The products shall be UL listed & classified and shall bear the UL approval logo on the packing..Engineering Judgements (EJs) should be used for situations where a tested system is not available. The application to be executed by manufacturer approved firestop contractor, (Ratio of Mortar to sealant can be assumed as 70% & 5% Respectively). Assumed 25% Penetrants Occupancy.
Fire shaft - Supply and installation of Fire stop mortar system with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, for openings in floors or slabs after passing service lines like Metal Pipes. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2- 57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Timehistory method and VERTEQII for seismic zone 4. The product shall be age tested as per Dafstb and DIBT standards. The product shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96. The product shall be UL listed & classified and shall bear the UL approval logo on the packing. .Engineering Judgements (EJs) should be used for situations where a tested system is not available. The application to be executed by manufacturer approved firestop contractor., Assumed 15% Penetrants Occupancy.
Electrical/ELV shaft - Supply and installation of Fire Barrier mortar with minimum 2 (two) hours fire rating when tested in accordance with UL 1479 standards , for fire rated vertical openings in floors or slabs and floors made of concrete, masonry,metal, gypsum partition, after passing service lines like Cable,Cable trays, Bus Duct or Metal pipes. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. Expanding fire stop foam with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, shall be used to seal areas that are highly dense or are not accessible and cannot be sealed with fire stop mortar properly. The expanding foam shall expand minimum seven times its volume to fill the cavity at the time of dispensing the material and shall fully cure within two minutes after dispensing. The expanding foam shall also be repenetratable. The products shall be age tested as per Dafstb and DIBT standards. The products shall carry test certificate for mold resistance rating of as determined by ASTM G21-96. The products shall be UL listed & classified and shall bear the UL approval logo on the packing.Engineering Judgements (EJs)should be used for situations where a tested system is not available. The application to be executed by manufacturer approved firestop contractor.
TALK-BACK SYSTEM
1.21.1 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
Supply, installation, testing and commisioning of Public Address speaker with talk back facility 6 Watts with L M T and call switch, made out of powder coated CRCA sheet, wall mounting type and to be installed at a height of not less than 150 CM from the finished floor levels, suitable for concealed mounting.
Providing, fixing / laying, test and commission 2Core x 1.5 mm2 FRLS Armored Cables with Green / Blue Colour / Finish, as per Technical Specifications.(Approx. Quantity for Networking)
HVAC WORKS
Supply Installation, Testing & Commissioning of variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling having all hermetically sealed inverter Compressors, minimum two compressors for above 14 HP modules, microprocessor-based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, necessary power cable from isolator to ODU, with suitable foundation etc. complete as required. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The efficiency of the equipment shall meet ECBC+ latest standards. Motor shall be minimum IE 3 rated as per IS 12615. Capacity - 36 HP. [combination (18+18)].
Supply Installation, Testing & Commissioning of Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling having all hermetically sealed inverter Compressors, minimum two compressors for above 14 HP modules, microprocessor-based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, necessary power cable from isolator to DU, with suitable foundation etc. complete as required. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 .The efficiency of the equipment shall meet ECBC+ latest standards. Motor shall be IE 3 rated as per IS 12615. Capacity - 34 HP [combination (16+18)]
Supply Installation, Testing & Commissioning of Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling having all hermetically sealed inverter Compressors, minimum two compressors for above 14 HP modules, microprocessor-based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, necessary power cable from isolator to ODU, with suitable foundation etc. complete as required. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The efficiency of the equipment shall meet ECBC latest standards. Motor shall be IE 3 rated as per IS 12615. Capacity - 28 HP. [combination (14+14)]
Supply Installation, Testing & Commissioning of variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling having all hermetically sealed inverter Compressors, minimum two compressors for above 14 HP modules, microprocessor-based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, necessary power cable from isolator to ODU, with suitable foundation etc. complete as required. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The efficiency of the equipment shall meet ECBC+ latest standards. Motor shall be minimum IE 3 rated as per IS 12615. Capacity - 44 HP. [combination (22+22)].
Supply Installation, Testing & Commissioning of Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter Compressors, minimum two compressors for above 14 HP modules, microprocessor-based Controller, topdischarge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, necessary power cable from isolator to ODU, with suitable foundation etc. complete as required. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The efficiency of the equipment shall meet ECBC latest standards. Motor shall be IE 3 rated as per IS 12615. Capacity - 26 HP. [combination 12+14]
Supply, Installation , testing and commissioning of the minimum capacity ceiling suspended indoor ductable units for VRF/VRV system with all standard fittings, flexible connectors, suitable capacity drive motor, electrical controller, complete with necessary vibration isolators, power cable etc. Rate shall include corded remote 10 TR VRF Ductable Indoor Unit
Supply, Installation, testing and commissioning of the minimum capacity ceiling suspended indoor ductable units for VRF/VRV system with all standard fittings, flexible connectors, suitable capacity drive motor, electrical controller, complete with necessary vibration isolators, power cable etc. Rate shall include corded remote 4.5 TR VRF Ductable Indoor Unit
Supply, Installation, testing and commissioning of the minimum capacity ceiling suspended indoor ductable units for VRF/VRV system with all standard fittings, flexible connectors, suitable capacity drive motor, electrical controller, complete with necessary vibration isolators, power cable etc. Rate shall include corded remote.2.5 TR VRF Ductable Indoor Unit.
Supply, Installation , testing and commissioning of the minimum capacity ceiling suspended indoor ductable units for VRF/VRV system with all standard fittings, flexible connectors, suitable capacity drive motor, electrical controller, complete with necessary vibration isolators, power cable etc. Rate shall include corded remote.1.6 TR VRF Ductable Indoor Unit
Supply, Installation, testing and commissioning of the minimum capacity ceiling suspended indoor ductable units for VRF/VRV system with all standard fittings, flexible connectors, suitable capacity drive motor, electrical controller, complete with necessary vibration isolators, power cable etc. Rate shall include corded remote.1.3 TR VRF Ductable Indoor Unit
Supply, Installation, testing and commissioning of the minimum capacity ceiling suspended indoor ductable units for VRF/VRV system with all standard fittings, flexible connectors, suitable capacity drive motor, electrical controller, complete with necessary vibration isolators, power cable etc. Rate shall include corded remote.1.0 TR VRF Ductable Indoor Unit.
Supply, installation, testing and commissioning of 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control, power cable etc., suitable for operation on single phase 230 V 50Hz AC supply 1.3 TR 4-way Cassette.
Supply, installation, testing and commissioning of 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control, power cable etc., suitable for operation on single phase 230 V 50Hz AC supply 1 TR 4-way Cassette
Supply, Installation, testing & commissioning of VRF/VRV compatible Hi wall air conditioning unit of following capacity complete with suitable capacity drive motor, all associated electrical works including power cabling, cordless remote, suitable for single phase 230 V supply etc. 2 TR VRF Hiwall unit.
Supply, Installation, testing & commissioning of VRF/VRV compatible Hi wall air conditioning unit of following capacity complete with suitable capacity drive motor, all associated electrical works including power cabling, cordless remote, suitable for single phase 230 V supply etc. 1.3 TR VRF Hiwall unit.
Supply, Installation, testing & commissioning of VRF/VRV compatible Hi wall air conditioning unit of following capacity complete with suitable capacity drive motor, all associated electrical works including power cabling, cordless remote, suitable for single phase 230 V supply etc. 1 TR VRF Hiwall unit.
Supply, Installation, testing & commissioning of VRF/VRV compatible Hi wall air conditioning unit of following capacity complete with suitable capacity drive motor, all associated electrical works including power cabling, cordless remote, suitable for single phase 230 V supply etc. 0.8 TR VRF Hiwall unit.
Supply, Installation and commissioning of copper refnet joint with insulation, all necessary support and accessories.
Supply, installation, testing and commissioning, of Transmission/Communication cabling, of 2 core 1.5 Sqmm shielded cable for interconnecting the Indoor and Outdoor Units of all the VRV/VRF Units for proper performance, Communication cable must be routed through PVC pipe.
VRV/VRF Master Controller to monitor & control the operation of all the ODUs and IDUs listed above including control wiring complete as required for a fully functional system. The controller should be capable of controlling systems with 20 outdoor unit and upto 80 indoor units.
Supply, Installation, Testing and commissioning of factory-built floor mounted double skin VRF compactable AIR-HANDLING UNIT including AHU kit units made of 50 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6mm outside layer and 0.6mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, thermal break profile, cooling coil section with aluminium finned copper tubes cooling coil, filter section with 50 mm thick metal viscous/ washable synthetic type air prefilters, fine filter, mixing box, supply air damper, return air damper,fresh air damper, plug fan with variable frequency drive suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply, IE3 motor, drain connections, necessary starter panel with bypass arrangement and power cable. 4.5 TR, 1600 cfm, 6 row coil floor mounted unit with Fine filter,hepa filter, mixing box and 3 x 0.5 KW heaters
Supply, Installation, Testing and commissioning of factory built floor mounted double skin VRF compactable AIR-HANDLING UNIT including AHU kit units made of 50 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6mm outside layer and 0.6mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection Moulding machine, thermal break profile, cooling coil section with aluminium finned copper tubes cooling coil, filter section with 50 mm thick metal viscous/ washable synthetic type air prefilters, fine filter, mixing box, supply air damper, return air damper,fresh air damper, plug fan with variable frequency drive suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply, IE3 motor, drain connections,necessary starter panel with bypass arrangement and power cable. 8.5 TR, 3200 cfm, 6 row coil floor mounted unit with Fine filter, heater, mixing box.
Supply, Installation, Testing and commissioning of factory built floor mounted double skin VRF compactable AIR-HANDLING UNIT inculding AHU kit units made of 50 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6mm outside layer and 0.6mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, thermal break profile,cooling coil section with aluminium finned copper tubes cooling coil, filter section with 50 mm thick metal viscous/ washable synthetic type air prefilters, fine filter, mixing box, supply air damper, return air damper,fresh air damper, plug fan with variable frequency drive suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply, IE3 motor, drain connections,necessary starter panel with bypass arrangement and power cable.12 TR, 4200 cfm, 6 row coil floor mounted unit with Fine filter,mixing box.
Supply, Installation, Testing and commissioning of factory built floor mounted double skin VRF compactable AIR-HANDLING UNIT inculding AHU kit units made of 50 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6mm outside layer and 0.6mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, thermal break profile,cooling coil section with aluminium finned copper tubes cooling coil, filter section with 50 mm thick metal viscous/ washable synthetic type air prefilters, fine filter, mixing box, supply air damper, return air damper,fresh air damper, plug fan with variable Frequency drive suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply, IE3 motor, drain Connections,necessary starter panel with bypass arrangement and power cable.5 TR, 1900 cfm, 6 row coil floor mounted unit with Fine filter, mixing box
VRF AHU-Supply, Installation, Testing and commissioning of factory built Ceiling Suspended double skin VRF compactable AIR-HANDLING UNIT inculding AHU kit units made of 40 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6mm outside layer and 0.6mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine,thermal break profile,cooling coil section with aluminium finned copper tubes cooling coil, filter section with 50 mm thick metal viscous/ washable synthetic type air prefilters, fine filter, mixing box, supply air damper, return air damper,fresh air damper, plug fan with variable frequency drive suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply, IE3 motor, drain connections,necessary starter panel with bypass arrangement and power cable from starter panel to AHU 3 TR, 1000 cfm WITH FINE FILTER , MIXING BOX
VRF AHU-Supply, Installation, Testing and commissioning of factory built Ceiling Suspended double skin VRF compactable AIR-HANDLING UNIT inculding AHU kit units made of 40 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6mm outside layer and 0.6mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine,thermal break profile,cooling coil section with aluminium finned copper tubes cooling coil, filter section with 50 mm thick metal viscous/ washable synthetic type air prefilters, fine filter, mixing box, supply air damper, return air damper,fresh air damper, plug fan with variable frequency drive suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply, IE3 motor, drain connections,necessary starter panel with bypass arrangement and power cable from starter panel to AHU 3 TR, 700 cfm WITH FINE FILTER HEPA FILTER WITH 99.99% EFFICENCY ,HEATER AND MIXING BOX
VRF AHU-Supply, Installation, Testing and commissioning of factory built floor mounted double skin VRF compactable AIR-HANDLING UNIT including AHU kit units made of 40 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6mm outside layer and 0.6mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine,thermal break profile,cooling coil section with aluminium finned copper tubes cooling coil, filter section with 50 mm thick metal viscous/ washable synthetic type air prefilters, fine filter, mixing box, supply air damper, return air damper,fresh air damper, plug fan with variable frequency drive suitable for 415 ± 10% V, 50Hz, 3 Phase AC supply, IE3 motor, drain connections,necessary starter panel with bypass arrangement and power cable from starter panel to AHU 4 TR, 1200 cfm WITH FINE FILTER HEATER ,MIXING BOX.
Liquid line - Refrigerant piping with 19 mm thick nitrile rubber insulation and with glass cloth & foster painting
Suction line - Refrigerant piping with 19 mm thick nitrile rubber insulation and with glass cloth & foster painting.
Inline Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen - 700 cfm Exhaust blower
Inline Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen - 600 cfm Exhaust Blower
Inline Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen - 300 cfm Exhaust Blower
Inline Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen - 200 cfm Exhaust Blower.
Inline Fans/wall mount fan - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen 100 cfm Exhaust blower.
Inline Fans/wall mount - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen 150 cfm Exhaust blower.
Inline Fans/wall mount - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen - 80 cfm Exhaust blower
Inline Fans - Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen -400 cfm duct inline fan
Inline Fans - Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen -1200 cfm duct inline fan
Inline Fans - Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with bird screen -1000 cfm duct inline fan
Inline Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum,HEPA filter with 99.9% efficency louvers with bird screen - 300 cfm Exhaust Blower
Inline Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum,HEPA filter with 99.9% efficency louvers with bird screen - 500 cfm Exhaust Blower
Supply, Installation testing and commissioning of Inline Circular/Cabinet fans of following minimum capacity with suitable blower, Single/3 phase (IE3) direct driven motor of following capacity for exhaust/fresh air, with applicable speed regulator /Starter panel, structural supports, vibration isolator if required, other accessories etc. complete in all respects. 2500 CFM 150 Pa
Supply, Installation testing and commissioning of Inline Circular/Cabinet fans of following minimum capacity with suitable blower, Single/3 phase phase (IE3) direct driven motor of following capacity for exhaust/fresh air, with applicable speed regulator /Starter panel, structural supports, vibration isolator if , other accessories etc. complete in all respects. 2000 CFM 150 Pa
Drain Piping: Supply, installation, testing & commissioning of following sizes insulated PVC drain pipe from terminal units drain pans to nearest floor drain complete with interconnection, flanges, elbows, tees, nuts, U-trap etc. The insulation shall be 9 mm thick closed cell Class O Nitrile Rubber foam insulation - 25 MM Dia
Drain Piping Supply, installation, testing & commissioning of following sizes insulated PVC drainpipe from terminal units drain pans to nearest floor drain complete with interconnection, flanges, elbows, tees, nuts, U-trap etc. The insulation shall be 9 mm thick closed cell Class O Nitrile Rubber foam insulation - 25 MM Dia
Drain Piping Supply, installation, testing & commissioning of following sizes insulated PVC drainpipe from terminal units drain pans to nearest floor drain complete with interconnection, flanges, elbows, tees, nuts, U-trap etc. The insulation shall be 9 mm thick closed cell Class O Nitrile Rubber foam insulation - 40 MM Dia
Supply installation testing and commissioning of PVC Pipes 4 KG for Fresh air to cassette units with necessary elbows, hangers and also with necessary supports and accessories. 100mm Dia
Supply Installation testing and commissioning of butterfly dampers to regulate the air flow to cassette units - 100mm Dia
16.12.1.1 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 0.63 mm sheet
16.12.1.2 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 0.80 mm sheet
16.12.1.3 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 1.00 mm sheet
16.13 Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. Gl volume control duct damper
16.15 Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
16.17 Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminum with aluminum volume control dampers with anti smudge ring and removable core
16.18 Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminum without volume control dampers with anti smudge ring and removable core.
Return Air Grills Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
Exhaust/Fresh Air Louvers with Damper: Supply, Installation, testing and commissioning of Aluminium extruded fresh air louvers with Exhaust/fresh air damper, bird screen etc. complete in all respects as required.
Supply & fixing of 25 mm or nearest thickness Class O nitrile rubber insulation with antimicrobial property with adhesive as per the recommendation of the manufacturer with density 45-55kg/m3. Moisture Diffusion Resistance Factor or ‘μ’ value of the base insulation material shall be minimum 7,000, thermal conductivity shall be 0.035W/mk. R value of the insulation material shall comply with the ECBC + building standards
Supply & fixing of 10 mm thick Class 1 acoustic nitrile rubber insulation with antimicrobial property with adhesive as per the recommendation of the manufacturer with density 140-180kg/m3
UNDER DECK INSULATION - Supply & fixing of 9 mm thick class O nitrile rubber insulation with adhesive as per the recommendation of the manufacture with density 45-55kg/m3
Roof(inside) insulation for exposed slabs/walls: Supply & fixing of 12 mm thick class O nitrile rubber insulation with adhesive as per the recommendation of the manufacture with density 45-55kg/m3
Supply and fix 1 1/2 hour fire rated fire dampers air ducts (main line) with fusible link & microswitch to shut of corresponding Ahu (including control cable.)
Medical Gas Pipeline System
SITC of Oxygen Manifold - 2 banks x 12 cylinders
SITC of Fully Automatic Oxygen Control Panel with minimum flow rate of 1500 LPM-Imported
SITC of Emergency Oxygen Manifold - 2 banks x 5 cylinders
SITC of Oxygen Flowmeters with humidifier bottle
SITC of Nitrous Oxide Manifold - 2 banks x 1 cylinders
SITC of Fully automatic Gas Control Panel for Nitrous Oxide with a minimum flow rate of 500 LPM
SITC of Emergency Nitrous Oxide Manifold - 1 bank x 1 cylinders
SITC of Carbon Dioxide Manifold - 2 banks x 1 cylinders
SITC of Fully automatic Gas Control Panel for Carbon Di Oxide with minimum flow rate of 500 LPM
SITC of Emergency Carbon Dioxide Manifold - 1 bank x 1cylinders
SITC of Duplex Compressed air plant system each compressor having minimum free air delivery of 1500 LPM with complete accessories as mentioned in technical specifications.(Imported)
SITC of Duplex vacuum plant system each pump having minimum free air aspirated of 2000 LPM at 450 mmHg with complete accessories as mentioned in technical specifications. (Imported)
Ward Vacuum Units
Theatre Vacuum Units
SITC of ICU Terminal Units - Imported - O2
SITC of ICU Terminal Units - Imported - Air
SITC of ICU Terminal Units - Imported - VAC
SITC of Ward Terminal Units - Indigenous - O2
SITC of Ward Terminal Units - Indigenous - Air 7 bar
SITC of Ward Terminal Units - Indigenous - Vac
SITC of Matching Probe - O2
SITC of Matching Probe - Air
SITC of Matching Probe - Air 7 bar
SITC of Matching Probe - VAC
SITC of Master Plant Alarm Panel (post source), BMS compatible,
SITC of Area Valve Service Units with Alarm Systems - 6 Services
SITC of Area Valve Service Units with Alarm Systems - 4 Services
SITC of Area Valve Service Units with Alarm Systems - 2 Services
SITC of Copper pipe - per mtr. - 12mm
SITC of Copper pipe - per mtr. - 15mm
SITC of Copper pipe - per mtr. - 22mm
SITC of Copper pipe - per mtr. - 28mm
SITC of Copper pipe - per mtr. - 35mm
SITC of Copper pipe - per mtr. - 42mm
SITC of Copper pipe - per mtr. - 54mm
SITC of Copper pipe - per mtr. - 76mm
SITC of Ball Valves - 15mm
SITC of Ball Valves - 22mm
SITC of Ball Valves - 28mm
SITC of Ball Valves - 35mm
SITC of Ball Valves - 42mm
SITC of Ball Valves - 54mm
SITC of Ball Valves - 76mm
SITC of Bed Head Units - 1200 mm for Wards
SITC of Bed Head Units - 1500 mm for ICU Category.
SITC of Bed Head Panel - Running Meter
SITC of Rigid Pendent
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 0.27 MB
Tenderdoc.pdf
Tender Documents • 1.34 MB
Technicalspec.pdf
Tender Documents • 3.04 MB
Dwng1.pdf
Tender Documents • 22.43 MB
Dwng2.pdf
Tender Documents • 23.06 MB
GRIHA.pdf
Tender Documents • 0.25 MB
Soilreport.pdf
Additional Documents • 9.26 MB
BOQ_1411914.xls
BOQ • 1.09 MB
Download all tender documents and submit your bid